Relion® Protection and Control

Grid Automation, Recloser Protection and


Control RER615
Product Guide
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Contents

1. Description.....................................................................3 16. Inputs and outputs......................................................13


2. Standard configurations.................................................3 17. Station communication................................................14
3. Protection functions........................................................8 18. Technical data.............................................................16
4. Application...................................................................10 19. Local HMI....................................................................44
5. Supported ABB solutions.............................................11 20. Mounting methods......................................................45
6. Control.........................................................................12 21. IED case and IED plug-in unit......................................45
7. Measurement...............................................................12 22. Selection and ordering data.........................................46
8. Disturbance recorder....................................................12 23. Accessories and ordering data....................................48
9. Event log......................................................................13 24. Tools...........................................................................48
10. Recorded data............................................................13 25. Connection diagrams..................................................50
11. Condition monitoring...................................................13 26. Certificates..................................................................52
12. Trip-circuit supervision.................................................13 27. References..................................................................52
13. Self-supervision...........................................................13 28. Functions, codes and symbols....................................52
14. Fuse failure supervision...............................................13 29. Document revision history...........................................56
15. Access control............................................................13

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2013 ABB.
All rights reserved.
Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
2 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0 Issued: 2013-09-17
Revision: A

1. Description Via the IED's front panel HMI or a remote control system, one
RER615 is a recloser controller designed for remote control recloser can be controlled. To protect the IED from
and monitoring, protection, fault indication, power quality unauthorized access and to maintain the integrity of
analyzing and automation in medium-voltage secondary information, the IED is provided with a four-level, role-based
distribution systems, including radial, looped and meshed user authentication system, with individual passwords for the
distribution networks, with or without distributed power viewer, operator, engineer and administrator levels. The
generation. access control system applies to the front panel HMI,
embedded Web browser-based HMI and Protection and
RER615 is a member of the Relion ® product family and a part Control IED Manager PCM600.
of its 615 protection and control product series. The 615
series IEDs are characterized by their compactness and RER615 supports a variety of communication protocols for
withdrawable-unit design. Re-engineered from the ground up, remote communication, such as IEC 60870-5-101/104, DNP3
the 615 series has been designed to unleash the full potential level 2 and Modbus, simultaneously also supporting IEC
of the IEC 61850 standard for communication and 61850 with GOOSE messaging.
interoperability between substation automation devices.

With RER615, grid reliability can be enhanced, ranging from 2. Standard configurations
basic, non-directional overload protection to extended RER615 is available in two standard configurations. An
protection functionality with power quality analyses. Thus, example configuration suitable for recloser applications is
RER615 meets today’s requirements for smart grids and delivered with each standard configuration. This minimizes
supports the protection of overhead line and cable feeders in the required amount of engineering, thus allowing fast
isolated neutral, resistance-earthed, compensated and solidly commissioning by just parametrizing the protection functions.
earthed networks. RER615 is freely programmable with For applications where the example configuration is not
horizontal GOOSE communication, thus enabling suitable, the standard signal configuration can be easily
sophisticated interlocking functions. The new adaptable altered using the graphical signal matrix or the graphical
standard configuration allows the IED to be taken into use application functionality of the Protection and Control IED
right after the application-specific parameters have been set. Manager PCM600. The application configuration functionality
of PCM600 also supports the creation of multilayer logic
As part of an ABB smart grid solution, RER615 provides functions using various logical elements, including timers and
superior fault location, isolation and restoration (FLIR) to lower flip-flops. By combining protection functions with logic
the frequency and shorten the duration of faults (SAIFI/SAIDI). function blocks, the IED configuration can be adapted to user-
specific application requirements.
RER615 offers a variety of features to enhance grid reliability.
• Sophisticated protection functionality to detect, isolate and Standard configuration A supports traditional current and
restore power in all types of network voltage transformers. The residual current for the earth-fault
• Especially powerful in compensated networks (including protection is derived from the phase currents in a Holmgren
recloser tripping curves) connection. The core balance current transformers can also
• Integrated power quality measurement, including voltage be used for measuring the residual current, especially when
dips and swells logging sensitive earth-fault protection is required.
• Freely programmable
• Load profile and event logging Standard configuration D supports traditional current and
• Flexible autoreclosing function voltage sensors, allowing for voltage measurement from both
• Six easily manageable setting groups the source and the load feeder in an application requiring
• Adaptable standard configuration for rapid commissioning syncrocheck. The residual current for the earth-fault
• Easy Web-based parametrization tool with download protection is derived from the phase currents in a Holmgren
possibility connection. The core balance current transformers can also
• Same configuration tools as for other ABB Relion IEDs such be used for measuring the residual current, especially when
as the 615/620/630 series sensitive earth-fault protection is required. The sensor inputs
• Cyber security features such as audit trail are highly flexible and are type-tested to support both ABB's
• Withdrawable-unit design capacitive and resistive voltage sensors.
• Large, easy-to-read LCD screen with SLD, local control and
parametrization possibilities with dedicated push buttons
for safe operation
• IEC 60870-5-101/104, DNP3 level 2, Modbus or IEC 61850
with GOOSE messaging communication for high-speed
protection, fault isolation and restoration
• Environmentally friendly design with RoHS compliance

ABB 3
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Source
RER615 RECLOSER PROTECTION AND CONTROL IED STANDARD
A
CONFIGURATION
Version 1.0

PROTECTION LOCAL HMI ALSO AVAILABLE


IEC
- Disturbance recorder
2× Configuration A
- Event log
Master Trip
System
HMI
Time

- Fault recorder
A Authorization

Lockout relay U12 0. 0 kV

- IED self-supervision
P 0.00 kW
Q 0.00 kVAr
I
94/86
ESC Clear
IL2 0 A

O R
L
- Load profile
I ESC Clear - Local/Remote push-button on LHMI
- Recorded data
O R

2× L
- User management
I2> I2/I1> 3Ith>F 3I>>> - Web HMI
46 46PD 49F 50P/51P ANSI
AND
REF615
OR
2× IA=0A

3I
IB=0A

3I>/Io>BF 3I> 3I>→


IC=0A
IG=0. 0A
VAB=0.00kV
VBC=0. 00kV
VCA=0. 00kV

51BF/51NBF 51P-1 67-1 3P=0kW


3Q=0kVAr

OR Close ESC Clear

Menu

Open R Help
L

3I>> 3I>>→ 3I2f>


51P-2 67-2 68
OR
1 0 1 0 0 0 1 1 0 0 1 1 0 0
CONDITION MONITORING COMMUNICATION 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
AND SUPERVISION 1 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0 0 1
2× 2× Protocols: 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0

Io>>> Io> Io>→ 3I FUSEF CBCM TCS Master:


1
IEC 61850-8-1
1
1
0
0
1
0
1
1
0
1
1
1
1
0
0
1
1
1
1
0
0
1
1
0
0 0
50N/51N 51N-1 67N-1 60 CBCM TCM Slave: IEC 101, IEC 104,
OR Modbus®, DNP3 Level 2
UL1UL2UL3

Io Io>> Io>>→
Interfaces:
Ethernet: TX (RJ-45), FX (LC)
51N-2 67N-2
Serial: Serial glass fiber (ST),
OR RS-485, RS-232/485
3× 3× D-sub 9, IRIG-B
Yo>→ Po>→ Io>HA
21YN 32N 51NHA
OR OR
CONTROL AND INDICATION 1) MEASUREMENT

- I, U, Io, P, Q, E, pf, f
- Symmetrical components
Object Ctrl 2) Ind 3)
- Limit value supervision
CB 1 - - Power Quality functions
Uo>
59G
Uo DC - 2
Analog interface types 1)

ES - 2
Current transformer 4
1)
Check availability of binary inputs/outputs
from technical documentation Voltage transformer 3
2)
Control and indication function for 1)
Conventional transformer inputs
primary object
3)
Status indication function for
3× primary object
3U< U2> U1< PQM3I PQM3U PQMU
UL1UL2UL3 27 47O- 47U+ PQM3I PQM3V PQMV

3× 2×
3U> f>/f<, O→I PQUUB
df/dt
59 79 PQVUB
81

REMARKS
6× Optional 3× No. of Calculated OR Alternative
MAP function instances value function to be
MAP Io/Uo defined when
ordering

Load

GUID-7BCC1E2C-B131-4347-ACDE-8354FE999164 V1 EN

Figure 1. Functionality overview of RER615 standard configuration A

4 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Source
RER615 RECLOSER PROTECTION AND CONTROL IED STANDARD
D
CONFIGURATION
UL1bUL2bUL3b Version 1.0

PROTECTION LOCAL HMI ALSO AVAILABLE


IEC
- Disturbance recorder
2× Configuration A
- Event log
Master Trip
System
HMI
Time

- Fault recorder
A Authorization

Lockout relay U12 0. 0 kV

- IED self-supervision
P 0.00 kW
Q 0.00 kVAr
I
94/86
ESC Clear
IL2 0 A

O R
L
- Load profile
I ESC Clear - Local/Remote push-button on LHMI
- Recorded data
O R

2× L
- User management
I2> I2/I1> 3Ith>F 3I>>> - Web HMI
46 46PD 49F 50P/51P ANSI
AND
REF615
OR
2× IA=0A

3I
IB=0A

3I>/Io>BF 3I> 3I>→


IC=0A
IG=0. 0A
VAB=0.00kV
VBC=0. 00kV
VCA=0. 00kV

51BF/51NBF 51P-1 67-1 3P=0kW


3Q=0kVAr

OR Close ESC Clear

Menu

Open R Help
L

3I>> 3I>>→ 3I2f>


51P-2 67-2 68
OR
1 0 1 0 0 0 1 1 0 0 1 1 0 0
CONDITION MONITORING COMMUNICATION 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
AND SUPERVISION 1 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
2× 2× Protocols: 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0

Io>>> Io> Io>→ 3I FUSEF CBCM TCS Master:


1
IEC 61850-8-1
1
1
0
0
1
0
1
1
0
1
1
1
1
0
0
1
1
1
1
0
0
1
1
0
0 0
50N/51N 51N-1 67N-1 60 CBCM TCM Slave: IEC 101, IEC 104,
OR Modbus®, DNP3 Level 2
UL1UL2UL3

Io Io>> Io>>→
Interfaces:
Ethernet: TX (RJ-45), FX (LC)
51N-2 67N-2
Serial: Serial glass fiber (ST),
OR RS-485, RS-232/485
3× 3× D-sub 9, IRIG-B
Yo>→ Po>→ Io>HA
21YN 32N 51NHA
OR OR
CONTROL AND INDICATION 1) MEASUREMENT

- I, U, Io, P, Q, E, pf, f
- Symmetrical components
Object Ctrl 2) Ind 3)
- Limit value supervision
CB 1 - - Power Quality functions
Uo>
59G
Uo DC - 2
Analog interface types 1)

ES - 2
Current transformer 4
6× 1)
Check availability of binary inputs/outputs
Uo> MAP from technical documentation Voltage sensor 6
59G MAP 2)
Control and indication function for 1)
Conventional transformer inputs and
primary object combi sensor inputs
3)
Status indication function for
Uo UL1bUL2bUL3b primary object
PQM3I PQM3U PQMU
PQM3I PQM3V PQMV


3U< 3U< U2> SYNC O→I PQUUB
27 27 47O- 25 79 PQVUB


3U> U1< 3U>
59 47U+ 59
REMARKS
UL1UL2UL3 2× Optional 3× No. of Calculated OR Alternative
f>/f<, function instances value function to be
df/dt Io/Uo
81 defined when
ordering

Load

GUID-D0D32AE3-D6A0-45C3-82FE-2CDE8432F2B9 V1 EN

Figure 2. Functionality overview of RER615 standard configuration D

ABB 5
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 1. Standard configurations

Description Std. conf.

Directional overcurrent and directional earth-fault protection with phase voltage-based protection and measurement functions,
voltage protection and frequency protection, CB condition monitoring and CB control A

Directional overcurrent and directional earth-fault protection with phase voltage-based protection and measurement functions,
voltage protection and frequency protection, synchro-check, CB condition monitoring, CB control and voltage sensor inputs D

6 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 2. Supported functions

Function1)2) A D Ordering
option digit

Protection

Three-phase non-directional overcurrent protection, low stage 13) 13)

Three-phase non-directional overcurrent protection, high stage 13) 13)

Three-phase non-directional overcurrent protection, instantaneous stage 1 1

Three-phase directional overcurrent protection, low stage (2) (2) #13 = B

Three-phase directional overcurrent protection, high stage (1) (1) #13 = B

Non-directional earth-fault protection, low stage 14) 14)

Non-directional earth-fault protection, high stage 14) 14)

Non-directional earth-fault protection, instantaneous stage 1 1

Directional earth-fault protection, low stage (2) (2) #13 = A

Directional earth-fault protection, high stage (1) (1) #13 = A

Admittance-based earth-fault protection (3) (3) #13 = C

Wattmetric-based earth-fault protection (3) (3) #13 = D

Harmonics-based earth-fault protection (1) (1) #13 = E

Negative-sequence overcurrent protection 2 2

Phase discontinuity protection 1 1

Residual overvoltage protection (1) (2)5) #14 = A

Three-phase undervoltage protection (3) (3)6) #14 = A

Three-phase overvoltage protection (3) (3)6) #14 = A

Positive-sequence undervoltage protection (1) (1) #14 = A

Negative-sequence overvoltage protection (1) (1) #14 = A

Frequency protection (2) (2) #14 = A

Three-phase thermal protection for feeders, cables and distribution transformers 1 1

Circuit-breaker failure protection 1 1

Three-phase inrush detector 1 1

Master trip 2 2

Multi-purpose protection 6 6

Power quality

Current total demand distortion (1) (1) #15 = A

Voltage total harmonic distortion (1) (1) #15 = A

Voltage variation (1) (1) #15 = A

Voltage unbalance (1) (1) #15 = A

Control

Circuit-breaker control 1 1

Disconnector position indication 2 2

Earthing switch indication 2 2

ABB 7
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 2. Supported functions, continued


Function1)2) A D Ordering
option digit

Protection

Autoreclosing 1 1

Synchronism and energizing check 1

Condition monitoring

Circuit-breaker condition monitoring 1 1

Trip circuit supervision 2 2

Fuse failure supervision 1 1

Measurement

Disturbance recorder 1 1

Three-phase current measurement 1 1

Sequence current measurement 1 1

Residual current measurement 1 1

Three-phase voltage measurement 1 25)

Sequence voltage measurement 1 25)

Three-phase power and energy measurement 1 1

Frequency measurement 1 1

Load profile 1 1

1, 2, ... = number of included instances


() = optional

1) All directional protection functions can also be used in the non-directional mode
2) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration
3) Not available when choosing optional directional E/F function
4) Not available when choosing optional directional O/C function
5) Voltage group B is used in the second (2) instance
6) Voltage group B is used in the third (3) instance

3. Protection functions A syncrocheck function is offered with standard configuration


To allow the customers to customize the IED according to D. The synchrocheck function ensures that the voltage, phase
their requirements, it can be ordered as a basic IED or angle and frequency on either side of an open circuit breaker
enhanced with selected protection functions. The selection meet the conditions for a safe interconnection of two
depends on the application, whether it is a compensated networks.
network, and whether the compensated network is with
distributed generation or closed-loop feeders. Some advanced protection functions are optionally available
in RER615.
As a standard offering, the IED includes non-directional
overcurrent and non-directional earth-fault functions, as well Directional earth-fault protection (optional)
as other protection functions commonly accepted as a means Directional earth-fault protection is typically required in
to significantly improve the grid reliability in recloser isolated or compensated networks, but also in all network
applications, such as breaker failure and negative-sequence types where distributed generation can feed the fault current
overcurrent protection to detect a broken conductor. from various locations.
Alternatively, a more sensitive phase-discontinuity protection
The directional earth-fault protection requires that the residual
is available. Also thermal protection, which is used for
voltage is calculated from the phase-to-earth or phase-to-
protecting feeders, cables and distribution transformers, is
phase voltage transformers.
included.

8 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

wide application can be achieved using horizontal


Directional overcurrent protection (optional) communication, where the detection of a faulty feeder is
Directional overcurrent protection is typically required in made by comparing the harmonic earth-fault current
closed-loop applications, or when distributed generation is measurements.
available.
Voltage protection (optional)
The directional overcurrent protection requires voltage Voltage protection includes a wide variety of both voltage-
information from the phase-to-earth or phase-to-phase and frequency-based protections required, for example, in
voltage transformers. distributed generation applications. In addition to the basic
overvoltage and undervoltage protection, a positive
Admittance earth-fault protection (optional)
undervoltage protection isused to detect loss of mains is
Admittance-based earth-fault protection is a modern
included.
directional earht-fault protection. The admittance method is a
commonly used directional method for detecting earth faults, Residual overvoltage protection, which is used as a backup
especially in compensated networks. It can also be used in protection for the earth-fault protection, and negative-
high-impedance earthed and unearthed networks. sequence overvoltage protection, which is used for detection
Admittance earth-fault protection uses the neutral admittance of broken conductors, are also included.
(Y0) criterion, ensuring correct operation even if information
on the status of the Petersen coil is missing. Furthermore, it The frequency protection includes overfrequency,
offers an easy, straightforward setting principle. underfrequency and frequency rate-of-change protections.

The phase-directional elements provide a variety of different The IED includes a fuse failure supervision function to prevent
polarizing quantities, such as positive- or negative-sequence misoperation in voltage-based protections due to failure in the
voltage, self-polarizing (faulted) and cross-polarizing (healthy secondary circuit between the voltage transformer and the
voltages). The IED includes a memory function to secure IED.
reliable and correct directional operation in case of close
short circuits when the polarizing quantity may be low. Autoreclosing (optional)
The IED includes a powerful and flexible multi-shot
Admittance earth-fault protection can be used as a autoreclosing function. The autoreclosing function provides
standalone protection or in conjunction with the directional up to five programmable autoreclosing sequences, which can
earth-fault protection to provide additional information. It is perform one to five successive autoreclosing shots of desired
also used in distributed generation applications. type and duration.

Wattmetric earth-fault protection (optional) Power quality measurement (optional)


The wattmetric method is a commonly used directional The power quality measurement function provides
method for detecting earth faults, especially in compensated measurements required by today's smart grid networks,
networks. It can also be used in high-impedance earthed and where power quality plays an important role in managing the
unearthed networks. The protection uses the residual power distribution networks. Values such as the total harmonic
component Io x Uo x CosΦ. values for both current and voltage up to 11th harmonics,
voltage sags and swells, voltage interruption and voltage
The phase-directional elements provide a variety of different unbalance, give comprehensive information on the network,
polarizing quantities, such as positive- or negative-sequence which is commonly required by regulators.
voltage, self-polarizing (faulted) and cross-polarizing (healthy
voltages). The IED includes a memory function to secure
reliable and correct directional operation in case of close
short circuits when polarizing quantity may be low.

Wattmetric-based earth-fault protection can be used as a


standalone protection or in conjunction with the directional
earth-fault protection to give additional information. It is also
used in distributed generation applications.

Harmonic earth-fault protection (optional)


Harmonics-based earth-fault protection is used in networks
where a fundamental frequency component of the earth-fault
current is low due to compensation. The harmonics-based
earth-fault protection needs substation-wide information since
the feeder with the highest harmonics value is the feeder with
the active earth fault and needs to be tripped. Substation-
ABB 9
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

4. Application generation and demanding interlocking applications. Because


The recloser protection IED RER615 is suitable for a variety of of the large number of protection functions, the illustrated
applications, ranging from basic applications on the line applications are only example applications which can be
recloser to sophisticated applications including distributed extended to meet tomorrow's requirements.

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

IL2 0 A

I ESC Clear

O R
L

3I
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

IL2 0 A
A

RER615
3U I ESC Clear
Std. conf. A
O R
L

ANSI IEC

21YN 1) Yo>→1)
46PD I2/I1>
49F 3Ith>F
50P/51P 3I>>>
67/67N 3I→/Io→
79 O→I

1)
or 51NHA (Io>HA), 32N (Po>→)

GUID-DFFEAC20-C31D-4D65-9E2A-0B42363196C8 V1 EN

Figure 3. Selective protection in radial feeder

Figure 3 illustrates selective protection in a radial feeder with earth-fault protection. Additionally, directional overcurrent
autoreclosing functionality and advanced admittance-based protection for distributed generation applications is included.

IEC 61850 and GOOSE IEC 61850 and GOOSE

RER615 RER615 RER615 RER615


A A

U12 0. 0 kV U12 0. 0 kV A A
P 0.00 kW P 0.00 kW
Q 0.00 kVAr Q 0.00 kVAr
U12 0. 0 kV U12 0. 0 kV
IL2 0 A IL2 0 A P 0.00 kW P 0.00 kW
Q 0.00 kVAr Q 0.00 kVAr
IL2 0 A IL2 0 A

I ESC Clear
I ESC Clear

I ESC Clear
I ESC Clear

O R
L O R
L

O R
L O R
L

Fault

RER615 RER615 RER615 RER615 RER615 RER615


A A A A A A

U12 0. 0 kV U12 0. 0 kV U12 0. 0 kV U12 0. 0 kV U12 0. 0 kV U12 0. 0 kV


P 0.00 kW P 0.00 kW P 0.00 kW P 0.00 kW P 0.00 kW P 0.00 kW
Q 0.00 kVAr Q 0.00 kVAr Q 0.00 kVAr Q 0.00 kVAr Q 0.00 kVAr Q 0.00 kVAr
IL2 0 A IL2 0 A IL2 0 A IL2 0 A IL2 0 A IL2 0 A

I ESC Clear
I ESC Clear
I ESC Clear
I ESC Clear
I ESC Clear
I ESC Clear

O R
L O R
L O R
L O R
L O R
L O R
L

Pre-fault state Post-fault state

GUID-2B2034FA-A359-4FE7-B166-21CD9B214255 V1 EN

Figure 4. Fault detection, isolation and restoration in radial feeder

Exact earth-fault and overcurrent protection enables the closed loop network is of radial type with one normal
autonomous fault detection, isolation and restoration, and open point (NOP). The fault is accurately located between two
can be achieved through IEC 61850 and GOOSE circuit breakers, isolating the faulty part and allowing NOP to
communication as illustrated in Figure 4. In the pre-fault state, be closed.

10 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

U12 0. 0 kV
A
IEC 61850 and GOOSE
P 0.00 kW
Q 0.00 kVAr

IL2 0 A

I ESC Clear

O R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

IL2 0 A

I ESC Clear

O R
L

DG
3I

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

IL2 0 A
A

3Ub U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

IL2 0 A
A

3U RER615
I ESC Clear
I ESC Clear
Std. conf. D
O R
L O R
L

ANSI IEC

21YN 1) Yo>→1)
25 SYNC
47O-/59 U2>/3U>
47U+/27 U1</3U<
49F 3Ith>F
50P/51P 3I>>>
67/67N 3I→/Io→
79 O→I
81 f</f>,df/dt
1)
or 51NHA (Io>HA), 32N (Po>→)

GUID-15D94072-4B19-49EA-95DF-4698B923C9CE V1 EN

Figure 5. Protection of distributed generation plant

The advanced protection functionality of RER615 ensures GOOSE communication as seen in Figure 5. Safe
secure protection of distributed generation against faults, and reconnection is enabled by using the synchrocheck
early indication of loss-of-mains through IEC 61850 and functionality.

5. Supported ABB solutions of the protection and communication system, and an inherent
RER615 integrates fully with other ABB products such as the flexibility regarding reconfiguration and upgrades.
grid automation controller COM600, MicroSCADA, SYS600,
DMS600, and with ABB's secure, reliable and tested At substation level, COM600 uses the data content of the bay-
communication solutions, RER601 and the M2M gateway. level IEDs to enhance substation level functionality. COM600
ABB can thus offer a solution which meets the demanding features a Web browser-based HMI, which provides a
customer requirements regarding smart grids, and which also customizable graphical display for visualizing single-line mimic
contributes to faster engineering. diagrams for switchgear bay solutions. The Web HMI of
COM600 also provides an overview of the whole substation,
To facilitate and streamline the system engineering, ABB's including IED-specific single-line diagrams, which makes
IEDs are supplied with connectivity packages. The information easily accessible. Substation devices and
connectivity packages include a compilation of software and processes can also be remotely accessed through the Web
IED-specific information, including single-line diagram HMI, which improves personnel safety.
templates and a full IED data model. The data model also
includes event and parameter lists. With the connectivity In addition, COM600 can be used as a local data warehouse
packages, the IEDs can be readily configured using PCM600 for the substation's technical documentation and for the
and integrated with the grid automation controller COM600 or network data collected by the IEDs. The collected network
the network control and management system MicroSCADA data facilitates extensive reporting and analyzing of network
Pro. fault situations, by using the data historian and event handling
features of COM600. The data historian can be used for
Compared to traditional hard-wired, inter-device signaling, accurate monitoring of process and equipment performance,
peer-to-peer communication over a switched Ethernet LAN using calculations based on both real-time and history values.
offers an advanced and versatile platform for power system A better understanding of the process dynamics is achieved
protection. Among the distinctive features of the protection by combining time-based process measurements with
system approach, enabled by the full implementation of the production and maintenance events.
IEC 61850 substation automation standard, are fast software-
based communication, continuous supervision of the integrity
ABB 11
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

COM600 can also function as a gateway and provides network-level control and management systems, such as
seamless connectivity between the substation IEDs and MicroSCADA Pro and System 800xA.

Table 3. Supported ABB solutions

Product Version

Grid automation controller COM600 4.0 or later

MicroSCADA Pro SYS 600 9.3 FP2 or later

System 800xA 5.1 or later

6. Control the residual current. The IED additionally offers frequency


One circuit breaker can be controlled via the front panel HMI measurement. The IED also calculates the demand value of
of RER615 or via a remote system. The IED also provides the current over a user-selectable, pre-set time frame, the
position indication for two disconnectors and two earthing thermal overload of the protected object, and the phase
switches. unbalance based on the ratio between the negative-sequence
and positive-sequence current. Active and reactive power as
Each controllable primary device requires two physical binary well as residual voltage are also calculated.
inputs and two physical binary outputs. For indication-only
objects, two physical inputs are enough. The number of Power quality measurement, such as total harmonic values
available binary inputs and outputs varies depending on the for both current and voltage, voltage sags and swells, and
chosen standard configuration for the IED. In addition, some voltage unbalance, is supported.
standard configurations also offer optional hardware modules,
which increases the number of available binary inputs and Furthermore, the IED offers three-phase power and energy
outputs. measurement including power factor.

If the amount of available binary inputs or outputs of the The values measured can be accessed locally via the user
chosen standard configuration is not sufficient, the interface on the IED front panel or remotely via the
configuration can be modified to release some binary inputs communication interface of the IED. The values can also be
or outputs originally configured for other purposes. In this accessed locally or remotely using the Web browser-based
case, an external input/output module, for example, RIO600, user interface.
can be integrated with the IED and its binary inputs and
outputs used for the less time-critical binary signals of the 8. Disturbance recorder
application. The IED is provided with a disturbance recorder with up to 12
analog and 64 binary signal channels. The analog channels
The suitability of the IED's binary outputs selected for
can be set to record either the waveform or the trend of the
controlling primary devices should be carefully verified, for
currents and voltages measured.
example, regarding the make and carry and the breaking
capacity. If the requirements for the control circuit of the The analog channels can be set to trigger the recording
primary device are not met, the use of external auxiliary IEDs function when the measured value falls below, or exceeds,
should be considered. the set values. The binary signal channels can be set to start
a recording either on the rising or the falling edge of the
The optional, large, graphical LCD of the IED's HMI includes a
binary signal or on both.
single-line diagram with position indication for the relevant
primary devices. Interlocking schemes required by the By default, the binary channels are set to record external or
application are configured using the signal matrix or the internal IED signals, for example, the start or trip signals of
application configuration function of PCM600. Depending on the IED stages, or external blocking or control signals. Binary
the standard configuration, the IED also has a synchrocheck IED signals, such as protection start and trip signals, or an
function to ensure that the voltage, phase angle and external IED control signal via a binary input, can be set to
frequency on either side of an open circuit breaker meet the trigger the recording. The recorded information is stored in a
conditions for a safe interconnection of two networks. non-volatile memory and can be uploaded for subsequent
fault analysis.
7. Measurement
The IED continuously measures the phase currents and
voltages, the symmetrical components of the currents, and
12 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

9. Event log 13. Self-supervision


To collect sequence-of-events information, the IED has a non- The IED’s built-in self-supervision system continuously
volatile memory with a capacity of storing 1024 events with monitors the state of the IED hardware and the operation of
associated time stamps. The non-volatile memory retains its the IED software. Any fault or malfunction detected is used
data also in case the IED temporarily loses its auxiliary supply. for alerting the operator.
The event log facilitates detailed pre- and post-fault analyses
of feeder faults and disturbances. The increased capacity to A permanent IED fault blocks the protection functions to
process and store data and events in the IED offers prevent incorrect operation.
prerequisites to support the growing information demand of
future network configurations. 14. Fuse failure supervision
The fuse failure supervision detects failures between the
The sequence-of-events information can be accessed either
voltage measurement circuit and the IED. The failures are
locally via the user interface on the IED front panel, or
detected either by the negative sequence-based algorithm or
remotely via the communication interface of the IED. The
by the delta voltage and delta current algorithm. Upon the
information can also be accessed using the Web browser-
detection of a failure, the fuse failure supervision function
based user interface, either locally or remotely.
activates an alarm and blocks voltage-dependent protection
functions from unintended operation.
10. Recorded data
The IED has the capacity to store the records of the 128
15. Access control
latest fault events. The records enable the user to analyze the
To protect the IED from unauthorized access and to maintain
power system events. The available measurement modes
information integrity, the IED is provided with a four-level, role-
include DFT, RMS and peak-to-peak. Fault records store IED
based authentication system with administrator-
measurement values at the moment when any protection
programmable individual passwords for the viewer, operator,
function starts. In addition, the maximum demand current
engineer and administrator level. The access control applies
with time stamp is separately recorded. By default, the
to the front-panel user interface, the Web browser-based
records are stored in the nonvolatile memory.
user interface and PCM600.
Furthermore, the IED includes a load profile recorder capable
of storing measurement values into the IED's memory. The 16. Inputs and outputs
selected measurement values averaged over the selected Depending on the selected standard configuration, the IED is
period, ranging from one minute to three hours, are stored in equipped with different analog input channels. Standard
a nonvolatile memory. Depending on the selected configuraton A provides three phase-current inputs, one
measurements and averaging period, the overall length of the residual current input and three voltage inputs. Standard
load profile recording ranges from some days to several configuration D provides three phase-current inputs, one
months, even a year, making this feature suitable for residual current input and six sensor voltage inputs.
monitoring long-time load behavior for the interested loads.
The phase-current inputs are rated 1/5 A and the residual
current input 0.2/1 A. The residual current is suitable for
11. Condition monitoring
applications requiring sensitive earth-fault protection and
The condition monitoring functions of the IED constantly
which have core balance current transformers. As the residual
monitors the performance and the condition of the circuit
current is usually limited to small values, it can also be used
breaker. The monitoring comprises the spring charging time,
in applications where even the phase current is 5A. The three
SF6 gas pressure, the travel-time and the inactivity time of
phase voltage inputs and the residual voltage input cover the
the circuit breaker.
rated voltages 60...210 V. Both phase-to-phase voltages and
The monitoring functions provide operational circuit breaker phase-to-earth voltages can be connected.
history data, which can be used for scheduling preventive
The nominal secondary voltage of voltage sensor inputs is
circuit-breaker maintenance.
user-programmable, supporting both capacitive and resistive
voltage sensors from 6 kV up to 36 kV.
12. Trip-circuit supervision
The trip-circuit supervision continuously monitors the The phase current input 1 A or 5 A, the residual current input
availability and operability of the trip circuit. It provides open- 0.2 A or 1 A and the rated voltage of the residual voltage
circuit monitoring both when the circuit breaker is in its input are selected in the IED software. In addition, the binary
closed and in its open position. It also detects loss of circuit- input thresholds 18…176 V DC are selected by adjusting the
breaker control voltage. IED's parameter settings.

ABB 13
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

All the binary input and output contacts are freely


configurable with the Signal Matrix or Application
Configuration tool in PCM600.

Table 4. Number of physical connections in standard configurations

Configuration Analog channels Binary channels

Currents Voltages Inputs Outputs

A 4 3 8(14)1) 10(13)1)

D 4 62) 12 10

1) With optional BIO0006 module


2) Support for phase voltage sensors with the SIM0001 module

17. Station communication and TCP modes. In addition to the standard Modbus
The IED supports a variety of communication protocols, functionality, the IED supports retrieval of timestamped
including IEC 61850 and the most common remote control events, changing the active setting group and uploading the
protocols IEC 60870-5-104, IEC 60870-5-101 Modbus and latest fault records. If a Modbus TCP connection is used, five
DNP3. Operational information and controls are available clients can be connected to the IED at the same time.
through these protocols. However, some communication Modbus serial and Modbus TCP can also be used in parallel
functionality, for example the horizontal communication and IEC 61850 and Modbus simultaneously, if required. In
between the IEDs, is only possible through the IEC 61850 addition to the basic standard functionality, the IED supports
communication protocol. changing of the active setting group and uploading of
disturbance recordings in the IEC 60870-5-101/104 format.
The IEC 61850 communication implementation supports all DNP3 supports both serial and TCP modes for connection to
the monitoring and control functions. Additionally, parameter one master. Also changing of the active setting group is
settings, disturbance recordings and fault records can be supported. When the IED uses the RS-485 bus for serial
accessed using the IEC 61850 protocol. Disturbance communication, both 2-wire and 4-wire connections are
recordings are available for any Ethernet-based application in supported. Termination and pull-up/down resistors can be
the standard COMTRADE file format. The IED supports configured with jumpers on the communication card, which is
simultaneous event reporting to five different clients over the why no external resistors are required.
station bus.
The IED supports several time synchronization methods with
The IED can send binary signals to other IEDs (so-called a time-stamping resolution of 1 ms.
horizontal communication) using the IEC 61850-8-1 GOOSE
profile. Binary GOOSE messaging can, for example, be used Ethernet-based
for protection and interlocking-based protection schemes. • SNTP
The IED meets the GOOSE performance requirements for
tripping applications in distribution substations, as defined by
With special time synchronization wiring
the IEC 61850 standard. Furthermore, the IED supports the
• IRIG-B
sending and receiving of analog values using GOOSE
messaging. Analog GOOSE messaging enables fast transfer
of the analog measurement values over the station bus. This In addition, the IED supports time synchronization via four
facilitates, for example, the sharing of RTD input values, such serial communication protocols.
as surrounding temperature, with other IED applications. • Modbus
• DNP3
All communication connectors, except for the front port • IEC 60870-5-101
connector, are placed on integrated optional communication • IEC 60870-5-104
modules. Modbus implementation supports the RTU, ASCII

14 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 5. Supported station communication interfaces and protocols

Interfaces/Protocols Ethernet Serial

100BASE-TX RJ-45 100BASE-FX LC RS-232/RS-485 Fibre-optic ST

IEC 61850 ● ● - -

MODBUS RTU/ASCII - - ● ●

MODBUS TCP/IP ● ● - -

DNP3 (serial) - - ● ●

DNP3 TCP/IP ● ● - -

IEC 60870-5-101 - - ● ●

IEC 60870-5-104 ● ● - -
● = Supported

ABB 15
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

18. Technical data

Table 6. Dimensions

Description Value

Width frame 177 mm

case 164 mm

Height frame 177 mm (4U)

case 160 mm

Depth 201 mm (153 + 48 mm)

Weight complete IED 4.1 kg

plug-in unit only 2.1 kg

Table 7. Power supply

Description Value

Uauxnominal 24, 30, 48, 60 V DC

Maximum interruption time in the auxiliary DC voltage without resetting


the IED

Uauxvariation 50...120% of Un (12...72 V DC)

Start-up threshold 19.2 V DC (24 V DC * 80%)

Burden of auxiliary voltage supply under quiescent (Pq)/operating DC <12.0 W (nominal)/<18.0 W (max.)
condition

Ripple in the DC auxiliary voltage Max. 15% of the DC value (at frequency of 100 Hz)

Fuse type T4A/250 V

Table 8. Energizing inputs

Description Value

Rated frequency 50/60 Hz

Current inputs Rated current, In 0.2/1 A1) 1/5 A2)

Thermal withstand capability

• Continuously 4A 20 A

• For 1 s 100 A 500 A

Dynamic current withstand

• Half-wave value 250 A 1250 A

Input impedance <100 mΩ <20 mΩ

Voltage inputs Rated voltage 60...210 V AC

Voltage withstand

• Continuous 240 V AC

• For 10 s 360 V AC

Burden at rated voltage <0.05 VA

1) Ordering option for residual current input


2) Residual current and/or phase current

16 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 9. Energizing inputs of SIM0001

Description Value

Voltage sensor input Rated voltage 5 kV...38 kV1)

Continuous voltage withstand 125 V AC2)

Input impedance at 50/60 Hz 1 MΩ3)

1) This range is covered with sensor division ratio of 10 000:1


2) Test to this voltage
3) Neutral input impedance is close to zero

Table 10. Binary inputs

Description Value

Operating range ±20% of the rated voltage

Rated voltage 24...250 V DC

Current drain 1.6...1.9 mA

Power consumption 31.0...570.0 mW

Threshold voltage 18...176 V DC

Reaction time 3 ms

Table 11. Signal output with high make and carry

Description Value 1)

Rated voltage 250 V AC/DC

Continuous contact carry 5A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R <40 ms 1 A/0.25 A/0.15 A

Minimum contact load 100 mA at 24 V AC/DC

1) X100: SO1
X110: SO1, SO2

Table 12. Signal outputs and IRF output

Description Value 1)

Rated voltage 250 V AC/DC

Continuous contact carry 5A

Make and carry for 3.0 s 10 A

Make and carry 0.5 s 15 A

Breaking capacity when the control-circuit time constant L/R <40 ms, at 1 A/0.25 A/0.15 A
48/110/220 V DC

Minimum contact load 10 mA at 5 V AC/DC

1) X100: IRF,SO2
X110: SO3, SO4

ABB 17
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 13. Double-pole power outputs with TCS function X100: PO3 and PO4

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R <40 ms, at 5 A/3 A/1 A
48/110/220 V DC (two contacts connected in a series)

Minimum contact load 100 mA at 24 V AC/DC

Trip-circuit monitoring (TCS)

• Control voltage range 20...250 V AC/DC

• Current drain through the monitoring circuit ~1.5 mA

• Minimum voltage over the TCS contact 20 V AC/DC (15...20 V)

Table 14. Single-pole power output relays X100: PO1 and PO2

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R <40 ms, at 5 A/3 A/1 A
48/110/220 V DC

Minimum contact load 100 mA at 24 V AC/DC

Table 15. Front port Ethernet interfaces

Ethernet interface Protocol Cable Data transfer rate

Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s

Table 16. Station communication link, fibre-optic

Connector Fibre type1) Wave length Max. distance Permitted path attenuation2)

LC MM 62.5/125 or 50/125 μm 1300 nm 2 km <8 dB


glass fibre core

ST MM 62.5/125 or 50/125 μm 820...900 nm 1 km <11 dB


glass fibre core

1) (MM) multi-mode fibre, (SM) single-mode fibre


2) Maximum allowed attenuation caused by connectors and cable together

18 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 17. IRIG-B

Description Value

IRIG time code format B004, B0051)

Isolation 500V 1 min

Modulation Unmodulated

Logic level TTL Level

Current consumption 2...4 mA

Power consumption 10...20 mW

1) According to the 200-04 IRIG standard

Table 18. Degree of protection of flush-mounted IED

Description Value

Front side IP 54

Rear side, connection terminals IP 20

Table 19. Environmental conditions

Description Value

Operating temperature range -25...+55ºC (continuous)

Short-time service temperature range -40...+85ºC (<16h)1)2)

Relative humidity <93%, non-condensing

Atmospheric pressure 86...106 kPa

Altitude Up to 2000 m

Transport and storage temperature range -40...+85ºC

1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For IEDs with an LC communication interface the maximum operating temperature is +70 ºC

ABB 19
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 20. Electromagnetic compatibility tests

Description Type test value Reference

1 MHz/100 kHz burst disturbance test IEC 61000-4-18


IEC 60255-22-1, class III
IEEE C37.90.1-2002

• Common mode 2.5 kV

• Differential mode 2.5 kV

3 MHz, 10 MHz and 30 MHz burst disturbance IEC 61000-4-18


test IEC 60255-22-1, class III

• Common mode 2.5 kV

Electrostatic discharge test IEC 61000-4-2


IEC 60255-22-2
IEEE C37.90.3-2001

• Contact discharge 8 kV

• Air discharge 15 kV

Radio frequency interference test

10 V (rms) IEC 61000-4-6


f = 150 kHz...80 MHz IEC 60255-22-6, class III

10 V/m (rms) IEC 61000-4-3


f = 80...2700 MHz IEC 60255-22-3, class III

10 V/m ENV 50204


f = 900 MHz IEC 60255-22-3, class III

20 V/m (rms) IEEE C37.90.2-2004


f = 80...1000 MHz

Fast transient disturbance test IEC 61000-4-4


IEC 60255-22-4
IEEE C37.90.1-2002

• All ports 4 kV

Surge immunity test IEC 61000-4-5


IEC 60255-22-5

• Communication 1 kV, line-to-earth

• Other ports 4 kV, line-to-earth


2 kV, line-to-line

Power frequency (50 Hz) magnetic field IEC 61000-4-8


immunity test

• Continuous 300 A/m


• 1...3 s 1000 A/m

Pulse magnetic field immunity test 1000 A/m IEC 61000-4-9


6.4/16 µs

Damped oscillatory magnetic field immunity test IEC 61000-4-10

• 2s 100 A/m

• 1 MHz 400 transients/s

Power frequency immunity test Binary inputs only IEC 61000-4-16


IEC 60255-22-7, class A

• Common mode 300 V rms

• Differential mode 150 V rms

20 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 20. Electromagnetic compatibility tests, continued


Description Type test value Reference

Emission tests EN 55011, class A


IEC 60255-25

• Conducted

0.15...0.50 MHz <79 dB (µV) quasi peak


<66 dB (µV) average

0.5...30 MHz <73 dB (µV) quasi peak


<60 dB (µV) average

• Radiated

30...230 MHz <40 dB (µV/m) quasi peak, measured at 10 m


distance

230...1000 MHz <47 dB (µV/m) quasi peak, measured at 10 m


distance

Table 21. Insulation tests

Description Type test value Reference

Dielectric tests 2 kV, 50 Hz, 1 min IEC 60255-5 and


500 V, 50 Hz, 1 min, communication IEC 60255-27

Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J IEC 60255-5 and
1 kV, 1.2/50 μs, 0.5 J, communication IEC 60255-27

Insulation resistance measurements >100 MΩ, 500 V DC IEC 60255-5 and


IEC 60255-27

Protective bonding resistance <0.1 Ω, 4 A, 60 s IEC 60255-27

Table 22. Mechanical tests

Description Reference Requirement

Vibration tests (sinusoidal) IEC 60068-2-6 (test Fc) Class 2


IEC 60255-21-1

Shock and bump test IEC 60068-2-27 (test Ea shock) Class 2


IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2

Seismic test IEC 60255-21-3 Class 2

Table 23. Environmental tests

Description Type test value Reference

Dry heat test • 96 h at +55ºC IEC 60068-2-2


• 16 h at +85ºC1)

Cold test • 96 h at -25ºC IEC 60068-2-1


• 16 h at -40ºC

Damp heat test • 6 cycles (12 h + 12 h) at +25°C…+55°C, IEC 60068-2-30


humidity >93%

Change of temperature test • 5 cycles (3 h + 3 h) IEC60068-2-14


at -25°C...+55°C

Storage test • 96 h at -40ºC IEC 60068-2-1


• 96 h at +85ºC IEC 60068-2-2

1) For IEDs with an LC communication interface the maximum operating temperature is +70 o C

ABB 21
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 24. Product safety

Description Reference

LV directive 2006/95/EC

Standard EN 60255-27 (2005)


EN 60255-1 (2009)

Table 25. EMC compliance

Description Reference

EMC directive 2004/108/EC

Standard EN 50263 (2000)


EN 60255-26 (2007)

Table 26. RoHS compliance

Description

Complies with RoHS directive 2002/95/EC

22 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Protection functions

Table 27. Three-phase non-directional overcurrent protection ((F)PHxPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

FPHLPTOC ±1.5% of the set value or ±0.002 × In

PHHPTOC ±1.5% of set value or ±0.002 × In


and (at currents in the range of 0.1…10 × In)
PHIPTOC ±5.0% of the set value
(at currents in the range of 10…40 × In)

Start time 1)2) Minimum Typical Maximum

PHIPTOC:
IFault = 2 × set Start value 16 ms 19 ms 23 ms
IFault = 10 × set Start value
11 ms 12 ms 14 ms

PHHPTOC and FPHLPTOC:


IFault = 2 x set Start value
22 ms 24 ms 25 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
±5.0% of the theoretical value or ±40 ms 3)4)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression

1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
4) Valid for FPHLPTOC

ABB 23
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 28. Three-phase non-directional overcurrent protection (FPHxPTOC) main settings

Parameter Function Value (Range) Step

Start Value FPHLPTOC 0.05...5.00 × In 0.01

PHHPTOC 0.10...40.00 × In 0.01

PHIPTOC 1.00...40.00 × In 0.01

Time multiplier FPHLPTOC 0.05...15.00 0.01

PHHPTOC 0.05...15.00 0.01

Operate delay time FPHLPTOC 40...200000 ms 10

PHHPTOC 40...200000 ms 10

PHIPTOC 20...200000 ms 10

Operating curve type1) FPHLPTOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19,
-1, -2, -3, -4, -5, -6, -7, -8, -9, -10, -11, -12, -13, -14, -15, -16, -17, -18,
-19, -20, -21, -22, -23, -24, -25, -26, -27, -28, -29, -30, -31, -32, -33,
-34, -35, -36, -37, -38, -39

PHHPTOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

PHIPTOC Definite time

1) For further reference, see Operation characteristics table

24 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 29. Three-phase directional overcurrent protection ((F)DPHxPDOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current/voltage measured: fn ±2 Hz

FDPHLPDOC Current:
±1.5% of the set value or ±0.002 × In
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°

DPHHPDOC Current:
±1.5% of the set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°

Start time1)2) Minimum Typical Maximum

IFault = 2.0 × set Start value 38 ms 43 ms 46 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
±5.0% of the theoretical value or ±40 ms 3)4)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Measurement mode and Pol quantity = default, current before fault = 0.0 × I n, voltage before fault = 1.0 × U n, f n = 50 Hz, fault current in one phase with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n, Start value multiples in range of 1.5 to 20
4) Valid for FDPHLPDOC

ABB 25
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 30. Three-phase directional overcurrent protection (FDPHxPDOC) main settings

Parameter Function Value (Range) Step

Start value FDPHLPDOC 0.05...5.00 × In 0.01

DPHHPDOC 0.10...40.00 × In 0.01

Time multiplier DPHxPDOC 0.05...15.00 0.01

Operate delay time DPHxPDOC 40...200000 ms 10

Directional mode DPHxPDOC 1 = Non-directional


2 = Forward
3 = Reverse

Characteristic angle DPHxPDOC -179...180° 1

Operating curve type1) FDPHLPDOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19, -1,
-2, -3, -4, -5, -6, -7, -8, -9, -10, -11, -12, -13, -14, -15, -16, -17, -18, -19,
-20, -21, -22, -23, -24, -25, -26, -27, -28, -29, -30, -31, -32, -33, -34,
-35, -36, -37, -38, -39

DPHHPDOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

1) For further reference, refer to the Operating characteristics table

Table 31. Non-directional earth-fault protection ((F)EFxPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

FEFLPTOC ±1.5% of the set value or ±0.002 × In

EFHPTOC ±1.5% of set value or ±0.002 × In


and (at currents in the range of 0.1…10 × In)
EFIPTOC ±5.0% of the set value
(at currents in the range of 10…40 × In)

Start time 1)2) Minimum Typical Maximum

EFIPTOC:
IFault = 2 × set Start value 16 ms 19 ms 23 ms
IFault = 10 × set Start value 11 ms 12 ms 14 ms

EFHPTOC and EFLPTOC:


IFault = 2 × set Start value 22 ms 24 ms 25 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
±5.0% of the theoretical value or ±40 ms 3)4)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression

1) Measurement mode = default (depends on stage), current before fault = 0.0 × I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 1.5...20
4) Valid for FEFLPTOC

26 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 32. Non-directional earth-fault protection (FEFxPTOC) main settings

Parameter Function Value (Range) Step

Start value FEFLPTOC 0.010...5.000 × In 0.005

EFHPTOC 0.10...40.00 × In 0.01

EFIPTOC 1.00...40.00 × In 0.01

Time multiplier FEFLPTOC 0.05...15.00 0.01

EFHPTOC 0.05...15.00 0.01

Operate delay time FEFLPTOC 40...200000 ms 10

EFHPTOC 40...200000 ms 10

EFIPTOC 20...200000 ms 10

Operating curve type1) FEFLPTOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19, -1,
-2, -3, -4, -5, -6, -7, -8, -9, -10, -11, -12, -13, -14, -15, -16, -17, -18, -19,
-20, -21, -22, -23, -24, -25, -26, -27, -28, -29, -30, -31, -32, -33, -34,
-35, -36, -37, -38, -39

EFHPTOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

EFIPTOC Definite time

1) For further reference, see Operation characteristics table

ABB 27
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 33. Directional earth-fault protection ((F)DEFxPDEF)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

FDEFLPDEF Current:
±1.5% of the set value or ±0.002 × In
Voltage
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°

DEFHPDEF Current:
±1.5% of the set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°

Start time 1)2) Minimum Typical Maximum

DEFHPDEF
IFault = 2 × set Start value 42 ms 44 ms 46 ms

FDEFLPDEF 61 ms 64 ms 66 ms
IFault = 2 × set Start value

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
±5.0% of the theoretical value or ±40 ms 3)4)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression

1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × I n , f n = 50 Hz, earth-fault current
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 1.5 to 20
4) Valid for FDEFLPDEF

28 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 34. Directional earth-fault protection (FDEFxPDEF) main settings

Parameter Function Value (Range) Step

Start Value FDEFLPDEF 0.010...5.000 × In 0.005

DEFHPDEF 0.10...40.00 × In 0.01

Directional mode FDEFLPDEF and DEFHPDEF 1 = Non-directional


2 = Forward
3 = Reverse

Time multiplier FDEFLPDEF 0.05...15.00 0.01

DEFHPDEF 0.05...15.00 0.01

Operate delay time FDEFLPDEF 60...200000 ms 10

DEFHPDEF 40...200000 ms 10

Operating curve type1) FDEFLPDEF Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19, -1,
-2, -3, -4, -5, -6, -7, -8, -9, -10, -11, -12, -13, -14, -15, -16, -17, -18, -19,
-20, -21, -22, -23, -24, -25, -26, -27, -28, -29, -30, -31, -32, -33, -34,
-35, -36, -37, -38, -39

DEFHPDEF Definite or inverse time


Curve type: 1, 3, 5, 15, 17

Operation mode FDEFLPDEF and DEFHPDEF 1 = Phase angle


2 = IoSin
3 = IoCos
4 = Phase angle 80
5 = Phase angle 88

1) For further reference, refer to the Operating characteristics table

Table 35. Admittance-based earth-fault protection (EFPADM)

Characteristic Value

Operation accuracy1) At the frequency f = fn

±1.0% or ±0.01 mS
(In range of 0.5...100 mS)

Start time2) Minimum Typical Maximum

56 ms 60 ms 64 ms

Reset time 40 ms

Operate time accuracy ±1.0% of the set value of ±20 ms

Suppression of harmonics -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Uo = 1.0 × Un
2) Includes the delay of the signal output contact. Results based on statistical distribution of 1000 measurements.

ABB 29
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 36. Admittance-based earth-fault protection (EFPADM) main settings

Parameter Function Value (Range) Step

Voltage start value EFPADM 0.01...2.00 × Un 0.01

Directional mode EFPADM 1 = Non-directional


2 = Forward
3 = Reverse

Operation mode EFPADM 1 = Yo


2 = Go
3 = Bo
4 = Yo, Go
5 = Yo, Bo
6 = Go, Bo
7 = Yo, Go, Bo

Operate delay time EFPADM 60...200000 ms 10

Circle radius EFPADM 0.05...500.00 mS 0.01

Circle conductance EFPADM -500.00...500.00 mS 0.01

Circle susceptance EFPADM -500.00...500.00 mS 0.01

Conductance forward EFPADM -500.00...500.00 mS 0.01

Conductance reverse EFPADM -500.00...500.00 mS 0.01

Conductance tilt Ang EFPADM -30...30° 1

Susceptance forward EFPADM -500.00...500.00 mS 0.01

Susceptance reverse EFPADM -500.00...500.00 mS 0.01

Susceptance tilt Ang EFPADM -30...30° 1

Table 37. Wattmetric based earth-fault protection (WPWDE)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

Current and voltage:


±1.5% of the set value or ±0.002 × In
Power:
±3% of the set value or ±0.002 × Pn

Start time 1)2) Typically 63 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in IDMT mode ±5.0% of the set value or ±20 ms

Suppression of harmonics -50 dB at f = n × fn, where n=2,3,4,5,…

1) Io varied during the test. Uo = 1.0 × U n = phase to earth voltage during earth-fault in compensated or un-earthed network. The residual power value before fault = 0.0 pu, f n = 50 Hz,
results based on statistical distribution of 1000 measurement.
2) Includes the delay of the signal output contact.

30 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 38. Wattmetric based earth-fault protection (WPWDE) main settings

Parameter Function Value (Range) Step

Directional mode WPWDE 2 = Forward


3 = Reverse

Current start value WPWDE 0.010...5.000 × In 0.001

Voltage start value WPWDE 0.010...1.000 × Un 0.001

Power start value WPWDE 0.003...1.000 × Pn 0.001

Reference power WPWDE 0.050...1.000 × Pn 0.001

Characteristic angle WPWDE -179...180° 1

Time multiplier WPWDE 0.05...2.00 0.01

Operating curve type WPWDE Definite or inverse time


Curve type: 5, 15, 20

Operate delay time WPWDE 60...200000 ms 10

Min operate current WPWDE 0.010...1.000 × In 0.001

Min operate voltage WPWDE 0.01...1.00 × Un 0.01

Table 39. Harmonics earth-fault protection (HAEFPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±5% of the set value or ±0.004 × In

Start time 1)2) Typically 77 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in IDMT mode 3) ±5.0% of the set value or ±20 ms

Suppression of harmonics -50 dB at f = fn

-3 dB at f = 13 × fn

1) Fundamental frequency current = 1.0 × I n. Harmonics current before fault = 0.0 × I n , harmonics fault current 2.0 × Start value. Results based on statistical distribution of 1000
measurement.
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 2 to 20

Table 40. HAEFPTOC main settings

Parameter Function Value (Range) Step

Start value HAEFPTOC 0.05...5.00 × In 0.01

Time multiplier HAEFPTOC 0.05...15.00 0.01

Operate delay time HAEFPTOC 100...200000 ms 10

Minimum operate time HAEFPTOC 100...200000 ms 10

Operating curve type HAEFPTOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

ABB 31
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 41. Three-phase overvoltage protection (PHPTOV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × Un

Start time1)2) Minimum Typical Maximum

UFault = 1.1 × set Start value 22 ms 24 ms 26 ms

Reset time Typically 40 ms

Reset ratio Depends of the set Relative hysteresis

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 × Un, Voltage before fault = 0.9 × U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 × U n, Start value multiples in range of 1.10... 2.00

Table 42. Three-phase overvoltage protection (PHPTOV) main settings

Parameter Function Value (Range) Step

Start value PHPTOV 0.05...1.60 × Un 0.01

Time multiplier PHPTOV 0.05...15.00 0.01

Operate delay time PHPTOV 40...300000 ms 10

Operating curve type1) PHPTOV Definite or inverse time


Curve type: 5, 15, 17, 18, 19, 20

1) For further reference, see Operation characteristics table

Table 43. Three phase undervoltage protection (PHPTUV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × Un

Start time1)2) Minimum Typical Maximum

UFault = 0.9 × set Start value 62 ms 64 ms 66 ms

Reset time Typically 40 ms

Reset ratio Depends on the set Relative hysteresis

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 × Un, Voltage before fault = 1.1 × U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20

32 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 44. Three-phase undervoltage protection (PHPTUV) main settings

Parameter Function Value (Range) Step

Start value PHPTUV 0.05...1.20 × Un 0.01

Time multiplier PHPTUV 0.05...15.00 0.01

Operate delay time PHPTUV 60...300000 ms 10

Operating curve type1) PHPTUV Definite or inverse time


Curve type: 5, 15, 21, 22, 23

1) For further reference, see Operation characteristics table

Table 45. Positive-sequence undervoltage protection (PSPTUV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × Un

Start time1)2) Minimum Typical Maximum

UFault = 0.99 × set Start value 51 ms 53 ms 54 ms


UFault = 0.9 × set Start value 43 ms 45 ms 46 ms

Reset time Typically 40 ms

Reset ratio Depends of the set Relative hysteresis

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 × Un, Positive sequence voltage before fault = 1.1 × U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact

Table 46. Positive-sequence undervoltage protection (PSPTUV) main settings

Parameter Function Value (Range) Step

Start value PSPTUV 0.010...1.200 × Un 0.001

Operate delay time PSPTUV 40...120000 ms 10

Voltage block value PSPTUV 0.01...1.0 × Un 0.01

Table 47. Frequency protection (FRPFRQ)

Characteristic Value

Operation accuracy f>/f< ±10 mHz

df/dt ±100 mHz/s (in range |df/dt| < 5 Hz/s)


± 2.0% of the set value (in range 5 Hz/s < |df/dt| < 15 Hz/s)

Start time f>/f< <80 ms

df/dt <120 ms

Reset time <150 ms

Operate time accuracy ±1.0% of the set value or ±30 ms

ABB 33
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 48. Frequency protection (FRPFRQ) main settings

Parameter Function Value (Range) Step

Operation mode FRPFRQ 1 = Freq<


2 = Freq>
3 = df/dt
4 = Freq< + df/dt
5 = Freq> + df/dt
6 = Freq< OR df/dt
7 = Freq> OR df/dt

Start value Freq> FRPFRQ 0.9000...1.2000 × fn 0.0001

Start value Freq< FRPFRQ 0.8000...1.1000 × fn 0.0001

Start value df/dt FRPFRQ -0.200...0.200 × fn/s 0.005

Operate Tm Freq FRPFRQ 80...200000 ms 10

Operate Tm df/dt FRPFRQ 120...200000 ms 10

Table 49. Negative-sequence overvoltage protection (NSPTOV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × Un

Start time1)2) Minimum Typical Maximum

UFault = 1.1 × set Start value 33 ms 35 ms 37 ms


UFault = 2.0 × set Start value 24 ms 26 ms 28 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Negative-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact

Table 50. Negative-sequence overvoltage protection (NSPTOV) main settings

Parameter Function Value (Range) Step

Start value NSPTOV 0.010...1.000 × Un 0.001

Operate delay time NSPTOV 40...120000 ms 1

34 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 51. Residual overvoltage protection (ROVPTOV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × Un

Start time1)2) Minimum Typical Maximum

UFault = 1.1 × set Start value 55 ms 56 ms 58 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Residual voltage before fault = 0.0 × U n, f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact

Table 52. Residual overvoltage protection (ROVPTOV) main settings

Parameter Function Value (Range) Step

Start value ROVPTOV 0.010...1.000 × Un 0.001

Operate delay time ROVPTOV 40...300000 ms 1

Table 53. Negative phase-sequence overcurrent protection (NSPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × In

Start time 1)2) Minimum Typical Maximum

IFault = 2 × set Start value 22 ms 24 ms 25 ms


IFault = 10 × set Start value 14 ms 16 ms 17 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Negative sequence current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n, Start value multiples in range of 1.5...20

ABB 35
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 54. Negative phase-sequence overcurrent protection (NSPTOC) main settings

Parameter Function Value (Range) Step

Start value NSPTOC 0.01...5.00 × In 0.01

Time multiplier NSPTOC 0.05...15.00 0.01

Operate delay time NSPTOC 40...200000 ms 10

Operating curve type1) NSPTOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

1) For further reference, see Operation characteristics table

Table 55. Phase discontinuity protection (PDNSPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±2% of the set value

Start time <70 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

Table 56. Phase discontinuity protection (PDNSPTOC) main settings

Parameter Function Value (Range) Step

Start value (Current ratio setting I2/ PDNSPTOC 10...100% 1


I1)

Operate delay time PDNSPTOC 100...30000 ms 1

Min phase current PDNSPTOC 0.05...0.30 × In 0.01

Table 57. Circuit breaker failure protection (CCBRBRF)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±1.5% of the set value or ±0.002 × In

Operate time accuracy ±1.0% of the set value or ±20 ms

Retardation time <20 ms

36 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 58. Circuit breaker failure protection (CCBRBRF) main settings

Parameter Function Value (Range) Step

Current value (Operating phase CCBRBRF 0.05...1.00 × In 0.05


current)

Current value Res (Operating CCBRBRF 0.05...1.00 × In 0.05


residual current)

CB failure mode (Operating mode CCBRBRF 1 = Current -


of function) 2 = Breaker status
3 = Both

CB fail trip mode CCBRBRF 1 = Off -


2 = Without check
3 = Current check

Retrip time CCBRBRF 0...60000 ms 10

CB failure delay CCBRBRF 0...60000 ms 10

CB fault delay CCBRBRF 0...60000 ms 10

Table 59. Three-phase thermal overload protection for feeders (T1PTTR)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

Current measurement: ±1.5% of the set value or ±0.002 × In (at


currents in the range of 0.01...4.00 × In)

Operate time accuracy1) ±2.0% of the theoretical value or ±0.50 s

1) Overload current > 1.2 × Operate level temperature

Table 60. Three-phase thermal overload (T1PTTR) main settings

Parameter Function Value (Range) Step

Env temperature Set (Ambient T1PTTR -50...100°C 1


temperature used when the
AmbSens is set to Off)

Current multiplier (Current T1PTTR 1...5 1


multiplier when function is used
for parallel lines)

Current reference T1PTTR 0.05...4.00 × In 0.01

Temperature rise (End T1PTTR 0.0...200.0°C 0.1


temperature rise above ambient)

Time constant (Time constant of T1PTTR 60...60000 s 1


the line in seconds)

Maximum temperature T1PTTR 20.0...200.0°C 0.1


(temperature level for operate)

Alarm value (Temperature level T1PTTR 20.0...150.0°C 0.1


for start (alarm)

Reclose temperature T1PTTR 20.0...150.0°C 0.1


(Temperature for reset of block
reclose after operate)

Initial temperature (Temperature T1PTTR -50.0...100.0°C 0.1


raise above ambient temperature
at startup)

ABB 37
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 61. Three-phase inrush current detection (INRPHAR)

Characteristic Value

Operation accuracy At the frequency f = fn

Current measurement:
±1.5% of the set value or ±0.002 × In
Ratio I2f/I1f measurement:
±5.0% of the set value

Reset time +35 ms / -0 ms

Reset ratio Typically 0.96

Operate time accuracy +35 ms / -0 ms

Table 62. Three-phase inrush detection (INRPHAR) main settings

Parameter Function Value (Range) Step

Start value (Ratio of the 2nd to the INRPHAR 5...100% 1


1st harmonic leading to restraint)

Operate delay time INRPHAR 20...60000 ms 1

Table 63. Multipurpose protection (MAPGAPC)

Characteristic Value

Operation accuracy ±1.0% of the set value or ±20 ms

Table 64. Multipurpose analog protection (MAPGAPC) main settings

Parameter Function Value (Range) Step

Start value MAPGAPC -10000.0...10000.0 0.1

Operate delay time MAPGAPC 0...200000 ms 100

Operation mode MAPGAPC Over -


Under

38 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 65. Operation characteristics

Parameter Value (Range)

Operating curve type 1 = ANSI Ext. inv.


2 = ANSI Very. inv.
3 = ANSI Norm. inv.
4 = ANSI Mod inv.
5 = ANSI Def. Time
6 = L.T.E. inv.
7 = L.T.V. inv.
8 = L.T. inv.
9 = IEC Norm. inv.
10 = IEC Very inv.
11 = IEC inv.
12 = IEC Ext. inv.
13 = IEC S.T. inv.
14 = IEC L.T. inv
15 = IEC Def. Time
17 = Programmable
18 = RI type
19 = RD type

Operating curve type (voltage protection) 5 = ANSI Def. Time


15 = IEC Def. Time
17 = Inv. Curve A
18 = Inv. Curve B
19 = Inv. Curve C
20 = Programmable
21 = Inv. Curve A
22 = Inv. Curve B
23 = Programmable

ABB 39
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Control functions

Table 66. Autoreclosing (DARREC)

Characteristic Value

Operate time accuracy ±1.0% of the set value or ±20 ms

Table 67. Synchrocheck (SECRSYN)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±1 Hz

Voltage:
±3.0% of the set value or ±0.01 × Un
Frequency:
±10 mHz
Phase angle:
±3°

Reset time <50 ms

Reset ratio Typically 0.96

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Table 68. Synchronism and energizing check (SECRSYN) main settings

Parameter Function Value (Range) Step

Live dead mode SECRSYN -1 = Off


1 = Both Dead
2 = Live L, Dead B
3 = Dead L, Live B
4 = Dead Bus, L Any
5 = Dead L, Bus Any
6 = One Live, Dead
7 = Not Both Live

Difference voltage SECRSYN 0.01...0.50 × Un 0.01

Difference frequency SECRSYN 0.001...0.100 × fn 0.001

Difference angle SECRSYN 5...90° 1

Synchrocheck mode SECRSYN 1 = Off


2 = Synchronous
3 = Asynchronous

Control mode SECRSYN 1 = Continuous


2 = Command

Dead line value SECRSYN 0.1...0.8 × Un 0.1

Live line value SECRSYN 0.2...1.0 × Un 0.1

Close pulse SECRSYN 200...60000 ms 10

Max energizing V SECRSYN 0.50...1.15 × Un 0.01

Phase shift SECRSYN -180...180° 1

Minimum Syn time SECRSYN 0...60000 ms 10

Maximum Syn time SECRSYN 100...6000000 ms 10

Energizing time SECRSYN 100...60000 ms 10

Closing time of CB SECRSYN 40...250 ms 10

40 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Measurement functions

Table 69. Three-phase current measurement (CMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn ±2 Hz

±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 70. Current sequence components (CSMSQI)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: f/fn = ±2 Hz

±1.0% or ±0.002 × In
at currents in the range of 0.01...4.00 × In

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

Table 71. Three-phase voltage measurement (VMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz


At voltages in range 0.01…1.15 × Un

±0.5% or ±0.002 × Un

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 72. Voltage sequence components (VSMSQI)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn ±2 Hz


At voltages in range 0.01…1.15 × Un

±1.0% or ±0.002 × Un

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

Table 73. Residual current measurement (RESCMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: f/fn = ±2 Hz

±0.5% or ±0.002 × In
at currents in the range of 0.01...4.00 × In

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…


RMS: No suppression

ABB 41
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 74. Three-phase power and energy (PEMMXU)

Characteristic Value

Operation accuracy At all three currents in range 0.10…1.20 × In


At all three voltages in range 0.50…1.15 × Un
At the frequency fn ±1 Hz
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| < 0.71

±1.5% for power (S, P and Q)


±0.015 for power factor
±1.5% for energy

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

Table 75. Frequency measurement (FMMXU)

Characteristic Value

Operation accuracy ±10 mHz


(in measurement range 35...75 Hz)

42 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Supervision functions

Table 76. Fuse failure supervision (SEQRFUF)

Characteristic Value

Operate time1) NPS function UFault = 1.1 × set Neg Seq voltage <33 ms
Lev
UFault = 5.0 × set Neg Seq voltage <18 ms
Lev

Delta function ΔU = 1.1 × set Voltage change rate <30 ms

ΔU = 2.0 × set Voltage change rate <24 ms

1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements

ABB 43
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

19. Local HMI apart from the default single line diagram. The SLD view can
The IED is available with two optional displays, a large one also be accessed using the Web browser-based user
and a small one. The large display is suited for IED interface. The default SLD can be modified according to user
installations where the front panel user interface is frequently requirements by using the Graphical Display Editor in
used and a single line diagram is required. The small display PCM600.
is suited for remotely controlled substations where the IED is
only occasionally accessed locally via the front panel user The local HMI includes a push button (L/R) for local/remote
interface. operation of the IED. When the IED is in the local mode, the
IED can be operated only by using the local front panel user
Both LCD displays offer front-panel user interface interface. When the IED is in the remote mode, the IED can
functionality with menu navigation and menu views. However, execute commands sent from a remote location. The IED
the large display offers increased front-panel usability with supports the remote selection of local/remote mode via a
less menu scrolling and improved information overview. In binary input. This feature facilitates, for example, the use of
addition, the large display includes a user-configurable single an external switch at the substation to ensure that all IEDs are
line diagram (SLD) with position indication for the associated in the local mode during maintenance work and that the
primary equipment. Depending on the chosen standard circuit breakers cannot be operated remotely from the
configuration, the IED displays the related measuring values, network control center.

IECA070904 V3 EN IECA070901 V3 EN

Figure 6. Small display Figure 7. Large display

Table 77. Small display

Character size1) Rows in the view Characters per row

Small, mono-spaced (6x12 pixels) 5 20

Large, variable width (13x14 pixels) 4 8 or more

1) Depending on the selected language

Table 78. Large display

Character size1) Rows in the view Characters per row

Small, mono-spaced (6x12 pixels) 10 20

Large, variable width (13x14 pixels) 8 8 or more

1) Depending on the selected language

44 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

20. Mounting methods • Flush mounting


By means of appropriate mounting accessories the standard • Semi-flush mounting
IED case for the 615 series IED can be flush mounted, semi- • Semi-flush mounting in a 25° tilt
flush mounted or wall mounted. The flush mounted and wall • Rack mounting
mounted IED cases can also be mounted in a tilted position • Wall mounting
(25°) using special accessories. • Mounting to a 19" equipment frame

Further, the IEDs can be mounted in any standard 19” Panel cut-out for flush mounting:
instrument cabinet by means of 19” mounting panels available • Height: 161.5±1 mm
with cut-outs for one or two IEDs. • Width: 165.5±1 mm

Mounting methods:

190

6
18

164
177

25°
160
160

177
177

230
98
107
48
1 53 133
103

IECA070900 V4 EN IECA070903 V4 EN IECA070902 V4 EN

Figure 8. Flush mounting Figure 9. Semi-flush mounting Figure 10. Semi-flush with a 25º tilt

21. IED case and IED plug-in unit


For safety reasons, the IED cases for current measuring IEDs
are provided with automatically operating contacts for short-
circuiting the CT secondary circuits when a IED unit is
withdrawn from its case. The IED case is further provided with
a mechanical coding system preventing current measuring
IED units from being inserted into a IED case for a voltage
measuring IED unit and vice versa, i.e. the IED cases are
assigned to a certain type of IED plug-in unit.

ABB 45
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

22. Selection and ordering data consists of a string of letters and digits generated from the
The IED type and serial number label identifies the protection IED's hardware and software modules.
IED. The label is placed above the HMI on the upper part of
the plug-in-unit. An order code label is placed on the side of Use the ordering key information to generate the order code
the plug-in unit as well as inside the case. The order code when ordering complete IEDs.

Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Device 1

Device 2

Device 3

Example code H B R A A A N A B A 1 A A A N 2 X F

# Description H B R A A A N A B A 1 A A A N 2 X F
1 IED
615 series IED (including case) H
2 Standard
IEC B
CN C
3 Main application
Recloser protection and control R
4-7 Standard configurations, analog and binary I/O options
Standard configuration descriptions in short:
A = Sectionalizer/Midpoint recloser application to be used with conventional transformers
- Phase voltage inputs based on conventional VT’s
- Phase current inputs based on conventional CT’s
- Residual current input based on conventional CT
D = Tie point recloser application with syncrocheck and voltage measurement functions to be
used with voltage sensors
- 6 pieces of phase voltage inputs based on voltage sensors
- Phase current inputs based on conventional CT’s
- Residual current input based on conventional CT
Std. conf. I/O options
A 4 CT (Io 0.2/1A) + 3 VT + 14 BI + 13 BO AAAA
A 4 CT (Io 0.2/1A) + 3 VT + 8 BI + 10 BO AAAN
D 4 CT (Io 0.2/1A) + 6 VD + 12 BI + 10 BO DADN
8-9 Communication modules (Serial/Ethernet)
RS-232/485 + input for IRIG-B + Ethernet 100Base-TX (1 x RJ45) AB
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (1 x RJ-45 + 2 x LC) BE
RS-232/485 + RS-485 + input for IRIG-B + Ethernet 100Base-TX (1 x RJ-45) CB
Ethernet 100Base-FX (1 x LC) NA
Ethernet 100Base-TX (1 x RJ-45) NB
Ethernet 100Base-TX (3 x RJ-45) ND
10 Communication protocols
IEC 61850 A
IEC 61850 + IEC 60870-5-101 (slave) + IEC 60870-5-104 (slave) B
IEC 61850 + DNP3 TCP/IP (slave) + Modbus (slave) C
GUID-95F30B6C-36A8-4288-B92E-039AFFEFD9B3 V1 EN

46 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

# Description H B R A A A N A B A 1 A A A N 2 X F
11 Language
English (IEC) + English (ANSI) 1 1)
English (IEC) + Chinese 2 2)
12 Front panel
Small LCD with IEC symbols A
Large LCD with single line diagram (SLD) and IEC symbols B
Small LCD with Chinese symbols C 2)
Large LCD with single line diagram (SLD) and Chinese symbols D 2)
Large LCD with single line diagram (SLD) and ANSI symbols F 1)
13 Option 1 - Additional current protection functions
Directional earth-fault protection A
Directional overcurrent protection and directional earth-fault protection B
Admittance based earth-fault protection, directional overcurrent protection and directional
C
earth-fault protection
Wattmetric based earth-fault protection, directional overcurrent protection and directional
D
earth-fault protection
Harmonics based earth-fault protection, directional overcurrent protection and directional
E
earth-fault protection
None N
14 Option 2 - Additional voltage protection functions
Voltage and Frequency protection A
None N
15 Option 3
Power quality A
None N
16 Power supply
24...60 VDC 2
17-18 Version
Version 1.0 XF
1)
This option is available for only IEC standard (digit #2 = B)
2)
This option is available for only CN standard (digit #2 = C)
GUID-AB44AF6D-6948-4497-B801-87BFE6379015 V1 EN

ABB 47
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

23. Accessories and ordering data

Table 79. Mounting accessories

Item Order number

Semi-flush mounting kit 1MRS050696

Wall mounting kit 1MRS050697

Inclined semi-flush mounting kit 1MRS050831

19” rack mounting kit with cut-out for one IED 1MRS050694

19” rack mounting kit with cut-out for two IEDs 1MRS050695

24. Tools Web browser-based user interface is disabled by default. The


The IED is delivered as a pre-configured unit. The default interface can be enabled with PCM600 or via the front panel
parameter setting values can be changed from the front-panel user interface. The functionality of the interface can be limited
user interface, the Web browser-based user interface to read-only access through PCM600.
(WebHMI) or the PCM600 tool in combination with the IED-
specific connectivity package. The IED connectivity package is a collection of software and
specific IED information, which enable system products and
The Protection and Control IED Manager PCM600 offers tools to connect and interact with the IED. The connectivity
extensive IED configuration functions such as IED signal packages reduce the risk of errors in system integration,
configuration, application configuration, graphical display minimizing device configuration and set-up times. Further, the
configuration including single line diagram configuration, and connectivity packages for this product series IEDs include a
IEC 61850 communication configuration including horizontal flexible update tool for adding one additional local HMI
GOOSE communication. language to the IED. The update tool is activated using
PCM600, and it enables multiple updates of the additional
When the Web browser-based user interface is used, the IED HMI language, thus offering flexible means for possible future
can be accessed either locally or remotely, using a Web language updates.
browser (IE 7.0 IE 8.0 or IE 9.0). For security reasons, the

Table 80. Tools

Configuration and setting tools Version

PCM600 2.5 or later

Web-browser based user interface IE 7.0, IE 8.0 or IE 9.0

RER615 Connectivity Package 1.0 or later

48 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 81. Supported functions

Function Web HMI PCM600

IED parameter setting ● ●

Saving of IED parameter settings in the IED ● ●

Signal monitoring ● ●

Disturbance recorder handling ● ●

Alarm LED viewing ● ●

Access control management ● ●

IED signal configuration (signal matrix) - ●

Modbus® communication configuration (communication


management) - ●

DNP3 communication configuration (communication


management) - ●

IEC 60870-5-103 communication configuration


(communication management) - ●

Saving of IED parameter settings in the tool - ●

Disturbance record analysis - ●

XRIO parameter export/import - ●

Graphical display configuration - ●

Application configuration - ●

IEC 61850 communication configuration, GOOSE


(communication configuration) - ●

Phasor diagram viewing ● -

Event viewing ● ●

Saving of event data on the user's PC ● -

Online monitoring - ●
● = Supported

ABB 49
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

25. Connection diagrams

L1
L2
L3

Positive
Current
Direction

a n N A RER615
X120 X100
60 -
+ 1
1 210V
U1 Uaux
2 N -
2
60 -
3 210V 3
U2
P1 4 N IRF
5 60 - 4
210V
S1
U3 5
6 N
S2
7 1/5A 2) PO1
IL1
8 N
P2 9 1/5A
6
IL2 7
10 N
11 1/5A PO2
IL3
12 N 8
13 0.2/1A 9
Io 10
P1 S1
14 N
SO1
S2
P2 11
12
13
X110 SO2
1
BI 1 14
2
16
3 PO3
BI 2
4 17
15
5 19
BI 3 TCS1 18
6
20
22
BI 4 PO4
7
21
8 23
BI 5
9 TCS2 24

BI 6
10

11
BI 7 X110
12
14
BI 8 SO1
13 16
15
17
SO2
X130 19
18
1 1) 20
BI 1
2 SO3
22
BI 2 21
3 23
4 SO4
BI 3 24
5

BI 4
6
X130
7
BI 5 10
8 1)
SO1
12
BI 6
9 11
13
SO2
15
14
16
SO3
18
17
1) Order selectable -Optional
2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached

GUID-EB2E66DA-219E-423A-BE97-C478B253B5C0 V1 EN

Figure 11. Connection diagram for the A configuration

50 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

L1
L2
L3

Positive
Current
Direction RER615
X120 X100
+ 1
1
BI 1 Uaux
2 -
2

3 3
BI 2 IRF
4
4 5
BI 3
P1 PO1
5
S1 BI 4 6
6
7
S2
7 1/5A 1)
IL1 PO2
8 N
9 1/5A
P2
IL2 8
10 N 9
11 1/5A 10
IL3 SO1
12 N
13 0.2/1A 11
Io 12
14 N 13
SO2

14
16
X130 PO3
1 17
U1 15
2
19
3 TCS1 18
20
4 22
U2
5 PO4
6 21
23
7 TCS2 24
U3
8

9 No Connection
10 No Connection
11
U1B
12
13
14
U2B
15
16
17
U3B
18

X110 X110
1 14
BI 1
2 SO1
3 16
BI 2 15
4 17
5 SO2
BI 3
6 19
18
20
BI 4
7 SO3
22
8 21
BI 5
9 23
SO4
BI 6 24
10

11
BI 7
12

BI 8
13

1) The IED features an automatic short-circuit


mechanism in the CT connector when plug-in
unit is detached

GUID-08A9DCFE-1336-486D-9179-69F2D82B6B8E V1 EN

Figure 12. Connection diagram for the D configuration

ABB 51
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

26. Certificates The download area to the right contains the latest product
KEMA has issued an IEC 61850 Certificate Level A1 for documentation, such as the technical manual, installation
Relion ® 615 series. Certificate number: 30920420-Consulting manual and operation manual.
09-1712.
The Features and Application tabs contain product-related
information in a compact format.
27. References
The www.abb.com/substationautomation portal provides
information on the entire range of distribution automation
28. Functions, codes and symbols
products and services.
All available functions are listed in the table. All of them may
You will find the latest relevant information on the RER615 not be applicable to all products.
protection IED on the product page.

52 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 82. Functions included in the IED

Function IEC 61850 IEC 60617 IEC-ANSI

Protection

Three-phase non-directional overcurrent protection,


FPHLPTOC1 3I> (1) 51P-1 (1)
low stage, instance 1

Three-phase non-directional overcurrent protection,


PHHPTOC1 3I>> (1) 51P-2 (1)
high stage, instance 1

Three-phase non-directional overcurrent protection,


PHIPTOC1 3I>>> (1) 50P/51P (1)
instantaneous stage, instance 1

Three-phase directional overcurrent protection, low


FDPHLPTOC1 3I> -> (1) 67-1 (1)
stage, instance 1

Three-phase directional overcurrent protection, low


FDPHLPTOC2 3I> -> (2) 67-1 (2)
stage, instance 2

Three-phase directional overcurrent protection, high


DPHHPDOC1 3I>> -> (1) 67-2 (1)
stage, instance 1

Non-directional earth-fault protection, low stage,


FEFLPTOC1 Io> (1) 51N-1 (1)
instance 1

Non-directional earth-fault protection, high stage,


EFHPTOC1 Io>> (1) 51N-2 (1)
instance 1

Non-directional earth-fault protection, instantaneous


EFIPTOC1 Io>>> (1) 50N/51N (1)
stage, instance 1

Directional earth-fault protection, low stage, instance 1 FDEFLPDEF1 Io> -> (1) 67N-1 (1)

Directional earth-fault protection, low stage, instance 2 FDEFLPDEF2 Io> -> (2) 67N-1 (2)

Directional earth-fault protection, high stage, instance 1 DEFHPDEF1 Io>> -> (1) 67N-2 (1)

Admittance-based earth-fault protection, instance 1 EFPADM1 Yo> -> (1) 21YN (1)

Admittance-based earth-fault protection, instance 2 EFPADM2 Yo> -> (2) 21YN (2)

Admittance-based earth-fault protection, instance 3 EFPADM3 Yo> -> (3) 21YN (3)

Wattmetric-based earth-fault protection, instance 1 WPWDE1 Po> -> (1) 32N (1)

Wattmetric-based earth-fault protection, instance 2 WPWDE2 Po> -> (2) 32N (2)

Wattmetric-based earth-fault protection, instance 3 WPWDE3 Po> -> (3) 32N (3)

Harmonics-based earth-fault protection, instance 1 HAEFPTOC1 Io>HA (1) 51NHA (1)

Negative-sequence overcurrent protection, instance 1 NSPTOC1 I2> (1) 46 (1)

Negative-sequence overcurrent protection, instance 2 NSPTOC2 I2> (2) 46 (2)

Phase discontinuity protection, instance 1 PDNSPTOC1 I2/I1> (1) 46PD (1)

Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)

Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)

Three-phase undervoltage protection, instance 1 PHPTUV1 3U< (1) 27 (1)

Three-phase undervoltage protection, instance 2 PHPTUV2 3U< (2) 27 (2)

Three-phase undervoltage protection, instance 3 PHPTUV3 3U< (3) 27 (3)

Three-phase overvoltage protection, instance 1 PHPTOV1 3U> (1) 59 (1)

Three-phase overvoltage protection, instance 2 PHPTOV2 3U> (2) 59 (2)

Three-phase overvoltage protection, instance 3 PHPTOV3 3U> (3) 59 (3)

Positive-sequence undervoltage protection, instance 1 PSPTUV1 U1< (1) 47U+ (1)

ABB 53
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 82. Functions included in the IED, continued


Function IEC 61850 IEC 60617 IEC-ANSI

Negative-sequence overvoltage protection, instance 1 NSPTOV1 U2> (1) 47O- (1)

Frequency protection, instance 1 FRPFRQ1 f>/f<,df/dt (1) 81 (1)

Frequency protection, instance 2 FRPFRQ2 f>/f<,df/dt (2) 81 (2)

Three-phase thermal protection for feeders, cables


T1PTTR1 3Ith>F (1) 49F (1)
and distribution transformers, instance 1

Circuit-breaker failure protection, instance 1 CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF (1)

Three-phase inrush detector, instance 1 INRPHAR1 3I2f> (1) 68 (1)

Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)

Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)

Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1)

Multi-purpose protection, instance 2 MAPGAPC2 MAP (2) MAP (2)

Multi-purpose protection, instance 3 MAPGAPC3 MAP (3) MAP (3)

Multi-purpose protection, instance 4 MAPGAPC4 MAP (4) MAP (4)

Multi-purpose protection, instance 5 MAPGAPC5 MAP (5) MAP (5)

Multi-purpose protection, instance 6 MAPGAPC6 MAP (6) MAP (6)

Power quality

Current total demand distortion, instance 1 CMHAI1 PQM3I (1) PQM3I (1)

Voltage total harmonic distortion, instance 1 VMHAI1 PQM3U (1) PQM3V (1)

Voltage variation, instance 1 PHQVVR1 PQMU (1) PQMV (1)

Voltage unbalance, instance 1 VSQVUB1 PQUUB (1) PQVUB (1)

Control

Circuit-breaker control, instance 1 CBXCBR1 I <-> O CB (1) I <-> O CB (1)

Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)

Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)

Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)

Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)

Autoreclosing, instance 1 DARREC1 O -> I (1) 79 (1)

Synchronism and energizing check, instance 1 SECRSYN1 SYNC (1) 25 (1)

Condition monitoring

Circuit-breaker condition monitoring, instance 1 SSCBR1 CBCM (1) CBCM (1)

Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)

Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)

Fuse failure supervision, instance 1 SEQRFUF1 FUSEF (1) 60 (1)

Measurement

Disturbance recorder, instance 1 RDRE1 DR (1) DFR (1)

Three-phase current measurement, instance 1 CMMXU1 3I (1) 3I (1)

Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)

Residual current measurement, instance 1 RESCMMXU1 Io (1) In (1)

54 ABB
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

Table 82. Functions included in the IED, continued


Function IEC 61850 IEC 60617 IEC-ANSI

Three-phase voltage measurement, instance 1 VMMXU1 3U (1) 3V (1)

Three-phase voltage measurement, instance 2 VMMXU2 3U (B) (1) 3V (B) (1)

Sequence voltage measurement, instance 1 VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)

Sequence voltage measurement, instance 2 VSMSQI2 U1, U2, U0 (B) (1) V1, V2, V0 (B) (1)

Three-phase power and energy measurement,


PEMMXU1 P, E (1) P, E (1)
instance 1

Frequency measurement, instance 1 FMMXU1 f (1) f (1)

Load profile, instance 1 LDPMSTA1 LOADPROF (1) LOADPROF (1)

Other

Minimum pulse timer (2 pcs), instance 1 TPGAPC1 TP (1) TP (1)

Minimum pulse timer (2 pcs), instance 2 TPGAPC2 TP (2) TP (2)

Minimum pulse timer (2 pcs, second resolution),


TPS (1) TPS (1)
instance 1 TPSGAPC1

Minimum pulse timer (2 pcs, minute resolution),


TPM (1) TPM (1)
instance 1 TPMGAPC1

Pulse timer (8 pcs), instance 1 PTGAPC1 PT (1) PT (1)

Pulse timer (8 pcs), instance 2 PTGAPC2 PT (2) PT (2)

Time delay off (8 pcs), instance 1 TOFGAPC1 TOF (1) TOF (1)

Time delay off (8 pcs), instance 2 TOFGAPC2 TOF (2) TOF (2)

Time delay on (8 pcs), instance 1 TONGAPC1 TON (1) TON (1)

Time delay on (8 pcs), instance 2 TONGAPC2 TON (2) TON (2)

Set reset (8 pcs), instance 1 SRGAPC1 SR (1) SR (1)

Set reset (8 pcs), instance 2 SRGAPC2 SR (2) SR (2)

Move (8 pcs), instance 1 MVGAPC1 MV (1) MV (1)

Move (8 pcs), instance 2 MVGAPC2 MV (2) MV (2)

Generic control point (16 pcs), instance 1 SPCGGIO1 SPCGGIO (1) SPCGGIO (1)

Generic control point (16 pcs), instance 2 SPCGGIO2 SPCGGIO (2) SPCGGIO (2)

Remote generic control points, instance 1 SPCRGGIO1 SPCRGGIO (1) SPCRGGIO (1)

Local generic control points, instance 1 SPCLGGIO1 SPCLGGIO (1) SPCLGGIO (1)

Generic up-down counters, instance 1 UDFCNT1 UDCNT (1) UDCNT (1)

Generic up-down counters, instance 2 UDFCNT2 UDCNT (2) UDCNT (2)

Generic up-down counters, instance 3 UDFCNT3 UDCNT (3) UDCNT (3)

ABB 55
1MRS757814 A
Grid Automation, Recloser Protection and Control RER615
Product version: 1.0

29. Document revision history

Document revision/date Product version History

A/2013-09-17 1.0 First release