IEC61850 ACSI Conformance Statement

GRL200 (Soft Z33 & Z37)


- 1435 -
6F2S1934 (0.0 )

IEC61850 PICS
Protocol Implementation Conformance Statement
GRL200

This document specifies the Protocol Implementation Conformance Statement (PICS) of


the IEC 61850 interface in GR series IED with communication firmware G2M850-01 series
version upper than E (G2M850-01-E).

Together with the MICS and the PIXIT, the PICS forms the basis for a conformance test
according to IEC 61850-10.

Each tables of this document is specified in IEC 61850-7-2 Annex A.3 “ACSI models
conformance statement”.

GRL200 (Soft Z33 & Z37)


- 1436 -
6F2S1934 (0.0 )

Client/ Server/ IED Remarks


subscriber publisher
Client-server roles
B11 Server side (of TWO-PARTY- - c1 Y
APPLICATION-ASSOCIATION)
B12 Client side of (TWO-PARTY- c1 - -
APPLICATION-ASSOCIATION)
SCSMs supported
B21 SCSM: IEC61850-8-1 used Y
B22 SCSM: IEC61850-9-1 used N
B23 SCSM: IEC61850-9-2 used N
B24 SCSM: other -
Generic substation event model (GSE)
B31 Publisher side - O Y
B32 Subscriber side O - Y
Transmission of sampled value model (SVC)
B41 Publisher side - O N
B42 Subscriber side O - N

If Server side (B11) supported


M1 Logical device c2 c2 Y
M2 Logical node c3 c3 Y
M3 Data c4 c4 Y
M4 Data set c5 c5 Y
M5 Substitution O O N
M6 Setting group control O O Y
Reporting
M7 Buffered report control O O Y
M7-1 sequence-number Y
M7-2 report-time-stamp Y
M7-3 reason-for-inclusion Y
M7-4 data-set-name Y
M7-5 data-reference Y
M7-6 buffer-overflow Y
M7-7 entryID Y
M7-8 BufTm Y
M7-9 IntgPd Y
M7-10 GI Y
Unbuffered report control O O Y
M8-1 sequence-number Y
M8-2 report-time-stamp Y
M8-3 reason-for-inclusion Y
M8-4 data-set-name Y
M8-5 data-reference Y
M8-6 BufTm Y
M8-7 IntgPd Y
M8-8 GI Y
Logging O O N
M9 Log control O O N
M9-1 IntgPd N
M10 Log O O N
M11 Control M M Y
If GSE (B31/B32) is supported
GOOSE O O Y

GRL200 (Soft Z33 & Z37)


- 1437 -
6F2S1934 (0.0 )

M13 GSSE O O N
If SVC (B41/B42) is supported
M14 Multicast SVC O O N
M15 Unicast SVC O O N
M16 Time M M Y
M17 File Transfer O O Y
Server
S1 GetServerDirectory M Y
Application association
S2 Associate M M Y
S3 Abort M M Y
S4 Release M M Y
Logical device
S5 GetLogicalDeviceDirectory M M Y
Logical node
S6 GetLogicalNodeDirectory M M Y
S7 GetAllDataValues O M Y
Data
S8 GetDataValues M M Y
S9 SetDataValues O O Y
S10 GetDataDirectory O M Y
S11 GetDataDefinition O M Y
Data set
S12 GetDataSetValues O M Y
S13 SetDataSetValues O O N
S14 CreateDataSet O O N
S15 DeleteDataSet O O N
S16 GetDataSetDirectory O O Y
Substitution
S17 SetDataValues M M N
Setting group control
S18 SelectActiveSG O O Y
S19 SelectEditSG O O N
S20 SetSGValues O O N
S21 ConfirmEditSGValues O O N
S22 GetSGValues O O N
S23 GetSGCBValues O O Y
Reporting
Buffered report control block (BRCB)
S24 Report c6 c6 Y
S24-1 data-change (dchg) Y
S24-2 quality-change (qchg) Y
S24-3 data-update (dupd) N
S25 GetBRCBValues c6 c6 Y
S26 SetBRCBValues c6 c6 Y
Unbuffered report control block (BRCB)
S27 Report c6 c6 Y
S27-1 data-change (dchg) Y
S27-2 quality-change (qchg) Y
S27-3 data-update (dupd) N
S28 GetURCBValues c6 c6 Y
S29 SetURCBValues c6 c6 Y
Logging
Log control block
S30 GetLCBValues M M N
S31 SetLCBValues O M N

GRL200 (Soft Z33 & Z37)


- 1438 -
6F2S1934 (0.0 )

Log
S32 QueryLogByTime c7 M N
S33 QueryLogAfter c7 M N
S34 GetLogStatusValues M M N
Generic substation event model (GSE)
GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage c8 c8 Y
S36 GetGoReference O c9 N
S37 GetGOOSEElementNumber O c9 N
S38 GetGoCBValues O O Y
S39 SetGoCBValues O O Y
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage c8 c8 N
S41 GetGsReference O c9 N
S42 GetGSSEDataOffset O c9 N
S43 GetGsCBValues O O N
S44 SetGsCBValues O O N
Transmission of sampled value model (SVC)
Multicast SVC
S45 SendMSVMessage c10 c10 N
S46 GetMSVCBValues O O N
S47 SetMSVCBValues O O N
Unicast SVC
S48 SendUSVMessage c10 c10 N
S49 GetUSVCBValues O O N
S50 SetUSVCBValues O O N
Control
S51 Select M O Y
S52 SelectWithValue M O Y
S53 Cancel O O Y
S54 Operate M M Y
S55 CommandTermination M O Y
S56 TimeActivatedOperate O O N
File Transfer
S57 GetFile O M Y
S58 SetFile O O N
S59 DeleteFile O O N
S60 GetFileAttributeValues O O Y
Time
T1 Time resolution of internal clock 1ms
T2 Time accuracy of internal clock 1ms T1
T3 Supported TimeStamp resolution 1ms
M – Mandatory
O – Optional
c1 – shall be ‘M’ if support for LOGICAL-DEVICE model has been declared.
c2 – shall be ‘M’ if support for LOGICAL-NODE model has been declared.
c3 – shall be ‘M’ if support for DATA model has been declared.
c4 – shall be ‘M’ if support for DATA-SET, Substitution, Report, Log Control, or Time model has been
declared.
c5 – shall be ‘M’ if support for Report, GSE, or SV models has been declared.
c6 – shall declare support for at least one (BRCB or URCB)
c7 – shall declare support for at least one (QueryLogByTime or QueryLogAfter).
c8 – shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage)
c9 – shall declare support if TWO-PARTY association is available.
c10 – shall declare support for at least one (SendMSVMessage or SendUSVMessage).

GRL200 (Soft Z33 & Z37)


- 1439 -
6F2S1934 (0.0 )

PICS for A-Profile support


A-Profile Profile Description Client Server IED Remarks
shortcut F/S F/S
A1 Client/server A-Profile c1 c1 Y
A2 GOOSE/GSE c2 c2 Y
management A-Profile
A3 GSSE A-Profile c3 c3 N
A4 TimeSync A-Profile c4 c4 Y
c1 Shall be ‘m’ if support for any service specified in Table 2 are declared within the ACSI basic conformance statement.
c2 Shall be ‘m’ if support for any service specified in Table 6 are declared within the ACSI basic conformance statement.
c3 Shall be ‘m’ if support for any service specified in Table 9 are declared within the ACSI basic conformance statement.
c4 Support for at least one other A-Profile shall be declared (e.g. in A1-A3) in order to claim conformance to IEC
61850-8-1.

PICS for T-Profile support


A-Profile Profile Description Client Server IED Remarks
shortcut F/S F/S
T1 TCP/IP T-Profile c1 c1 Y
T2 OSI T-Profile c2 c2 N
T3 GOOSE/GSE T-Profile c3 c3 Y
T4 GSSE T-Profile c4 c4 N
T5 TimeSync T-Profile o o Y
c1 Shall be ‘m’ if support for A1 is declared. Otherwise, shall be 'i'.
c2 Shall be ‘o’ if support for A1 is declared. Otherwise, shall be 'i'.
c3 Shall be ‘m’ if support for A2 is declared. Otherwise, shall be 'i'.
c4 Shall be ‘m’ if support for A3 is declared. Otherwise, shall be 'i'.

GRL200 (Soft Z33 & Z37)


- 1440 -
6F2S1934 (0.0 )

MMS InitiateRequest general parameters


Client-CR Server-CR
InitiateRequest IED
Base F/S Value/range Base F/S Value/range
InitiateRequest
localDetailCalling m m m m Y
proposedMaxServOutstandingCalling m m 1 or greater m m 1 or greater Y
proposedMaxServOustandingCalled m m 1 or greater m m 1 or greater Y
initRequestDetail m m m m Y

InitiateRequestDetail
proposedVersionNumber m m shall be 2.1 m m shall be 2.1 Y
proposedParameterCBB m m m m Y
servicesSupportedCalling m m m m Y
additionalSupportedCalling c1 x c1 x N
additionalCbbSupportedCalling c1 x c1 x N
privilegeClassIdentityCalling c1 x c1 x N
c1 Conditional upon Parameter CBB CSPI

MMS InitiateResponse general parameters


Client-CR Server-CR
InitiateResponse IED
Base F/S Value/range Base F/S Value/range
InitiateResponse
localDetailCalled m m m m Y
negotiatedMaxServOutstandingCalling m m 1 or greater m m 1 or greater Y
negotiatedMaxServOustandingCalled m m 1 or greater m m 1 or greater Y
initResponseDetail m m m m Y

InitiateResponseDetail
negotiatedVersionNumber m m shall be 2.1 m m shall be 2.1 Y
negotiatedParameterCBB m m m m Y
servicesSupportedCalled m m m m Y
additionalSupportedCalled c1 x c1 x N
additionalCbbSupportedCalled c1 x c1 x N
privilegeClassIdentityCalled c1 x c1 x N
c1 Conditional upon Parameter CBB CSPI

GRL200 (Soft Z33 & Z37)


- 1441 -
6F2S1934 (0.0 )

MMS service supported conformance table


Client-CR Server-CR
MMS service supported CBB IED
Base F/S Value/range Base F/S Value/range
status o o o m Y
getNameList o o o c1 Y
identify o o m m Y
rename o o o o N
read o o o c2 Y
write o o o c3 Y
getVariableAccessAttributes o o o c4 Y
defineNamedVariable o o o o N
defineScatteredAccess o i o i N
getScatteredAccessAttributes o i o i N
deleteVariableAccess o o o o N
defineNamedVariableList o o o o N
getNamedVariableListAttributes o o o c5 Y
deleteNamedVariableList o o o c6 N
defineNamedType o i o i N
getNamedTypeAttributes o i o i N
deleteNamedType o i o i N
input o i o i N
output o i o i N
takeControl o i o i N
relinquishControl o i o i N
defineSemaphore o i o i N
deleteSemaphore o i o i N
reportPoolSemaphoreStatus o i o i N
reportSemaphoreStatus o i o i N
initiateDownloadSequence o i o i N
downloadSegment o i o i N
terminateDownloadSequence o i o i N
initiateUploadSequence o i o i N
uploadSegment o i o i N
terminateUploadSequence o i o i N
requestDomainDownload o i o i N
requestDomainUpload o i o i N
loadDomainContent o i o i N
storeDomainContent o i o i N
deleteDomain o i o i N
getDomainAttributes o o o c14 Y
createProgramInvocation o i o i N

GRL200 (Soft Z33 & Z37)


- 1442 -
6F2S1934 (0.0 )

Client-CR Server-CR
MMS service supported CBB IED
Base F/S Value/range Base F/S Value/range
deleteProgramInvocation o i o i N
start o i o i N
stop o i o i N
resume o i o i N
reset o i o i N
kill o i o i N
getProgramInvocationAttributes o i o i N
obtainFile o c9 o c9 N
defineEventCondition o i o i N
deleteEventCondition o i o i N
getEventConditionAttributes o i o i N
reportEventConditionStatus o i o i N
alterEventConditionMonitoring o i o i N
triggerEvent o i o i N
defineEventAction o i o i N
deleteEventAction o i o i N
alterEventEnrollment o i o i N
reportEventEnrollmentStatus o i o i N
getEventEnrollmentAttributes o i o i N
acknowledgeEventNotification o i o i N
getAlarmSummary o i o i N
getAlarmEnrollmentSummary o i o i N
readJournal o c13 o c13 N
writeJournal o o o o N
initializeJournal o o o c12 N
reportJournalStatus o i o i N
createJournal o i o i N
deleteJournal o i o i N
fileOpen o c8 o c8 Y
fileRead o c8 o c8 Y
fileClose o c8 o c8 Y
fileRename o i o i N
fileDelete o c9 o c9 N
fileDirectory o c11 o c11 Y
unsolicitedStatus o i o i N
informationReport o c7 o c7 Y
eventNotification o i o i N
attachToEventCondition o i o i N
attachToSemaphore o i o i N
conclude m m m m Y
cancel o o o m Y
getDataExchangeAttributes o c10 o c10 N
exchangeData o c10 o c10 N

GRL200 (Soft Z33 & Z37)


- 1443 -
6F2S1934 (0.0 )

Client-CR Server-CR
MMS service supported CBB IED
Base F/S Value/range Base F/S Value/range
defineAccessControlList o c10 o c10 N
getAccessControlListAttributes o c10 o c10 N
reportAccessControlledObjects o c10 o c10 N
deleteAccessControlList o c10 o c10 N
alterAccessControl o c10 o c10 N
reconfigureProgramInvocation o c10 o c10 N
c1 Shall be ‘m’ if logical device or logical node model support is declared in ACSI basic conformance statement.
c2 Shall be ‘m’ if logical node model support is declared in ACSI basic conformance statement or if support for the MMS
write service is declared.
c3 Shall be ‘m’ if ACSI support for SetDataValues service is declared or implied.
c4 Shall be ‘m’ if logical node model support is declared in ACSI basic conformance statement.
c5 Shall be ‘m’ if data set support is declared in the ACSI basic conformance statement.
c6 Shall be ‘m’ if support for defineNamedVariableList is declared.
c7 Shall be 'm' if support for ACSI Report or ACSI command termination is declared.
c8 Shall be 'm' if support for ACSI GetFile is declared.
c9 Shall be 'm' if support for ACSI SetFile is declared.
c10 Shall not be present since MMS minor version is declared to be 1.
c11 Shall be 'm' if support for ACSI GetFileAttributeValues is declared.
c12 Shall be 'm' if support for the ACSI log model is declared.
c13 Shall be 'm' if support for the ACSI QueryLogByTime or QueryLogAfter is declared.
c14 Shall be 'm' if support for the ACSI logical device model is declared.

MMS Parameter CBB


Client-CR Server-CR
MMS parameter CBB IED
Base F/S Value/range Base F/S Value/range
STR1 o o o c1 Y
STR2 o o o o N
1 1 or 1 c2 Y(10
gre )
NEST ater
VNAM o o o c1 Y
VADR o o o o N
VALT o o o c1 Y
bit x x x x N
TPY o o o o N
VLIS o c1 o c3 Y
bit x x x x N
bit x x x x N
CEI o i o i N
ACO o c4 o c4 N
SEM o c4 o c4 N
CSR o c4 o c4 N
CSNC o c4 o c4 N
CSPLC o c4 o c4 N
CSPI o c4 o c4 N
c1 Shall be ‘m’ if ACSI logical node model support declared.
c2 Shall be five(5) or greater if ACSI logical node model support is declared.
c3 Shall be ‘m’ if ACSI data set, reporting, GOOSE, or logging model support is declared.
c4 Shall not be present. Receiving implementations shall assume not supported.

GRL200 (Soft Z33 & Z37)


- 1444 -
6F2S1934 (0.0 )

GetNameList conformance statement


Client-CR Server-CR
GetNameList IED
Base F/S Value/range Base F/S Value/range
Request
ObjectClass m m m m Y
ObjectScope m m m m Y
DomainName o o m m Y
ContinueAfter o m m m Y
Response+
List Of Identifier m m m m Y
MoreFollows m m m m Y
Response-
Error Type m m m m Y
NOTE Object class ‘vmd' (formerly VMDSpecific in MMS V1.0) shall not appear. If a request contains this ObjectClass, an
MMS Reject shall be issued.

AlternateAccessSelection conformance statement


Not applicable.

VariableAccessSpecification conformance statement


Client-CR Server-CR
VariableAccessSpecification IED
Base F/S Value/range Base F/S Value/range
listOfVariable o o o c1 Y
variableSpecification o o o c1 Y
alternateAccess o o o c1 Y
variableListName o o o c2 Y
c1 Shall be ‘m’ if ACSI support for Logical Node Model is declared.
c2 Shall be ‘m’ if ACSI support for ACSI DataSets, reporting, or logging is declared.

VariableSpecification conformance statement


Client-CR Server-CR
VariableSpecification IED
Base F/S Value/range Base F/S Value/range
name o o o m Y
address o o o i N
variableDescription o o o i N
scatteredAccessDescription o x o x N
invalidated o x o x N

Read conformance statement


Client-CR Server-CR
Read IED
Base F/S Value/range Base F/S Value/range
Request
specificationWithResult o o o m Y
variableAccessSpecification m m m m Y
Response
variableAccessSpecification o o o m Y
listOfAccessResult m m m m Y

GRL200 (Soft Z33 & Z37)


- 1445 -
6F2S1934 (0.0 )

Write conformance statement


Client-CR Server-CR
Write IED
Base F/S Value/range Base F/S Value/range
Request
variableAccessSpecification m m m m Y
listOfData m m m m Y
Response
failure m m m m Y
success m m m m Y

InformationReport conformance statement


Client-CR Server-CR
InformationReport IED
Base F/S Value/range Base F/S Value/range
Request
variableAccessSpecification m m m m Y
listOfAccessResult m m m m Y

GetVariableAccessAttributes conformance statement


Client-CR Server-CR
GetVariableAccessAttributes IED
Base F/S Value/range Base F/S Value/range
Request
name o o m m Y
address o o m x N
Response
mmsDeletable m m m m Y
address o x o x N
typeSpecification m m m m Y

DefineNamedVariableList conformance statement


Not applicable.

GetNamedVariableListAttributes conformance statement


Client-CR Server-CR
GetNamedVariableListAttributes IED
Base F/S Value/range Base F/S Value/range
Request
ObjectName m m m m Y
Response
mmsDeletable m m m m Y
listOfVariable m m m m Y
variableSpecification m m m m Y
alternateAccess o m o i N

DeleteNamedVariableList conformance statement


Not applicable.

GRL200 (Soft Z33 & Z37)


- 1446 -
6F2S1934 (0.0 )

ReadJournal conformance statement


Not applicable.

JournalEntry conformance statement


Not applicable.

InitializeJournal conformance statement


Not applicable.

FileDirectory conformance statement


Client-CR Server-CR
FileDirectory IED
Base F/S Value/range Base F/S Value/range
Request
filespecification o o m m Y
continueAfter o o m m Y
Response+
listOfDirectoryEntry m m m m Y
MoreFollows m m m m Y

FileOpen conformance statement


Client-CR Server-CR
FileOpen IED
Base F/S Value/range Base F/S Value/range
Request
filename m m m m Y
initialPosition o o m m Y
Response+
frsmID m m m m Y
fileAttributes m m m m Y

FileRead conformance statement


Client-CR Server-CR
FileRead IED
Base F/S Value/range Base F/S Value/range
Request
frsmID m m m m Y
Response+
fileData m m m m Y
MoreFollows m m m m Y

GRL200 (Soft Z33 & Z37)


- 1447 -
6F2S1934 (0.0 )

FileClose conformance statement


Client-CR Server-CR
FileClose IED
Base F/S Value/range Base F/S Value/range
Request
frsmID m m m m Y
Response+ m m m m Y

GOOSE conformance statement


Subscriber Publisher Value/comment IED
GOOSE Services c1 c1 Y
SendGOOSEMessage m m Y
GetGoReference o c3 N
GetGOOSEElementNumber o c4 N
GetGoCBValues o o Y
SetGoCBValues o o Y
GSENotSupported c2 c5 N
GOOSE Control Block (GoCB) o o Y
c1 Shall be ‘m’ if support is declared within ACSI basic conformance statement.
c2 Shall be ‘m’ if ACSI basic conformance support for either GetGoReference or GetGOOSEElementNumber is
declared.
c3 Shall be ‘m’ if support for ACSI basic conformance of GetGoReference is declared.
c4 Shall be ‘m’ if support for ACSI basic conformance of GetGOOSEElementNumber.
c5 Shall be ‘m’ if no support for ACSI basic conformance of GetGOOSEElementNumber is declared.

GSSE conformance statement


Not applicable.

GRL200 (Soft Z33 & Z37)


- 1448 -
6F2S1934 (0.0 )

(This page is intentionally blank.)

GRL200 (Soft Z33 & Z37)

- 1449 -
6F2S1934 (0.0 )

IEC61850 Model Implementation


Conformance Statement (MICS)
GR series (Differential protection)

GRL200 (Soft Z33 & Z37)


- 1450 -
6F2S1934 (0.0 )

The GR relay supports IEC 61850 logical nodes and common data classes as indicated in the following tables.

Logical nodes in IEC 61850-7-4


Logical Nodes GRL GGIO_GOOSE Yes
L: System Logical Nodes GSAL ---
LPHD Yes I: Logical Nodes for Interfacing and archiving
Common Logical Node Yes IARC ---
LLN0 Yes IHMI ---
P: Logical Nodes for Protection functions ITCI ---
PDIF Yes ITMI ---
PDIR --- A: Logical Nodes for Automatic control
PDIS Yes ANCR ---
PDOP --- ARCO ---
PDUP --- ATCC ---
PFRC --- AVCO ---
PHAR Yes M: Logical Nodes for Metering and measurement
PHIZ --- MDIF Yes
PIOC --- MHAI ---
PMRI --- MHAN ---
PMSS --- MMTR ---
POPE --- MMXN ---
PPAM --- MMXU Yes
PSCH Yes MSQI Yes
PSDE --- MSTA ---
PTEF --- S: Logical Nodes for Sensors and monitoring
PTOC Yes SARC ---
PTOF Yes SIMG ---
PTOV Yes SIML ---
PTRC Yes SPDC ---
PTTR Yes X: Logical Nodes for Switchgear
PTUC Yes XCBR Yes
PTUV Yes XSWI ---
PUPF --- T: Logical Nodes for Instrument transformers
PTUF Yes TCTR ---
PVOC --- TVTR ---
PVPH --- Y: Logical Nodes for Power transformers
PZSU --- YEFN ---
R: Logical Nodes for protection related functions YLTC ---
RDRE --- YPSH ---
RADR --- YPTR ---
RBDR --- Z: Logical Nodes for Further power system
RDRS --- equipment
RBRF Yes ZAXN ---
RDIR --- ZBAT ---
RFLO Yes ZCAB ---
RPSB Yes ZCAP ---
RREC Yes ZCON ---
RSYN Yes ZGEN ---
C: Logical Nodes for Control ZGIL ---
CALH --- ZLIN ---
CCGR --- ZMOT ---
CILO Yes ZREA ---
CPOW --- ZRRC ---
CSWI Yes ZSAR ---
G: Logical Nodes for Generic references ZTCF ---
GAPC Yes ZTCR ---
GGIO Yes
Nodes GRL

GRL200 (Soft Z33 & Z37)


- 1451 -
6F2S1934 (0.0 )

Common data classes in IEC61850-7-3


Common data classes GRL
Status information
SPS Yes
DPS ---
INS Yes
ACT Yes
ACT_ABC Yes
ACD Yes
ACD_ABC Yes
SEC ---
BCR ---
Measured information
MV Yes
CMV Yes
SAV ---
WYE Yes
WYE_ABCN Yes
DEL Yes
SEQ Yes
HMV ---
HWYE ---
HDEL ---
Controllable status information
SPC Yes
DPC Yes
INC Yes
BSC ---
ISC ---
Controllable analogue information
APC ---
Status settings
SPG ---
ING Yes
Analogue settings
ASG Yes
CURVE ---
Description information
DPL Yes
LPL Yes
CSD ---

GRL200 (Soft Z33 & Z37)


- 1452 -
6F2S1934 (0.0 )

LPHD class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
PhyName DPL Physical device name plate M Y
PhyHealth INS Physical device health M Y
OutOv SPS Output communications buffer overflow O N
Proxy SPS Indicates if this LN is a proxy M Y
InOv SPS Input communications buffer overflow O N
NumPwrUp INS Number of Power ups O N
WrmStr INS Number of Warm Starts O N
WacTrg INS Number of watchdog device resets detected O N
PwrUp SPS Power Up detected O N
PwrDn SPS Power Down detected O N
PwrSupAlm SPS External power supply alarm O N
RsStat SPC Reset device statistics T O N

Common Logical Node class


Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Mandatory Logical Node Information (Shall be inherited by ALL LN but LPHD)
Mod INC Mode M Y
Beh INS Behaviour M Y
Health INS Health M Y
NamPlt LPL Name plate M Y
Optional Logical Node Information
Loc SPS Local operation O N
EEHealth INS External equipment health O N
EEName DPL External equipment name plate O N
OpCntRs INC Operation counter resetable O N
OpCnt INS Operation counter O N
OpTmh INS Operation time O N
Data Sets (see IEC 61850-7-2)
Inherited and 1453pecialized from Logical Node class (see IEC 61850-7-2)
Control Blocks (see IEC 61850-7-2)
Inherited and 1453pecialized from Logical Node class (see IEC 61850-7-2)
Services (see IEC 61850-7-2)
Inherited and 1453pecialized from Logical Node class (see IEC 61850-7-2)

LLNO class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
Loc SPS Local operation for complete logical device O Y
OpTmh INS Operation time O N
Controls
Diag SPC Run Diagnostics O Y
LEDRs SPC LED reset T O Y

GRL200 (Soft Z33 & Z37)


- 1453 -
6F2S1934 (0.0 )

PDIF class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD_ABC Start O Y
Op ACT_ABC Operate T M Y
TmAst CSD Active curve charactristic O N
Measured Values
DifAClc WYE_ABCN Differential Current O Y
RstA WYE_ABCN Restraint Current O Y
Settings
LinCapac ASG Line capacitance (for load currents) O N
LoSet ING Low operate value, percentage of the nominal current O N
HiSet ING High operate value, percentage of the nominal current O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
RstMod ING Restraint Mode O N
RsDlTmms ING Reset Delay Time O N
TmACrv CURVE Operating Curve Type O N

GRL200 (Soft Z33 & Z37)


- 1454 -
6F2S1934 (0.0 )

PDIS class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD_ABC Start M Y
Op ACT_ABC Operate T M Y
Settings
PoRch ASG Polar Reach is the diameter of the Mho diagram O Y
PhStr ASG Phase Start Value O Y
GndStr ASG Ground Start Value O Y
DirMod ING Directional Mode O Y
PctRch ASG Percent Reach O N
Ofs ASG Offset O Y
PctOfs ASG Percent Offset O N
RisLod ASG Resistive reach for load area O N
AngLod ASG Angle for load area O N
TmDlMod SPG Operate Time Delay Mode O N
OpDlTmms ING Operate Time Delay O Y
PhDlMod SPG Operate Time Delay Multiphase Mode O N
PhDlTmms ING Operate Time Delay for Multiphase Faults O N
GndDlMod SPG Operate Time Delay for Single Phase Ground Mode O N
GndDlTmms ING Operate Time Delay for single phase ground faults O N
X1 ASG Positive sequence line (reach) reactance O Y
LinAng ASG Line Angle O Y
RisGndRch ASG Resistive Ground Reach O Y
RisPhRch ASG Resistive Phase Reach O Y
K0Fact ASG Residual Compensation Factor K0 O N
K0FactAng ASG Residual Compensation Factor Angle O N
RsDlTmms ING Reset Time Delay O N

PHAR class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD_ABC Start M Y
Settings
HarRst ING Number of harmonic restrained O N
PhStr ASG Start Value O Y
PhStop ASG Stop Value O N
OpDlTmms ING Operate Delay Time O N
RsDlTmms ING Reset Delay Time O N

GRL200 (Soft Z33 & Z37)


- 1455 -
6F2S1934 (0.0 )

PSCH class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
ProTx SPS Teleprotection signal transmitted T M Y
ProRx SPS Teleprotection signal received T M Y
Str ACD_ABC Carrier Send M Y
Op ACT_ABC Operate T M Y
CarRx ACT Carrier received after unblock logic O N
LosOfGrd SPS Loss of guard O N
Echo ACT_ABC Echo signal from weak end infeed function O Y
WeiOp ACT_ABC Operate signal from weak end infeed function O Y
RvABlk ACT_ABC Block signal from current reversal function O Y
GrdRx SPS Guard Received O N
Settings
SchTyp ING Scheme Type O N
OpDlTmms ING Operate Delay Time O N
CrdTmms ING Co-ordination timer for blocking scheme O Y
DurTmms ING Minimum duration of carrier send signal O N
UnBlkMod ING Unblock function mode for scheme type O N
SecTmms ING Pickup security timer on loss of carrier guard signal O N
WeiMod ING Mode of weak end infeed function O N
WeiTmms ING Co-ordination time for weak end infeed function O N
PPVVal ASG Voltage level for weak end infeed function -phase-phase O N
PhGndVal ASG Voltage level for weak end infeed function -phase-ground O N
RvAMod ING Mode of current reversal function O N
RvATmms ING Pickup time for current reversal logic O N
RvRsTmms ING Delay time for reset of current reversal output O Y

GRL200 (Soft Z33 & Z37)


- 1456 -
6F2S1934 (0.0 )

PTOC class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD_ABC Start M Y
Op ACT_ABC Operate T M Y
TmASt CSD Active curve characteristic O N
Settings
TmACrv CURVE Operating Curve Type O N
StrVal ASG Start Value O Y
TmMult ASG Time Dial Multiplier O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
OpDITmms ING Operate Delay Time O Y
TypRsCrv ING Type of Reset Curve O N
RsDITmms ING Reset Delay Time O N
DirMod ING Directional Mode O N

PTOF class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T M Y
BlkV SPS Blocked because of voltage O Y
Settings
StrVal ASG Start Value (frequency) O Y
BlkVal ASG Voltage Block Value O Y
OpDITmms ING Operate Delay Time O Y
RsDITmms ING Reset Delay Time O N

GRL200 (Soft Z33 & Z37)


- 1457 -
6F2S1934 (0.0 )

PTOV class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD_ABC Start M Y
Op ACT_ABC Operate T O Y
TmVSt CSD Active curve characteristic O N
Settings
TmVCrv CURVE Operating Curve Type O N
StrVal ASG Start Value O Y
TmMult ASG Time Dial Multiplier O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
OpDlTmms ING Operate Delay Time O Y
RsDlTmms ING Reset Delay Time O N

PTRC class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Tr ACT_ABC Trip C Y
Op ACT Operate (combination of subscribed Op from protection functions) C N
Str ACD Sum of all starts of all connected Logical Nodes O N
Settings
TrMod ING Trip Mode O N
TrPlsTmms ING Trip Pulse Time O N

Condition C: At least one of the two status information (Tr, Op) shall be used.

GRL200 (Soft Z33 & Z37)


- 1458 -
6F2S1934 (0.0 )

PTTR class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Measured Values
Amp MV Current for thermal load model O N
Tmp MV Temperature for thermal load O N
TmpRl MV Relation between temperature and max. temperature O N
LodRsvAlm MV Load reserve to alarm O N
LodRsvTr MV Load reserve to trip O N
AgeRat MV Ageing rate O N
Status Information
Str ACD Start O Y
Op ACT Operate T M Y
AlmThm ACT Thermal Alarm O Y
TmTmpSt CSD Active curve characteristic O N
TmASt CSD Active curve characteristic O N
Settings
TmTmpCrv CURVE Characteristic Curve for temperature measurement O N
TmACrv CURVE Characteristic Curve for current measurement /Thermal model O N
TmpMax ASG Maximum allowed temperature O N
StrVal ASG Start Value O Y
OpDlTmms ING Operate Delay Time O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
RsDlTmms ING Reset Delay Time O N
ConsTms ING Time constant of the thermal model O N
AlmVal ASG Alarm Value O N

PTUC class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD_ABC Start M Y
Op ACT_ABC Operate T O Y
TmVSt CSD Active curve characteristic O N
Settings
TmACrv CURVE Operating Curve Type O N
StrVal ASG Start Value O Y
OpDlTmms ING Operate Delay Time O Y
TmMult ASG Time Dial Multiplier O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
TypRsCrv ING Type of Reset Curve O N
RsDlTmms ING Reset Delay Time O N
DirMod ING Directional Mode O N

GRL200 (Soft Z33 & Z37)


- 1459 -
6F2S1934 (0.0 )

PTUV class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD_ABC Start M Y
Op ACT_ABC Operate T M Y
TmVSt CSD Active curve characteristic O N
Settings
TmVCrv CURVE Operating Curve Type O N
StrVal ASG Start Value O Y
TmMult ASG Time Dial Multiplier O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
OpDlTmms ING Operate Delay Time O Y
RsDlTmms ING Reset Delay Time O N

PTUF class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T M Y
BlkV SPS Blocked because of voltage O Y
Settings
StrVal ASG Start Value (frequency) O Y
BlkVal ASG Voltage Block Value O Y
OpDlTmms ING Operate Delay Time O Y
RsDlTmms ING Reset Delay Time O N

GRL200 (Soft Z33 & Z37)


- 1460 -
6F2S1934 (0.0 )

RBRF class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD_ABC Start, timer running O Y
OpEx ACT Breaker failure trip (“external trip”) T C N
OpIn ACT_ABC Operate, retrip (“internal trip”) T C Y
Setting
Breaker Failure Detection Mode (current, breaker status, both,
FailMod ING O Y
other)
FailTmms ING Breaker Failure Time Delay for bus bar trip O Y
SPlTrTmms ING Single Pole Retrip Time Delay O N
TPTrTmms ING Three Pole Retrip Time Delay O N
DetValA ASG Current Detector Value O Y
ReTrMod ING Retrip Mode O N
Condition C: At least one of either data shall be used depending on the applied tripping schema.

RFLO class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Measured values
FltZ CMV Fault Impedance M Y
FltDiskm MV Fault Distance in km M Y
Status Information
FltLoop INS Fault Loop O Y
Setting
LinLenKm ASG Line length in km O Y
R1 ASG Positive-sequence line resistance O Y
X1 ASG Positive-sequence line reactance O Y
R0 ASG Zero-sequence line resistance O Y
X0 ASG Zero-sequence line reactance O Y
Z1Mod ASG Positive-sequence line impedance value O N
Z1Ang ASG Positive-sequence line impedance angle O N
Z0Mod ASG Zero-sequence line impedance value O N
Z0Ang ASG Zero-sequence line impedance angle O N
Rm0 ASG Mutual resistance O Y
Xm0 ASG Mutual reactance O Y
Zm0Mod ASG Mutual impedance value O N
Zm0Ang ASG Mutual impedance angle O N

GRL200 (Soft Z33 & Z37)


- 1461 -
6F2S1934 (0.0 )

RPSB class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start (Power Swing Detected) C1 Y
Op ACT Operate (Out of step Tripping) T C2 N
BlkZn SPS Blocking of correlated PDIS zone C1 Y
Setting
ZeroEna SPG Zero Enable O N
NgEna SPG Negative Sequence Current Supervision Enabled O N
MaxEna SPG Max Current Supervision Enabled O N
SwgVal ASG Power Swing Delta O Y
SwgRis ASG Power Swing Delta R O N
SwgReact ASG Power Swing Delta X O N
SwgTmms ING Power Swing Time O Y
UnBlkTmms ING Unblocking Time O N
Maximum number of pole slips until tripping (Op, Out of step
MaxNumSlp ING O N
tripping)
EvTmms ING Evaluation time (time window, Out of step tripping) O N
Condition C1: Mandatory if RPSB is used for “Power swing blocking”
Condition C2: Mandatory if RPSB is used for “Out of step tripping”

GRL200 (Soft Z33 & Z37)


- 1462 -
6F2S1934 (0.0 )

RREC class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Controls
BlkRec SPC Block Reclosing O N
ChkRec SPC Check Reclosing O N
Status Information
Auto SPS Automatic Operation (external switch status) O N
Op ACT Operate (used here to provide close to XCBR) T M Y
AutoRecSt INS Auto Reclosing Status M Y
Setting
Rec1Tmms ING First Reclose Time O N
Rec2Tmms ING Second Reclose Time O N
Rec3Tmms ING Third Reclose Time O N
PlsTmms ING Close Pulse Time O Y
RclTmms ING Reclaim Time O Y

GRL200 (Soft Z33 & Z37)


- 1463 -
6F2S1934 (0.0 )

RSYN class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Controls
RHz SPC Raise Frequency O N
LHz SPC Lower Frequency O N
RV SPC Raise Voltage O N
LV SPC Lower Voltage O N
Status Information
Rel SPS Release M Y
VInd SPS Voltage Difference Indicator O N
AngInd SPS Angle Difference Indicator O N
HzInd SPS Frequency Difference Indicator O N
SynPrg SPS Synchronising in progress O N
Measured values
DifVClc MV Calculated Difference in Voltage O N
DifHzClc MV Calculated Difference in Frequency O N
DifAngClc MV Calculated Difference of Phase Angle O N
Setting
DifV ASG Difference Voltage O N
DifHz ASG Difference Frequency O N
DifAng ASG Difference Phase Angle O Y
LivDeaMod ING Live Dead Mode O N
DeaLinVal ASG Dead Line Value O N
LivLinVal ASG Live Line Value O N
DeaBusVal ASG Dead Bus Value O N
LivBusVal ASG Live Bus Value O N
PlsTmms ING Close Pulse Time O N
BkrTmms ING Closing time of breaker O N

GRL200 (Soft Z33 & Z37)


- 1464 -
6F2S1934 (0.0 )

CILO class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
Status Information
EnaOpn SPS Enable Open M Y
EnaCls SPS Enable Close M Y

CSWI class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Controls
Pos DPC Switch, general M Y
PosA DPC Switch L1 O N
PosB DPC Switch L2 O N
PosC DPC Switch L3 O N
OpOpn ACT Operation “Open Switch” T O N
OpCls ACT Operation “Close Switch” T O N

GRL200 (Soft Z33 & Z37)


- 1465 -
6F2S1934 (0.0 )

GAPC class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Controls
SPCSO SPC Single point controllable status output O N
DPCSO DPC Double point controllable status output O N
ISCSO INC Integer status controllable status output O N
Status Information
Auto SPS Automatic operation O N
Str ACD_ABC Start M Y
Op ACT_ABC Operate T M Y
Setting
StrVal ASG Start Value O N

GRL200 (Soft Z33 & Z37)


- 1466 -
6F2S1934 (0.0 )

GGIO class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Measured values
AnIn MV Analogue input O N
Controls
SPCSO SPC Single point controllable status output O N
DPCSO DPC Double point controllable status output O N
ISCSO INC Integer status controllable status output O N
Status Information
IntIn INS Integer status input O N
Alm SPS General single alarm O N
Ind01 SPS General indication (binary input) O Y
Ind02 SPS General indication (binary input) O Y
Ind03 SPS General indication (binary input) O Y
Ind04 SPS General indication (binary input) O Y
Ind05 SPS General indication (binary input) O Y
Ind06 SPS General indication (binary input) O Y
Ind07 SPS General indication (binary input) O Y
Ind08 SPS General indication (binary input) O Y
Ind09 SPS General indication (binary input) O Y
Ind10 SPS General indication (binary input) O Y
:
:
:
Ind64 SPS General indication (binary input) O Y

GRL200 (Soft Z33 & Z37)


- 1467 -
6F2S1934 (0.0 )

GGIO_GOOSE class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Measured values
AnIn MV Analogue input O N
Controls
SPCSO SPC Single point controllable status output O N
DPCSO DPC Double point controllable status output O N
ISCSO INC Integer status controllable status output O N
Status Information
IntIn INS Integer status input O N
Alm SPS General single alarm O N
Ind01 SPS General indication (binary input) O Y
Ind02 SPS General indication (binary input) O Y
Ind03 SPS General indication (binary input) O Y
Ind04 SPS General indication (binary input) O Y
Ind05 SPS General indication (binary input) O Y
Ind06 SPS General indication (binary input) O Y
Ind07 SPS General indication (binary input) O Y
Ind08 SPS General indication (binary input) O Y
Ind09 SPS General indication (binary input) O Y
Ind10 SPS General indication (binary input) O Y
Ind11 SPS General indication (binary input) O Y
Ind12 SPS General indication (binary input) O Y
Ind13 SPS General indication (binary input) O Y
Ind14 SPS General indication (binary input) O Y
Ind15 SPS General indication (binary input) O Y
Ind16 SPS General indication (binary input) O Y

GRL200 (Soft Z33 & Z37)


- 1468 -
6F2S1934 (0.0 )

MDIF class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node
M
Class
Measured values
OpARem WYE_ABCN Operate Current (phasor) of the remote current measurement C Y
Amp1 SAV Current (Sampled value) phase A C N
Amp2 SAV Current (Sampled value) phase B C N
Amp3 SAV Current (Sampled value) phase C C N
Condition C: Either OpARem or Amp1/Amp2/Amp3 shall be used.

MMXU class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
Measured values
TotW MV Total Active Power (Total P) O N
TotVAr MV Total Reactive Power (Total Q) O N
TotVA MV Total Apparent Power (Total S) O N
TotPF MV Average Power factor (Total PF) O N
Hz MV Frequency O Y
PPV DEL Phase to phase voltages (VL1VL2, …) O Y
PhV WYE Phase to ground voltages (VL1ER, …) O Y
A WYE Phase currents (IL1, IL2, IL3) O Y
W WYE Phase active power (P) O Y
VAr WYE Phase reactive power (Q) O Y
VA WYE Phase apparent power (S) O Y
PF WYE Phase power factor O Y
Z WYE Phase Impedance O N

GRL200 (Soft Z33 & Z37)


- 1469 -
6F2S1934 (0.0 )

MSQI class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Measured values
SeqA SEQ Positive, Negative and Zero Sequence Current C Y
SeqV SEQ Positive, Negative and Zero Sequence Voltage C Y
DQ0Seq SEQ DQ0 Sequence O N
ImbA WYE Imbalance current O N
ImbNgA MV Imbalance negative sequence current O N
ImbNgV MV Imbalance negative sequence voltage O N
ImbPPV DEL Imbalance phase-phase voltage O N
ImbV WYE Imbalance voltage O N
ImbZroA MV Imbalance zero sequence current O N
ImbZroV MV Imbalance zero sequence voltage O N
MaxImbA MV Maximum imbalance current O N
MaxImbPPV MV Maximum imbalance phase-phase voltage O N
MaxImbV MV Maximum imbalance voltage O N
Condition C: At least one of either data shall be used.

GRL200 (Soft Z33 & Z37)


- 1470 -
6F2S1934 (0.0 )

XCBR class
Attribute Name Attr. Type Explanation T M/O GRL
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
OpCnt INS Operation counter M Y
Controls
Pos DPC Switch position M Y
BlkOpn SPC Block opening M Y
BlkCls SPC Block closing M Y
ChaMotEna SPC Charger motor enabled O Y
Metered Values
SumSwARs BCR Sum of Switched Amperes, resetable O N
Status Information
CBOpCap INS Circuit breaker operating capability M Y
POWCap INS Point On Wave switching capability O N
MaxOpCap INS Circuit breaker operating capability when fully charged O N

GRL200 (Soft Z33 & Z37)


- 1471 -
6F2S1934 (0.0 )

SPS class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
stVal BOOLEAN ST dchg TRUE | FALSE M Y
q Quality ST qchg M Y
t TimeStamp ST M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal BOOLEAN SV TRUE | FALSE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13

INS class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
stVal INT32 ST dchg M Y(*1)
q Quality ST qchg M Y
t TimeStamp ST M Y
Substitution
subEna BOOLEAN SV PICS_SUBST N
subVal INT32 SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13

(*1): “ENUM” type is also used.

GRL200 (Soft Z33 & Z37)


- 1472 -
6F2S1934 (0.0 )

ACT class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
phsA BOOLEAN ST dchg O N
phsB BOOLEAN ST dchg O N
phsC BOOLEAN ST dchg O N
neut BOOLEAN ST dchg O N
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
operTm TimeStamp CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13

ACT_ABC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
phsA BOOLEAN ST dchg O Y
phsB BOOLEAN ST dchg O Y
phsC BOOLEAN ST dchg O Y
neut BOOLEAN ST dchg O N
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
operTm TimeStamp CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13

GRL200 (Soft Z33 & Z37)


- 1473 -
6F2S1934 (0.0 )

ACD class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
dirGeneral ENUMERATED ST dchg unknown | forward | backward | both M Y
phsA BOOLEAN ST dchg GC_2 (1) N
dirPhsA ENUMERATED ST dchg unknown | forward | backward GC_2 (1) N
phsB BOOLEAN ST dchg GC_2 (2) N
dirPhsB ENUMERATED ST dchg unknown | forward | backward GC_2 (2) N
phsC BOOLEAN ST dchg GC_2 (3) N
dirPhsC ENUMERATED ST dchg unknown | forward | backward GC_2 (3) N
neut BOOLEAN ST dchg GC_2 (4) N
dirNeut ENUMERATED ST dchg unknown | forward | backward GC_2 (4) N
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13

ACD_ABC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
dirGeneral ENUMERATED ST dchg unknown | forward | backward | both M Y
phsA BOOLEAN ST dchg GC_2 (1) Y
dirPhsA ENUMERATED ST dchg unknown | forward | backward GC_2 (1) Y
phsB BOOLEAN ST dchg GC_2 (2) Y
dirPhsB ENUMERATED ST dchg unknown | forward | backward GC_2 (2) Y
phsC BOOLEAN ST dchg GC_2 (3) Y
dirPhsC ENUMERATED ST dchg unknown | forward | backward GC_2 (3) Y
neut BOOLEAN ST dchg GC_2 (4) N
dirNeut ENUMERATED ST dchg unknown | forward | backward GC_2 (4) N
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13

GRL200 (Soft Z33 & Z37)


- 1474 -
6F2S1934 (0.0 )

MV class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
measured values
instMag AnalogueValue MX O N
mag AnalogueValue MX dchg M Y
range ENUMERATED MX dchg normal | high | low | high-high | low-low |… O N
q Quality MX qchg M Y
t TimeStamp MX M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal AnalogueValue SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
units Unit CF see Annex A O Y
db INT32U CF 0 … 100 000 O N
zeroDb INT32U CF 0 … 100 000 O N
sVC ScaledValueConfig CF AC_SCAV N
rangeC RangeConfig CF GC_CON N
smpRate INT32U CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21

GRL200 (Soft Z33 & Z37)


- 1475 -
6F2S1934 (0.0 )

CMV class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
measured values
instCVal Vector MX O N
cVal Vector MX dchg M Y
range ENUMERATED MX dchg normal | high | low | high-high | low-low |… O N
q Quality MX qchg M Y
t TimeStamp MX M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal Vector SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
units Unit CF see Annex A O Y
db INT32U CF 0 … 100 000 O N
zeroDb INT32U CF 0 … 100 000 O N
rangeC RangeConfig CF GC_CON N
magSVC ScaledValueConfig CF AC_SCAV N
angSVC ScaledValueConfig CF AC_SCAV N
angRef ENUMERATED CF V | A | other … O N
smpRate INT32U CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21

GRL200 (Soft Z33 & Z37)


- 1476 -
6F2S1934 (0.0 )

WYE class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
phsA CMV GC_1 Y
phsB CMV GC_1 Y
phsC CMV GC_1 Y
neut CMV GC_1 N
net CMV GC_1 N
res CMV GC_1 N
DataAttribute
configuration, description and extension
angRef ENUMERATED CF Va | Vb | Vc | Aa | Ab | Ac | Vab | Vbc | Vca | O N
Vother | Aother
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21

WYE_ABCN class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
phsA CMV GC_1 Y
phsB CMV GC_1 Y
phsC CMV GC_1 Y
neut CMV GC_1 Y
net CMV GC_1 N
res CMV GC_1 N
DataAttribute
configuration, description and extension
angRef ENUMERATED CF Va | Vb | Vc | Aa | Ab | Ac | Vab | Vbc | Vca | O N
Vother | Aother
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21

GRL200 (Soft Z33 & Z37)


- 1477 -
6F2S1934 (0.0 )

DEL class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
phsAB CMV GC_1 Y
phsBC CMV GC_1 Y
phsCA CMV GC_1 Y
DataAttribute
configuration, description and extension
angRef ENUMERATED CF Va | Vb | Vc | Aa | Ab | Ac | Vab | O N
Vbc | Vca | Vother | Aother
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21

SEQ class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
c1 CMV M Y
c2 CMV M Y
c3 CMV M Y
DataAttribute
measured attributes
seqT ENUMERATED MX pos-neg-zero | dir-quad-zero M Y
configuration, description and extension
phsRef ENUMERATED CF A|B |C |… O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21

GRL200 (Soft Z33 & Z37)


- 1478 -
6F2S1934 (0.0 )

SPC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal BOOLEAN CO off (FALSE) | on (TRUE) AC_CO_M N
operTm TimeStamp CO AC_CO_O N
origin Originator_RO CO, ST AC_CO_O Y
ctlNum INT8U_RO CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_M N
SBOw SBOW CO AC_CO_SBOW_E_M N
Oper Oper CO AC_CO _M Y
Cancel Cancel CO AC_CO_SBO_N_M N
and
AC_CO_SBOW_E_M
and
AC_CO_TA_E_M
stVal BOOLEAN ST dchg FALSE | TRUE AC_ST Y
q Quality ST qchg AC_ST Y
t TimeStamp ST AC_ST Y
stSeld BOOLEAN ST dchg AC_CO_O N
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal BOOLEAN SV FALSE | TRUE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
pulseConfig PulseConfig CF AC_CO_O N
CtlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31

GRL200 (Soft Z33 & Z37)


- 1479 -
6F2S1934 (0.0 )

DPC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal BOOLEAN CO off (FALSE) | on (TRUE) AC_CO_M Y
operTm TimeStamp CO AC_CO_O N
origin Originator CO, ST AC_CO_O Y
ctlNum INT8U CO, ST 0..255 AC_CO_O Y
SBO VISIBLE STRING65 CO AC_CO_SBO_N_M N
SBOw SBOW CO AC_CO_SBOW_E_M Y
Oper Oper CO AC_CO _M Y
Cancel Cancel CO AC_CO_SBO_N_M Y
and
AC_CO_SBOW_E_M
and
AC_CO_TA_E_M
stVal CODED ENUM ST dchg intermediate-state | off | on | M Y
bad-state
q Quality ST qchg M Y
t TimeStamp ST M Y
stSeld BOOLEAN ST dchg AC_CO_O N
Substitution
subEna BOOLEAN SV PICS_SUBST N
subVal CODED ENUM SV intermediate-state | off | on | PICS_SUBST N
bad-state
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
pulseConfig PulseConfig CF AC_CO_O N
ctlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O Y
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31

GRL200 (Soft Z33 & Z37)


- 1480 -
6F2S1934 (0.0 )

INC class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal INT32 CO AC_CO_M N
operTm TimeStamp CO AC_CO_O N
origin Originator CO, ST AC_CO_O N
ctlNum INT8U CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_M N
SBOw SBOW CO AC_CO_SBOW_E_M N
Oper Oper CO AC_CO _M N
Cancel Cancel CO AC_CO_SBO_N_M N
and
AC_CO_SBOW_E_M
and
AC_CO_TA_E_M
stVal INT32 ST dchg M Y
Q Quality ST qchg M Y
T TimeStamp ST M Y
stSeld BOOLEAN ST dchg AC_CO_O N
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal INT32 SV FALSE | TRUE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
CtlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O N
minVal INT32 CF O N
maxVal INT32 CF O N
stepSize INT32U CF 1 … (maxVal – minVal) O N
D VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31

GRL200 (Soft Z33 & Z37)


- 1481 -
6F2S1934 (0.0 )

ING class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
setting
setVal INT32 SP AC_NSG_M Y(*3)
setVal INT32 SG, SE AC_SG_M N
configuration, description and extension
minVal INT32 CF O N
maxVal INT32 CF O N
stepSize INT32U CF 1 … (maxVal – minVal) O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 39
(*3): “ENUM” type is also used.

ASG class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
setting
setMag AnalogueValue SP AC_NSG_M Y
setMag AnalogueValue SG, SE AC_SG_M N
configuration, description and extension
units Unit CF see Annex A O Y
sVC ScaledValueConfig CF AC_SCAV Y
minVal AnalogueValue CF O N
maxVal AnalogueValue CF O N
stepSize AnalogueValue CF 1 … (maxVal – minVal) O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 42

GRL200 (Soft Z33 & Z37)


- 1482 -
6F2S1934 (0.0 )

DPL class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
configuration, description and extension
vendor VISIBLE STRING255 DC M Y
hwRev VISIBLE STRING255 DC O N
swRev VISIBLE STRING255 DC O Y
serNum VISIBLE STRING255 DC O N
model VISIBLE STRING255 DC O Y
location VISIBLE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 45

LPL class
Attribute Attribute Type FC TrgOp Value/Value Range M/O/C GRL
Name
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
configuration, description and extension
vendor VISIBLE STRING255 DC M Y
swRev VISIBLE STRING255 DC M Y
d VISIBLE STRING255 DC M Y
dU UNICODE STRING255 DC O N
configRev VISIBLE STRING255 DC AC_LN0_M Y
ldNs VISIBLE STRING255 EX shall be included in LLN0 only; AC_LN0_EX N
for example "IEC 61850-7-4:2003"
lnNs VISIBLE STRING255 EX AC_DLD_M N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 45

GRL200 (Soft Z33 & Z37)


- 1483 -
6F2S1934 (0.0 )

(This page is intentionally blank.)

GRL200 (Soft Z33 & Z37)

- 1484 -
6F2S1934 (0.0 )

Protocol implementation extra information

for testing (PIXIT)

on the IEC61850 communication interface (Ver. 0.6)

Note: The template of this document is “Protocol Implementation eXtra Information for
Testing (PIXIT) for the IEC 61850 interface in G2 series IED” published by UCA
International Using Group with note” PIXIT template extracted from server test
procedures version 2.3 and updated according to TPCL version 1.5” in March
12,2012 .

GRL200 (Soft Z33 & Z37)


- 1485 -
6F2S1934 (0.0 )

This document specifies the protocol implementation extra information for testing (PIXIT) of
the IEC 61850 interface in G2 series IED with communication firmware G2M850-01 series
version upper than E (G2M850-01-E).

Together with the PICS and the MICS the PIXIT forms the basis for a conformance test
according to IEC 61850-10.

Each chapter specifies the PIXIT for each applicable ACSI service model as structured in IEC
61850-10.

GRL200 (Soft Z33 & Z37)


- 1486 -
6F2S1934 (0.0 )

Maximum number of clients that can set-up an


As1 6
association simultaneously
Configurable from 1 to 20 seconds
As2 TCP_KEEPALIVE value
(default is 20 seconds)
From 10 to 30 seconds
As3 Lost connection detection time
(TCP_KEEPALIVE + 10sec.)
As4 Is authentication supported N
Transport selector N
Session selector N
What association parameters are necessary for
As5 Presentation selector N
successful association
AP Title N
AE Qualifier N
If association parameters are necessary for
As6 N.A.
association, describe the correct values e.g.
Max MMS PDU size 8172
What is the maximum and minimum MMS PDU
As7 Min MMS PDU size Not limited. It
size
depends on a request.
Typically about 130 seconds

Please check LCD


Monitoring -> Communication
What is the maximum start up time after a power
As8 -> 61850STAT as “Active”
supply interrupt
(Note) The startup time depends
on the type of IED and
its configuration/setting.
Same as “Lost connection detection time”
As9 Physical link disconnection
above

GRL200 (Soft Z33 & Z37)


- 1487 -
6F2S1934 (0.0 )

Validity:
Y Good,
Y Invalid,
N Reserved,
Y Questionable
N Overflow
N OutofRange
N BadReference
Which analogue value (MX) quality bits are supported (can be N Oscillatory
Sr1
set by server) N Failure
N OldData
N Inconsistent
N Inaccurate (Only Hz)
Source:
N Process
N Substituted
Y Test
N OperatorBlocked
Validity:
Y Good,
Y Invalid,
N Reserved,
Y Questionable
N BadReference
N Oscillatory
Which status value (ST) quality bits are supported (can be set N Failure
Sr2
by server) N OldData
N Inconsistent
N Inaccurate
Source:
N Process
N Substituted
Y Test
N OperatorBlocked
Not restricted;
What is the maximum number of data values in one depend on the max.
Sr3
GetDataValues request MAX PDU size given
in previous page.
Not restricted; depend on the
What is the maximum number of data values in one
Sr4 max. MAX PDU size given in
SetDataValues request
previous page.
On Y
Blocked N
Sr5 Which Mode / Behavior values are supported Test Y
Test/Blocked N
Off N
Front-to-back order. This
might influence on write
The order of interpretation of write requests involving a list of
Sr6 request involving RptEna and
variables.
other variables in the same
RCB.

GRL200 (Soft Z33 & Z37)


- 1488 -
6F2S1934 (0.0 )

Not limited by an internal


configuration parameter.

This IED does not have


What is the maximum number of data elements in one data CreateDataSet service. But
Ds1
set (compare ICD setting) any DataSet can be defined
by using engineering tool.
The maximum number
depends on the memory size
of IED.
How many persistent data sets can be created by one or more
Ds2 clients N.A.
(this number includes predefined datasets)
How many non-persistent data sets can be created by one or
Ds3 N.A.
more clients

Not applicable

GRL200 (Soft Z33 & Z37)


- 1489 -
6F2S1934 (0.0 )

What is the number of supported setting groups


Sg1 for each logical device (compare NumSG in the 8
SGCB)
Just SelectActiveSG service will be
supported according to PICS.

When an IED receives correct


SelectActiveSG request, the IED returns
Response+ within 10 seconds. And the
What is the effect of when and how the ActSG and LActTm variable are updated
Sg2 non-volatile storage is updated within 10 seconds after the Response+.
(compare IEC 61850-8-1 $16.2.4) (These times are typical values, and they
depend on IED types and its
configurations/settings.)

After changing setting group number with


LED panel, you can see new setting group
with GetSGCBValue service.
Sg3 Can multiple clients edit the same setting group N.A.
What happens if the association is lost while
Sg4 N.A.
editing a setting group
Sg5 Is EditSG value 0 allowed? N.A.

GRL200 (Soft Z33 & Z37)


- 1490 -
6F2S1934 (0.0 )

integrity Y
data change Y
quality change Y
data update Y*
The supported trigger conditions are
Rp1 general interrogation Y
(compare PICS)
*data-update can be set, but IED
doesn’t send the report caused by
data update
sequence-number Y
report-time-stamp Y
reason-for-inclusion Y
data-set-name Y
Rp2 The supported optional fields are data-reference Y
buffer-overflow Y
entryID Y
conf-rev Y
segmentation Y
Rp3 Can the server send segmented reports Y
Mechanism on second internal data change Send report immediately
Rp4 notification of the same analogue data value within
buffer period (Compare IEC 61850-7-2 $14.2.2.9)
Multi client URCB approach Each URCB is visible to all clients
Rp5
(compare IEC 61850-7-2 $14.2.1)
It is made up of the circular buffer
Rp6 What is the format of EntryID counter at the time the event was
entered.
What is the buffer size for each BRCB or how many For example, LLN0$ST$Health can
Rp7
reports can be buffered be stored 408 events.
Pre-configured RCB attributes that cannot be <data set name>
Rp8 changed online when RptEna = FALSE
N.A.
(see also the ICD report settings)
May the reported data set contain:
Rp9 - structured data objects? Y
- data attributes? Y

What is the scan cycle for binary events? More than 1.6 milliseconds
Rp10
Is this fixed, configurable Configurable
Does the device support to pre-assign a RCB to a
Rp11 N
specific client in the SCL
This is incremented when DatSet is
Rp12 ConfRev value
updated.
Rp13 Is it supported to change LLN0.Mod online? N

GRL200 (Soft Z33 & Z37)


- 1491 -
6F2S1934 (0.0 )

Not applicable

What elements of a subscribed GOOSE header N source MAC address


are checked to decide the message is valid and Y destination MAC address
the allData values are accepted? If yes, describe = as configured
the conditions. Y Ethertype = 0x88B8
Note: the VLAN tag may be removed by a Y APPID = as configured
ethernet switch and should not be checked Y gocbRef = as configured
N timeAllowedtoLive
N datSet
Go1
Y goID = as configured
N t
N stNum
Y sqNum
Y test
N confRev
Y ndsCom
N numDatSetEntries
Can the test flag in the published GOOSE be
Go2 N
turned on / off
What is the behavior when the GOOSE publish If the configuration is incorrect, the
Go3
configuration is incorrect GOOSE isn’t published.
When is a subscribed GOOSE marked as lost?
(TAL = time allowed to live value from the last
Go4 Message does not arrive prior to TAL.
received GOOSE message)

What is the behavior when one or more [stNum is out-of-order, or missed]


subscribed GOOSE messages isn’t received or No fail will be detected.
syntactically incorrect (missing GOOSE)
[sqNum is out-of-order, or missed]
GOOSE subscribe quality information
will become QUESTIONABLE |
INCONSISTENT (=1100 0000 1000 0).
Go5
After receiving message with correct
sqNum order, the quality information is
set to GOOD (=0000 0000 0000 0).

You can assign the information to any


data attribute using our configuration
tool.
What is the behavior when a subscribed GOOSE Refer to Gos5
Go6
message is out-of-order
What is the behavior when a subscribed GOOSE GOOSE subscribe quality information
Go7 message is duplicated will become QUESTIONABLE |
INCONSISTENT (=1100 0000 1000 0).
Does the device subscribe to GOOSE messages Yes for both
Go8
with/without the VLAN tag?
May the GOOSE data set contain: Subscribed Published
- structured data objects (FCD)? Y Y
Go9
- timestamp data attributes? N Y
Note: data attributes (FCDA) is mandatory

GRL200 (Soft Z33 & Z37)


- 1492 -
6F2S1934 (0.0 )

Published FCD supported common data classes /


Go10 All CDC/data types can be published.
data types are
[Supported CDC]
All

[Supported data type]


Boolean
BitString
Integer
Subscribed FCD supported common data classes / Unsigned Integer
Go11
data types are
Other types
(TimeStamp, OctetString, etc) will be
ignored by IED.

(NOTE)
But each data size shall be less than 32
bits.
What is the slow retransmission time? 60 seconds with TAL = 120 seconds
Go12
Is it fixed or configurable? Fixed.
What is the minimum supported retransmission 1sec
time?
What is the maximum supported retransmission 1 – 60sec(configurable)
Go13
time?

Is it fixed or configurable? Configurable


Can the Goose publish be turned on / off by using
Go14 Y
SetGoCBValues(GoEna)
What is the fast retransmission scheme?
Go15 1sec
Is it fixed or configurable?
When expected time (TAL) spends
without GOOSE message, GOOSE
subscribe quality information will
become QUESTIONABLE (=1100 0000
0000 0).

After that, when IED receive time


exceeded GOOSE with SqNum=0,
What is the behavior when one subscribed
GOOSE subscribe quality information
Go16 GOOSE message exceeds the previous time
will become GOOD (=0000 0000 0000 0).
Allowed to Live (TAL)
When IED receive time exceeded
GOOSE with SqNum!=0, GOOSE
subscribe quality information will
become QUESTIONABLE |
INCONSISTENT (=1100 0000 1000 0)

Payload data consistency is not used to


determine if TAL is exceeded.
GOOSE subscribe quality information
What is the behavior when a subscribed GOOSE
Go17 will become QUESTIONABLE | TEST
message is “test”
(=1100 0000 0001 0).
GOOSE subscribe quality information
What is the behavior when a subscribed GOOSE
Go18 will become QUESTIONABLE |
message is “ndsCom”
INACCURATE (=1100 0000 0100 0).

GRL200 (Soft Z33 & Z37)


- 1493 -
6F2S1934 (0.0 )

This is not checked. Two GOOSEs,


which have same header (e.g.GoID) and
different dataset structure, are treated
as the same GOOSEs.

And if received GOOSEs have same


header, the fixed position of the GOOSE
dataset is read. E.g. the 1st element of
the dataset is set to read, it keeps
Go19 Dataset structure of a subscribed GOOSE
reading the 1st element even if the
dataset structure is different.

Note:
Subscribed payload data structure is
checked to determine if IED
accepts/discards the data; however the
TAL timeout is reset even when such
data is discarded.
The device starts sending GOOSE from
Go20 What is the behavior when the device starts up?
stNum=1 and sqNum=1.
Go21 Is it supported to set the “ndsCom” as TRUE? N
TAL = Time Allowed to Live

GRL200 (Soft Z33 & Z37)


- 1494 -
6F2S1934 (0.0 )

Y status-only
Y direct-with-normal-security
What control models are supported
Ct1 Y sbo-with-normal-security
(compare PICS)
Y direct-with-enhanced-security
Y sbo-with-enhanced-security
Is the control model fixed, configurable and/or
Ct2 Fixed
online changeable?
Ct3 Is TimeActivatedOperate supported N
Ct4 Is “operate-many” supported N
Will the DUT activate the control output
when the test attribute is set in the
Ct5 SelectWithValue and/or Operate request Y
(when N test procedure Ctl2 is
applicable)
What are the conditions for the time (T) attribute
Ct6 N.A.
in the SelectWithValue and/or Operate request
Ct7 Is pulse configuration supported N
What is the behaviour of the DUT when the check Both bits are checked.
conditions are set
(NOTE) The result of Opening
operation (ctval = F) is not
influenced by SynchroCheck bit.
Ct8
This behavior is fixed.

Is this behaviour fixed, configurable, online


changeable?
Y Not-supported
Y Blocked-by-switching-hierarchy
Y Select-failed
Y Invalid-position
Y Position-reached
Y Parameter-change-in-execution
N Step-limit
Y Blocked-by-Mode
N Blocked-by-process
Ct9 What additional cause diagnosis are supported
Y Blocked-by-interlocking
Y Blocked-by-synchrocheck
Y Command-already-in-execution
Y Blocked-by-health
Y 1-of-n-control
Y Abortion-by-cancel
Y Time-limit-over
Y Abortion-by-trip (only for BCPU)
Y Object-non-selected
Set orCat with unsupported value. See
How to force a “test-not-ok” respond with
Ct10 below “Which origin categories are
SelectWithValue request?
supported?” .
Send SELECT request to the control
How to force a “test-not-ok” respond with Select
Ct11 object which is not mapped to control
request?
application.

GRL200 (Soft Z33 & Z37)


- 1495 -
6F2S1934 (0.0 )

DOns, SBOns, DOes:


[Example1]
Set orCat as unsupported value
-> Cause AddCause as
“Not-supported(1)”

[Example2]
Set ctlCat same as stVal
-> Cause AddCause as
How to force a “test-not-ok” respond with Operate
Ct12 “Position-reached(5)”
request?
SBOes:
Same as above. Or,
[Example3]
Set Oper parameters as different
parameter from the parameter of
SelectWithVal
-> Cause AddCause as
“Parameter-change-in-execution (6)”
not-supported (0):N
bay-control (1):N
station-control (2):Y
remote-control (3):Y
Ct13 Which origin categories are supported? automatic-bay (4):N
automatic-station (5):Y
automatic-remote (6):Y
maintenance (7):N
process (8):N
DOns, SBOns, DOes, SBOes:
Ct14 What happens if the orCat value is not supported?
“test-not-ok” IED respond
Does the IED accept a SelectWithValue/Operate
Ct15 DOns, SBOns, DOes, SBOes: N
with the same ctlVal as the current status value?
DOns: N
SBOns: N
DOes: N
Does the IED accept a select/operate on the same SBOes: N
Ct16 control object from 2 different clients at the same
time? Note:
Commands are refused until the new
position is not reached or a timeout does
not occur.
Does the IED accept a Select/SelectWithValue SBOns: N
Ct17 from the same client when the control object is SBOes: N
already selected (tissue 334)
Is for SBOes the internal validation performed Yes for both SelectWithValue and
Ct18
during the SelectWithValue and/or Operate step? Operate
N.A.
Can a control operation be blocked by Mod=Off or
Ct19 (Only “On” and ”Test” are supported as
Blocked
Mod.)
Ct20 Does the IED support local / remote operation? Y
Does the IED send an InformationReport with
SBOns: N
Ct21 LastApplError as part of the Operate response-
DOns: N
for control with normal security?

GRL200 (Soft Z33 & Z37)


- 1496 -
6F2S1934 (0.0 )

If IED is set to test mode, IED outputs


What is the behavior of the DUT when the test control command to primary equipment
Ct22 attribute is set in the SelectWithValue and/or same as in normal mode. Otherwise IED
Operate request? rejects the request with
“Blocked-by-Mode”.
N.A.
Can a control operation be blocked by Mod=Off or
Ct23 (Only “Normal” and ”Test” are supported
Blocked
as Mod.)
Ct24 Does the IED support local / remote operation? Y
Y instance-not-available
N instance-in-use
Y access-violation
N access-not-allowed-in-current-state
N parameter-value-inappropriate
Y parameter-value-inconsistent
Ct25 What service error types are supported? N class-not-supported
Y instance-locked-by-other-client
N control-must-be-selected
Y type-conflict
Y failed-due-to-communications
N constraint failed-due-to-server –
constraint
N No Error
N Unknown
Ct26 What “Error” in LastApplError are supported?
Y Timeout Test Not OK
Y Operator Test Not OK
IED reply with LastApplError and
Write-.
Ct27 When Oper request has invalid data type data But LastApplError does not include
request parameters because IED cannot
retrieve them from Oper request.
Instance-not-available
(object-non-existent)
access-violation (object-access-denied)
ServiceError related to Control service: parameter-value-inconsistent
It is only included in Write- response. (invalid-address)
Ct28
According to table23 in part8-1, IED will send instance-locked-by-other-client
ServiceError as right in the case “Control”. (temporarily-unavailable)
type-conflict (type-inconsistent)
failed-due-to-communications
(hardware-failure)

Test flag
FALSE TRUE
IED On Accepted Rejected
Mode Test Rejected Accepted
The behavior of DUT according to the relationship
Ct29 between IED mode and Test flagged control Accepted:
request The control request is accepted by IED,
and Activate Binary Output

Rejected:
The control request is rejected by IED
with AddCause “Blocked-by-Mode”.

GRL200 (Soft Z33 & Z37)


- 1497 -
6F2S1934 (0.0 )

Select timeout
Configurable from 30 to 300sec
(default is 30 sec.)
Ct30 Select and Operate timeout value
Operate timeout
Configurable from 1 to 100sec
(default is 30 sec.)

GRL200 (Soft Z33 & Z37)


- 1498 -
6F2S1934 (0.0 )

N LeapSecondsKnown
What quality bits are supported (may be set
Tm1 N ClockFailure
by the IED)
Y ClockNotSynchronized
The quality attribute
Describe the behavior when the time
Tm2 “ClockNotSynchronized” will be set to
synchronization signal/messages are lost
TRUE.
When is the time quality bit "ClockFailure" RTC is out-of-order
Tm3
set?
It depends on the condition of
When is the time quality bit "Clock not
Tm4 synchronization. Typically from 1 to 10
synchronized” set?
minutes.
Is the timestamp of a binary event adjusted to Y
Tm5
the configured scan cycle? (More than 1.6 milliseconds)
Does the device support time zone and Yes for both.
Tm6
daylight saving?
Y Leap indicator not equal to 3?
N Mode is equal to SERVER
N OriginateTimestamp is equal to
value sent by the SNTP client as
Which attributes of the SNTP response
Tm7 Transmit Timestamp
packet are validated?
Y RX/TX timestamp fields are
checked for reasonableness
Y SNTP version 3 and/or 4
N other (describe)
What kinds of quality accuracy bits are Y Invalid
Tm8
supported? N Unspecified

GRL200 (Soft Z33 & Z37)


- 1499 -
6F2S1934 (0.0 )

What is structure of files and directories? Support tree structure

Where are the COMTRADE files stored? “/COMTRADE/” directory

(NOTE)
At root directory in IED,
Ft1 the directory “/COMTRADE/” is
hidden.
Therefore a client shall directly
access this directory.

Are comtrade files zipped and what files are Not zipped
included in each zip file?
Directory names are separated from the file name
Ft2 “/”
by
The maximum file name size including path
Ft3 64 chars
(recommended 64 chars)
Ft4 Are directory/file name case sensitive N
Maximum file size Not limited by implementation or
Ft5 configuration. It depends on available
memory.
Is the requested file path included in the MMS
Ft6 N
fileDirectory respond file name?
Is the wild char supported MMS fileDirectory
Ft7 N
request?
Is it allowed that 2 clients get a file at the same
Ft8 Y
time?
Ft9 Is the IETF FTP protocol also implemented? N

GRL200 (Soft Z33 & Z37)


- 1500 -
6F2S1934 (0.0 )

IEC61850 Tissues conformance statement (TICS)

on the IEC61850 communication interface (Ver. 0.3)

Note: The template of this document is “TISSUES Implementation Conformance


Statement for the IEC 61850 interface in G2 series IED” published by KEMA
consulting with document number “2008-v0.2”.

GRL200 (Soft Z33 & Z37)


- 1501 -
6F2S1934 (0.0 )

According to the UCA IUG QAP the tissue conformance statement is required to perform a
conformance test and is referenced on the certificate.

This document is applicable for G2 series IED with communication firmware G2M850-01
series version upper than D (G2M850-01-D).

During the October 2006 meeting IEC TC57 working group 10 decided that:
• green Tissues with the category “IntOp” are mandatory for IEC 61850 edition 1
• Tissues with the category “Ed.2” Tissues should not be implemented.

Below table gives an overview of the implemented IntOp Tissues.

GRL200 (Soft Z33 & Z37)


- 1502 -
6F2S1934 (0.0 )

116 GetNameList with empty response? Y


8-1 165 Improper Error Response for GetDataSetValues Y
183 GetNameList error handling Y
7-4 None
28 Definition of APC n.a.
54 Point def xVal, not cVal n.a.
55 Ineut = Ires ? n.a.
7-3 60 Services missing in tables Y
63 mag in CDC CMV Y
219 operTm in ACT n.a.
270 WYE and DEL rms values Y
30 control parameter T Y
31 Typo n.a.
32 Typo in syntax n.a.
35 Typo Syntax Control time n.a.
36 Syntax parameter DSet-Ref missing n.a.
37 Syntax GOOSE "T" type Y
39 Add DstAddr to GoCB Y
40 GOOSE Message “AppID” to “GoID” Y
41 GsCB “AppID” to “GsID” n.a.
42 SV timestamp: “EntryTime” to “TimeStamp" n.a.
43 Control "T" semantic Y
44 AddCause - Object not sel n.a.
45 Missing AddCauses (neg range) Y
46 Synchro check cancel n.a.
7-2
47 "." in LD Name? Y
49 BRCB TimeOfEntry (part of #453) Y
50 LNName start with number? Y
51 ARRAY [0..num] missing n.a.
52 Ambiguity GOOSE SqNum Y
53 Add DstAddr to GsCB, SV n.a.
151 Name constraint for control blocks etc. Y
166 DataRef attribute in Log n.a.
185 Logging - Integrity periode n.a.
189 SV Format n.a.
190 BRCB: EntryId and TimeOfEntry (part of #453) Y
191 BRCB: Integrity and buffering reports (part of #453) Y
234 New type CtxInt (Enums are mapped to 8 bit integer) n.a.
275 Confusing statement on GI usage (part of #453) Y
278 EntryId not valid for a server (part of #453) Y
1 Syntax Y
5 tExtensionAttributeNameEnum is restricted Y
8 SIUnit enumeration for W n.a.
6 10 Base type for bitstring usage Y
17 DAI/SDI elements syntax Y
169 Ordering of enum differs from 7-3 Y
534 Dpos Y
Note: Tissue 49, 190, 191, 275 and 278 are part of the optional tissue #453, all other
technical tissues in the table are mandatory if applicable.
Note: Editorial tissues are marked as “n.a.”.
Note: Final proposal on tissue 45 is not defined yet

GRL200 (Soft Z33 & Z37)


- 1503 -
6F2S1934 (0.0 )

After the approval of the server conformance test procedures version 2.2 the following IntOp
tissues were added or changed. It is optional to implement these tissues.

8-1 246 Control negative response (SBOns) with LastApplError N


8-1 545 Skip file directories with no files Y
7-2 333 Enabling of an incomplete GoCB n.a.
7-2 453 Combination of all reporting and logging tissues N
6 245 Attribute RptId in SCL N
6 529 Replace sev - Unknown by unknown n.a.

GOOSE, GSE, SV Addresses Y


File directory Y
8-1
GOOSE subscriber behavior Y
TimeOfEntry misspelled Y
7-4 CBOpCap and SwOpCap N
7-3 Deadband calculation of a Vector and trigger option Y
7-2 Syntax "AppID" or "GoID" Y
Missing ENUMs Y
ReportControl/OptFields N
6 Duplication of attributes N
Schema for IP Addr? N
bufOvfl in Schema? Y