MUNICIPAL CORPORATION OF GREATER MUMBAI

MUMBAI FIRE BRIGADE


BUILDING DETAILS FORM I (For Passive Fire Safety Measure)
SUBJECT: Proposed Development on plot bearing C.S. No. 1545 of Lower Parel Division, Pandurang
Budhkar Marg, G/South Ward,Worli, Mumbai.

File No. EB/4104/GS/A


Sr. Particulars Reference To be filled by MEP Remarks
No.
1 Name and address of the MEP Rohit Shetye
Consultant C 13 Suryaprakash Azad Road Vile Parle
East 400057
2 Name and address of the Firm Techno Group
of MEP Consultant 105 1a Orchid Patliputra Nagar
Oshiwara Jogeshwari West 400102
3 Tel. No. 022 26126619
4 Fax No. 022 26126620
5 Email ID rohitshetye@gmail.com
6 Registration Number
7 Under Ground Water Storage NBC 5.1.6 or D.C.R 24. 150 KL x 2 Nos.
Tank Low Rise Building – In
general U.G Tank is not
required. But may be
provided if OH tank is not
provided. It shall be
stipulated in case of special
types of building.
High Rise Building-
(24 mtrs and above)
Appendix VIII Reg 43-Table
24
8 Over Head Water Storage NBC 5.1.6 30 KL x 2 Nos.
Tank Low Rise residential building
For each staircase-10000
liters. And shall be provided
with fire services inlet to the
down comer.
High Rise residential
building( 24m to 45 m)
For each staircase – 20000
liters. And shall be provided
with the fire service inlet to
the down comer.
High rise residential building
above 70 mtrs-
Gross built up area upto
10000 sqmtrs- 30000 liters
per wing.
If the staircase are at the
remote and complied with
the travel distance as per the
NBC, then 30000 liters for
each staircase.
For Gross Built-up Area
more than 10000 sq mtrs-
30000 liters for each
staircase.
9 Whether glass façade It shall fulfill the fire safety No
proposed requirements amended NBC
3.4.9

10 PUMP Room Shall be of adequate size to 8 Mtrs x 5 Mtrs & 6 Mtrs x 6.5 Mtrs with
accommodate required dedicated staircases.
pumps, panels. Shall be
located on ground floor or
basements or in open space.
If the Pump Room is in
basement and not
accessible directly with main
entrance, then dedicated
staircase shall be provided
to the pump room from
ground floor having width of
mim.0.75 mtrs.
11 Fire Panel Boards Shall be provided ground Yes will provide at ground level in
floor at the easily accessible dedicated panel room
place.
12 Alternate source of power Residential buildings up to Both separate substation and DG set will
supply for firefighting 70 mtrs- either from separate be provided as alternate source
installation and fire lifts. sub-station or DG set.
All commercial buildings of
any height and residential
building above 70 mtrs.
From separate substation as
well as DG set.
13 Only if Bldg height is more than NBC Annex C (C-5) shall be Fire Control room provided at Ground
70 mtrs or in special building- provided on the ground floor Level
Fire Control Room. at easily accessible place.

Certified that all above parameters are incorporated in the Buildings and schematic drawings will be submitted before
commissioning of the fixed fire-fighting installations.

Signature of MEP Consultant


(Reg. No. )

Note : Each column is mandatory.