You are on page 1of 16

SEL-487B

SEL-487B TỔNG QUAN

• BẢO VỆ SO LỆCH F87B


• BẢO VỆ 50BF
• BẢO VỆ DỰ PHÒNG F50
• TÍCH HỢP TỰ ĐỘNG HÓA, ĐIỀU KHIỂN
BẢO VỆ SO LỆCH F87B

BUSBAR
SƠ ĐỒ NGUYÊN LÝ

Transfer Bus
Bus 2
Bus 1

FDR1_A
SEL-487B

Relay 1
52 ••• 52 ••• 52 FDR18_A
FDR1_B
SEL-487B

Relay 2
FDR18_B
C B A C B A C B A
FDR1_C
SEL-487B

Relay 3
FDR18_C

FBT FBC FLL


IOP & IRT

I0 1 I0 2
C T1 C T2
B usbar

D iffe r e n tia l
R e la y

IO P = | I0 1 + I0 2 | IR T = | I0 1 | + | I0 2 |
XÁC ĐỊNH VÙNG SO LỆCH VÀ VÙNG HÃM

I OP
• IOP1(IRT1)=SLT1*IRT1
Operating Region

I PU Restraining
Region

I RT
NGUYÊN LÝ SO LỆCH
MỤC TIÊU CÀI ĐẶT

➤ Protect the busbars for all operating conditions

➤ Eliminate all dead zones

➤ Open the minimum number of breakers when tripping

➤ Implement the check zone without disconnect supervision,


if a check zone is required
CÀI ĐẶT ZONE

Transfer Bus
Bus 2
Bus 1

ZONE 1 = BUS 1
52 ••• 52 ••• 52 ZONE 2 = BUS 2
CHECK ZONE

C B A C B A C B A

FBT FBC FLL


CÀI ĐẶT ALIAS

SET T
IO1,FBT_F01
IO2,FTI_F02
IO3,FTI_F03
IO4,FTI_F04
IO5,FLL_F05
...
BZ1,BUS_1
BZ2,BUS_2
87Z1,Z1_TRIP
THÔNG TIN ĐẦU VÀO LỰA CHỌN ZONE

 CỰC TÍNH CT
 TERMINALS TO BUS-ZONE
 BUS-ZONE TO BUS-ZONE
CỰC TÍNH CT

B u s -Z o n e

I0 1 I0 2

S E L -4 8 7 B
P N
TERMINALS TO BUS-ZONE

BUS 1

DS1 Terminal, Bus-Zone,


SEL-487B Polarity(P,N)
? FBT_F01,BUS_1,P
I01 P

FBT_F01
BUS-ZONE TO BUS-ZONE

Bus-Zone, Bus-Zone
? BUS_1,BUS_2

SEL-487B
BUS_1 to BUS_2 Connection
(SELOGIC Equation)
••• 52
BZ1BZ2V := NA
? DS1 AND DS2
C B A

FLL
BẢO VỆ 50BF
BẢO VỆ QUÁ DÒNG DỰ PHÒNG F50

t
• 18 THÀNH PHẦN QUÁ DÒNG ĐẶC TUẾN THỜI GIAN PHỤ THUỘC
• 5 US, 5 IEC curve families
• Torque controllable
• 18 THÀNH PHẦN QUÁ DÒNG ĐẶC TUYẾN THỜI GIAN ĐỘC LẬP

Definite Time