Project Ref --- Area Ref: Most Unfavourable Inst. Number: 1
Tel: Fax:
Project Data and Design Parameters
Project name : 58l/s@80 Area reference : Most Unfavourable Address / location : --- Project number : --- Installation number(s) : 1 Drawing number(s) : --- Issue no / date : --- Designers reference : --- Project Data File : sp-58@80.FHC Hazard classification : Domestic Design authority : National Fire Protection Association Insurance company : --- Specified density of discharge : 14.40 mm/min (l/min/m2) Assumed maximum area of operation : 240.00 m2 Number of operating sprinkler heads : 20 Maximum area covered per head : 12.00 m2 Highest head / nozzle above source : 5.50 m Number of pipes in system : 97 from 25 to 200 mm Pressure loss equation used : Hazen-Williams Fluid : Water Pipe Data Table : STD_PIPE.PDT Maximum fluid velocity : 10.15 m/s in pipe 178 179 Volume of pipework and fittings : 8.48 m3 Elbows are welded for : 0 mm and above Comment : --- Checked by & Date :
Source duty = 4022.4 l/min @ 6.909 bar at node no 100
Canute FHC Ver: 1.8.4 Sunday, September 12, 2021 - 17:16
www.canutesoft.com Page: 1/6 FHC - Hydraulic Calculation Report Submitted by user number: Project: 58l/s@80 Project Ref --- Tel: Area Ref: Most Unfavourable Fax: Inst. Number: 1