10 PUMP Room Shall be of adequate size to 8 Mtrs x 5 Mtrs & 6 Mtrs x 6.5 Mtrs with
accommodate required dedicated staircases.
pumps, panels. Shall be
located on ground floor or
basements or in open space.
If the Pump Room is in
basement and not
accessible directly with main
entrance, then dedicated
staircase shall be provided
to the pump room from
ground floor having width of
mim.0.75 mtrs.
11 Fire Panel Boards Shall be provided ground Yes will provide at ground level in
floor at the easily accessible dedicated panel room
place.
12 Alternate source of power Residential buildings up to Both separate substation and DG set will
supply for firefighting 70 mtrs- either from separate be provided as alternate source
installation and fire lifts. sub-station or DG set.
All commercial buildings of
any height and residential
building above 70 mtrs.
From separate substation as
well as DG set.
13 Only if Bldg height is more than NBC Annex C (C-5) shall be Fire Control room provided at Ground
70 mtrs or in special building- provided on the ground floor Level
Fire Control Room. at easily accessible place.
Certified that all above parameters are incorporated in the Buildings and schematic drawings will be submitted before
commissioning of the fixed fire-fighting installations.