You are on page 1of 5

Printed: 12/24/2020

FIXTURE UNIT CALCULATIONS PER MICHIGAN PLUMBING CODE

PROJECT NAME: XX
DATE:

TOTAL TOTAL
TOTAL DRAINAGE
TOTAL WSFU COLD HOT
DFU
CWFU HWFU

RESULTS 92.9 80.5 79.9 31.9

WSFU DFU
SAFETY
111.5 96.6 38.3
FACTOR USE WSFU, DFU AND HWFU FROM THIS ROW FOR DESIGN PURPOSES

FLUSH VALVE SYSTEM DEMAND GPM (MOSTLY USED)


TOTAL
TOTAL WSFU GPM HOT HWFU
GPM

GPM 74.3 26.1

WATER LOAD VALUES (WSFU) DRAINAGE FIXTURE


QUANTITY FIXTURE TAGS FIXTURE TYPE OCCUPANCY COLD WTR HOT WTR TOTAL UNITS (DFU)
FU EACH SUM FU EACH SUM FU EACH SUM DFU EACH SUM

BATHTUB(FAUCET) PUBLIC 3.0 0.0 3.0 0.0 4.0 0.0 2.0 0.0
DENTAL LAVATORY PUBLIC 1.5 0.0 1.5 0.0 2.0 0.0 1.0 0.0
DENTAL UNIT CUSPIDOR PUBLIC 1.0 0.0 1.0 0.0 1.4 0.0 1.0 0.0
EWC-1 DRINKING FOUNTAIN (3/8" VALVE) OFFICES, ETC. 0.25 0.0 0 0.0 0.25 0.0 0.5 0.0
FLOOR DRAINS 2" ALL 0 0.0 0 0.0 0 0.0 2.0 0.0
FD-1 FLOOR DRAINS 3" ALL 0 0.0 0 0.0 0 0.0 5.0 0.0
FLOOR DRAINS 4" ALL 0 0.0 0 0.0 0 0.0 6.0 0.0
FOOD WASTE GRINDER ALL 0 0.0 0 0.0 0 0.0 3.0 0.0
EHB HOSE BIB ALL 2.5 0.0 0 0.0 2.5 0.0 0.0 0.0
HOTEL,
KITCHEN SINK (FAUCET) RESTAURANT 3.0 0.0 3.0 0.0 4.0 0.0 2.0 0.0
1 L-1,L-2 LAVATORY (FAUCET) PUBLIC 1.5 1.5 1.5 1.5 2 2.0 1.0 1.0
1 SS-1 SERVICE SINK (FAUCET) PUBLIC 2.25 2.3 2.25 2.3 3 3.0 2.0 2.0
1 SINK WASH PUBLIC 2.25 2.3 2.25 2.3 3 3.0 2.0 2.0
1 SINK CLINICAL (HEALTHCARE) PUBLIC 2.5 2.5 2.5 2.5 3 3.0 4.0 4.0
1 SHOWER HEAD (MIXING VALVE) PUBLIC 3.0 3.0 3.0 3.0 4.0 4.0 2.0 2.0
1 URINAL (1" FLUSH VALVE) PUBLIC 10.0 10.0 0 0.0 10 10.0 4.0 4.0
1 UR-1 URINAL (3/4" FLUSH VALVE) PUBLIC 5.0 5.0 0 0.0 5 5.0 4.0 4.0
1 URINAL (FLUSH TANK) PUBLIC 3.0 3.0 0 0.0 3 3.0 4.0 4.0
1 URINAL WATERLESS PUBLIC 0.0 0.0 0 0.0 0 0.0 0.5 0.5
1 WASHING MACHINE (8LB) PUBLIC 2.25 2.3 2.25 2.3 3 3.0 2.0 2.0
1 WASHING MACHINE (15LB) PUBLIC 3.0 3.0 3.0 3.0 4.0 4.0 3.0 3.0
1 WATER CLOSET (FLUSH VALVE) PUBLIC 10.0 10.0 0 0.0 10 10.0 6.0 6.0
1 WC-1 WATER CLOSET (FLUSH TANK) PUBLIC 5.0 5.0 0 0.0 5 5.0 4.0 4.0
1 WATER CLOSET (FLUSHOMETER TANK) ALL 2.0 2.0 0 0.0 2 2.0 4.0 4.0
1
KITCHEN EQUIPMENT 1 - WATER GPM
KITCHEN EQUIPMENT 2 - WATER GPM
KITCHEN EQUIPMENT 3 - WATER GPM
1
1 BATHROOM GROUP (FLUSH TANK) PRIVATE 2.7 2.7 1.5 1.5 3.6 3.6 5.0 5.0
1 BATHROOM GROUP (FLUSH VALVE) PRIVATE 6.0 6.0 3.0 3.0 8.0 8.0 6.0 6.0
1 BATHTUB (FAUCET) PRIVATE 1.0 1.0 1.0 1.0 1.4 1.4 2.0 2.0
1 BIDET (FAUCET) PRIVATE 1.5 1.5 1.5 1.5 2 2.0 1.0 1.0
1 COMBINATION FIXTURE (FAUCET) PRIVATE 2.25 2.3 2.25 2.3 3 3.0 2.0 2.0
1 DISHWASHING MACHINE (AUTOMATIC) PRIVATE 0 0.0 1.4 1.4 1.4 1.4 2.0 2.0
1 KITCHEN SINK (FAUCET) PRIVATE 1.0 1.0 1.0 1.0 1.4 1.4 2.0 2.0
1 LAUNDRY TRAY (1 TO 3) (FAUCET) PRIVATE 1.0 1.0 1.0 1.0 1.4 1.4 2.0 2.0
1 LAVATORY (FAUCET) PRIVATE 0.5 0.5 0.5 0.5 0.7 0.7 1.0 1.0
1 SHOWER HEAD (MIXING VALVE) PRIVATE 1.0 1.0 1.0 1.0 1.4 1.4 2.0 2.0
1 WASHING MACHINE (8LB) (AUTOMATIC) PRIVATE 1.0 1.0 1.0 1.0 1.4 1.4 2.0 2.0
1 WATER CLOSET (FLUSH VALVE) PRIVATE 6.0 6.0 0 0.0 6 6.0 4.0 4.0
1 WATER CLOSET (FLUSH TANK) PRIVATE 2.2 2.2 0 0.0 2.2 2.2 3.0 3.0
1 WATER CLOSET(FLUSHOMETER TANK) ALL 2.0 2.0 0 0.0 2 2.0 4.0 4.0
TABLE E103.3(3)

TABLE FOR ESTIMATING DEMAND


SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS
LOAD DEMAND

(Water supply fixture units) (Gallons per minute) (Cubic feet per minute)

FTWSFU FTGPM
1 3 0.041040
2 5 0.068400
3 6.5 0.868920
4 8 1.069440
5 9.4 1.256592
6 10.7 1.430376
7 11.8 1.577424
8 12.8 1.711104
9 13.7 1.831416
10 14.6 1.951728
11 15.4 2.058672
12 16 2.138880
13 16.5 2.205720
14 17 2.272560
15 17.5 2.339400
16 18 2.906240
17 18.4 2.459712
18 18.8 2.513184
19 19.2 2.566656
20 19.6 2.620128
25 21.5 2.874120
30 23.3 3.114744
35 24.9 3.328632
40 26.3 3.515784
45 27.7 3.702936
50 29.1 3.890088
60 32 4.277760
70 35 4.678800
80 38 5.079840
90 41 5.480880
100 43.5 5.815080
120 48 6.416640
140 52.5 7.018200
160 57 7.619760
180 61 8.154480
200 65 8.689200
225 70 9.357600
250 75 10.026000
275 80.0 10.694400
300 85.0 11.362800
400 105.0 14.036400
500 124.0 16.576320
750 170.0 22.725600
1,000 208.0 27.805440
1,250 239.0 31.949520
1,500 269.0 35.959920
1,750 297.0 39.702960
2,000 325.0 43.446000
2,500 380.0 50.798400
3,000 433.0 57.883440
4,000 535.0 70.182000
5,000 593.0 79.272240
TABLE E103.3(3)

FOR ESTIMATING DEMAND


SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH VALVES
LOAD DEMAND

(Water supply fixture units) (Gallons per minute) (Cubic feet per minute)

FVWSFU FTGPM
- - -
- - -
- - -
- - -
5 15 2.005200
6 17.4 2.326032
7 19.8 2.646364
8 22.2 2.967696
9 24.6 3.288528
10 27 3.609360
11 27.8 3.716304
12 28.6 3.823248
13 29.4 3.930192
14 30.2 4.037136
15 31 4.144080
16 31.8 4.241024
17 32.6 4.357968
18 33.4 4.464912
19 34.2 4.571856
20 35 4.678800
25 38 5.079840
30 42 5.613560
35 44 5.881920
40 46 6.149280
45 48 6.416640
50 50 6.684000
60 54 7.218720
70 58 7.753440
80 61.2 8.181216
90 64.3 8.595624
100 67.5 9.023400
120 73 9.758640
140 77 10.293360
160 81 10.828080
180 85.5 11.429640
200 90 12.031200
225 95.5 12.766440
250 101 13.501680
275 104.5 13.969560
300 108.0 14.437440
400 127.0 16.977360
500 143.0 19.116240
750 177.0 23.661360
1,000 208.0 27.805440
1,250 239.0 31.949520
1,500 269.0 35.959920
1,750 297.0 39.702960
2,000 325.0 43.446000
2,500 380.0 50.798400
3,000 433.0 57.883440
4,000 525.0 70.182000
5,000 593.0 79.272240