Professional Documents
Culture Documents
Exp-8
Aim:
To study about Measurement of Insulation Resistance withstand of Motors.
• If the motor is not put into operation immediately upon arrival, it is important to protect it against
external factors like moisture, high temperature and impurities in order to avoid damage to the
insulation.
• Before the motor is put into operation after a long period of storage, it is necessary to measure the
winding insulation resistance.
Three points are worth mentioning:
o Insulation Resistance
o The minimum insulation resistance of new, cleaned or repaired windings with respect to
ground shall be 10 Megohm or more.
o The minimum insulation resistance, R, is calculated by multiplying the rated voltage Un with
the constant factor 0.5 Megohm/kV.
o Example: If the rated voltage is 690 V = 0.69 kV, the minimum insulation resistance is: 0.69
kV x 0.5 Megohm/kV = 0.35 Megaohm
o Measurement
o Minimum insulation resistance of the winding to ground is measured with 500 V DC. The
winding temperature should be 25°C ± 15°C.
o Maximum insulation resistance should be measured with 500 V DC with the windings at a
operating temperature of 80-120°C depending on the motor type and efficiency.
o Checking
o If the insulation resistance of a new, cleaned or repaired motor that has been stored for
some time is less than 10 M ohm, the reason might be that the windings are humid and
need to be dried.
o If the motor has been operating for a long period of time, the minimum insulation
resistance may drop to a critical level. As long as the measured value does not fall below
the calculated value of minimum insulation resistance, the motor can continue to run.
However, if it drops below this limit, the motor has to be stopped immediately.
o
Accessories in Installation
o Selection of Rubber Gloves
o Insulating gloves offer personal hand protection for workers against electrical shocks when
working near or on live wires, cables and electrical equipment including substation
switchgear and transformers
o Risk assessment identifies electrical shock during the jointing of cables or excavating around
live cables as a potential cause of accident which can be avoided when appropriate safety
precautions and gloves are worn
References
• IS:15652-2006, "Insulating Mats for Electrical Purposes"
• IEC 61111:2009, "Electrical Insulation Matting"
• IEC 60903: 2008, "Gloves of Insulation Material"
• NFPA 70E: 2018, "Electrical Safety in Workplace"
• IS 4770: 1991, Reaffirmed 2012, "Rubber Gloves- Electrical Purposes"
• All of the above factors are vital to consider in order to achieve the adequate level of protection
required
• Some gloves will also require an under-glove for comfort or a leather over-glove to maintain
product longevity
• All gloves must be visibly inspected after each inflation and before each use
• No tears or abrasion to the gloves prior to use, maintaining their dielectric properties
• Acid
• H-Oil
• Z-O-Zone
• R-Acid, Oil and O-Zone
• C-Very Low Temperatures