Head loss calculation PROJECT : SOUQ WAQIF - CAR PARKING

Head loss calculation using (2) HAZEN-WILLIAMS Formula

Local factors of fittings

Total heal (DH+GH) / pipe

Accumulative Pressure
ID Pipe Inner diameter

RE Reynolds number
DN Nominal diameter

Loss m per 100 m


C Hazen constant

flexible connection
Double Reg. valve

Total local factors

V Mean Velocity

dh(2) Local loss


dh(1) Liner loss
elbow ( 45 deg.)

elbow ( 90 deg.)
no. part of pipe

GH Static heal

Loss m per m

DH Total loss
L Pipe length

3-Way Valve
Q Flow rate

check valve
gate valve

Strainer
reducer
tee
0.20

0.20
6.10
2.00

0.19

0.36
0.72
0.50
2.00
1.00
no. DN mm m mm GPM l/s 1/1 m m/s 1/1 1/1 m m m m m m

P1 -chiller In 8" ST 202.74 7 140 943.00 59.4 2 1 2 2 1 1 2.92 1.840278179 373097.998 0.01438 1.44 0.1 0.5 0.6 0.6 0.605

P2 -chiller Out 8" ST 202.74 10 140 943.00 59.4 2 1 1 2 2 1 1 9.02 1.840278179 373097.998 0.01438 1.44 0.14 1.56 1.7 1.7 1.701

P3- chiller suction headers 12" ST 303.18 35 140 1886.00 119 4 4 1 4.14 1.645853818 498989.9605 0.00731 0.73 0.26 0.57 0.83 0.83 0.828

P4- chiller discharge headers 12" ST 303.18 40 140 1886.00 119 3 1 1 1.79 1.645853818 498989.9605 0.00731 0.73 0.29 0.25 0.54 0.54 0.54

P5 - Pump suction and discharge 8" ST 202.74 8 140 943.00 59.4 2 2 1 1 2 2 2 12.1 1.840278179 373097.998 0.01438 1.44 0.12 2.08 2.2 2.2 2.197

P6- Pump suction and discharge header 12" ST 303.18 12 140 1886.00 119 2 2 2 4 4.38 1.645853818 498989.9605 0.00731 0.73 0.09 0.6 0.69 0.69 0.692

P7 12" ST 303.18 56 140 1765.00 111 2 2 2 3.16 1.540260864 466976.2886 0.00647 0.65 0.36 0.38 0.74 0.74 0.744

P8 8" ST 202.74 18 140 975.50 61.5 2 1 2 4 10.1 1.9037024 385956.6246 0.01532 1.53 0.28 1.87 2.14 2.14 2.141

P9 8" ST 202.74 56 140 701.00 44.2 2 2 2 2 3.54 1.368011669 277350.6857 0.00831 0.83 0.47 0.34 0.8 0.8 0.803

P10 6" ST 154.08 40 140 584.00 36.8 2 2 2 3.16 1.973199404 304030.5642 0.02255 2.25 0.9 0.63 1.53 1.53 1.529

P11 5" ST 128.2 80 140 350.50 22.1 4 2 2.88 1.710655823 219306.0765 0.02145 2.15 1.72 0.43 2.15 2.15 2.146

P12 5" ST 128.2 50 140 233.70 14.7 2 2 2 2.82 1.140599902 146224.9075 0.01013 1.01 0.51 0.19 0.69 0.69 0.693

P13 3" ST 77.92 75 140 116.80 7.36 4 2 1 10 2 1 1 15.3 1.543105514 120238.7816 0.03169 3.17 2.38 1.86 4.24 4.24 4.238

TOTAL 387 8 2 2 6 24 20 8 1 1 6.69 6.3 13 18.86

Static head = M
total friction loss = 18.86 M
total dynamic head = 18.86 M
Air Seperator 2M
Chiller 6M
Y-Strainer 3M
AHU 3M
Automatic balancing Valve 3M
Other Line Accessories 2M

TOTAL PUMP HEAD 37.86 M


PUMP HEAD WITH 15 % SAFETY FACTOR 43.54 M
PUMP HEAD WITH 15 % SAFETY FACTOR 142.84 FT