Professional Documents
Culture Documents
Contents
1 Description ...............................................................3 26 Accessories and ordering data...........................67
2 Standard configurations........................................3 27 Tools........................................................................ 68
3 Protection functions............................................. 11 28 Cyber security........................................................ 70
4 Application.............................................................. 12 29 Terminal diagrams................................................ 70
5 Supported ABB solutions..................................... 15 30 Certificates............................................................. 74
6 Control..................................................................... 17 31 References.............................................................. 74
7 Measurements........................................................18 32 Functions, codes and symbols........................... 75
8 Power quality..........................................................18 33 Document revision history.................................. 78
9 Fault location..........................................................18
10 Disturbance recorder............................................18
11 Event log..................................................................19
12 Recorded data ....................................................... 19
13 Condition monitoring...........................................20
14 Trip-circuit supervision........................................ 20
15 Self-supervision..................................................... 20
16 Current circuit supervision..................................20
17 Protection communication and supervision....21
18 Access control........................................................ 22
19 Inputs and outputs................................................22
20 Station communication........................................23
21 Technical data........................................................ 27
22 Local HMI................................................................ 65
23 Mounting methods............................................... 67
24 Relay case and plug-in unit..................................67
25 Selection and ordering data................................67
Disclaimer Conformity
The information in this document This product complies with following directive and
is subject to change without notice regulations.
and should not be construed as a
commitment by ABB. ABB assumes no Directives of the European parliament and of the council:
responsibility for any errors that may • Electromagnetic compatibility (EMC) Directive
appear in this document. 2014/30/EU
© Copyright 2022 ABB • Low-voltage Directive 2014/35/EU
• RoHS Directive 2011/65/EU
All rights reserved.
Trademarks UK legislations:
2 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
RED615 3
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Lockout relay
HMI
Time
Authorization
2× - Web HMI
I2> 3I>>> 3I>/Io>BF I
AND
ESC Clear
3I 46 50P/51P 51BF/51NBF
O R
L
OR
2×
3I> 3I>> 3I2f> 3dI>L
51P-1 51P-2 68 87L
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
I∑ Protocols:
Io IEC 61850-8-1
PHIZ MCS 3I OPTS Modbus®
HIZ MCS 3I OPTM IEC 60870-5-103
DNP3
Interfaces:
2× Ethernet: TX (RJ45), FX (LC)
BST PCS TCS Serial: Serial glass fiber (ST),
BST PCS TCM RS-485, RS-232
Redundant protocols:
HSR
PRP
18× RSTP
MAP SOTF
MAP SOTF
- I, Io
Object Ctrl 2) Ind 3)
- Limit value supervision
CB 1 - - Load profile record
- Symmetrical components
DC 2 3
ES 1 2
1)
Check availability of binary inputs/outputs
Analog interface types 1)
REMARKS
Optional 3× No. of Calculated OR Alternative
function instances value function to be
Io/Uo defined when
Sum of phase ordering
currents
3I I∑
RED615
AT REMOTE
END
4 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Uo
Lockout relay
HMI
Time
Authorization
2× - Web HMI
I2> I2/I1> 3Ith>F I
AND
ESC Clear
3I 46 46PD 49F
O R
L
OR
3Ith>T/G/C 3I>>>
49T/G/C 50P/51P
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
Protocols:
3I>/Io>BF 3I>
IEC 61850-8-1
51BF/51NBF 51P-1
Modbus®
IEC 60870-5-103
2× DNP3
3I>> 3I2f> 3dI>L CBCM MCS 3I OPTS Interfaces:
51P-2 68 87L CBCM MCS 3I OPTM Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass fiber (ST),
RS-485, RS-232
Io Redundant protocols:
2× HSR
BST PCS TCS PRP
BST PCS TCM RSTP
Io
3× 18×
Uo> MAP SOTF O→I
59G MAP SOTF 79
REMARKS
Optional 3× No. of Calculated OR Alternative
function instances value function to be
Io/Uo defined when
3I ordering
RED615
AT REMOTE
END
RED615 5
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Lockout relay
HMI
Time
Authorization
2× - Web HMI
I2> I2/I1> 3Ith>F I
AND
ESC Clear
3I 46 46PD 49F
O R
L
OR
3Ith>T/G/C 3I>>>
49T/G/C 50P/51P
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
3I>/Io>BF 3I> Io Protocols:
IEC 61850-8-1
51BF/51NBF 51P-1
Modbus®
IEC 60870-5-103
2× DNP3
3I>> 3I2f> 3dI>L CBCM MCS 3I OPTS Interfaces:
51P-2 68 87L CBCM MCS 3I OPTM Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass fiber (ST),
RS-485, RS-232
Redundant protocols:
2× HSR
BST PCS TCS PRP
BST PCS TCM RSTP
Io
O→I
79
REMARKS
Optional 3× No. of Calculated OR Alternative
function instances value function to be
Io/Uo defined when
3I ordering
RED615
AT REMOTE
END
6 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
UL1UL2UL3
Uo
Lockout relay
HMI
Time
Authorization
2× - Web HMI
I2> I2/I1> 3Ith>F I ESC Clear
AND
3I 46 46PD 49F
O R
L
OR
3Ith>T/G/C 3I>>>
49T/G/C 50P/51P
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
2×
Protocols:
3I>/Io>BF 3I>→ 3I>>→
IEC 61850-8-1/-9-2LE
51BF/51NBF 67-1 67-2
Modbus®
IEC 60870-5-103
DNP3
3I2f> 3dI>L 3I FUSEF CBCM MCS 3I Interfaces:
68 87L 60 CBCM MCS 3I Ethernet: TX (RJ45), FX (LC)
U12 Serial: Serial glass fiber (ST),
RS-485, RS-232
Redundant protocols:
Io 2× HSR
BST OPTS PCS TCS PRP
BST OPTM PCS TCM RSTP
Io
3× 3×
3U< U2> U1< 3U> SYNC O→I PQM3I PQM3U PQMU
27 47O- 47U+ 59 25 79 PQM3I PQM3V PQMV
U12
UL1UL2UL3 3× 4×
Uo> f>/f<, PQUUB
df/dt PQVUB
59G
81
REMARKS
18× Optional 3× No. of Calculated OR Alternative
2xRTD
1xmA
FLOC MAP SOTF function instances value function to be
21FL MAP SOTF Io/Uo defined when
3I ordering
RED615
AT REMOTE
END
RED615 7
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Lockout relay
HMI
Time
Authorization
2× - Web HMI
I2> I2/I1> 3Ith>F I ESC Clear
AND
3I 46 46PD 49F
O R
L
OR
3Ith>T/G/C 3I>>>
49T/G/C 50P/51P
CONDITION MONITORING COMMUNICATION
AND SUPERVISION
2× Protocols:
3I>/Io>BF 3I>→ 3I>>→
IEC 61850-8-1
51BF/51NBF 67-1 67-2
IEC 61850-9-2LE
UL1UL2UL3 Io Modbus®
IEC 60870-5-103
3I2f> 3dI>L 3I FUSEF CBCM MCS 3I DNP3
68 87L 60 CBCM MCS 3I Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass fiber (ST),
RS-485, RS-232
2× 2× Redundant protocols:
Io Io>→ Io>>→ BST OPTS PCS TCS HSR
67N-1 67N-2 BST OPTM PCS TCM PRP
RSTP
1)
Combi sensor inputs with conventional
primary object
Io input
3× 3×
3U< U2> U1< 3U> SYNC O→I PQM3I PQM3U PQMU
27 47O- 47U+ 59 25 79 PQM3I PQM3V PQMV
UL1
3× 4×
Uo> f>/f<, PQUUB
df/dt
59G PQVUB
81
18×
FLOC MAP SOTF REMARKS
21FL MAP SOTF Optional 3× No. of Calculated OR Alternative
function instances value function to be
Io/Uo defined when
3I ordering
RED615
AT REMOTE
END
Description Std.conf
Line differential protection with directional earth-fault protection and circuit-breaker condition monitor- B
ing
Line differential protection with non-directional earth-fault protection and circuit-breaker condition C
monitoring
8 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Description Std.conf
Line differential protection with directional overcurrent and earth-fault protection, voltage and frequen- D
cy based protection and measurements, synchro-check and circuit-breaker condition monitoring (RTD
option, optional power quality and fault locator)
Line differential protection with directional overcurrent and earth-fault protection, voltage and frequen- E
cy based protection and measurements, and circuit-breaker condition monitoring (sensor inputs, op-
tional power quality, fault locator and synchro-check with IEC 61850-9-2 LE)
Protection
RED615 9
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Power quality
Control
10 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Measurement
(1) 7
Other
1, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection
function blocks available in the standard configuration.
() = optional
3. Protection functions
RED615 11
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
12 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Protection
communication
A
A
U12 0. 0 kV
U12 0. 0 kV
P 0.00 kW
P 0.00 kW
Q 0.00 kVAr
Q 0.00 kVAr
IL2 0 A
IL2 0 A
O
I ESC Clear
R
3I 3I I ESC Clear
L O R
L
I∑ I∑
RED615 RED615
Std. conf. A Std. conf. A
ANSI IEC ANSI IEC
46 I2> 46 I2>
50P/51P 3I>>> 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
87L 3ΔI> 87L 3ΔI>
BST BST BST BST
MCS 3I MCS 3I MCS 3I MCS 3I
Figure 6: Line differential protection for an interconnecting feeder between two primary distribution
substations using standard configuration A
Figure 6 illustrates line differential protection protection is offered for a in-zone power
for an interconnecting feeder between transformer, when available and located in the
two primary distribution substations using protection zone.
standard configuration A. Additionally,
RED615 13
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
3U Uo RED615
A
Std. conf. D
U12 0. 0 kV
P 0.00 kW
ANSI IEC
Q 0.00 kVAr
IL2 0 A
3I I ESC Clear
46 I2>
O R
L
47O-/59 U2>/3U>
47U+/27 U1</3U<
Io 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
67N-1/67N-2 Io>→/Io>>→
Protection
communication 87L 3ΔI>
BST BST
Io MCS 3I MCS 3I
RED615
3I
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
A
I ESC Clear
ANSI IEC
O R
L
46 I2>
49F/49T 3Ith>F/3Ith>T
50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
51N Io>
87L 3ΔI>
BST BST
MCS 3I MCS 3I
Figure 7: Line differential protection of a feeder using the standard configurations D and B or C
Line differential protection of a feeder using offered for an in-zone power transformer, when
the standard configurations D and B or C is available and located in the protection zone.
shown in Figure 7. Additionally, protection is
14 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
RED615
3I I ESC Clear
Std. conf. E
O R
L
ANSI IEC
3U
46 I2>
47O-/59 U2>/3U>
47U+/27 U1</3U<
50P/51P 3I>>>
Io
51BF/51NBF 3I>/Io>BF
67N-1/67N-2 Io>→/Io>>→
Protection 87L 3ΔI>
communication BST BST
Io
RED615
Std. conf. E
ANSI IEC
3U
46 I2>
3I A
47O-/59 U2>/3U>
U12 0. 0 kV
P 0.00 kW
47U+/27 U1</3U<
Q 0.00 kVAr
IL2 0 A
I ESC Clear
O R
L
50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
67N-1/67N-2 Io>→/Io>>→
87L 3ΔI>
BST BST
Figure 8 illustrates line differential protection Frequency protection functions and third
of a feeder using the standard configuration instances of voltage protection functions must
E, in which current sensors (Rogowski coil) be added with the Application Configuration
and voltage sensors (voltage divider) are used tool. To ensure the performance of the relay,
for the measurements. Additionally, protection the user-specific configuration load is verified
is offered for an in-zone power transformer, with the Application Configuration tool in
when available and located in the protection PCM600.
zone. The standard configuration E has been
preconfigured especially for ABB switchgears,
for example, UniGear Digital. However, the use 5. Supported ABB solutions
of this configuration is not restricted for this
purpose only. The 615 series protection relays together with
the Substation Management Unit COM600S
Standard configurations D and E are not
constitute a genuine IEC 61850 solution
designed for using all the available functionality
for reliable power distribution in utility and
content in one relay at the same time.
industrial power systems. To facilitate the
RED615 15
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
system engineering, ABB's relays are supplied switchgear bay solutions. The SLD feature
with connectivity packages. The connectivity is especially useful when 615 series relays
packages include a compilation of software and without the optional single-line diagram feature
relay-specific information, including single-line are used. The Web HMI of COM600S also
diagram templates and a full relay data model. provides an overview of the whole substation,
The data model includes event and parameter including relay-specific single-line diagrams,
lists. With the connectivity packages, the relays which makes information easily accessible.
can be readily configured using PCM600 and Substation devices and processes can also be
integrated with COM600S or the network remotely accessed through the Web HMI, which
control and management system MicroSCADA improves personnel safety.
Pro.
In addition, COM600S can be used as a
The 615 series relays offer native support local data warehouse for the substation's
for IEC 61850 Edition 2 also including binary technical documentation and for the network
and analog horizontal GOOSE messaging. data collected by the devices. The collected
In addition, process bus with the sending network data facilitates extensive reporting
of sampled values of analog currents and and analyzing of network fault situations by
voltages and the receiving of sampled values of using the data historian and event handling
voltages is supported. Compared to traditional features of COM600S. The historical data can
hard-wired, inter-device signaling, peer-to-peer be used for accurate monitoring of process
communication over a switched Ethernet LAN and equipment performance, using calculations
offers an advanced and versatile platform based on both real-time and historical values.
for power system protection. Among the A better understanding of the process
distinctive features of the protection system dynamics is achieved by combining time-based
approach, enabled by the full implementation process measurements with production and
of the IEC 61850 substation automation maintenance events.
standard, are fast communication capability,
COM600S can also function as a gateway
continuous supervision of the protection and
and provide seamless connectivity between
communication system's integrity, and an
the substation devices and network-level
inherent flexibility regarding reconfiguration
control and management systems, such as
and upgrades.This protection relay series
MicroSCADA Pro and System 800xA.
is able to optimally utilize interoperability
provided by the IEC 61850 Edition 2 features. GOOSE Analyzer interface in COM600S enables
the following and analyzing the horizontal IEC
At substation level, COM600S uses the data
61850 application during commissioning and
content of the baylevel devices to enhance
operation at station level. It logs all GOOSE
substation level functionality. COM600S
events during substation operation to enable
features a Web browser-based HMI, which
improved system supervision.
provides a customizable graphical display
for visualizing single-line mimic diagrams for
Product Version
Substation Management Unit COM600S 4.0 SP1 or later
4.1 or later (Edition 2)
MicroSCADA Pro SYS 600 9.3 FP2 or later
9.4 or later (Edition 2)
System 800xA 5.1 or later
16 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
ABB
MicroSCADA Pro/
System 800xA
COM600S COM600S
Web HMI Web HMI
Figure 9: ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System
800xA
RED615 17
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
primary devices. Interlocking schemes required fact, the majority of power quality problems are
by the application are configured using the localized within customer facilities. Thus, power
signal matrix or the application configuration quality monitoring is not only an effective
functionality of PCM600. customer service strategy but also a way to
protect a utility's reputation for quality power
and service.
7. Measurements
The protection relay has the following power
quality monitoring functions.
The relay continuously measures the phase
currents, the symmetrical components of the • Voltage variation
currents and the residual current. If the • Voltage unbalance
relay includes voltage measurements, it also • Current harmonics
measures the residual voltage. The relay also • Voltage harmonics
calculates the demand value of the current
over a user-selectable, pre-set time frame, The voltage unbalance and voltage variation
the thermal overload of the protected object, functions are used for measuring short-
and the phase unbalance based on the ratio duration voltage variations and monitoring
between the negativesequence and positive- voltage unbalance conditions in power
sequence current. transmission and distribution networks.
Furthermore, the relay monitors the phase The voltage and current harmonics functions
differential, bias and remote-end phase provide a method for monitoring the power
currents. quality by means of the current waveform
distortion and voltage waveform distortion.
The measured values can be accessed via the The functions provide a short-term three-
local HMI or remotely via the communication second average and a long-term demand
interface of the relay. The values can also be for total demand distortion TDD and total
accessed locally or remotely using the Web HMI. harmonic distortion THD.
The relay is provided with a load profile
recorder. The load profile feature stores the
historical load data captured at a periodical
9. Fault location
time interval (demand interval). The records are
in COMTRADE format. RED615 features an optional impedance-
measuring fault location function suitable for
locating short-circuits in radial distribution
8. Power quality systems. Earth faults can be located
in effectively and low-resistance earthed
In the EN standards, power quality is defined networks. Under circumstances where the fault
through the characteristics of the supply current magnitude is at least of the same order
voltage. Transients, short-duration and long- of magnitude or higher than the load current,
duration voltage variations and unbalance earth faults can also be located in isolated
and waveform distortions are the key neutral distribution networks. The fault location
characteristics describing power quality. The function identifies the type of the fault and
distortion monitoring functions are used for then calculates the distance to the fault point.
monitoring the current total demand distortion An estimate of the fault resistance value is also
and the voltage total harmonic distortion. calculated. The estimate provides information
about the possible fault cause and the accuracy
Power quality monitoring is an essential of the estimated distance to the fault point.
service that utilities can provide for their
industrial and key customers. A monitoring
system can provide information about system 10. Disturbance recorder
disturbances and their possible causes. It can
also detect problem conditions throughout the The relay is provided with a disturbance
system before they cause customer complaints, recorder featuring up to 12 analog and 64
equipment malfunctions and even equipment binary signal channels. The analog channels can
damage or failure. Power quality problems are
not limited to the utility side of the system. In
18 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
be set to record either the waveform or the faults and disturbances. The considerable
trend of the currents and voltages measured. capacity to process and store data and
events in the relay facilitates meeting the
The analog channels can be set to trigger the
growing information demand of future network
recording function when the measured value
configurations.
falls below or exceeds the set values. The binary
signal channels can be set to start a recording The sequence-of-events information can be
either on the rising or the falling edge of the accessed either via local HMI or remotely via
binary signal or on both. the communication interface of the relay. The
information can also be accessed locally or
By default, the binary channels are set to record
remotely using the Web HMI.
external or internal relay signals, for example,
the start or trip signals of the relay stages,
or external blocking or control signals. Binary 12. Recorded data
relay signals, such as protection start and
trip signals, or an external relay control signal
The relay has the capacity to store the records
via a binary input, can be set to trigger the
of the 128 latest fault events. The records can
recording. Recorded information is stored in a
be used to analyze the power system events.
nonvolatile memory and can be uploaded for
Each record includes, for example, phase,
subsequent fault analysis.
differential and bias current values and a time
stamp. The fault recording can be triggered by
11. Event log the start or the trip signal of a protection block,
or by both. The available measurement modes
include DFT, RMS and peak-to-peak. Fault
To collect sequence-of-events information,
records store relay measurement values at the
the relay has a nonvolatile memory capable
moment when any protection function starts.
of storing 1024 events with the associated
In addition, the maximum demand current with
time stamps. The non-volatile memory retains
time stamp is separately recorded. The records
its data even if the relay temporarily loses
are stored in the non-volatile memory.
its auxiliary supply. The event log facilitates
detailed pre- and post-fault analyses of feeder
RED615 19
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
IEC 61850-8-1
PCM600
IEC 103
Modbus
WHMI
events
DNP3
LHMI
(FIFO) 1024
Fault
records
(FIFO) 128
BASIC FUNCTIONS
Fault summary;
Trip timestamp, Function, Currents, Voltages, etc.
Audit
trail
events
(FIFO) 2048
n…100
Load profile
record
...7 yrs Historical load data captured at a periodical
time interval (Demand interval 1...180min)
20 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
RED615 21
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
RED615 RED615
RED615 RED615
22 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
RED615 23
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
process bus based applications use IEEE 1588 availability for the substation communication.
for high accuracy time synchronization. The network redundancy is based on two
complementary protocols defined in the IEC
For redundant Ethernet communication, the
62439-3 standard: PRP and HSR protocols. Both
relay offers two optical Ethernet network
the protocols are able to overcome a failure
interfaces. Ethernet network redundancy can
of a link or switch with a zero switch-over
be achieved using the high-availability seamless
time. In both the protocols, each network node
redundancy (HSR) protocol or the parallel
has two identical Ethernet ports dedicated for
redundancy protocol (PRP) or a with self-
one network connection. The protocols rely on
healing ring using RSTP in managed switches.
the duplication of all transmitted information
Ethernet redundancy can be applied to
and provide a zero switch-over time if the
Ethernet-based IEC 61850, Modbus and DNP3
links or switches fail, thus fulfilling all the
protocols.
stringent real-time requirements of substation
All communication card variants support automation.
self-healing ring based Ethernet redundancy.
In PRP, each network node is attached to
Communication card variants with two optical
two independent networks operated in parallel.
interfaces for station bus communication have
The networks are completely separated to
support for HSR and PRP redundancy protocols.
ensure failure independence and can have
These variants include also support for IEEE
different topologies. The networks operate in
1588 based time synchronization.
parallel, thus providing zero-time recovery and
The IEC 61850 standard specifies network continuous checking of redundancy to avoid
redundancy which improves the system failures.
COM600
SCADA
HSR applies the PRP principle of parallel sender node receives the frame it sent, the
operation to a single ring. For each message sender node discards the frame to avoid loops.
sent, the node sends two frames, one through The HSR ring with 615 series relays supports
each port. Both the frames circulate in opposite the connection of up to 30 relays. If more
directions over the ring. Every node forwards than 30 relays are to be connected, it is
the frames it receives from one port to another recommended to split the network into several
to reach the next node. When the originating
24 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Ethernet switch
The choice between the HSR and PRP Ethernet ring solution supports the connection
redundancy protocols depends on the required of up to 30 615 series relays. If more than 30
functionality, cost and complexity. relays are to be connected, it is recommended
to split the network into several rings. The
The self-healing Ethernet ring solution enables
self-healing Ethernet ring solution avoids single
a cost-efficient communication ring controlled
point of failure concerns and improves the
by a managed switch with standard Rapid
reliability of the communication.
Spanning Tree Protocol (RSTP) support. The
managed switch controls the consistency of the The self-healing Ethernet ring solution avoids
loop, routes the data and corrects the data flow single point of failure concerns and improves
in case of a communication switch-over. The the reliability of the communication. The
relays in the ring topology act as unmanaged solution can be applied for the Ethernetbased
switches forwarding unrelated data traffic. The IEC 61850, Modbus and DNP3 protocols.
RED615 25
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Client A Client B
Network A
Network B
All communication connectors, except for active setting and reading fault records are
the front port connector, are placed on supported. DNP serial and DNP TCP can be used
integrated optional communication modules. in parallel. If required, both IEC 61850 and DNP
The relay can be connected to Ethernet- protocols can be run simultaneously.
based communication systems via the RJ-45
615 series supports Profibus DPV1 with support
connector (100Base-TX) or the fiber optic LC
of SPA-ZC 302 Profibus adapter. If Profibus
connector (100Base-FX).
is required the relay must be ordered with
Modbus implementation supports RTU, ASCII Modbus serial options. Modbus implementation
and TCP modes. Besides standard Modbus includes SPA-protocol emulation functionality.
functionality, the relay supports retrieval of This functionality enables connection to SPA-ZC
time-stamped events, changing the active 302.
setting group and uploading of the latest
When the relay uses the RS-485 bus for the
fault records. If a Modbus TCP connection is
serial communication, both two- and four wire
used, five clients can be connected to the
connections are supported. Termination and
relay simultaneously. Further, Modbus serial
pull-up/down resistors can be configured with
and Modbus TCP can be used in parallel, and if
jumpers on the communication card so external
required both IEC 61850 and Modbus protocols
resistors are not needed.
can be run simultaneously.
The relay supports the following time
The IEC 60870-5-103 implementation supports
synchronization methods with a time-stamping
two parallel serial bus connections to two
resolution of 1 ms.
different masters. Besides basic standard
functionality, the relay supports changing of Ethernet-based
the active setting group and uploading of
• SNTP (Simple Network Time Protocol)
disturbance recordings in IEC 60870-5-103
format. Further, IEC 60870-5-103 can be used With special time synchronization wiring
at the same time with the IEC 61850 protocol.
• IRIG-B (Inter-Range Instrumentation Group -
DNP3 supports both serial and TCP modes for Time Code Format B)
connection up to five masters. Changing of the
Remote-end station time reference
26 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
21.1 Dimensions
Table 6: Dimensions
Description Value
Case 164 mm
Case 160 mm
RED615 27
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Fuse type T4A/250 V
Description Value
Rated frequency 50/60 Hz
Current inputs Rated current, I n 0.2/1 A 1 1/5 A 2
Thermal withstand capability:
• Continuously 4A 20 A
• Continuous 240 V AC
• For 10 s 360 V AC
28 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Description Value
Current sensor input Rated current voltage 75 mV ... 9000 mV 1
Continuous voltage withstand 125 V
Input impedance at 50/60Hz 2...3 MΩ 2
Voltage sensor input Rated secondary voltage 346 mV…1733 mV 3
Continuous voltage withstand 50 V
Input impedance at 50/60Hz 3 MΩ
Description Value
Description Value
Operating range ±20% of the rated voltage
Rated voltage 24...250 V DC
RED615 29
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Description Value
RTD inputs Supported RTD sensors 100 Ω platinum TCR 0.00385 (DIN 43760)
250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
10 Ω copper TCR 0.00427
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/ 1 A/0.25 A/0.15 A
R<40 ms, at 48/110/220 V DC
Minimum contact load 100 mA at 24 V AC/DC
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 15 A
Breaking capacity when the control-circuit time constant L/ 1 A/0.25 A/0.15 A
R<40 ms, at 48/110/220 V DC
Minimum contact load 10 mA at 5 V AC/DC
30 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time con- 5 A/3 A/1 A
stant L/R<40 ms, at 48/110/220 V DC (two contacts
connected in series)
Minimum contact load 100 mA at 24 V AC/DC
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/ 5 A/3 A/1 A
R<40 ms, at 48/110/220 V DC
Minimum contact load 100 mA at 24 V AC/DC
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 6A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time con- 5 A/3 A/1 A
stant L/R <40 ms, at 48/110/220 V DC
Table continues on the next page
RED615 31
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Description Value
Operate time <1 ms
Reset <20 ms, resistive load
Connector Fibre type Wave length Typical max. length9 Permitted path
attenuation10
LC MM 62.5/125 or 50/125 1300 nm 2 km <8 dB
μm
LC SM 9/125 μm11 1300 nm 20 km <8 dB
21.13 IRIG-B
Description Value
IRIG time code format B004, B005 1
Isolation 500V 1 min
Modulation Unmodulated
Logic level 5 V TTL
Current consumption <4 mA
Power consumption <20 mW
9 Maximum length depends on the cable attenuation and quality, the amount of splices and
connectors in the path.
10 Maximum allowed attenuation caused by connectors and cable altogether.
11 Use single-mode fiber with recommended minimum length of 3 m to connect RED615 to the pilot
wire modem RPW600.
1 According to the 200-04 IRIG standard
32 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Description Value
Front side IP 54
Description Value
Operating temperature range -25...+55ºC (continuous)
Short-time service temperature range -40...+70ºC (<16 h) 12, 13
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude Up to 2000 m
Transport and storage temperature range -40...+85ºC
• Contact discharge 8 kV
• Air discharge 15 kV
12 Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
13 For relays with an LC communication interface the maximum operating temperature is +70 ºC
RED615 33
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
• All ports 4 kV
6.4/16 µs
• 2s 100 A/m
60%/100 ms
60%/1000 ms
>95%/5000 ms
34 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
• Conducted
• Radiated
1,5 kV, 1,2/50 µs, 0,5 J, sensor inputs of SIM0005 IEC 61869-6
Insulation resistance measurements >100 M Ω, 500 V DC IEC 60255-27
Protective bonding resistance <0.1 Ω, 4 A, 60 s IEC 60255-27
RED615 35
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
at -25°C...+55°C
Description Reference
LV directive 2014/35/EU
Standard EN / BS EN 60255-27
EN / BS EN 60255-1
14 For relays with an LC communication interface the maximum operating temperature is +70 oC
36 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Description Reference
EMC directive 2014/30/EU
Standard EN / BS EN 60255-26
Description
RoHS Directive 2011/65/EU
Characteristic Value
PHIPTOC:
16 ms 19 ms 23 ms
I Fault = 2 × set Start value
11 ms 12 ms 14 ms
I Fault = 10 × set Start value
15 Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode
= default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
16 Includes the delay of the signal output contac
RED615 37
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 17
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
Characteristic Value
Operation accuracy Depending on the frequency of the current/voltage measured:
f n ±2 Hz
DPHLPDOC Current:
±1.5% of the set value or ±0.002 × I n
Voltage:
±1.5% of the set value or ±0.002 × U n
Phase angle: ±2°
38 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
DPHHPDOC Current:
±1.5% of the set value or ±0.002 × I n
(at currents in the range of 0.1…10 × I n)
±5.0% of the set value
(at currents in the range of 10…40 × I n)
Voltage:
±1.5% of the set value or ±0.002 × U n
Phase angle: ±2°
19 Measurement mode and Pol quantity = default, current before fault = 0.0 × I n, voltage before
fault = 1.0 × U n, f n = 50 Hz, fault current in one phase with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
20 Includes the delay of the signal output contact
21 Maximum Start value = 2.5 × I n, Start value multiples in range of 1.5...20
RED615 39
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2
Hz
EFLPTOC ±1.5% of the set value or ±0.002 × I n
EFIPTOC:
16 ms 19 ms 23 ms
I Fault = 2 × set Start value
11 ms 12 ms 14 ms
I Fault = 10 × set Start value
40 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz
DEFLPDEF Current:
±1.5% of the set value or ±0.002 × I n
Voltage
±1.5% of the set value or ±0.002 × U n
Phase angle:
±2°
DEFHPDEF Current:
±1.5% of the set value or ±0.002 × I n
(at currents in the range of 0.1…10 × I n)
±5.0% of the set value
(at currents in the range of 10…40 × I n)
Voltage:
±1.5% of the set value or ±0.002 × U n
Phase angle:
±2°
RED615 41
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
DEFHPDEF
42 ms 46 ms 49 ms
I Fault = 2 × set Start value
DEFLPDEF 58 ms 62 ms 66 ms
I Fault = 2 × set Start value
2 = Forward
3 = Reverse
2 = IoSin
3 = IoCos
4 = Phase angle 80
5 = Phase angle 88
42 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy 31 At the frequency f = f n
±1.0% or ±0.01 mS
(In range of 0.5...100 mS)
2 = Forward
3 = Reverse
2 = Go
3 = Bo
4 = Yo, Go
5 = Yo, Bo
6 = Go, Bo
7 = Yo, Go, Bo
31 Uo = 1.0 × Un
32 Includes the delay of the signal output contact, results based on statistical distribution of 1000
measurements
RED615 43
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy Depending on the frequency of the measured current:
fn ±2 Hz
3 = Reverse
33 Io varied during the test, Uo = 1.0 × Un = phase-to-earth voltage during earth fault in compensa-
ted or unearthed network, the residual power value before fault = 0.0 pu, fn = 50 Hz, results
based on statistical distribution of 1000 measurements
34 Includes the delay of the signal output contact
35 For further reference, refer to the Operating characteristics table
44 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy (Uo criteria with transient protection) Depending on the frequency of the measured current: f n ±2
Hz
±1.5% of the set value or ±0.002 × Uo
Operate time accuracy ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5
2 = Forward
3 = Reverse
2 = Transient EF
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz
±5% of the set value or ±0.004 × I n
Start time 36, 37 Typically 77 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode 38 ±5.0% of the set value or ±20 ms
Suppression of harmonics -50 dB at f = f n
-3 dB at f = 13 × f n
36 Fundamental frequency current = 1.0 × I n, harmonics current before fault = 0.0 × I n, harmonics
fault current 2.0 × Start value, results based on statistical distribution of 1000 measurements
37 Includes the delay of the signal output contact
38 Maximum Start value = 2.5 × I n, Start value multiples in range of 2...20
RED615 45
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n
±1.5% of the set value or ±0.002 × I n
Start time 40, 41 Minimum Typical Maximum
46 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2
Hz
±2% of the set value
Start time <70 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,…
Characteristic Value
Operation accuracy Depending on the frequency of the measured voltage: f n ±2
Hz
±1.5% of the set value or ±0.002 × U n
Start time 44, 45 Minimum Typical Maximum
U Fault = 2 × set Start value 48 ms 51 ms 54 ms
44 Residual voltage before fault = 0.0 × U n, f n = 50 Hz, residual voltage with nominal frequency in-
jected from random phase angle, results based on statistical distribution of 1000 measurements
45 Includes the delay of the signal output contact
RED615 47
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: f n ±2
Hz
±1.5% of the set value or ±0.002 × U n
Start time 46, 47 Minimum Typical Maximum
U Fault = 0.9 × set Start value 62 ms 66 ms 70 ms
46 Start value = 1.0 × U n, Voltage before fault = 1.1 × U n, f n = 50 Hz, undervoltage in one phase-to-
phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
47 Includes the delay of the signal output contact
48 Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
49 For further reference, see the Operation characteristics table
48 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy Depending on the frequency of the measured voltage: f n ±2
Hz
±1.5% of the set value or ±0.002 × U n
Start time 50, 51 Minimum Typical Maximum
U Fault = 1.1 × set Start value 23 ms 27 ms 31 ms
Characteristic Value
Operation accuracy Depending on the frequency of the measured voltage: f n ±2
Hz
±1.5% of the set value or ±0.002 × U n
Start time 54,55 Minimum Typical Maximum
Table continues on the next page
50 Start value = 1.0 × U n, Voltage before fault = 0.9 × U n, f n = 50 Hz, overvoltage in one phase-to-
phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
51 Includes the delay of the signal output contact
52 Maximum Start value = 1.20 × U n, Start value multiples in range of 1.10...2.00
53 For further reference, see the Operation characteristics table
54 Start value = 1.0 × U n, positive-sequence voltage before fault = 1.1 × U n, f n = 50 Hz, positive
sequence undervoltage with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
55 Includes the delay of the signal output contact
RED615 49
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: f n
±1.5% of the set value or ±0.002 × U n
Start time 56,57 Minimum Typical Maximum
50 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy f>/f< ±5 mHz
2 = Freq>
3 = df/dt
4 = Freq< + df/dt
5 = Freq> + df/dt
6 = Freq< OR df/dt
7 = Freq> OR df/dt
21.23.33 Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR)
Table 62: Three-phase thermal protection for feeders, cables and distribution transformers
(T1PTTR)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz
Current measurement: ±1.5% of the set value or ±0.002 × I n
(at currents in the range of 0.01...4.00 × I n)
Operate time accuracy 58 ±2.0% of the theoretical value or ±0.50 s
RED615 51
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
21.23.34 Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR)
main settings
Table 63: Three-phase thermal protection for feeders, cables and distribution transformers
(T1PTTR) main settings
Table 64: Three-phase thermal overload protection, two time constants (T2PTTR)
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2 Hz
Current measurement: ±1.5% of the set value or ±0.002 x I n (at
currents in the range of 0.01...4.00 x I n)
Operate time accuracy 59 ±2.0% of the theoretical value or ±0.50 s
21.23.36 Three-phase thermal overload protection, two time constants (T2PTTR) main settings
Table 65: Three-phase thermal overload protection, two time constants (T2PTTR) main settings
5 = off
52 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Signalling delay Fiber optic link <5 ms
Galvanic pilot wire link <10 ms
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f n ±2
Hz
±1.5% of the set value or ±0.002 × I n
Operate time accuracy ±1.0% of the set value or ±20 ms
Reset time Typically 40 ms
Retardation time <20 ms
2 = Breaker status
3 = Both
2 = Without check
3 = Current check
RED615 53
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy At the frequency f = f n
Current measurement:
±1.5% of the set value or ±0.002 × I n
Ratio I2f/I1f measurement:
±5.0% of the set value
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
Characteristic Value
Operation accuracy ±1.0% of the set value or ±20 ms
54 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
2 = Under
Characteristic Value
Measurement accuracy At the frequency f = f n
Impedance:
±2.5% or ±0.25 Ω
Distance:
±2.5% or ±0.16 km/0.1 mile
XC0F_CALC:
±2.5% or ±50 Ω
IFLT_PER_ILD:
±5% or ±0.05
RED615 55
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Table 77: Line differential protection with in-zone power transformer (LNPLDF)
Characteristics Value
Operation accuracy 60 Depending on the frequency of the measured current: f n ±2
Hz
Low stage ±2.5% of the set value
High stage ±2.5% of the set value
Minimum Typical Maximum
High stage, operate time 61, 62 22 ms 25 ms 29 ms
21.23.49 Line differential protection with in-zone power transformer (LNPLDF) main settings
Table 78: Line differential protection with in-zone power transformer (LNPLDF) main settings
60 With the symmetrical communication channel (as when using dedicated fiber optic).
61 Without additional delay in the communication channel (as when using dedicated fiber optic).
62 Including the delay of the output contact. When differential current = 2 × High operate value and
f n = 50 Hz with galvanic pilot wire link + 5 ms.
63 Low operate value multiples in range of 1.5...20.
56 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
2 = Ungrounded
RED615 57
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy ±1.5% of the set value or ±0.2% of reference voltage
Reset ratio Typically 0.96 (Swell), 1.04 (Dip, Interruption)
Characteristic Value
Operation accuracy ±1.5% of the set value or ±0.002 × U n
Reset ratio Typically 0.96
Operation VSQVUB 1 = on -
5 = off
58 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: f n ±1
Hz
Voltage:
±3.0% of the set value or ±0.01 × U n
Frequency:
±10 mHz
Phase angle:
±3°
1 = Both Dead
2 = Live L, Dead B
3 = Dead L, Live B
4 = Dead Bus, L Any
5 = Dead L, Bus Any
6 = One Live, Dead
7 = Not Both Live
RED615 59
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
2 = Synchronous
3 = Asynchronous
2 = Command
Characteristic Value
±5.0%
Characteristic Value
60 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operate time 65 NPS function U Fault = 1.1 × set Neg Seq volt- <33 ms
age Lev
Description Value
65 Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency
injected from random phase angle, results based on statistical distribution of 1000 measure-
ments
66 Of the reading, for a stand-alone relay, without time synchronization
RED615 61
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
±0.5% or ±0.002 × I n
RMS: No suppression
Characteristic Value
Operation accuracy Depending on the frequency of the measured current: f/f n =
±2 Hz
±1.0% or ±0.002 × I n
at currents in the range of 0.01...4.00 × I n
Characteristic Value
Operation accuracy Depending on the frequency of the current measured: f/f n =
±2 Hz
±0.5% or ±0.002 × I n
at currents in the range of 0.01...4.00 × I n
62 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: f n ±2
Hz
At voltages in range 0.01…1.15 × U n
±0.5% or ±0.002 × U n
Characteristic Value
Operation accuracy Depending on the frequency of the measured voltage: f/f n =
±2 Hz
±0.5% or ±0.002 × U n
Characteristic Value
Operation accuracy Depending on the frequency of the voltage measured: f n ±2
Hz
At voltages in range 0.01…1.15 × U n
±1.0% or ±0.002 × U n
Suppression of harmonics DFT: -50 dB at f = n × f n, where n = 2, 3, 4, 5,…
RED615 63
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy At all three currents in range 0.10…1.20 × I n
At all three voltages in range 0.50…1.15 × U n
At the frequency f n ±1 Hz
Description Value
RTD inputs Supported RTD sensors 100 Ω platinum TCR 0.00385 (DIN 43760)
250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
10 Ω copper TCR 0.00427
64 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Characteristic Value
Operation accuracy ±5 mHz
(in measurement range 35...75 Hz)
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
RED615 65
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
selection of local/remote mode via a binary during maintenance work and that the circuit
input. This feature facilitates, for example, the breakers cannot be operated remotely from the
use of an external switch at the substation network control center.
to ensure that all relays are in the local mode
66 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
190
6
18
164
177
25°
160
160
177
177
230
98
107
48 133
153
103
Figure 18: Flush mounting Figure 19: Semi-flush mounting Figure 20: Semi-flush mounting
in a 25º tilt
RED615 67
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Pilot Wire communication package including two Pilot Wire modems: RPW600AM (master) and RPW600AMF
RPW600AF (follower)
Diagnostics kit including the RPW-diagnostic tool, a diagnostic cable and a CD with necessary RPW600ADP
drivers and information
3.0 meter LC-LC single-mode fiber-optic patch cable for connecting one Pilot Wire modem to the 1MRS120547-3
RED615 relay69
19” rack mounting kit with cut-out for one relay 1MRS050694
19” rack mounting kit with cut-out for two relays 1MRS050695
Mounting bracket for one relay with test switch RTXP in 4U Combiflex (RHGT 19” variant C) 2RCA022642P0001
Mounting bracket for one relay in 4U Combiflex (RHGT 19” variant C) 2RCA022643P0001
19” rack mounting kit for one relay and one RTXP18 test switch (the test switch is not included in the 2RCA021952A0003
delivery)
19” rack mounting kit for one relay and one RTXP24 test switch (the test switch is not included in the 2RCA022561A0003
delivery)
Replacement kit for a Strömberg SP_J40 series relay (cut-out in the center of the installation plate) 2RCA027871A0001
Replacement kit for a Strömberg SP_J40 series relay (cut-out on the left or the right of the installa- 2RCA027874A0001
tion plate)
19” rack replacement kit for Strömberg SP_J3/J6 series relays (one cut-out) 2RCA027894A0001
19” rack replacement kit for Strömberg SP_J3/J6 series relays (two cut-outs) 2RCA027897A0001
69 Two patch cables are required for connecting the Pilot Wire communication package
(RPW600AMF).
70 Cannot be used when the protection relay is mounted with the Combiflex 19" equipment frame
(2RCA032826A0001)
68 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Description Version
Signal monitoring ● ●
RED615 69
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
Application configuration – ●
Event viewing ● ●
Online monitoring – ●
70 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
RED615 71
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
72 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
RED615
X120 X100
1 + 1
BI 1 U aux
2 2
-
3 3
BI 2
IRF
4
4 5
BI 3
PO1
5
BI 4
6 6
7 1/5A 2) 7
IL1
8 N PO2
9 1/5A
IL2 8
10 N 9
11 1/5A 10
IL3 SO1
12 N
1/5A 11
Io 12
14 N 13
SO2
X130 14
1 6) 16
BI 1 PO3
2
17
3 15
BI 2 19
4 TCS1 18
5 20
BI 3 22
6
PO4
7 21
BI 4
8 23
60 - TCS2 24
9 210V
U12B
10 N
60 -
11 210V
U1
12 N
60 -
13 210V
U2
14 N
60 -
15 210V
U3
16 N
60 -
17 210V
Uo
18 N
X110 X110
1 14
BI 1
2 SO1
16
3 15
BI 2
4 17
SO2
5
BI 3 19
6 18
20
BI 4 SO3
7
22
8 21
BI 5 23
9
SO4
BI 6 24
10
11
BI 7
12
BI 8
13
X1
1) 3)
LAN
X2
1) 3)
LAN
X5 1) 4)
1 GND
2 GNDC
3 IRIG-B -
4 IRIG-B + 1) Optional
5 AGND
6 B/- / TX 2) The IED features an automatic short-circuit
7 A/+ mechanism in the CT connector when plug-in
8 B/- unit is detached
9 A/+ / RX 3) 100BaseFx / LC or 100BaseTx / RJ-45
4) RS-485 serial bus
X12 5) Fibre Optic (ST) Serial Bus
1) 5)
RX 6) AIM0006 (5U+4BI)
TX Alternative Module AIM0003 (5U+2RTD+1mA)
X16
Line Differential Protection Communication
RED615 73
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
RED615
X130 X100
+ 1
1 0,2/1A
U aux
Io 2
2 N -
3
X131 IRF
4
4 5
IL1
5
7 PO1
U1
8
6
X132 7
4 PO2
IL2
5
8
7 9
U2
8 10
X133 SO1
11
4 12
IL3
5 13
7 SO2
U3
8 14
16
PO3
17
15
19
TCS1 18
20
22
X110 PO4
1 21
BI 1 23
2
TCS2 24
3
BI 2
4
5 X110
BI 3
6 14
SO1
BI 4 16
7 15
8 17
BI 5 SO2
9
19
18
BI 6 20
10
SO3
11 22
BI 7
12 21
23
BI 8 SO4
13 24
X1
1) 3)
LAN
X2
1) 3)
LAN
X5 1) 4)
1 GND
2 GNDC
3 IRIG-B -
4 IRIG-B +
5 AGND
6 B/- / TX
7 A/+
8 B/- 1) Optional
9 A/+ / RX 2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
X12 unit is detached
1) 5) 3) 100BaseFx / LC or 100BaseTx / RJ-45
RX
TX 4) RS-485 serial bus
5) Fibre Optic (ST) Serial Bus
X16
Line Differential Protection Communication
74 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
RED615 75
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
76 RED615
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
RED615 77
Product Guide
Line Differential Protection and Control RED615 1MRS756500 N
78 RED615
Product Guide
—
ABB Distribution Solutions
Digital Substation Products
P.O.Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
www.abb.com/mediumvoltage
www.abb.com/relion
www.abb.com/substationautomation
1MRS756500 N