ABB Oy Medium Voltage Products, Distribution Automation

Relion® 615 series IEC Ver 5.0


General Presentation

© ABB Group
August 5, 2016 | Slide 1 | 1MRS756700 G
Relion® 615 series
Contents

 The 615 series of IEDs


 New features for product version 5.0
 Capacitor Bank Protection and Control REV615
 Common features of the 615 series
 Feeder Protection and Control REF615
 Line Differential Protection and Control RED615
 Motor Protection and Control REM615
 Voltage Protection and Control REU615
 Transformer Protection and Control RET615
 ABB solutions
 Conclusions

© ABB Group
August 5, 2016 | Slide 2
Relion® 615 series
Products

 The 615 series IEDs (intelligent electronic devices) are


members of ABB’s Relion® product family and part of its
615 protection and control product series
 The 615 series IEDs are characterized by their
compactness and withdrawable-unit design

© ABB Group
August 5, 2016 | Slide 3
New features for version 5.0
Relion® 615 series

© ABB Group
August 5, 2016 | Slide 4 | 1MRS
615 series
New standard configurations

 New standard configurations have been introduced for


existing products
 REF615
 RED615
 REM615
 More information of the new standard configurations is
available in the product description parts of this
presentation (in blue colour)

© ABB Group
August 5, 2016 | Slide 5
615 series
Fault locator

 Impedance based fault location for radial


feeder networks, as option in some of the
standard configurations in REF615 and
RED615
 Short-circuit location
 Earth-fault location
 Effectively and low-resistance earthed
networks
 Isolated neutral point
 Information offered
 Fault type
 Fault distance
 Fault resistance estimate
 Up to three different line sections with
independent impedance settings
 The fault current magnitude should be at
least on the same level or higher than the
load current
 External and internal triggering possibilities

© ABB Group
August 5, 2016 | Slide 6
615 series
High-speed outputs for time critical applications

 High-speed output (HSO) module for


time critical applications such as arc
fault protection
 Three high speed hybrid outputs
 4-6 ms faster than conventional
power outputs but with same rating
of output contacts
 One master trip function available per
800
high-speed output
 Can be configured for any protection
that requires fast operate time
kA2

400
Sheet steel burn-up

Copper burn-up
 Available as an option
Cable fire

0
0 100 200 300 400
ms

© ABB Group
August 5, 2016 | Slide 7
615 series
Load profile recorder

 Capturing and storing of longer time history


of measurement values in non-volatile
memory
 Currents
 Voltages
 Power
 Up to 12 quantities selectable
 Settable time interval of 1 to 180 minutes
 Average value of the quantity over the
selected time interval
 Total load profile recording length depends
on amount of quantities and time interval
 6 quantities, 60min interval ~ 1year
 12 quantities, 10min interval ~1month
 Load profile record is stored in COMTRADE
format in the IED
 Use load profile tool in PCM600 to read the
load profile file from the IED

© ABB Group
August 5, 2016 | Slide 8
615 series
Profibus DPV1

 Protocol used typically in the industrial


system applications
 Profibus DPV1 protocol available using
SPA-ZC 302 communication adapter
 IED must have Modbus® serial (RS 485)
protocol option available
 Modbus® serial option includes
functionality to emulate SPA protocol for
SPA-ZC 302
 Control, events, measurements and
time synchronization
 Can be used in parallel with IEC 61850

© ABB Group
August 5, 2016 | Slide 9
615 series
Process bus

 Process bus with sampled values of analog phase voltages


 An IED can act as a merging unit and measure phase
voltages in the substation and send them as Sampled
Measured Values (SMV) over Ethernet
 Other IEDs in the substation having phase voltage based
functions, can receive the SMV over Ethernet and use these
values instead of physically (VT or voltage sensor) measured
phase voltages
 Communication protocol used is IEC 61850-9-2 LE (light edition)
 The used time synchronization method is IEEE 1588 v2 Precision
Time Protocol (PTP) with Power Profile

 Benefits
 Simplicity (reduces wiring and terminals)
 Flexibility
 Improved diagnostic
 Longer maintenance cycles

© ABB Group
August 5, 2016 | Slide 10
615 series
System example of utilizing process bus

Common Ethernet
Station bus (IEC 61850-8-1), process bus (IEC 61850-9-2 LE) and IEEE 1588 v2 time synchronization

GOOSE

GOOSE

GOOSE
GOOSE
GOOSE

GOOSE

GOOSE

SMV
SMV

SMV

SMV

SMV
© ABB Group
August 5, 2016 | Slide 11
615 series
IEEE 1588 time synchronization

 615 series supports IEEE 1588 v2 Precision


Time Protocol (PTP) with Power Profile
 Provides high accuracy time
synchronization of 1 μs
 Required especially in process bus
applications with sampled values using
protocol IEC 61850-9-2 LE
 IED has a time-stamp resolution of < 4
μs
 The IEEE 1588 support is included in
variants having a redundant Ethernet
communication module and with the following
protocols
 IEC 61850

 Modbus®

 DNP

 IEC 60870-5-103

© ABB Group
August 5, 2016 | Slide 12
615 series
IEEE 1588 time synchronization example using HSR

© ABB Group
August 5, 2016 | Slide 13
615 series
IEC 61850 conformance

 IEC 61850 Certificate Level A1


 IEC 61850 First Edition Parts 6, 7-1, 7-
2, 7-3, 7-4 and 8-1
 Communication networks and
systems in substations
 For complete 615 series by KEMA

© ABB Group
August 5, 2016 | Slide 14
615 series
Usability enhancements

 Up to ten Single Line Diagram (SLD) pages can be created


 U12B measurement available in standard configurations with
synchro-check
 In measurement view as default

 Can be configured to SLD view

 Run time counter can be added into SLD


 Frequency measurement in all REF615 standard configurations
having voltage measurement
 Event definitions for LHMI and WHMI
 Unneccessary settings automatically dimmed
 Basic and advanced setting views

© ABB Group
August 5, 2016 | Slide 15
615 series
Engineering enhancements

 Enhanced library of Single Line Diagram symbols


 Improved structure of configurations in ACT with different main
application sheets for different purposes
 User definable composite function blocks
 Analog move function block SCA4GAPC
 Integer value move function MVI4GAPC
 Increased amount of Multi-purpose function MAPGAPC
 AND logic function block with 20 inputs
 OR logic function block with 20 inputs

© ABB Group
August 5, 2016 | Slide 16
615 series
Other enhancements

 RTD inputs in REF615


 Power Quality functions included in more standard
configurations
 Intermittent / transient E/F with sensor voltage
measurements
 Energy measurements with IEC 103
 Settable phase correction factor for instrument transformer
and sensors
 Run time counter included in most std confs
 Secured Web HMI
 Fault records for DNP clients

© ABB Group
August 5, 2016 | Slide 17
REV615
Relion® 615 series

© ABB Group
August 5, 2016 | Slide 18 | 1MRS
REV615
Description

 REV615 is a dedicated IED


(intelligent electronic
device) designed for the
protection, control,
measurement and
supervision of capacitor
banks used for
compensation of reactive
power in utility substations
and industrial power
systems.

© ABB Group
August 5, 2016 | Slide 19
REV615
Area of application

 Designed for capacitor bank


applications calling for overload,
unbalance, overcurrent and earth-fault
protection
 Main application area: H-bridge, double
star or single star connected capacitor
banks for reactive power compensation
 Can also be used for protection of
harmonic filter circuits, if there is no
significant harmonic component higher
than 11th

© ABB Group
August 5, 2016 | Slide 20
REV615
Two standard configurations

Standard configuration A
Capacitor bank overload, undercurrent and unbalance protection,
non-directional overcurrent and non-directional earth-fault protection,
CB control and CB condition monitoring

Standard configuration B
Capacitor bank overload, undercurrent and unbalance protection,
non-directional overcurrent and directional earth-fault protection,
voltage based protection, CB control and CB condition monitoring

© ABB Group
August 5, 2016 | Slide 21
Common features
Relion® 615 series

© ABB Group
August 5, 2016 | Slide 22 | 1MRS
615 series designed for IEC 61850
Interoperability between substation devices

 Native support for IEC 61850


communication between devices in
substations
 IEC 61850 enables binary and analog
“GOOSE” (Generic Object Oriented
Substation Event) messaging between
IEDs
 Optional redundant galvanic or optical
Ethernet solution (not in RED615)
 Optional communication protocols for
connecting the IEDs to applications
using Modbus, DNP3, or
IEC 60870-5-103 protocols

© ABB Group
August 5, 2016 | Slide 23
615 series predefined standard configurations
Rapid setup and commissioning

 Ready-made adaptations
(standard configurations)
 The IEDs can be rapidly set up and
commissioned once they have been
given the application-specific settings
 The standard signal configuration
setting can be adjusted using the
PCM600 setting and configuration tool

© ABB Group
August 5, 2016 | Slide 24
615 series application configuration
Modification of the standard configuration

 The support for the graphical application


configuration (ACT) functionality in
PCM600 enables the creation of multi-
layer logics
 By combining protection function with
logical elements the IED configuration
can be adapted to user specific
application requirements
 The ACT support offers improved
documentation of the standard
configuration when altered

Note!, the utilization of the analog channels is defined by the


standard configuration and cannot be changed using the ACT

© ABB Group
August 5, 2016 | Slide 25
615 series control of primary devices
Dedicated push-buttons

 Control of primary devices via the IED’s


human-machine interface (HMI) or a
remote control system
 Forcing of local/remote switch to local
position via a binary input prohibits
remote control during, for example,
maintenance thus increasing the safety
on site
 Interlocking schemes
 Optional multi-shot auto-reclosing of
one CB

© ABB Group
August 5, 2016 | Slide 26
615 series patented and compact plug-in design
Contributes to a shortened mean time to repair

 Speeds up installation, maintenance


and testing of the protection
 Shortened MTTR (mean time to repair)
 Allows the cases to be installed and
wired before the plug-in units are
inserted
 Mechanical coding system for
preventing insertion of a wrong plug-in
unit in a case
 Sealable and screw secured pull-out
handle to prevent accidental (or
unauthorized) withdrawal of the
plug-in unit

© ABB Group
August 5, 2016 | Slide 27
615 series disturbance recorder
For in-depth analysis of network disturbances

 Up to 100 recordings can


be recorded
 Flexible setting of the
sampling rate and the
channels enables
maximizing the recording of
user relevant data

Example:

40 recordings of 500 ms with the


highest sampling rate and the
maximum number of channels

© ABB Group
August 5, 2016 | Slide 28
615 series operation traceability
For pre and post fault analysis

 The critical data is stored in a


non-volatile memory to prevent loss of
data in case of a power failure
 Disturbance recorder data
 Events including time stamps
 User audit trail
 Recorded data
 Circuit breaker conditioning
monitoring values
 Thermal loading level
 Operation indications and alarm LEDs
show the status of the IED
 Trip lock-out
 IED setting values
 IED configuration

© ABB Group
August 5, 2016 | Slide 29
615 series condition monitoring
Continous control of the operational availability

 Circuit breaker condition monitoring


provides information for scheduling CB
maintenance
 Runtime counter for machines and
devices enables scheduling of time-
based maintenance of the motor or
transformer
 Continous supervision of the state of the
IED hardware and software to ensure
operational availability of the protection

© ABB Group
August 5, 2016 | Slide 30
615 series role-based access control
Authorized IED operation

 Role-based access control protects the


IED from unauthorized access
 Four access levels: viewer, operator,
engineer and administrator
 Applies to:
 Front-panel user interface
 Web browser based user interface
 PCM600
 Passwords are programmable by the
administrator

© ABB Group
August 5, 2016 | Slide 31
615 series versatile tools
Supporting engineering and operation

 PCM600
 One single tool for managing settings, signal
configuration and disturbance handling
 Web browser based user interface
 Local or remote IED access using a web
browser
 Internet Explorer version 8.0, 9.0 and 10.0 are
supported
 IED specific connectivity packages
 For automatic configuration via MicroSCADA
Pro SYS600, Grid Automation controller
COM600 or PCM600
 Grid Automation controller COM600 ver 4.0
 MicroSCADA Pro 9.3 FP2 or later
 PCM600 2.6 or later

© ABB Group
August 5, 2016 | Slide 32
615 series single line diagram (SLD)
Bay level information overview

 Predefined SLD for fast commissioning of the IED


 Position indication for the associated primary equipment
 Shows the related measuring values
 Independent of the role based access control
 Optional local/remote access using the web HMI
 Customizable according to user requirements

© ABB Group
August 5, 2016 | Slide 33
615 series IEC 61850 communication
Sending and receiving of analog GOOSE messages

 By using the IEC 61850 GOOSE


messaging analog values can be sent
and received by the IEDs
 Measurement values can be shared
over the station bus
 Analog GOOSE messaging can, for
example, be employed for control
schemes of parallel running
transformers, thus saving costs for
hard wiring
 By sharing measurement values the
need for separate, for example ambient
temperature, transducers is reduced

© ABB Group
August 5, 2016 | Slide 34
615 series RTD/mA measuring
Extended thermal overload protection

 Preventing premature aging of the


motor or transformer and reducing the
risk of costly thermal overload failures
 Contributing to an optimal life span of
the motor/transformer
 Measuring of:
 Motor bearing temperature
 Stator winding temperature
 Oli temperature
 Ambient temperature
 Pressure
 Tap changer position

© ABB Group
August 5, 2016 | Slide 35
615 series
Extended control of primary network devices

 In addition to the circuit-breaker control the


IEDs also feature:
 Two control blocks for control of motor-
operated disconnectors or a circuit-
breaker truck and their position
indications.
 A control block for control of motor-
operated earthing switch and it´s
position indication.
 The number of controllable devices depends
on the number of available I/O’s in the
selected configuration
 Devices can be controlled via the IED’s local
HMI or a remote control system
 The single line diagram indicates the position
of the primary devices

© ABB Group
August 5, 2016 | Slide 36
615 series
Fault records and events

 Up to 128 fault records (non-volatile memory)


 Up to 1024 events stored (non-volatile memory)
 Events can be viewed using the PCM600

© ABB Group
August 5, 2016 | Slide 37
615 series
Parallel protocols

 Support for parallel use of the following protocols


 IEC 61850 and Modbus®

 IEC 61850 and DNP3

 IEC 61850 and IEC 60870-5-103

 Flexibility to change the communication protocol


 Enables connection between two substation systems with
different communication protocol

© ABB Group
August 5, 2016 | Slide 38
615 series
Redundancy solutions

 Redundant Ethernet solutions


 High availability seamless redundancy (HSR)
 Parallel redundancy protocol (PRP)
 Both HSR and PRP are supported in IEC 61850 standard
 HSR and PRP are available for all products, except RED615
 HSR
 The nodes in a HSR are connected with two ports to network
 HSR is used in a ring topology
 Data is sent from both ports to both directions in ring
 PRP
 Each network node is connected to two parallel local area
networks, LANA and LANB
 Same data is sent to both local area networks

© ABB Group
August 5, 2016 | Slide 39
615 series IEC 61850 Ethernet redundancy HSR
Eliminating communication downtime

 An optional second fiber-optic or galvanic port available


 Not available for RED615
 Enables a redundant Ethernet communication controlled by a
managed switch with IEC 61850 HSR protocol support
 Avoids single point of failure without any delay
 Secures highly critical communication between devices
 If the ring is broken, messages still arrive over the intact path
 Broken ring is easily detected since duplicate messages cease to
come to receiver

© ABB Group
August 5, 2016 | Slide 40
615 series IEC 61850 Ethernet redundancy HSR
Operation principle – unicast frames

© ABB Group
August 5, 2016 | Slide 41
615 series IEC 61850 Ethernet redundancy PRP
Eliminating communication downtime

 An optional second fiber-optic or galvanic port available


 Not available for RED615
 Enables a redundant Ethernet communication controlled by a
managed switch with IEC 61850 standard PRP support
 Avoids single point of failure without any delay
 Secures highly critical communication between devices
 The communication network is fully duplicated
 If only one packet is received, the receiver knows the other path is
broken

© ABB Group
August 5, 2016 | Slide 42
615 series self-healing Ethernet ring
Reducing communication downtime

 An optional second fibre-optic or galvanic


port on the communication module
 The optional communication module with two
fibre-optic ports is not available for RED615
 Enables the creation of a cost efficient self-
healing Ethernet communication ring
controlled by a managed switch with rapid
spanning tree protocol (RSTP) support
 Avoids single point of failure concerns
 Secures critical communication between
devices

© ABB Group
August 5, 2016 | Slide 43
REF615
Relion® 615 series

© ABB Group
August 5, 2016 | Slide 44 | 1MRS
REF615
Description

 REF615 is a dedicated  REF615 is a dedicated feeder IED


feeder IED (intelligent (intelligent electronic device) designed
electronic device) designed for the protection, control,
for the protection, control, measurement and supervision of utility
measurement and substations and industrial power
supervision of utility systems including radial, looped and
substations and industrial meshed distribution networks with or
power systems including without distributed power generation
radial, looped and meshed
distribution networks with or
without distributed power
generation

© ABB Group
August 5, 2016 | Slide 45
REF615
Area of application

 Designed for general applications calling


for over-current and earth-fault
protection
 Main application area: cable or
overhead line feeders in solidly earthed,
resistance earthed, isolated or
compensated networks
 Optional three-channel arc protection
system

© ABB Group
August 5, 2016 | Slide 46
REF615
Twelve standard configurations (1/2)

Standard configuration A
Non-directional overcurrent and directional earth-fault protection and CB control
Standard configuration B
Non-directional overcurrent and directional earth-fault protection, CB condition monitoring,
CB control and with the optional I/O module control of two network objects
Standard configuration C
Non-directional overcurrent and non-directional earth-fault protection and CB control
Standard configuration D
Non-directional overcurrent and non-directional earth-fault protection, CB condition
monitoring, CB control and with the optional I/O module control of two network objects
Standard configuration E
Non-directional overcurrent and directional earth-fault protection with phase-voltage based
measurements, CB condition monitoring and CB control
Standard configuration F
Directional overcurrent and directional earth-fault protection with phase-voltage based
measurements, undervoltage and overvoltage protection, CB condition monitoring and CB
control

© ABB Group
August 5, 2016 | Slide 47
REF615
Twelve standard configurations (2/2)

Standard configuration G
Directional overcurrent and directional earth-fault protection, phase-voltage based
protection and measurement functions, CB condition monitoring, CB control and sensor
inputs for phase currents and phase voltages
Standard configuration H
Non-directional overcurrent and non-directional earth-fault protection, phase-voltage and
frequency based protection and measurement functions, synchro check, CB condition
monitoring and CB control
Standard configuration J
Directional overcurrent and directional earth-fault protection, phase-voltage and frequency
based protection and measurement functions, synchro check, CB condition monitoring and
CB control
Standard configuration K (NEW)
Directional overcurrent and directional earth-fault protection, high impedance restricted
earth-fault protection, phase voltage and frequency based protection and measurements
functions, synchro-check, CB condition monitoring, CB control and fault locator (optional)
Standard configuration L (NEW)
Directional overcurrent and directional earth-fault protection, phase voltage and frequency
based protection and measurement functions and CB condition monitoring, CB control,
sensor inputs for phase currents and phase voltages and fault locator (optional)
Standard configuration N (NEW)
Directional and non-directional overcurrent and earth-fault protection, phase voltage and
frequency based protection and measurements, synchro-check, CB condition monitoring,
CB control and fault locator (optional)

© ABB Group
August 5, 2016 | Slide 48
RED615
Relion® 615 series

© ABB Group
August 5, 2016 | Slide 49 | 1MRS
RED615
Description

 RED615 is a phase-segregated two-end


line differential protection and control
IED (intelligent electronic device)
designed for utility and industrial power
systems, including radial, looped,
meshed distribution networks with or
without distributed power generation
 Applicable for feeder sections with in-
zone transformer
 The RED615s communicate between
substations over a fibre-optic link or a
galvanic pilot wire connection

© ABB Group
August 5, 2016 | Slide 50
RED615
Selective protection for a dedicated zone

 Unit protection for applications calling


for absolutely selective protection for a
dedicated zone
 Main application area: two-terminal
protection for cable or overhead line
feeders, can be used also with in-zone
transformer
 Phase segregated protection algorithm
 Protection communication using a
dedicated optical link or a galvanic pilot
wire connection

© ABB Group
August 5, 2016 | Slide 51
RED615
Line differential protection applications

 Parallel feeders
 Looped feeder construction
 Doubled feeders
 Two interconnected feeders between a
primary substation
 Reserve connections or meshed type
of network
 Distributed generation
 Power generation at the remote end of
the feeder
 Weak grid supplying relatively long
distribution lines

© ABB Group
August 5, 2016 | Slide 52
RED615
Five standard configurations

 Standard configuration A
Line-differential protection and CB control
 Standard configuration B
Line-differential protection with directional earth-fault
protection, CB condition monitoring and CB control
 Standard configuration C
Line-differential protection with non-directional earth-
fault protection, CB condition monitoring and CB
control
 Standard configuration D (NEW)
Line-differential protection, directional overcurrent
and directional earth-fault protection, phase-voltage
and frequency based protection and measurement
functions, CB condition monitoring, CB control and
fault locator (optional)
 Standard configuration E (NEW)
Line-differential protection with directional
overcurrent and directional earth-fault protection,
phase-voltage and frequency based protection and
measurement functions, CB condition monitoring, CB
control, sensor inputs for phase currents and phase
voltages and fault locator (optional)

© ABB Group
August 5, 2016 | Slide 53
REM615
Relion® 615 series

© ABB Group
August 5, 2016 | Slide 54 | 1MRS
REM615
Description

 REM615 is a dedicated  REM615 is a dedicated motor


motor protection and protection and control IED (intelligent
control IED (intelligent electronic device) designed for the
electronic device) designed protection, control, measurement and
for the protection, control, supervision of asynchronous motors in
measurement and manufacturing and process industry
supervision of
asynchronous motors in
manufacturing and process
industry

© ABB Group
August 5, 2016 | Slide 55
REM615
Area of application

 Circuit-breaker or contactor controlled


high-voltage (HV) motors
 Contactor controlled medium sized and
large low-voltage (LV) motors
 Manufacturing, process and refinery
industry
 Protection for a variety of drives
such as:
 Pumps and conveyors

 Crushers and choppers

 Mixers and agitators

 Fans and aerators

 Compressors

© ABB Group
August 5, 2016 | Slide 56
REM615
Standard configurations

 Standard configuration A
Motor protection, optional RTD/mA inputs,
CB condition monitoring and CB control
 Standard configuration B
Motor protection with current, voltage and
frequency based protection and
measurement functions, optional RTD/mA
inputs, CB condition monitoring and CB
control
 Standard configuration C
Motor protection with current, voltage and
frequency based protection and
measurement functions, CB condition
monitoring and CB control
 Standard configuration D (NEW)
Motor protection with current, voltage and
frequency based protection and
measurements functions , CB condition
monitoring, CB control and sensor inputs for
phase currents and phase voltages

© ABB Group
August 5, 2016 | Slide 57
REU615
Relion® 615 series

© ABB Group
August 5, 2016 | Slide 58 | 1MRS
REU615
Voltage Protection and Control

 Two standard configurations denoted


A and B
 The area of application is dependant of
the standard configuration
 Optional RTD/mA module (std. conf. B)
 Optional three-channel arc protection
system

© ABB Group
August 5, 2016 | Slide 59
REU615 standard configuration A
Description

 Configuration A is
preadapted for voltage and
frequency based protection
schemes in utility and
industrial power systems
distribution systems
including networks with
distributed power
generation

© ABB Group
August 5, 2016 | Slide 60
REU615 standard configuration A
Area of application

 Network under and overvoltage,


residual overvoltage and frequency
supervision
 Load shedding or generation rejection
for enhanced network stability
 Generator and motor applications:
 Detection of deviations from the permitted
frequency and voltage values
 Integrated synchro-check function:
 Synchronized connection of the equipment
into the network
 Distribution networks with distributed
power generation:
 Loss-of-mains (LOM) protection for single
power-generating units

© ABB Group
August 5, 2016 | Slide 61
REU615 standard configuration B
Description

 The B configuration is
designed for automatic
voltage regulation of power
transformers equipped with
an on-load tap-changer

© ABB Group
August 5, 2016 | Slide 62
REU615 standard configuration B
Area of application

 Automatic and manual voltage


regulation of power transformers
equipped with motor driven on-load tap-
changers
 Load-side voltage regulation
 A single power transformer
 Several (up to four) parallel running
power transformers
 Line voltage drop compensation

© ABB Group
August 5, 2016 | Slide 63
RET615
Relion® 615 series

© ABB Group
August 5, 2016 | Slide 64 | 1MRS
RET615
Description

 RET615 is a dedicated  RET615 is a dedicated transformer


transformer protection and protection and control IED (intelligent
control IED (intelligent electronic device) for power
electronic device) for power transformers, unit and step-up
transformers, unit and step- transformers including power
up transformers including generator-transformer blocks in utility
power generator- and industry power distribution
transformer blocks in utility systems
and industry power
distribution systems

© ABB Group
August 5, 2016 | Slide 65
RET615
Area of application

 Designed for unit protection


applications calling for
stabilized differential
protection
 Main application area: two
winding transformers in
power distribution networks
 Optional three-channel arc
protection system

© ABB Group
August 5, 2016 | Slide 66
RET615
Eight standard configurations

 Standard configuration A
Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-
fault protection for the high-voltage (HV) side, CB control and optional six RTD / two mA inputs
 Standard configuration B
Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-
fault protection for the low-voltage (LV) side, CB control, optional six RTD / two mA inputs
 Standard configuration C
Three-phase transformer differential protection for two-winding transformers, high-impedance based
restricted earth-fault protection for the high-voltage (HV) side, optional six RTD / two mA inputs
 Standard configuration D
Three-phase transformer differential protection for two-winding transformers, high-impedance based
restricted earth-fault protection for the low-voltage (LV) side, CB control and optional six RTD / two mA
inputs
 Standard configuration E
Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-
fault protection for the high-voltage (HV) side, phase-voltage based protection and measurement functions,
CB control and optional two RTD / one mA inputs
 Standard configuration F
Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-
fault protection for the low-voltage (LV) side, phase-voltage based protection and measurement functions
and CB control and optional two RTD / one mA inputs
 Standard configuration G
Three-phase transformer differential protection for two-winding transformers, high-impedance based
restricted earth-fault protection for the high-voltage (HV) side, phase-voltage based protection and
measurement functions and CB control and optional two RTD / one mA inputs
 Standard configuration H
Three-phase transformer differential protection for two-winding transformers, high-impedance based
restricted earth-fault protection for the low-voltage (LV) side, phase-voltage based protection and
measurement functions and CB control and optional two RTD / one mA inputs

© ABB Group
August 5, 2016 | Slide 67
ABB solutions
Relion® 615 series

© ABB Group
August 5, 2016 | Slide 68 | 1MRS
615 series
Supported ABB solutions, page 1(2)

 The ABB products constitute a genuine IEC


61850 solution for reliable power distribution
in utility and industrial power systems
 The native IEC 61850 support offer:
 High communication performance
 Continuous supervision of the protection and
communication system integrity
 No additional CPUs or adapters
 Faster protection applications
Supported ABB solutions Version  ABB’s Connectivity Package concept
Grid Automation controller COM600 4.0 or later enables:
MicroSCADA Pro SYS600 9.3 FP2 or  Streamlines IEC 61850 system engineering
later and IED configuration
System 800xA 5.1 or later
 Enables easy integration with COM600 and
MicroSCADA Pro.
 Helps to automate the engineering part, e.g.
event lists and single line diagram
 Shortens the system engineering time

© ABB Group
August 5, 2016 | Slide 69
615 series
Supported ABB solutions, page 2(2)

 The 615 series IEDs complemented with COM600 offer


several benefits:
 Enhanced substation level functionality using the data content
of the bay level IEDs
 A web HMI providing single-line mimic diagrams for
switchgear bay solutions
 COM600 can be used as a local data warehouse for
technical documentation and for network data
 Extensive reporting and analyzing of network fault situations
 Seamless connectivity to MicroSCADA Pro SYS600 and
System 800xA

© ABB Group
August 5, 2016 | Slide 70
615 series
Supported ABB solutions example

© ABB Group
August 5, 2016 | Slide 71
Conclusions

© ABB Group
August 5, 2016 | Slide 72 | 1MRS
615 series
Conclusions

 Native support for IEC 61850 and GOOSE messaging


 Patented plug-in design for flexible mounting, fast
installation and commissioning
 IEDs are available in predefined standard configurations
 The 615 series IEDs include a comprehensive range of
monitoring and watchdog functions
 Versatile tools including IED specific connectivity packages

© ABB Group
August 5, 2016 | Slide 73
Please visit our website for the latest
product information
www.abb.com/substationautomation