You are on page 1of 19

Vogt Valves

The Connection Bulletin for


A Treatise on Leakage
CB 13
Flow Control Division

Vogt Valves
A Treatise On Leakage
NOMENCLATURE ABSTRACT
(Unless otherwise stated, all symbols used Laminar type leakage across leak paths
in this article are defined as follows:) occurs with such a frequency that count-
d = Internal diameter of pipe/ able “drops” of liquid or “bubbles” of gas
QL = Leakage rate of liquid across a
capillary, in inches. leakage can be observed and volume
leak path, in cubic inches per
determined. Some leak paths will leak gas
D = Internal diameter of pipe/ second at flowing conditions.
but will not leak a liquid such as water.
capillary, in feet. m = Molecular weight of gas. This paper discusses the theoretical aspects
f = Friction factor for piping. P = Pressure, in pounds per square of liquid and isothermal gas laminar flow
g = Acceleration of gravity = 32.2 foot. across theoretical capillaries. The impor-
feet per second per second or tance of surface tension, viscosity and
P‘a = Average pressure across a capil- pressure differential to flow (or leakage) of
32.2 ft./sec2. lary/pipe or leak path, in gases and liquids is theoretically present-
hL = Loss of static pressure head due pounds per square inch absolute ed. Leakage equations based on the lami-
to fluid flow, in feet of fluid. (psia). nar flow equations and utilizing a resis-
K = Resistance coefficient or velocity Re = Reynolds Number tance factor (KL) for leak paths are present-
head loss in the formula. Sg Specific gravity of gas relative to ed that can be used to compare liquid and
h = KV2/2g. air = the ratio of the molecular gas leakage across a given leak path.
KL = Resistance coefficient for leak weight of the gas to that of air. Using the theoretical equations presented
path for use in laminar flow v = Mean velocity of flow, in feet per in the paper, some general observations
equation. second. are presented that explain why air leakage
exceeds water leakage and why testing a
L = Length of pipe, in feet. DP = Differential pressure across capil- product with water may not always find
Li = Length of capillary/pipe, lary/pipe or leak path, in psi. the product that leaks in a gas service.
in inches. MU m = Absolute (dynamic) vis-
qs = Rate of liquid flow, in cubic cosity, in centipoise. ABOUT THE AUTHOR
inches per second at flowing RHO r = Weight density of fluid, Mr. Jolly is Chief Engineer of the Valve
conditions. in pounds per cubic Division at Vogt Valves. He is a registered
foot. For water = 62.4 professional engineer in the State of
q’s = Rate of gas flow, in cubic
lb/ft3. Kentucky. He holds a BS degree in
inches per second at standard Mechanical Engineering from the
conditions (14.7 psia @ 60°F). SIGMA s = Surface tension of liquid University of Kentucky and a MA degree in
Qg = Leakage rate of gas across a to air interface, in Mathematics from the University of
leak path, in cubic inches per Lb./Ft. Louisville.
second at standard conditions } = Proportional to... He is active in the American Society of
(14.7 psia @ 60°F). Mechanical Engineers (ASME), the
American Petroleum Institute (API), the
Valve Manufacturers Association (VMA),
and the Manufacturing Standardization 2
Flow Control Division

Vogt Valves
A Treatise On Leakage
Society of the Valve and Fitting Industry gases, large volumetric increases occur in explanation of leakage with an estimated
(MSS). He currently serves as President. gas flow as the pressure drops across the diameter is accurate enough as it relates to
leak path and very small leak rates are comparison of leakage given in this paper.
INTRODUCTION perceived as large because they are Very close accuracy of the volumetric leak
This article gives some practical and theo- observed as “bubbles” at atmospheric con- rates can be obtained by methods illustrat-
retical considerations that can be used in ditions (14.7 psia @ ambient temperature). ed in Figure Nos. 1A and 1B. These leak-
evaluating leakage. Laminar type leaks are Since a unit of leaking gas from a pressur- age rates can be theoretically equated to
discussed; especially, the relationship that ized product has its greatest natural vol- “drop” or “bubble” diameter by correlat-
exists between gas and liquid leakage. ume at atmospheric conditions, the leak- ing the drops or bubbles per minute to the
From the information given, a comparative age observed is in its worst case condi- volume collected over a measured length
leakage analysis can be conducted on a tion. of time.
laminar type leak path. Since a leakage Gas leakage, as used in this paper, is A theoretical review of some basics of fluid
path has no uniqueness as it relates to defined as the volume of gas that passes mechanics is required as we develop our
equipment, the concepts given in this arti- through a leak path and observed and basis for analyzing leakage. Any good
cle may be applied to leakage of valves, measured at standard conditions (14.7 text on fluid mechanics indicates that flow
pumps, tanks, pressure vessels, etc. It is not psia @ 60°F) over a measured period of through pipe and capillaries can be char-
the intention of this article to present a time. (See Figures 1A & 1B.) acterized by one of the following flow
series of theoretical equations in which modes:
exact leakage rates across a leak path can THEORETICAL
be calculated, but to present a general Turbulent: The flow stream is character-
By theoretical methods we can set up com- ized by flow particles moving randomly
method that can be used to predict or com- mon ground on which to discuss this leak-
pare gas and liquid leakage across a leak in magnitude and direction in the flow
age in drops and bubbles per unit of time stream. Turbulent flow exists for flow
path whose leak rate has been specified or and to establish the leakage rate occurring
has been established by some leakage rates in conduits in which the Reynolds
across a leakage path. Since the volume of Number, Re > 4000. Turbulent flow is
method. a “drop of liquid” or a “bubble of gas” the most common flow mode and nor-
can be calculated, based on the assump-
DEFINITION tion that they are spherical in nature, and
mally occurs in piping systems designed
Leakage as used in this article is defined to move fluids.
time can be measured, leakage rates can
as flow per unit of time. Specifically, the Laminar: Sometimes known as streamline
be calculated. Table 1 gives the volume
leakage to be addressed is that type of flow because particles of fluid move
and leakage rates for various bubble or
flow that emanates from a leak path in a along the conduit in straight, parallel
drop diameters when developing at vari-
pressurized product that produces count- laminar layers. Laminar flow exists for
ous intervals of time.
able and/or measurable “drops” of liquid flow rates in conduits in which the Rey-
or “bubbles” of gas (when tested under From a practical standpoint, the diameter nolds Number, Re˜ 2000. Laminar flow
water) over a measured period of time. of a “drop” or “bubble” observed by an may occur in piping systems that move
inspector (tester), operator or maintenance highly viscous fluids at low velocities.
Volumetric changes to liquids do not man of a piece of equipment is not known
appreciably change as they flow from a and really not important to the analysis Transition: The flow stream is unpre-
pressurized product through a leak path to presented herein. The usually mentioned dictable in that either laminar or turbu-
the atmosphere. Due to compressibility of “drops/minute” or “bubbles/minute” lent modes may exist. Transition flow
3
Flow Control Division

Vogt Valves
A Treatise On Leakage
occurs in a Reynolds Number Range of Some well known general equations* for Laminar Flow – Equation #3
2000 - 4000. flow through pipe or capillaries for the
It can be shown that the leakage rate Turbulent and Laminar Flow Modes
ranges that are addressed in Table 1 described above are needed to develop a
(countable drops or bubbles) include leaks theoretical position on leakage.
that are in the Laminar Flow Range. This Turbulent Flow – Equation #1 For laminar flow across a pipe or capil-
can be done by a comparison analysis of lary, Equation #3 indicates the friction fac-
flow rates across theoretical capillaries, tor is replaced by a function of the
that have fixed dimensions and can be the- Reynolds Number.
oretically analyzed, to those in Table 1 Equation #3 can be refined to specifically
and showing that such flow rates have From the above equation, it can be noted cover liquid and gas flow in the Laminar
Reynolds numbers in the laminar flow that pipe or capillary friction have an influ- Flow Mode across pipe or capillaries, as
region. Unlike capillaries, leak paths can- ence on head or pressure loss during flow. follows:
not be described by exact dimensions. Turbulent Flow – Equation #2 Liquid Flow
Their dimensions and geometries are gen- Laminar Flow – Equation #3A
erally unknown. Even the flow direction
and cross-section may vary across the leak
path. There are no pure theoretical equa-
tions available to calculate flow rates This equation is equal to Equation #1
across leak paths. Empirical methods must except that the (fL/D) term has been
be used to show that the flow across a Gas Flow
replaced by K. K is a resistance coefficient Laminar Flow – Equation #3B
leak path is laminar. Modified theoretical that can be experimentally determined for
equations may be used to predict the leak- products such as valves, fittings, strainers,
age rate across leak paths that have been filters, etc. Once determined, this “K” fac-
experimentally evaluated. The treatment of tor can be used in Equation #2, or deriva-
flow through valves and other similar prod- tions thereof, to determine head loss (or
ucts, in the turbulent flow mode, and the Since the Reynolds Number is important to
pressure drop) for any fluid flow rate when leak rate analysis, the general equations
modification of theoretical flow equation to the flow rate is in the turbulent flow mode
include a flow resistance factor (K) will be for Reynolds Number are given as follows:
(Re˜ 4000). The equation, or derivation
used to support the use of a resistance fac- thereof, could also be used to apply the Reynolds Number – Equation #4
tor (KL) for laminar leak paths. Since the leakage rates across large leak paths
leak rates addressed in Table 1 parallel where leakage rates are in the turbulent
laminar flow across capillaries, the KL mode. Leak rates in the turbulent mode,
resistance factor for leaks will be applied however, are expected to greatly exceed
to the theoretical laminar flow equations. those of countable “drops” and “bubbles”
listed in Table 1. The equation is used here
because a parallelism of applying a simi-
lar resistance coefficient (KL) to leak paths
in the laminar flow mode is suggested. 4
*(See Appendix #1 for background of equations.)
Flow Control Division

Vogt Valves
A Treatise On Leakage
or, Liquid Flow – Equation #4A The Reynolds Number for this flow rate tions leads to the first obvious conclusion:
can be calculated from Equation #4A, as The flow of air @ 60°F versus that of
follows: water @ 60°F across the same capillary
at the same pressure drop is greatly
different. In fact, Equations 3A and 3B
or, Gas Flow – Equation #4B can be equated to show that 60°F water
Since Re = 87 is less than 2000, the flow flow across the same capillary at an
is laminar. equal pressure drop can be generalized
as follows:
From Equation #3B, we can calculate the
The above equations shall be used in flow flow rate of air at 100 psig @ 50°F across Air/Water Flow Comparison –
calculations of capillaries to show that the the same .002” diameter capillary, 1” Equation #5
flow rates noted in Table 1 lead to long, as follows:
Reynolds Numbers in the Laminar Flow
Range.
This equation indicates air flow mea-
The viscosity of the flowing fluid is also
sured in bubbles passing through a cap-
important in laminar flow analysis. Tables
illary would be 245 times greater than
2, 3, and 4 list viscosities of many com-
water in equivalent size drops passing
mon liquids and gases.
through the same capillary when both
are at a pressure of 100 psig. The dif-
Example #1 –
ference between air and water flow
Water/Air Flow Comparison: across a capillary becomes even greater
which greatly exceeds any of the bubble
From equation #3A, we can calculate the rates noted in Table 1. In fact, the bubble as the pressure drop and average pres-
flow rate of water at 100 psig @ 60°F rate of this leak would not be countable, sure increase.
across a .002” diameter capillary, 1” forming the equivalent of 3448 - 1/8”
long, as follows: bubbles per minute. Example #2 –
Air/Water Flow Comparison:
The Reynolds Number for this flow rate To make a further comparison of air/water
can be calculated from Equation #4B, as flow, the flow across a 1” long capillary
follows: that is flowing 500 psig air @ 60°F at 8.5
x 10-5 standard cubic inch/second (or 1 -
1/8” dia. bubble every 12 secs. – See
Table 1) is compared with water flow at
the same conditions. What is the likelihood
that this capillary would flow water?
which is the equivalent of approximately This calculation requires the arrangement
16 drops per minute (1/8” Dia. —See which is less than 2000 and is in the lami- of Equation #3B to read as follows:
Table 1) from the capillary. nar range. Comparison of the two calcula-
5
Flow Control Division

Vogt Valves
A Treatise On Leakage
Surface Tension – Capillary Flow:
It has been suggested that surface tension
may be the reason for the tremendous dif-
ference in air flow versus water flow
From this equation, the diameter of the across capillaries. Surface tension of water For surface tension to play a significant
capillary that will permit air flow at the flow through a capillary with a round flow role in the flow of 60°F water at high pres-
above rate can be calculated, as follows: cross-section venting to the atmosphere can sure across a capillary, the diameter of the
be calculated by use of the following gen- capillary needs to be in the 1 x 10-6 inch
eral formula: range, as illustrated by the following calcu-
Surface Tension – Equation #6 lation:

Now that the diameter that will flow this


This formula clearly indicates as the diame-
small volume of air has been calculated,
ter of the capillary decreases, the pressure
calculate the volume of water at the same
to overcome the surface tension increases.
conditions (500 psig @ 60°F) that will flow
If the pressure drop across the capillary is
across the same capillary:
greater than the surface tension, flow is
From Equation #3A: expected to take place. Note that the This calculation indicates that a pressure
length of the capillary would not affect this drop of 1680 psig would be required just
calculation, only the diameter of the capil- to overcome the effects of surface tension.
lary in which the liquid is flowing. The sur-
face tension o for a number of liquids is Laminar Flow Range/Capillaries:
shown in Table 5. Equation #6 can be
It can be established that the leak rates
applied to water flow for the capillary in
illustrated in Table #1 for 60°F water are
Example #2 above, as follows:
in the Laminar Flow Range as long as the
This calculation indicates that 9.38 PSI is following ratio calculated from Equation
required to overcome the surface tension in #4A for Re 2000 is satisfied:
At this low flow, it would require 3.69 the 1.79 x 10-4 “ capillary. For pressure
hours for the equivalent of 1 drop (1/8” Flow/Capillary Diameter Ratio (Water) –
drops less than 9.38 psi, surface tension
dia.) of water to pass through the capil- Equation #4C
would not allow water flow to occur. For
lary. From a practical standpoint, this high pressure drops, it can be concluded
water flow would never be detected by that the main reason that water flow is
visual means. One (1) bubble of air flow retarded across the 1.79 x 10-4” capillary
every 12 seconds is expected to be visual- Likewise, Equation #4B can be used to
more so than air is because of the high vis-
ly detectable and illustrates the advantage show that the leak rates illustrated in Table
cosity of water relative to air and not
of using air as a test medium in lieu of #1 for 60°F air are in the Laminar Flow
because of surface tension. Surface tension
water. Range, as long as the following ratio is
would not stop a flow of water at 500 psig
satisfied:
as the above calculation indicates. 6
Flow Control Division

Vogt Valves
A Treatise On Leakage
Flow Capillary Diameter Ratio (Air) – But unlike capillaries, leak paths do not
Equation #4D have any easy ratio like Equation #4C and
#4D to verify if laminar flow exists since a
Reynolds Number calculation is impossible
with a variable d dimension. Another
As long as the above ratios are met, 60°F method must be used to determine if lami-
water and air flow in capillaries are in the nar flow exists across leak paths.
laminar flow mode. If the ratios are As was done with Equations #1 and #2, or
exceeded, the flow mode will be in the those variables in Equations #3A and #3B,
transition or turbulent flow modes. characteristic of the leak path, can be com-
bined into a leak path resistance factor. By
Leakage Mechanics: doing so, some common equations evolve
that offer some hope of calculating or com- where Qg and m g have been subscripted
Moving away from theoretical analysis of to denote gas leakage and leaking gas vis-
capillary flow but making a modification of paring leakage of gas and liquids across a
leak path. cosity, respectively.
those equations to apply to leak paths
seems logical. From Equation #3A for liquid flow across Equation #8 indicates gas leakage to be a
a capillary, the equation is modified for function of the product of pressure drop
Since leak paths, areas, geometries, flow (DP) and average pressure (P’a) across the
cross-sections and diameters vary, the lami- leakage as follows:
leak path and inversely proportional to vis-
nar flow equations for capillary flow can- cosity (m g).
not be used to calculate leakage. The mod-
ification of Equation #1 to Equation #2 To determine if laminar flow exists across a
typically for valves for turbulent flow, sug- leak path for gas leakage, a plot of experi-
gests that a similar approach for flow mentally determined leak rate (y axis) ver-
across laminar flow leak paths can be sus pressure drop (x axis) on log/log
used. The experimentally determined resis- graph paper would suggest that laminar
tance factor (K) for valves with varying flow exists if the slope of the curve equals
flow path geometries and characteristics to 2. This can be equated from Equation
paralleling what might be expected in leak #8 which indicates laminar flow gas leak
paths has been used for many years of where QL and m L have been subscripted to rate is proportional to DP2, which is equiv-
determination of flow and/or pressure denote liquid leakage and leaking liquid alent to the (DP • P’a) factor. A logarithmic
drop for valves. viscosity, respectively. conversion of the equation would show
Equation #7 indicates that liquid leakage that the slope of 2 could be expected.
In general, leakage rates in the following Likewise for liquid leakage, Equation #7
range are expected to represent Laminar across a leak path is directly proportional
to the pressure drop (DP) and inversely would indicate that a leak rate/pressure
Type leaks: drop plot on log/log graph paper would
proportional to the viscosity (m L).
have a slope of 1.
Similarly, Equation #3B for gas flow across
a capillary, can be modified, as follows: Equations #7 and #8 suggest that if a
leakage rate for a leak path can be deter-
7
Flow Control Division

Vogt Valves
A Treatise On Leakage
mined for a liquid or gas having a known is probably greater than capillaries
viscosity and pressure drop, a resistance because many leak paths have a slit cross-
factor (KL) can be determined for the leak section. The pressure to overcome surface
path. This KL factor can be used in tension can be 2 - 3 times greater for leak
Equations #7 or #8 to predict or compare Not readily evident by this equation is that paths that have a slit cross-section than a
the leakage across the same leak path at the leakage of air across a given leak path capillary with its round cross-section.
different pressure drops, or for a different is several orders of magnitude greater than The comparative pressure to overcome sur-
type liquid and/or gas. Clearly viscosity of water because of its lower viscosity and face tension in a slit leak path versus a
the leaking fluid is the principal factor to expansion characteristic. As an example, capillary with the same cross-sectional
be considered when comparing leakage the comparative leakage of 1000 psig air area can be equated as follows:
rates. A comparison of gas to liquid leak- @ 60°F versus 1000 psig water @ 60°F
age across the same leak path can be across the same leakage path can be cal- Equation #10
equated from Equations #7 and #8, as fol- culated from Equation #9A, as follows:
lows:
where Pc = Surface Tension Pressure
(Capillary)
Ps = Surface Tension Pressure
(Slit)
R = Ratio of Length/Width of Slit
Some information suggests that no visible
or Comparative Gas/Liquid Leakage – meaning that air would leak at a rate of water leak when dry air at the same pres-
Equation #9 2166 times greater than water at the stat- sure will leak at the rate of 1.00 x 10-4
ed conditions. in3/sec. probably due to surface tension.
Equation #9 also indicates that a 46 psig As the above calculations on capillaries
air test would be just as effective as a indicate, it may not be due to surface ten-
6000 psig water test in determining leak- sion but more so due to the viscosity of
where P’a is average absolute pressure age across the same leak path calculated water.
across the gas leak path and DPg and DPL as follows: Vogt’s own testing has discovered leaks
have been subscripted to denote pressure that leak during high pressure (500 psig
drop across the gas leak path and liquid and 2000 psig) air testing in the 1.7 x 10 -
leak path, respectively. 2 to 7.4 x 10-2 standard in3/sec. but will

For the special case where the pressure not pass water in any reasonable time
drop across the leak path for gas and liq- meaning that 46 psig air would leak at the period. These leaks, once tested with
uid is equal, Equation #9 can be further same rate as 6000 psig water across the water, become plugged, probably due to
simplified, as follows: same leak path. surface tension or capillary action, and
Comparative Gas/Liquid Leakage – will not leak air until the water is driven
Equation #9A
Surface Tension/Leak Paths from the leak path by a high temperature
The effect of surface tension on leak paths 8
Flow Control Division

Vogt Valves
A Treatise On Leakage
furnace soak. This points up a disadvan- volumetric leaks expressed in weight flow operating pressure or at maximum pressure
tage to testing with water prior to testing terms would not be very impressive, as fol- differential (DP) the product is expected to
with air. Small leaks may become clogged lows: see. This will increase sensitivity and locate
with water and not leak on air test. leaks that have leak paths enhanced by
Typical Time for Time for pressure. For leak paths that are not
There is another gas leak flow method that Volumetric 1 Pound 1 Pound
is not addressed in this paper. This gas Leak* Air to Leak Water to Leak enhanced or physically affected by pres-
flow is known as Molecular Flow. sure, a low pressure gas test may be more
1 x 10-6 scis 677 Years 9.9 Months
Molecular flow across a leak path occurs -3
sensitive than a high pressure liquid test.
1 x 10 scis 8.4 Months 7.27 Hours (Ref. Equation #9.)
by individual molecules and can be detect-
ed only by sophisticated electronic leak *See Table 1 for typical drops/bubble frequency. If a product cannot be leak tested at oper-
detection equipment such as a helium mass Leak paths that have pressure induced ating pressure, consideration should be
spectrometer. Such a small leak would be characteristics will not follow the rules of given to testing with a low pressure gas to
so small that “bubble” formation would not laminar flow leakage. Some leak paths determine small leaks that will not pass a
occur. Molecular flow is proportional to the may act as check valves at low test pres- test fluid such as water.
DP across the leak path and inversely pro- sures and open up at high pressure, per- Vogt has recognized the value of high
portional to the square root of the leaking mitting leakage. Other type leak paths pressure gas testing and have their own in-
gas molecular weight, as follows: may clean themselves during pressurization house supplemental high pressure gas test
and/or become enlarged as a result of procedure used for valves that go in criti-
pressurization. Such leak paths when plot- cal service or where a history of leakage
ted on graph paper will show a disparity has occurred in valves that have historical-
The perception that the molecular weight to the laminar flow plot. ly passed the Industry Standard test.
(m) of a gas is the property most influenc-
ing leakage across a leak path applies to Pressure induced distortions of leak path Leak detection is time sensitive. Leaks that
molecular leakage flow. As Equation #8 geometry may throw off correlation of leak may rapidly be detectable during gas test-
indicates, the critical gas property that has rates based on Equations #7 and #8. ing may not have time to develop when
the greatest influence on laminar leakage Application of Equation #9A would show testing with a liquid such as water.
is the gas’s viscosity. For visible “bubble” the big advantage of testing products with Most valve industry standards require test-
type leakage, viscosity is the gas property gas. Because of the low viscosity of gases ing with water and/or air. The high pres-
that we must evaluate. Molecular type leak- versus liquids and because a leaking gas sure shell testing is limited to water, or a
age could be the subject of another paper. reveals itself a t its greatest volume, gases fluid having a viscosity equal to or less
are superior to liquids in leak detection than water. The closure testing of gate
GENERAL OBSERVATIONS: work. The big disadvantage to using high valves requires an 80 – 100 psig air test.
The equations given in this paper generally pressure gas for testing is the increased Review of Tables #2 and #3 would indi-
apply to leak paths whose characteristics danger of testing and is the primary rea- cate that water and air are very good
are not affected by pressure. The physical son gas test pressures above 100 psig are choices as test fluids because of their vis-
dimensions of the leak path remain fixed seldom specified or used in production test- cosity. Few liquids have a lower viscosity
and unaffected by pressure. Leaks are also ing. than water. Those that do would have eco-
equated on a volumetric basis. Equations #7 and #8 indicate that liquid nomical and safety constraints limiting their
It may be interesting to note that visible or gas pressure testing should be at the use. Air is an economical choice, as well.
9
Flow Control Division

Vogt Valves
A Treatise On Leakage
Kerosene has also been used for many
years as a testing medium because of its
lubricating quality. A review of Equation INLET WATER Figure 1A
#7 and viscosity Table 2 indicates that a TEST PRESSURE

leak path would leak twice as much water


as kerosene in a given period of time.
Table 5 would indicate a preference for
kerosene over water if surface tension is
considered.
Surface tension pressure (Equation #6) is a
measure of a flow or leak path capillarity.
The higher the surface tension pressure, the
greater the leak path capability to draw in
water and plug itself. Once plugged with
water, a gas such as air is not expected to
pass through the leak path unless it
exceeds the surface tension pressure. Air
testing when used to determine very small
leaks should precede water testing.
LEAKAGE OF
As noted from Table 3, the viscosities of WATER DROPS

several gases normally used in testing –


air, nitrogen, and helium – are very simi-
lar. Therefore, a change in test gas will not
markedly improve the sensitivity of leak
detection using gas-under-water techniques. GRADUATED
BEAKER
50
Vogt valves are tested to meet industry
standards MSS-SP-61 and/or API-598.
40
Both these specs require high pressure test-
ing of the shell. Normally water is used as 30
NOTE: In this illustration a gate valve
the test fluid for safety reasons. Both these under a high pressure water
standards give a good test, yet if a valve 20 seat test (typically 1.1 x 100°F
goes into a high pressure dry gas or steam rating of valve using water) has
a gate leak. The leak can be
service, the valve could still have a small 10 VOLUMETRIC MEASUREMENT
OF LEAK (WATER) collected in a graduated
leak not detectable during the water test- beaker over a measured period
of time and the leak rate can
ing. The perception of the user is that the be calculated as follows:
valve was not tested, but in reality, the
Leak Rate = Collected Liquid Leakage
lower viscosity of gases (Table 3) and Time to Collect Leakage
steam (Table 4) pass through a leak path
10
Flow Control Division

Vogt Valves
A Treatise On Leakage
much more rapidly than water, as project-
ed by Equations #9 or #9A.
The two (2) industry standards noted
10 Figure 1B
GRADUATED VOLUMETRIC MEASUREMENT
above require that products be shell tested BEAKER 20 OF LEAK (AIR)

with water at a pressure 1.5 times the 30 WATER FILLED


I00°F valve rating. In addition to leak tight- TANK

ness, this test would also verify the structur- 40


WATER LEVEL
al integrity of the product. Safety consider- 50
ations do not permit the testing of many of
these valves with a gas test to the 1.5 x LEAKAGE OF
I00°F valve rating requirement. AIR DROPS

A review of Table 2 would indicate which


liquids leak the greatest as predicted by
Equation #7. The smaller the viscosity of a
liquid, the greater the leakage. A typical
comparison would indicate that ammonia
liquid would leak at a rate approximately
ten (10) times greater than water.
A review of Tables 3 and 4 and Equation
#8 indicates which gases and vapors leak
the greatest as predicted by Equation #8.
The smaller the viscosity of a gas, the INLET AIR
greater the leakage. A typical comparison TEST PRESSURE

would indicate that hydrogen gas would


leak at a rate approximately twice as great
as air.
A review of Tables 2, 3, and 4 and
Equation #9A indicates that most all
gases, including steam, leak at a greater
rate than water. NOTE: In this illustration a gate valve under a low pressure gas-under-water seat test (typically 100 psig air)
has agate leak, To collect the leak, the graduated beaker is initially filled with water and beaker
Because the viscosity of liquids decreases inlet is kept below the surface of the water of the tank. The bubbles of leakage are collected in the
with increasing temperature, a product that beaker which displaces the water, as illustrated. The displaced water represents the volume of the
gas leakage. The pressure of the collected gas is basically at 14.7 psia or atmospheric pressure.
has been tested with water at ambient The leak is collected over a measured period of time and the leak rate can be calculated as follows:
temperature may leak if placed in similar
Leak Rate = Collected Volume of Gas (Std. Conditions)
service at a higher temperature. Example: Time to Collect Gas Leakage
A valve tested with 78°F water and placed
in saturated water service may leak due to
the difference in viscosity. Reference: 11
Flow Control Division

Vogt Valves
A Treatise On Leakage
Equation #7 and viscosity Table 2. (Refer to Equation #8.) It is generally believed leak paths that leak
The viscosity of gas and vapors, including Increasing the water test DP across a leak air at a rate less than 1 x 10-5 SCIS will
steam, increase with increasing tempera- path by a factor of 5 (500 psig to 2500 not pass water. Vogt’s testing confirms this
ture and, therefore, their tendency to leak psig), unlike gas testing, only increases the but we have also experienced much larger
decreases with increasing temperature. liquid leakage by a factor of 5. (Refer to leaks of air that will not pass water over
Equation #7.) any reasonable period of time.
Increasing the gas test DP across a leak
path by a factor of 5 (100 psig to 500 If a detected gas leak is in the laminar Vogt has recorded water leaks at 2 cc/hr.
psig) will increase the leakage rate by a flow range, extrapolation to higher internal (3.4 x 10-5 In.3/Sec.) during extended test
factor of 25. Increasing the pressure pressures using the relationship Qg } DP2 periods. Water leaks smaller than this are
across the leak path is the simplest method may be carried out. seldom ever observed and/or recorded,
to improve leakage detection sensitivity. indicating that such a water leak is at the
threshold of delectability or occurrence.
TABLE 1
Leak Rate (SCIS) (2) (3)
Size Volume (1)
(Spherical) Drop/Bubble Drops/Bubbles per Minute
Drop or Bubble
Diameter In3 4 5 6 8 10 16 20 25 32 50 64
1.06 x 1.33 x 1.59 x 2.13 x 2.66 x 4.26 x 5.33 x 6.65x 8.52 x 1.33 x 1.70 x
1/32” 1.598 x 10-5 10-6 10-6 10-6 10-6 10-6 10-6 10-6 10-6 10-6 10-5 10-5
8.52 x 1.06 x 1.28 x 1.70 x 2.12 x 3.41 x 4.24 x 5.30 x 6.82 x 1.06 x 13.64 x
1/16” 1.278 x 10-4 10-6 10-5 10-5 10-5 10-5 10-5 10-5 10-5 10-5 10-4 10-4
2.88 x 3.60 x 4.32 x 5.76 x 7.20 x 1.15 x 1.44 x 1.80 x 2.30 x 3.60 x 4.60 x
3/32” 4.314 x 10-4 10-5 10-5 10-5 10-5 10-5 10-4 10-4 10-4 10-4 10-4 10-4
6.82 x 8.52 x 1.02 x 1.36 x 1.71 x 2.73 x 3.42 x 4.26 x 5.45 x 8.52 x 1.09 x
1/8” 1.023 x 10-3 10-5 10-5 10-4 10-4 10-4 10-4 10-4 10-4 10-4 10-4 10-3
1.33 x 1.66 x 2.00 x 2.66 x 3.33 x 5.32 x 6.66 x 8.30 x 1.06 x 1.66 x 2.12 x
5/32” 1.997 x 10-3 10-4 10-4 10-4 10-4 10-4 10-4 10-4 10-4 10-3 10-3 10-3
2.30 x 2.88 x 3.45 x 4.6 x 5.75 x 9.2 x 1.15 x 1.44 x 1.84 x 2.88 x 3.68 x
3/16” 3.451 x 10-3 10-4 10-4 10-4 10-4 10-4 10--4 10-3 10-3 10-3 10-3 10-3

1) Volume of drop or bubble = p/6 (diameter)3


2) SCIS - Standard Cubic Inch per Second Leakage.

3) Standard in SCIS refers to the collection of bubbles in gas-under-water type tests in which the visible bubble is observed or collected at standard
conditions - 14.7 psia @ 60°F. 12
Since the volume of a leaking liquid does not change across a leak path, the leak rates noted above are equal to cubic inches/sec. when
referring to liquid leakage rates.
Flow Control Division

Vogt Valves
A Treatise On Leakage
TABLE 2
VISCOSITY OF LIQUIDS
(At Atmospheric Pressure - In Centipoise)
Viscosity Viscosity Viscosity
Liquid Centipoise Temp. Liquid Centipoise Temp. Liquid Centipoise Temp.
Acetic Acid 1.04 86°F Ethane .05 60°F Propane .15 60°F
Alcohol-Allyl 1.17 86°F Ethyl Bromide .37 86°F Propionic Acid .96 86°F
Alcohol-Ethyl 1.20 86°F Ethyl Ether .22 86°F Propyl Alcohol 1.78 86°F
Alcohol-Isopropyl 2.00 80°F Ethylene Bromide 1.48 86°F RP-1 Fuel 1.17 100°F
Alcohol-Methyl .60 86°F Ethylene Chloride .74 86°F SAE 10 Lube Oil 2.00 60°F
Ammonia .10 80°F Ethylene Glycol 19.90 68°F SAE 30 Lube Oil 450.00 60°F
Benzene .65 70°F Formic Acid 1.46 86°F Sodium Hydroxide (20%) 3.50 80°F
.50 100°F Freon 11 .42 80°F Sulfuric Acid (20%) 1.30 80°F
Benzol .57 86°F Freon 12 .26 80°F Toluene .52 86°F
Brine, CaCl (20% Salt) 2.30 70°F Freon 113 .65 80°F Tupentine 1.27 86°F
1.30 100°F Freon 114 .37 80°F Water 1.80 32°F
Brine, NaCl (20% Salt) 2.00 70°F Gasoline (SIG. 0.68) .28 70°F 1.55 40°F
1.40 100°F Glycerol 207.00 68°F 1.31 50°F
Bromide .91 86°F Glycerine 830.00 68.54°F 1.13 60°F
Butane .18 60°F Heptane .38 86°F .98 70°F
Butyric Acid 1.30 86°F Hexane .30 86°F .86 80°F
Carbon Disulfide .35 86°F Hydrazine .90 77°F .80 86°F
Carbon Tetrachloride .97 70°F Kerosene 2.10 60°F .68 100°F
.74 100°F 1.90 77°F .56 120°F
.85 86°F Linseed Oil 3.10 86°F .43 150°F
Chlorine Trifluoride .41 77°F Mercury 1.50 80°F .31 200°F
Chloroform .52 86°F Methyl Chloride .25 80°F .28* 212°F
Dowtherm A 2.60 100°F Methyl Iodine .46 86°F .19* 300°F
Dowtherm A .38 400°F Nitrogen Tetraoxide .34 100°F .14* 400°F
Dowtherm E 1.05 100°F Oxtane .48 86°F .095* 500°F
Dowtherm E .27 400°F Pentame .22 86°F .065* 600°F
NOTES: 1. The viscosity of liquids decreases with increasing temperatures.
2. The viscosity of liquids is negligently affected by pressure expect at extremely high pressures. 13
*At Saturated Pressure.
Flow Control Division

A Treatise On Leakage Vogt Valves

TABLE 3
VISCOSITY OF GASES & VAPORS
(At Atmospheric Pressure – In Centipoise)
Viscosity Viscosity
Gas/Vapor Centipoise Temp. Gas/Vapor Centipoise Temp. VISCOSITY OF AIR
Acetylene .010 70°F Freon 11 .010 70°F (At Atmospheric Pressure –
Ammonia .010 70°F Freon 12 .013 70°F
In Centipoise)
Argon .021 32°F Freon 113 .013 80°F Viscosity
Benzene .009 177°F Freon 114 .015 80°F Temp. Centipoise
Butane .008 70°F Helium .020 70°F 0°F .016
Carbon Dioxide .015 70°F Hydrogen .009 70°F 40°F .017
Carbon Monoxide .014 70°F Hydrogen Chloride .014 32°F 60°F .018
Chlorine .013 70°F Hydrogen Sulfide .012 32°F 100°F .019
Chloroform .011 143°F Methane .011 70°F
120°F .020
Dowtherm A .0092 400°F Neon .030 32°F
Dowtherm E .0012 400°F Nitrogen .018 70°F NOTE: The viscosity of gases
increases with increasing
Ethane .010 70°F Propane .008 32°F temperature and are
negligently affected by
Ethylene .010 70°F Oxygen .020 70°F
pressure except at
Sulfur Dioxide .013 70°F extremely high pressures.
Water Vapor .013 212°F

VISCOSITY OF SUPERHEATED STEAM


TABLE 4 VISCOSITY OF SATURATED STEAM (In Centipoise)
(In Centipoise) Pressure Viscosity
Pressure Viscosity PSIG Temp. Centipoise
PSIG Temp. Centipoise 100 800°F .025
100 1000°F .028
0 212°F .014
400 800°F .027
100 338°F .017 400 1000°F .030
400 448°F .021 600 800°F .028
600 488°F .024 600 1000°F .031
800 800°F .029
800 520°F .027
800 1000°F .032
1200 569°F .032 1200 800°F .032
NOTE: Viscosity of Saturated Steam increases with 1200 1000°F .034
increasing pressure and temperature.
NOTE: Viscosity of Superheated Steam at pres- 14
sure less than 800 psig increases with
increased superheat.
Flow Control Division

Vogt Valves
A Treatise On Leakage
TABLE 5
SURFACE TENSION OF LIQUIDS IN CONTACT WITH AIR
(At 1 Atmosphere Pressure In Lb/Ft)
Surface Tension
(In. Air)
Liquid Temp. Lb/Ft
Alcohol, Ethyl 68°F .00153 REFERENCES
Benzene 68°F .00198
1. BURMEISTER, Louis C., LOSER, John B. and SNEE-
Carbon Tetrachloride 68°F .00183 GAS, Eldon C., Advanced Valve Technology,
Crude Oil 68°F .00200 National Aeronautics and Space Administration
Dowtherm A 68°F .00275
(NASA) Publication SP 5019, 1967, Chapter 2.
Dowtherm E 68°F .00254 2. DODGE, Russell A. and THOMPSON, Milton J.,
Fluid Mechanics, McGraw-Hill, 1937.
Gasoline (SG = 0.68)* 68°F .0013 - .0016
3. DOW CHEMICAL Company, “Dowtherm
Glycerin 68°F .00435
Handbook”, Midland, Michigan, 1971, Pages 12,
Hexane 68°F .00126 18, 19, 85, and 86.
Kerosene (SG = 0.907)* 68°F .00260
4. FOX, Robert W., & McDONALD, Alan T.,
Mercury 68°F .03280 Introduction to Fluid Mechanics, 2nd Edition, John
Octane 68°F .00149 Wiley & Sons, 1978.
Oil, Machine (SG = 0.907)* 68°F .00260 5. “Flow of Fluids Through Valves, Fillings, and Pipe”,
SAE 10 Oil 68°F .00240 Technical Paper No. 410, Crane Company, 1957.
SAE 30 Oil 68°F .00500 6. GILES, Ronald V., Fluid Mechanics & Hydraulics,
Salt Water 68°F .00504
2nd Edition, Schaum’s Outline Series, McGraw-Hill,
1962.
Water 32°F .00518
7. JOHN, James E. A., and HABERMAN, William L.,
40°F .00514 Introduction to Fluid Mechanics, 2nd Edition,
50°F .00508 Prentice-Hall, Inc., 1980.
60°F .00504 8. MARR, Dr. J. W., “Leak Detection and Measurement,
70°F .00497 Appendix D, Studies of Special Topics in Sealing,
NASA Document N63-19498, 1963.
80°F .00492
9. SHAMES, Irving H., Mechanics of Fluids, 2nd
100°F .00479
Edition, McGraw-Hill Book Co., 1982.
120°F .00466
NOTE: Surface tension decreases slightly with increasing temperatures.
*SG,= Specific Gravity 15
Flow Control Division

Vogt Valves
A Treatise On Leakage
APPENDIX #1 #1. Darcy Equation Equation #3B is derived for laminar gas
Source of Equations in Paper (Head Loss thru Straight Pipe – flow across straight pipe, starting with the
Turbulent Flow) following equation and assumptions:
NOMENCLATURE
(The following symbols are used in this Simplified Compressible Flow –
appendix only. For other nomenclature, see Gas Pipeline Flow
inside front cover.)
#2. Modified Darcy Equation
A = Cross sectional are of
(Head Loss thru Valves –
pipe/capillary, in square feet
Turbulent Flow)
P’1 & P’2 = Inlet/Outlet pressure, in
pounds per square inch
absolute. 1. Isothermal Flow exists
Ps = Surface Tension Pressure for 2. No mechanical work is done on or by
slit flow path, in pounds per #3. Darcy Equation – Laminar Flow the system.
square foot. (Head Loss thru Straight Pipe or 3. Steady flow exists.
Pc = Surface Tension Pressure for Capillaries – Laminar Liquid Flow.)
4. The flowing gas obeys the gas laws.
Capillary, in pounds per
square foot. 5. The velocity may be represented by the
average velocity of a cross-section.
q1 = Rate of Flow, in cubic feet
per second at inlet 6. The friction factor is represented by
conditions. 64/Re since laminar flow exists.
q2 = Rate of Flow, in cubic feet 7. The pipeline is long (compared to diam-
per second at outlet eter) and straight between end points.
conditions. 8. Flow acceleration can be neglected
V1 = Specific Volume of fluid, in because the pipeline is long compared
cubic feet per pound. Equation #3 can be converted to Equation to diameter.
W = Rate of Flow, in pounds per #3A, as follows:
hour.
w = Rate of Flow, in pounds per
second.
me = Absolute (Dynamic) Viscosity,
in pounds mass per foot
second.

16
Flow Control Division

Vogt Valves
A Treatise On Leakage
---------------------------------
Ratio of q’s to qs from Equations #3B and
#3A across same capillary, same DP, and
same temperature.
Since m = 0.18 (air) and m = 1.13 (water)
@ 60°F, Equation #5 can be determined.
#5.
Equation #4B can be derived as follows:
#4B. ---------------------------------
Equations #7, #8, #9, and #9A are
derived as illustrated in the paper.
from Equation #4A ---------------------------------

Equation #3B can be derived as follows: #6


Let Re ≤ 2000 (laminar flow), r = 6.24
Lb./Ft.3, and m = 1.13 (for water). General Surface Tension Equation –
Round Capillary.

--------------------------------- Equation #4C can be derived as follows:


Reynolds Number Equation – General #4C.

Since

Equation #4 can be derived as follows: Since from Equation #4B


for elongated leak path (slit) of width
#4. Let Re ≤ 2000, (w) and length (L).
Sg = 1.00 and m = .018 (for air).
Equation #4D can be derived as follows:
Let
#4D.
Area Slit = Area Capillary
Equation #4 can be converted to
Equation #4A.
#4A. and
Ratio of Length/Width of Slit
17
Flow Control Division

Vogt Valves
A Treatise On Leakage
World Class Quality
then Vogt is the world’s foremost manufacturer
of high quality forged steel valves and fit-
tings. Vogt has also proven itself successful
at building computer engineered gas tur-
bine heat recovery boilers and high effi-
and since
ciency commercial ice making machines.
Since 1880 uncompromised quality has
made Vogt products the universal choice
for demanding applications throughout the
world.
Vogt offers a wide range of 1/4” through
which is Equation #10, as follows: 4” forged steel gate, glove, angle and
check valves in all popular materials, trims
and bonnet configurations. Special prod-
#10
ucts are produced for nuclear, NACE, HF
Alkylation, chlorine, total containment and
actuated applications. Vogt valves and fit-
tings are available through carefully select-
ed distributors with access to the world’s
largest ready-to-ship inventory.
With a broad line of high quality products,
over a century of experience and a global
distribution and service network, it is easy
to understand how Vogt has earned its rep-
utation for world class quality.

18
Flow Control Division

Vogt Valves

Vogt Valves US Sales Offices


1511 Jefferson Street Phone: 903-885-3151
Sulphur Springs, TX 75482 Fax: 903-439-3386

Toll-Free Telephone Service Visit Our Website


1-800-225-6989 www.flowserve.com

After Hours Customer Service


1-800-543-3927

Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended function safely during its useful life.
However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can (and often does)
provide general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation,
and maintenance of Flowserve products. The purchaser/user should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees and contractors in the safe use of
Flowserve products in connection with the specific application.

While the information and specifications contained in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by
reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its product
design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any
one of its worldwide operations or offices.

For more information about Flowserve Corporation, contact www.flowserve.com or call USA 1-800-225-6989.

FLOWSERVE CORPORATION
FLOW CONTROL DIVISION
Vogt Valves
1511 Jefferson Street
Sulphur Springs, TX 75482
Phone: 903-885-3151
Facsimile: 903-439-3386

© 2003 Flowserve Corporation, Irving, Texas, USA. Flowserve and Vogt Valves are registered trademarks of Flowserve Corporation. CB 13 3/03 Printed in USA

You might also like