You are on page 1of 1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

A A

CENTER OF GRAVITY 5152


M30 HEX NUT
2108

B B

50
EPOXY GROUT

PROTECTIVE SLEEVE
975

C C

(1000)
A
CONCRETE FOUNDATION

4200
12500

20
D D

250

2,00

2,00
2,00

2,00

2,00

2,00
M30 STUD BAR

10340

11380

12380
12440
1440

2540

3140

5190

5690

7740

8240

9840
940

E E
60
0

F3 NOTE:
F1 F2 F4 F5 F6 F7
-Industry recommended best practice is to use a full bed epoxy grout between the bottom
L2
of the skid and top of the concrete below compressor-engine skid.
L1 L3 L4 L5 L6
4140 - Epoxy grout thickness shall be in accordance with the grout supplier recommandations.
4080 2,00 - EGS specialist should be called to perform pre-grout inspection of the unit placement
F prior grouting being performed. F
- Keep foundation free of contamination by oil, dirt, water, and so forth until the time of
EGS specialist arrival to the site for pre-grout inspection.
- Proper grouting is an extremely important step in the unit installation for proper long
term operation of the compressor package.
-If it is done incorrectly it can/will lead to vibration problems and correcting improper
grouting is an expensive and time consuming endeavor. It is highly recommended to use
an experienced grouting company, to install the grout whom will work in accordance with
G the grout manufacturer's procedures and recommandations. G

TOP VIEW/ -Foundation bolt shown for reference lenght only


-Foundation an foundation bolt design to be determined by a foundation engineer
VEDERE DE SUS
F1-F14 - COMPRESSOR UNIT FOUNDATION HOLES 36
L1-L12 - COMPRESSOR UNIT LEVELING SCREW HOLES 36
H H

0
60
L12 L11 L10 L9 L8 L7
I F14 F13 F12 F11 F10 F9 F8 I
60
0

940

2,00

2540

2,00

5190

2,00

7740

2,00

9840

2,00

11440

2,00
12440
1440

3140

5690

8240

10340

12380
J J

A(1:5)

K K
ESTIMATED WEIGHT: 50000 Kg
MIN 20 - MAX 90 mm

PRELIMINARY!
Designed by Checked by Approved by Scale Date
A1
T.H. A.P. A.P. 07.07.2020
Natural Gas Compression Unit: CI164
L
EGS
Euro Gas Systems
Project No.: 9002-0056
Name: Foundation bolt holes - 23-PK-021-A/B
Tag/Serial no.: Revision No.
PCS/Unit

1
Sheet
L

Parc Industrial / Industrial Park 1C 547551 Chirileu, Sanpaul, Mures


County, Romania Drawing No.: 0 1/1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16