Professional Documents
Culture Documents
www.elsevier.com/locate/ijepes
Abstract
A new method to discriminate between internal fault current and inrush current is presented in this paper. A short time correlation function
is used to extract the dead angle from the differential current. The effect of CT saturation on inrush current is considered and test results with
the data obtained from a prototype device on a dynamic power system model verify the effectiveness of the proposed scheme. Another
advantage of this algorithm is that it has very small computation requirement. Thus can be applied for real-time applications. q 2002
Elsevier Science Ltd. All rights reserved.
Keywords: Power transformer protection; Short-time correlation transform (STCT); CT saturation; Dead angle
2.2. The short-time correlation transform The STCT results are quite different for inrush or internal
fault current signal. The asymmetry of the two half cycles
The short-time correlation function (STCT) of xn is
and the dead angles are special characteristics of inrush
de®ned as below
current which can be extracted by the STCT. The STCT
n0 1X
l=2 2 1 result of the original signal can be called the decomposition
STCT
x Rxx
n0 ; k xn xn1k
6 result in the ®rst scale. In the same way, the data in the ®rst
nn0 2 l=2 scale can be the target of the STCT and the result is called
where l is the length of the computation window and n0 is decomposition in the second scale. STCT are performed a
the window center. For white noise xn ; STCT
x < 0: Set number of times according to practical need. For inrush
Fig. 1. The STCT of a symmetrical waveform. Fig. 3. The STCT of inrush current.
H. Zhang et al. / Electrical Power and Energy Systems 24 (2002) 557±562 559
Fig. 7. Symmetrical inrush current without a long line, (a) inrush current
Fig. 5. Dynamic power system model. and its STCT result, (b) change of restraint percentage.
560 H. Zhang et al. / Electrical Power and Energy Systems 24 (2002) 557±562
Fig. 10. Analysis of a phase to ground fault with a long line connected,
Fig. 8. Analysis of inrush current with a long line, (a) inrush current and its (a) internal fault current and its STCT result, (b) change of restraint
STCT result, (b) change of restraint percentage. percentage.
Results of a phase B to ground fault are shown in Figs. 9± tested system is loaded and a long line is connected to it. It
11 for the models without any loads and lines, with a long will operate with a time delay for the second harmonic
line, only and with both loads and a long line, respectively. restraint scheme. Therefore, the tests shown in Fig. 12
It can be seen from a comparison of Figs. 9(b), 10(b) and through Fig. 15 are with the transformer loaded and a
11(b) that, the second harmonic content is higher when the long line connected to it.
A phase B to phase C internal fault on the primary
winding is shown in Fig. 12. The current at 20 ms is
distorted but no dead angle is detected. From the ®rst posi-
tive peak value (5 ms) to the second one (32 ms) of the
Fig. 12. B to C phase internal fault on primary, (a) internal fault current and
its STCT result, (b) change of restraint percentage. Fig. 14. B phase 4.35% winding fault on primary, (a) internal fault current
and its STCT result, (b) change of restraint percentage.
original signal, no continuous zero points are detected.
Therefore, the operation time is about 32 ms using the winding is shown in Fig. 13. The operation time of second
STCT. Whereas, the transformer is allowed to operate harmonic restraint principle is 58 ms while the STCT result
only at about 90 ms using a traditional scheme based on shows that it has a faster operation, operating at 30 ms.
the detection of the second harmonic component of the Results of a phase B 4.35% winding internal fault on the
current because the ratio of the second harmonic to the primary, are shown in Fig. 14. It can be seen from Fig. 14(b)
fundamental is not less than 0.15 until after 32 ms. that the harmonic content is very small and thus both
A phase A to phase B internal fault on the secondary schemes will operate quickly.
Energization with an internal phase B to ground fault on
Fig. 13. A to B phase internal fault on secondary, (a) internal fault current Fig. 15. Energization with a B to ground fault on primary (a) internal fault
and its STCT result, (b) change of restraint percentage. current and its STCT result, (b) change of restraint percentage.
562 H. Zhang et al. / Electrical Power and Energy Systems 24 (2002) 557±562
the primary is shown in Fig. 15. In this case, the fault current ² Small computation requirements that make it appropriate
is affected by the energization and hence the harmonic for industrial application.
cannot be quickly attenuated. The operation time of the ² Insensitivity to CT saturation.
proposed scheme is about 35 ms and that of the second
harmonic restraint scheme is about 80 ms. The superiority A dynamic model was constructed to verify the effective-
of the new scheme is obvious. ness of the proposed scheme. Simulation results show that
The current in Fig. 7 is phase A differential inrush this algorithm is effective in distinguishing inrushes from
current with no fault and no line is connected to the different kinds of transformer internal faults with or without
transformer, but the model in Fig. 8 has a long line transmission lines.
connected on the primary side. Although they are
symmetrical inrush and their dead angles have disappeared References
due to CT saturation, the STCT can block the relay by
extracting the dead angles. [1] Liu Pei, Malik OP, et al. Improved operation of differential protection
of power transformers for internal faults. IEEE Trans Power Delivery
1992;7(4):1912±9.
[2] Shang Guocai, Yu Dachuan. Identifying internal faults of transformers
5. Conclusions
through the similarity degree between voltage and current. Proceed-
ings, IEEE PES 2000 Winter Meeting, Singapore.
One part of an on-going research and development [3] Yabe Kuniaki. Power differential method for discrimination between
work on integrated digital differential power transformer fault and magnetizing inrush current in transformers. IEEE Trans
protection with emphasis on possible improvements in Power Delivery 1997;12(3):1109±18.
operation speed and reliability is proposed in this paper. [4] Jiang F, Bo ZQ. Power transformer protection based on transient detec-
tion using discrete wavelet transform (DWT). Proceedings, IEEE PES
Improvement has been achieved by using the short-time 2000 Winter Meeting, Singapore.
correlation transform to discriminate between internal [5] Xiangning Lin, Pei Liu, Shijie Cheng. A wavelet transform based
fault and magnetizing inrush current. The proposed scheme for power transformer inrush identi®cation. Proceedings,
method is aimed at magnifying the asymmetry of inrush IEEE PES 2000 Winter Meeting, Singapore.
currents by extracting dead angles. Main advantages of [6] Pihler J, Grcar B, Dolinar D. Improved operation of power transformer
protection using arti®cial neural network. IEEE Trans Power Delivery
this method are: 1997;12(3):1128±36.
[7] Kasztenny B, Rosolowski E, et al. A self-organizing fuzzy logic based
² Reliable identi®cation even when the internal currents protective relay- an application to power transformer protection. IEEE
are seriously distorted by harmonics. Trans Power Delivery 1997;12(3):1119±27.