Professional Documents
Culture Documents
Street Light Pole Voltage Drop Calculation (1.1.17)
Street Light Pole Voltage Drop Calculation (1.1.17)
Street Light Pole Cable Route System Detail Voltage Distribution at each Pole
System Voltage System Voltage Phase for Select Phase
Pole (From) Pole (To) P.F
(P-P) (L-N) Pole for Luminar
A B 415 230 1Ph R 0.75
B C 415 230 1Ph Y 0.75
C D 415 230 1Ph B 0.75
D E 415 230 1Ph Y 0.75
E F 415 230 1Ph Y 0.75
F G 415 230 1Ph B 0.75
G H 415 230 1Ph R 0.75
H I 415 230 1Ph Y 0.75
I J 415 230 1Ph B 0.75
J K 415 230 1Ph R 0.75
K L 415 230 1Ph Y 0.75
L M 415 230 1Ph B 0.75
M N 415 230 1Ph R 0.75
N O 415 230 1Ph Y 0.75
O P 415 230 1Ph B 0.75
P Q 415 230 3Ph - 0.75
Q
Voltage Drop Calculator
Jignesh.Parmar www.elect
:Summary: :Voltage Drop Detail:
0.8 Km Cable Voltage Drop Permissible Actual Status
8 Watt Voltage Drop in R Phase 6.0% 3.81% O.K
16 Nos Voltage Drop in Y Phase 6.0% 5.27% O.K
32 Nos Voltage Drop in B Phase 6.0% 5.38% O.K
Cable Detail
Rsistance Reactance Voltage Drop
(Ω/Km) (Ω/Km)
2.29 0.097 0.11%
2.29 0.097 0.22%
2.29 0.097 0.34%
2.29 0.097 0.45%
2.29 0.097 0.56%
2.29 0.097 0.67%
2.29 0.097 0.79%
2.29 0.097 0.90%
2.29 0.097 1.01%
2.29 0.097 1.12%
2.29 0.097 1.23%
2.29 0.097 1.35%
2.29 0.097 1.46%
2.29 0.097 1.57%
2.29 0.097 1.68%
2.29 0.097 1.00%