Air system Input Data

Project Name: FIBDD 09/11/2021


Prepared by: zeezuu 09:42am

1. General Details:
Air System Name Air system
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 55.0 °F
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type Forward Curved with Dampers
Configuration Draw-thru
Fan Performance 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems Not Used
Return and/or exhaust airflow control devices Not Used
Exhaust filters, scrubbers, or other exhaust treatment Not Used
Particulate Filtration Credit: MERV 9 through 12 Not Used
Particulate Filtration Credit: MERV 13 through 15 Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters Not Used
Carbon and other gas-phase air cleaners Not Used
Energy recovery device, or coil runaround loop Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section Not Used
Exhaust system serving Fume hoods Not Used

Fan Control 1-speed fan, cooling and heating

Duct System Data:


Supply Duct Data:
Duct Heat Gain 5 %
Duct Leakage 5 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
Bedroom 1 B+D FF x1
Bedroom 2 B+D FF x1
Bedroom1 FF x1
Bedroom2 FF x1
Entertainment Room FF x1
GYM GF x1
Half Bath GF x1
Living Room GF x1
Living Room SF x1
Living+Dining FF x1
Main Kitchen FF x1
Main Kitchen GF x1
Main Kitchen SF x1
Master Bed FF x1
Master Bed SF x1
Masterbed B+D FF x1
Masterbed B+D GF x1
Masterbed B+D SF x1
Masterbed GF x1
Movie Room FF x1

Hourly Analysis Program v4.90 Page 1 of 2


Air system Input Data
Project Name: FIBDD 09/11/2021
Prepared by: zeezuu 09:42am

Office GF x1
Servant Bath FF x1
Servant Room FF x1
Servant Room GF x1
SR Kitchen GF x1
SR Living FF x1
Stairs Area GF x1

Thermostats and Zone Data:


Zone All
Cooling T-stat: Occ. 75.0 °F
Cooling T-stat: Unocc. 80.0 °F
Heating T-stat: Occ. 70.0 °F
Heating T-stat: Unocc. 65.0 °F
T-stat Throttling Range 1.50 °F
Diversity Factor 100 %
Direct Exhaust Airflow 0.0 CFM
Direct Exhaust Fan kW 0.0 kW

Thermostat Schedule Thermostat Schedule


Unoccupied Cooling is Available

Supply Terminals Data:


Zone All
Terminal Type Diffuser
Minimum Airflow 0.00 CFM/person

Zone Heating Units:


Zone All
Zone Heating Unit Type None

Zone Unit Heat Source Electric Resistance


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 55.0 °F
Supply Fan Airflow 7865.4 CFM
Ventilation Airflow 731.2 CFM

Hydronic Sizing Specifications:


Chilled Water Delta-T 10.0 °F
Hot Water Delta-T 20.0 °F

Safety Factors:
Cooling Sensible 0 %
Cooling Latent 0 %
Heating 0 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(CFM) (MBH) (MBH) (CFM)
1 7472.1 - -

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 264.1 MBH
Design OAT 95.0 °F
Equipment Sizing (Auto-Sized) 264.1 MBH
Capacity Oversizing Factor 0 %
ARI Performance Rating 11.000 EER
DX System Configuration 1-stage compression, 1 circuit
Conventional Cutoff OAT 55.0 °F
Low Temperature Operation Used
Low Temperature Cutoff OAT 0.0 °F

Hourly Analysis Program v4.90 Page 2 of 2