Table of Contents
2
Water Treatment Manual
1.12 Boiler lay-up ..................................................................................................................................... 54
1.12.1 Short term lay-up (< 1-2 months) .................................................................................................. 54
1.12.2 Long term lay-up (> 1-2 months) ................................................................................................... 55
3
Water Treatment Manual
2.6.2 Cathodic inhibitors ............................................................................................................................. 81
2.6.3 Combination and organic inhibitors ................................................................................................... 81
4
Water Treatment Manual
1.1 Introduction
A boiler is a steel pressure vessel in which water under pressure is converted into steam by
the application of combustion. In other words, it is simply a heat exchanger which uses
radiant heat and hot flue gases, liberated from burning fuel, to generate steam and hot water
for heating and processing loads.
In early designs the boiler was a simple metal shell with a feedwater inlet and a steam outlet.
Fuel was burned on a grate within a fire space below this shell and in early years of steam
powered ships the fuel used was coal. Steam propulsion has in the main been replaced by
the use of diesel engines and these engines are usually fired on heavy fuel oil. The marine
industry has also seen an increase in the number of boiler systems designed to raise steam
using heat rejected from diesel engines (exhaust gas boilers). Steam is raised mainly for
heating the heavy fuel oil used to fire the ‘diesel engines’, for space heating, to power cargo
handling pumps and as an aid to cleaning storage tanks and surfaces.
The water cycle is used to describe the life cycle of water on the earth. The water cycle (also
known as the hydrologic cycle) is the journey water takes as it circulates from the land to the
sky and back again.
The sun's heat provides energy to evaporate water from the earth's surface (oceans, lakes,
etc.). Plants also lose water to the air which is called transpiration. The water vapour
eventually condenses, forming tiny droplets in clouds. When the clouds meet cool air over
land, precipitation (rain, sleet, or snow) is triggered, and water returns to the land (or sea).
Some of the precipitation soaks into the ground. Some of the underground water is trapped
between rock or clay layers; this is called groundwater. But most of the water flows downhill
as runoff (above ground or underground), eventually returning to the seas as slightly salty
water.
As water flows through rivers, it picks up small amounts of mineral salts from the rocks and
soil of the river beds. This very-slightly salty water flows into the oceans and seas. The water
in the oceans only leaves by evaporating (and the freezing of polar ice), but the salt remains
dissolved in the ocean - it does not evaporate. So the remaining water gets saltier and saltier
as time passes. Pure rain water, flowing through rock strata such as limestone or dolomite
will slowly dissolve the minerals present in the rock and take them into solution.
5
Water Treatment Manual
The most soluble minerals are those containing calcium, magnesium and sodium.
These exist in water as calcium and magnesium bicarbonates and sulphates and sodium
chloride. Sea water has a predominance of sodium chloride with significantly amounts of
calcium and magnesium salts.
The bicarbonate salts are termed alkaline hardness (or temporary hardness) while other
calcium and magnesium salts are termed non-alkaline hardness (or permanent hardness).
The salts of calcium and magnesium we typically encounter in water exhibit an inverse
solubility. That is, as the water temperature rises their solubility reduces and at temperatures
above 70°C they will come out of solution and redeposit as scale.
In the boiler system, by returning a high proportion of good quality condensate, the amount
of hardness entering the boiler can be reduced but in many cases the hardness salts must
be removed before the water can be fed to the boiler.
Guidance about maximum feedwater hardness and maximum total dissolved solids in
various types of boiler is given in several available standards. Among these are BS
1170:1983, Treatment of water for marine boilers and BS 2486:1997, Recommendations for
Treatment of Water for Land Boilers.
6
Water Treatment Manual
Calcium carbonate
Calcium carbonate scale appears as a pale cream yellow deposit and is formed by the
thermal decomposition of calcium bicarbonate at heat transfer surfaces:
Magnesium silicate
Magnesium Silicate scale is a rough textured, tan to off-white deposit found in boilers where
sufficient amounts of Magnesium are present in conjunction with adequate amounts of
silicate ions coupled with a deficiency of OH Alkalinity.
Mg 2+ + OH- → MgOH+
H2SiO3 → H+ + HSiO3-
We will see later that the maintenance of an adequate amount of OH alkalinity is a key step
in the prevention of magnesium silicate scale.
7
Water Treatment Manual
Iron oxide deposits
Hematite (Fe2O3)
This type of red/brown iron oxide deposit is found because of active corrosion occurring
within the steam/boilers system. This could arise from the Feed, Boiler or Condensate
systems.
Magnetite (Fe3O4)
This type of black/grey iron oxide deposit is formed on the surface of steel in the absence of
stoichiometric levels of oxygen and is generally considered to be an indication of that good
corrosion protection is being achieved at the point where it is found.
Magnetite forms a protective layer on steel surfaces and prevents further corrosion attack.
The presence of Magnetite can be problematic in high pressure boiler if the layer becomes
too thick and acts to insulate the metal surface and cause overheating.
Copper
The presence of copper deposits in a boiler presents a very serious corrosion risk because
of the initiation of galvanic corrosion mechanisms with boiler steel.
The boiler metal is anodic to the copper and rapid loss of boiler metal will occur. Copper can
appear in various form as a deposit in the boiler.
Copper in the boiler usually arises from corrosion and/or erosion of copper condensate lines
or clorifiers but can also arise due to corrosion/erosion of feed pump impellers and from
feed-lines fabricated from copper. Erosion of copper in the condensate system is very
common when the boiler is priming or foaming as the presence of suspended matter plus
high pH acts to scour copper surfaces. Excess amounts of hydrazine will decompose to
ammonia which is steam-volatile and is well documented as a corrosive agent for copper
and its alloys. It is quite normal to find mixtures of the above compounds in a boiler deposit
and it is the relative amounts of these compounds that can help us to deduce the most
probable scaling mechanisms.
8
Water Treatment Manual
Figure 2: Typical mixed scale deposit has caused overheating of boiler tube
The loss of efficiency may not be too serious but consider the effect of 1 mm of scale on the
waterside of the furnace of a shell boiler, the furnace being 25 mm (2.5 cm) thick and subject
to a heat flux of 378 kW/m2 (37.8 W/cm2).
Let the thermal conductivities be 45 W/m.K (0.45 W/cm.K) for the steel and 2.25 W/m.K
(0.0225 W/cm.K) for the scale, both being typical values:
9
Water Treatment Manual
Temperature drop through metal 37.8 x 2.5 = 210 °C
0.45
Temperature drop through scale 37.8x 0.1 = 168 °C
0.0225
Temperature drop through waterside film, say 16 °C
Total temperature drop 394 °C
If the saturation temperature is 205°C, the fireside metal temperature will be 599°C which is
well beyond the temperature of about 445°C, where creep begins to dominate the elastic
properties of the metal.
If scale were not present the temperature would have been only 431°C; within the safety
range. Moreover, the higher the furnace temperature, the greater its expansion and hence
its thrust on the end plates of the boiler. These factors illustrate the importance of preventing
scale formation, and that current and future trends in boiler design will require high quality
feedwater treatment.
The most common deposits encountered are carbonates, silicates and phosphates of
calcium and magnesium. The second most common deposit encountered is iron oxide which
may be present in the raw water or may originate from corrosion occurring in the feed or
condensate system. In water tube boilers, in particular, iron can form deposits which adhere
very tenaciously and insulate the tube causing rapid overheating and failure of the tube.
The salts of silica and can produce scales of extremely low thermal conductivity and even in
very thin layers can produce the effects described earlier.
The chemical structure of the scale as well as the design and method of operation of the
boiler, all influence the amount of heat lost. Heat transfer may be reduced by as much as 10
- 12% by the presence of scale. A scale of 3 mm (1/8 “) can cause an overall loss of
efficiency of 2 - 3 % in fire tube boiler and water-tube boilers without heat recovery.
10
Water Treatment Manual
In general as the boiler pressure and heat flux increase there is a requirement for higher
purity feed-water:
11
Water Treatment Manual
1.4.1 Sea water evaporation
The evaporator is a critical part of the integrated water systems found on sea-going vessels.
These units are essentially low or negative pressure boilers designed to evaporate,
condense and collect pure water from sea-water make-up.
They are normally fed with warm sea-water that has been used to cool the engine cooling
system and extra heat is applied to cause evaporation. Pure water is condensed and
collected for subsequent use in:
The evaporation of pure water from sea-water is probably the most common route to
produce high quality feed water for marine boilers.
These units typically function by distilling pure water from heated sea-water under an
induced vacuum. The water vapour is condensed using a sea-water cooling jacket and
pumped to storage. The concentrated brine produced is ejected to waste.
1. Evaporators operation
2. Seawater feed
3. Heating medium in
4. Heating medium out
5. Seawater cooling in
6. Seawater cooling out
7. Fresh water out
8. Evaporated steam
9. Demister
10. Condenser
11. Evaporator
12. Brine out
12
Water Treatment Manual
13
Water Treatment Manual
Operational Issues
There are numerous suppliers and types of evaporators and they all function to produce
pure water with concentrated sea-water as waste.
This concentration effect can lead to the formation of damaging scales within the evaporator
and lead to downtime for cleaning and maintenance. Over concentration is usually
prevented by having a continuous stream of sea-water passing through the unit thus
maintaining a satisfactory dilution of the sea-water side of the evaporator. However, because
of the high salt content, when sea-water is elevated to temperatures above 30°C scales can
begin to form on heat transfer surfaces.
Depending on the degree of concentration these scales can be:
Calcium carbonate
Magnesium carbonate
Calcium/magnesium sulphate
Additionally as the majority of evaporators operate under vacuum there is a tendency for the
make-up water side to foam, which can give rise to carry-over and contamination of the pure
water stream. There are many mechanisms governing the rate of scale formation but the
main ones are:
Supersaturation
This is where the concentration of dissolved salts exceeds their solubility at the particular
temperature encountered and precipitation begins to occur. When deposition occurs under
these conditions heavy scale deposits can rapidly build up and lead to a loss of heat transfer
efficiency. Scale deposition due to supersaturation is often localised in areas of elevated
temperature such as heat transfer surfaces in heat-exchangers. This is because of localised
over concentration of salts with respect to the temperature of the thin water layer at the
surface of the metal. Scale deposition can therefore occur on heat-exchange surfaces even
when the conditions in the bulk of the water are not scale forming.
Nucleation
This effect describes the initial precipitation of scale particles which can occur in a
spontaneous manner or when a foreign particle acts as a ‘seed’ or nucleation site for the
scale to bind onto and form around. The roughness of internal surfaces plays an important
factor in this process and metal surfaces contain many microscopic peaks and valleys that
act as nucleation sites for scale.
Contact time
In the environment at the heat transfer surface, scale is being precipitated and re-dissolved
continuously and it is only when the rate of precipitation exceeds the rate of dissolution that
scale deposition occurs. In general the contact time required for scale deposition to occur
will reduce as temperature at the surface rises and as flow rate reduces.
pH and alkalinity
As the pH and alkalinity of water increase there is naturally a greater tendency for the water
to be scale forming.
14
Water Treatment Manual
Temperature
Compounds such as calcium carbonate and calcium sulphate exhibit an inverse solubility
with temperature i.e. as temperature rises these compounds become less soluble.
Flow velocity
Low flow rates can lead to non-turbulent or laminar flow across heat transfer surfaces.
This effect will increase the incidence of scaling as it will allow the water to reach higher
temperatures and increase the contact time in an environment for scale formation.
Concentration Factor
In order to prevent excessive concentration of salts in the body of sea-water in the
evaporator it is necessary to apply a continuous blowdown. The maximum concentration
which can be tolerated before calcium and magnesium sulphate or carbonate scales will
begin to form is around 2. Thus for an evaporator producing 5 tons/day or distilled water the
minimum feed rate should be 10 tons/day, and 5 tons of blowdown is required to maintain
the concentration factor below 2.
The concentration factor of the evaporator can be calculated from the amount of feed
divided by input, less the output of distilled water:
15
Water Treatment Manual
Chemical treatment
Even when the concentration factor is maintained in recommended limits there is still a great
risk of scale formation at the heat transfer surfaces due to the mechanisms already
described and it is necessary to apply a suitable scale inhibitors and antifoams to the sea-
water make up line to minimise the occurrence of such problems.
A suitable automatic dosing system can be fitted to provide accurate treatment application.
Successful evaporator performance will be achieved by paying close attention to the
following parameters:
Approvals
Where water from the evaporator is used to provide drinking water or water for cooking, then
the scale inhibitors and antifoams must have suitable approval status such as that from the
U.K. Department Of Transport, Marine Safety Agency, Norwegian National Institute for
Public Hygiene and Health, Japan Food Research Laboratories.
This treatment is capable of removing up to 90% of dissolved solids depending upon the age
of the plant. Further treatment is required if water of demineralised quality is required. Water
containing high levels of hardness is usually pre-treated prior being fed onto the RO
membranes to prevent them becoming fouled with calcium salts.
16
Water Treatment Manual
17
Water Treatment Manual
18
Water Treatment Manual
When these reactive sites are exposed to concentrations of similar ions they will chemically
exchange with these ions. This technology is employed to remove troublesome ions such as
calcium, magnesium and silica for low pressure boilers and even sulphates and chlorides for
high pressure boilers.
19
Water Treatment Manual
Demineralisation
For high pressure boiler it is usual to employ ion-exchange systems that are designed to
remove all cations and anions from the incoming water supply. The most common
arrangement is a strong acid cation exchanger in the hydrogen form in series with a strong
base anion exchanger in the hydroxide form (with or without a degassing tower between
them). Water passes first through the cation exchanger where it is converted to a solution of
dilute acids. The partially treated water passes through the anion exchanger where the
anions (chloride, sulphate, nitrate etc.) are exchanged for hydroxide ions. The hydrogen ions
produced in the first stage react with the hydroxide ions from the second stage to produce
water:
H+ + OH- = H2O
The resins are regenerated when all reaction sites are used up. Cation resins are
regenerated using dilute hydrochloric or sulphuric acids and the anion resin with dilute
sodium hydroxide. For lower water throughputs a single vessel, mixed bed treatment
approach can be utilised for demineralisation.
20
Water Treatment Manual
21
Water Treatment Manual
The following table shows the effect of various routes for pre-treatment. The best approach
for any boiler system is dependent on the quality of raw water, and the quality of water
recommended to supply the boiler.
22
Water Treatment Manual
In a simple water tube circuit, steam bubbles form on the heated side of the tube. The
resulting steam-water mixture weighs less than the cooler water on the unheated side and is
displaced. When the steam water mixture reaches the steam drum the steam bubbles rise to
the surface and disengage into the steam distribution system.
This repeated pattern ensures that steam is produced continuously with adequate water
circulation to prevent overheating of the internal surfaces of the boiler. Most steam boilers
found on ships rely on this principle for water circulation.
A cylindrical shell contains a hemispherical or cylindrical furnace chamber at the base of the
shell. The burner is fired onto this space. From the furnace the hot gases pass through a
single internal flue to the stack. To compensate for the short retention time of gases, water
tubes can be disposed horizontally, vertically, or obliquely (cross-tubes) in the furnace
section. Natural water circulation is effected by having a series of non-heated down-comers
connecting the upper steam/water chamber to the lower ring-shaped bottom header.
Maximum design pressures do not normally exceed 17 bar (250 psig).
23
Water Treatment Manual
24
Water Treatment Manual
High pressure Water Tube boiler systems are fabricated from heavier gauge pipe-work and
this design means that much higher steam pressures and flows can be obtained. Water-tube
boiler can operate at pressures up to 140 bar with steam outputs up to 300 tons/hr. Large
water-tube boiler utilities used for power generation can be around 5 stories high. Smaller
‘packaged’ units are the most common steam boiler arrangement found on marine vessels.
Figure 20 shows a D-type water-tube boiler with an approximate output of 5 tons/hr. The
burner fires onto the loop of the D causing steam/water circulation up the inner tubes and
down the cooler outer tubes. There are a large number of these circuits within the boiler
which are linked by the horizontal pipe-work of the steam and mud drums and sometimes by
ancillary header pipes. The large upper steam drum ensures clean steam and water
separation and blowdown is taken from the bottom mud-drum.
Here the primary steam circuit operates as a closed cycle and the steam/water circuit is
used to evaporate steam from the secondary circuit. The secondary circuit can also be
linked to an exhaust gas boiler for improved efficiency. For water treatment applications the
two systems have to be considered separately and individual treatment regimes applied.
25
Water Treatment Manual
26
Water Treatment Manual
27
Water Treatment Manual
The combustion chamber is pressurised and heat is released at a higher rate than in a
conventional boiler. A combination of forced flow on both the gas and water sides of the
coiled tube provides high turbulence and velocities for efficient and rapid heat transfer. The
fully automatic controls and proportioning system for fuel and air enable the unit to be
operated with the minimum of supervision. The boiler is a packaged unit in the sense that it
is mounted with its auxiliaries on a single base plate. High quality feedwater is essential.
28
Water Treatment Manual
29
Water Treatment Manual
From the general range of TDS in this type of boiler (2,000 - 4,000 ppm) the TDS in
condensate may therefore range from 30 to 160 ppm with the above wetness figures,
without any unusual carryover having occurred.
A frequent cause of priming is sudden increases in boiler loading. Even though the final
steam output is not greater than the boiler rating, rapid changes in steam demand can
require rates of load increase which the boiler cannot handle. This position can be met by
installing an orifice plate after the steam stop valve to control maximum output at any time to
100-125% of nominal rating. If a greater demand develops, the steam after the orifice
expands. The quantity required is thus supplied, although at somewhat lower pressure, until
the boiler 'catches up' with the demand rate. It must be emphasised that an orifice plate is
not useful where the boiler is undersized for the output required. The orifice size can be
calculated approximately by the following formula:
G = 18796 f pV where:
30
Water Treatment Manual
improvement may be achieved by enlarging the holes in the pipe, or shortening the
perforated length. Some boiler makers have taken the latter process to its logical
conclusions and entirely dispensed with an internal feed pipe, providing only a baffle plate
over the feed entry port.
Good control of pre-treatment (e.g. softening) and modern treatment regimes have largely
eliminated precipitation problems.
1.6.4 Superheaters
Superheaters are additional heat recovery systems designed to take extra heat from the
furnace of the boiler into the steam. They are usually fitted to water-tube boiler systems and
consist of a bank of pendant tubes hanging in the furnace chamber. Steam passing through
this arrangement can absorb heat which raises its temperature above its saturation point.
This gives a good thermodynamic gain in efficiency and also acts to further dry the steam
which prevents condensation in turbines if fitted.
31
Water Treatment Manual
Operating mechanism
On start-up a thermostatic air vent allows air to by-pass the main valve (1) to prevent air-
locking. As soon as condensate reaches the trap, the float is raised and the lever
mechanism opens the main valve (2) to allow condensate water to flow into the return pipe-
work. When steam arrives at the float it drops and closes off the main valve ensuring that
live steam does not enter the condensate return system. This cyclic process ensures
efficient removal of condensate water.
Turbines can be categorised into two main classes, condensing and non-condensing.
Condensing turbines exhaust steam at less than atmospheric pressure and non-condensing
turbines exhaust steam at pressures higher than atmospheric.
Operational Concerns
The efficiency and reliability of modern steam turbines can be seriously impaired when
contaminated steam is admitted to the unit. Contaminants in the steam usually cause
deposits on the turbine blades or act to erode the blades due to an increase in abrasive
action.
32
Water Treatment Manual
In all cases the important factor is impure steam. Where turbines are employed it is vital to
ensure that high purity steam is produced by the correct control of water chemistry and
blowdown.
33
Water Treatment Manual
Bottom blowdown
Periodic bottom blowdown is necessary if the boiler operates on shore water as this may
produce calcium phosphate sludge deposits. These will often settle in the bottom of the
boiler, and periodic operation of the bottom blowdown will aid in removing these deposits.
Failure to do so may result in excessive amounts of sludge deposits in the boiler and the risk
of potential overheating of the boiler heating surfaces.
Surface skimmer
Surface skimmers may not be present on all boilers. If the water is distilled or very soft, the
need for bottom blowdowns may be less and the dissolved solids in the water may be
controlled by the surface skimmer. Some boilers may have automatic systems for
maintaining the conductivity in the boiler water.
Cycles of concentration
This term is defined as the ratio of the dissolved solids content between the feed water and
the boiler water. There are several ways to calculate this, measuring chloride levels in the
feed water and the boiler water is a common approach. Figure 31 shows a basic example of
a boiler with 5% blowdown. In this case the cycles of concentration is 20 (10 t / 0.5 t).
Typically this value will be in the range of 10-30.
34
Water Treatment Manual
Steam
9,5 ton/day
Boiler water
Feed water
10 ton/day
Blowdown
250 liter x 2/day
(0,5 ton/day)
Figure 31: Schematic of boiler blowdown
35
Water Treatment Manual
Serpentine, MgSiO3Mg(OH)2H2O
Since these products have extremely low solubility they will precipitate in the boiler water
and can subsequently be removed by blowdown. Again it is important to incorporate
dispersants in the treatment programme to ensure that precipitated compounds are
maintained in suspension and facilitate removal by blowdown.
Silicate scales
Where phosphate cycle chemistry is employed it is important to maintain adequate OH
alkalinity levels to ensure that magnesium precipitates as magnesium hydroxide or as
hydrated magnesium silicate, which are not adherent. To achieve these conditions then we
must aim for a Silica : OH alkalinity ratio of 0.4 : 1 and secondly a PO4 : OH alkalinity ratio of
1 :10. Overdosing of phosphate must also be avoided to prevent the formation of phosphate
scales.
All polymer treatments can be described to inhibit scales by the following mechanisms:
Crystal modification:
The dispersant acts on the surface of the scale as it is formed to prevent the formation of
large angular crystals which are adherent to the heat transfer This action causes the scale to
form in smaller, more rotund particles which are less adherent to surfaces.
Dispersion
36
Water Treatment Manual
The negatively charged polymers attach to boiler metal and surround particles in the boiler-
water. This mechanism sets up repulsive forces that inhibit the particles from agglomerating
to form scale or sludge deposits.
Complexation
Negatively charged polymers can form weak sub-stoichiometric complexes with calcium,
magnesium and iron which allow these impurities to exceed their normal solubility levels and
acts to inhibit deposition at heat transfer surfaces. For best scale control it is important to
maintain an adequate reserve of free polymer in the boiler water at all times.
37
Water Treatment Manual
Corrosion can occur throughout the boiler system. The most common causes of corrosion
are:
Oxygen attack
Over concentration of alkalinity
Acid attack due to presence of Carbon dioxide and Carbonic Acid
Ammonia Attack
With reference to the corrosion cell the corrosion process can be represented as an
electrochemical reaction:
At the Anode:
At the Cathode:
The variables pH, temperature and the concentration of oxygen affect the rate of corrosion.
38
Water Treatment Manual
As temperature and/or oxygen levels rise the corrosion rate accelerates. pH and oxygen
corrosion are inversely related to corrosion rate. This is why alkaline conditions are
maintained in the boiler system.
Oxygen reacts with iron to give ferric oxide (rust) Fe2O3 which will not protect the metal from
further attack and metal is continuously dissolved.
by reducing the level of oxygen as far as possible using mechanical means which
include deaeration and/or judicious heating, coupled with good feed-system design
by ensuring that there is an adequate and controlled reserve of alkalinity in the boiler
water at all times.
It should be noted that not all metal oxides are detrimental. Under low oxygen conditions iron
oxide forms a very thin, dense and adherent layer on the metal, protecting the metal from
further attack. An example is the outside layer of the boiler metal which oxidises and forms
the protective magnetic iron oxide film Fe3O4 (magnetite). Corrosion will only take place if
this film is removed or penetrated and not immediately repaired.
39
Water Treatment Manual
16
14
12
10
Oxygen/ppm
0
0 10 20 30 40 50 60 70 80 90 100
Temperature/°C
40
Water Treatment Manual
This mechanism is exacerbated by the presence of deposits such as scale and iron oxide. If
even small amounts of deposit are present alkalinity levels of up to 20000 ppm have been
reported to exist in such environments.
Magnetite film
breaks down
3. 4 H + C → CH4 (methane)
In high pressure boilers close control of free OH alkalinity is vital to the prevention of
alkalinity attack. We will see later that there are specialised treatment programme designed
to minimise the occurrence of this type of corrosion.
Calcium or Calcium or
Magnesium Bicarbonate Magnesium Carbonate
Sodium Hydroxide
Breakdown of carbonate (2) proceed 70 - 100% completion depending upon boiler pressure.
The CO2 liberated in both reactions is carried over with the steam and dissolves with the
condensate. As it dissolves it forms Carbonic Acid.
41
Water Treatment Manual
Carbonic Acid
Since condensed water is very pure, even small quantities of carbonic acid can significantly
reduce the pH of the condensate and greatly increase its corrosivity.
As little as 1 ppm CO2 in the steam can reduce the condensate pH from 7.0 to 5.5 (Figure
38). At a pH of 5.5 rapid corrosion of steel will occur.
Corrosion due to acid attack usually shows as thinning of metal. Especially at bends and
threaded joints. The on-set of condensate line corrosion can occur very quickly, leading to
steam leaks and high replacement costs.
Ammonia can be present as part of a treatment approach to raise the condensate pH and
reduce corrosivity to steel or by the thermal degradation of other treatments such as
hydrazine. Ammonia is especially corrosive to copper and its alloys in the presence of
oxygen.
42
Water Treatment Manual
The oxygen reacts with copper to produce a copper oxide coating on the metal which can be
rapidly dissolved by ammonia. The reaction cycle produces a soluble cupric ammonia
complex and cause rapid metal loss.
Cu + 1/2O2 → CuO
Pitting often occurs in low pressure boilers due to oxygen attack at breaks in the protective
magnetite film. This form of attack can be very localised and can result in a deep pit leading
to perforation of the metal.
Tuberculation is normally confined to feed-tank and feed-lines of plants using poor quality
feedwater with a high dissolved oxygen content, high bicarbonate alkalinity and low pH.
Crevice attack can occur where tubes are rolled into the boiler end plates and is due to the
setting up of a concentration cell where there are differences in the concentration of salts,
oxygen content and hydrogen ions.
Caustic cracking occurs in areas of high stress, where caustic soda can concentrate and
attack the steel. The advent of all welded boilers, and stress relieving has greatly reduced
the incidence of this type of attack.
Hydrogen embrittlement is confined to high pressure boilers and is the result of the direct
attack of caustic soda on the boiler steel in areas of high heat flux. The hydrogen generated
by the reaction penetrates the grain boundaries of the steel leading to metal failure.
43
Water Treatment Manual
Feed tank design
To obtain the best and most consistent removal of dissolved oxygen especially in lower
pressure boilers with open feed-systems, attention must be paid to the internal configuration
of the Feed-tank.
Figure 39 shows an idealised design which incorporates some common-sense features that
are used to achieve a consistent and even water temperature. It is advised that this diagram
is referred to as the optimum required configuration for the minimisation of oxygen in the
feed-water system.
Note: Significant amounts of Carbon dioxide are not removed by simple heating as the level
of CO2 encountered is usually associated with bicarbonate and carbonate impurities in the
feed-water.
Cavitation
Care must be taken when heating the feed-water as at temperatures above 90°C, with a low
suction head on the feed-pump there is a risk of cavitation on the feed-pump impellers. This
phenomenon occurs because the reduced pressure on the suction side of the impellers
causes the water to boil and steam bubbles to form. Subsequent collapse of these steam
bubbles can be so energetic as to physically destroy the metal surface. The onset of this
problem can be rapid and impeller failure has been known to occur within hours of operation.
44
Water Treatment Manual
Deaeration
This is a process of removing dissolved gasses down to very low levels for increased
corrosion protection, especially in high pressure boiler systems. Deaeration relies on the fact
that when water is raised to its saturation point (boiling point), all freely dissolved gases
become insoluble. In practice this effect is made more efficient by agitating the water and
breaking it up into small droplets. In high pressure boiler plants it is normal practice to
employ a deaerating plant in which dissolved gases (oxygen and carbon dioxide) are
removed from solution by steam heating either under pressure or under vacuum. These
gases are then ejected to atmosphere. The dissolved oxygen content of the water leaving
the deaerator should be as low as possible (0.007 - 0.02 ppm). The trace quantities of
dissolved oxygen remaining after mechanical deaeration should be removed by chemical
treatment. In those cases where a deaerator is not fitted, full oxygen removal by chemical
treatment should be employed. The need for the installation of a mechanical deaerator is
dependent upon various factors such as plant loading, percentage condensate return etc.
45
Water Treatment Manual
Generally speaking, however, plants with an hourly evaporation in excess of 22,000 kg/hr
irrespective of boiler pressure should be provided with full flow mechanical deaeration.
Here, feed-water enters via the first stage heater through spring loaded spray valves.
Droplets formed by spraying increases the surfaces area of the water which improves
heating efficiency and removal of dissolved gases. The feed-water then enters the second
stage heater where it rises to within 0.5 - 2°C of the steam temperature. Oxygen levels are
further lowered and gases are vented to atmosphere. The fully deaerated feed-water then
drops into the storage section.
46
Water Treatment Manual
Again the feedwater is sprayed into the heating chamber. The water is then allowed to
contact the gas free steam as a thin film passing over a series of trays. The gas free water
falls into the bottom section for storage.
47
Water Treatment Manual
Deaerating heads can also be employed to reduce oxygen levels. These units more simply
apply the principles outlined previously and will significantly reduce the level of dissolved
gases in the boiler feedwater.
Trouble shooting
Poor deaeration is the result of either a mechanical malfunction or flow control. Problems,
such as:
Sulphite
Sodium sulphite (Na2SO3) is widely used for oxygen scavenging. Sodium sulphite has been
found satisfactory at pressures up to about 62 bar (900 psig). Above these pressures
48
Water Treatment Manual
decomposition products such as H2S and SO2 can affect steam purity. The preferred method
of application is to dose the feedwater continuously to maintain the concentration in the
boiler water within a specific range. Sodium sulphite reacts with oxygen to give sodium
sulphate.
2 Na2SO3 + O2 → 2 Na2SO4
Where corrosion is experienced in the feed system, the use of a catalysed form of sodium
sulphite is an advantage. The effect of the catalyst (usually a cobalt salt) is to speed up the
oxygen / sulphite reaction, so that it is complete well before the feedwater reaches the boiler,
thus giving a greater degree of protection to feed lines and economisers. The speed of
reaction is influenced by pH of the feedwater which should be between 8.0 and 9.5. Sodium
sulphite adds some solids to the feed-water and care should be taken not to overdose or
utilise cold feed-water as this may lead to and increased blowdown requirement.
Hydrazine
Hydrazine, unlike sodium sulphite, does not increase the dissolved solids content of the
boiler water. Hydrazine is very volatile and should be injected at the earliest possible point in
the feed system. The reaction with oxygen is:
N2H4 + O2 → N2 + 2 H2O
The ammonia produced by the decomposition of excess hydrazine can provide a suitable
alkaline condition in the steam and in the condensate system.
3 N2H4 → 4 NH3 + N2
Provided the excess is controlled to avoid an undue rise in the ammonia level in the steam,
there is little danger of copper corrosion in the condensing plant. Hydrazine is a hazardous
chemical and precautions are essential when handling the product. It is also important to
note that hydrazine is not permitted for use where the steam comes in contact with
foodstuffs.
DEHA
DEHA (DiEthylHydroxylAmine) is an organic oxygen scavenger and metal passivator,
enhancing formation of a protective magnetite layer. It is significantly more volatile than
hydrazine, resulting in increased protection in the steam and condensate system. Being an
amine, it has also some neutralising properties. It is more thermally stable than hydrazine
and can be used for all types of boilers from low to high pressures. The reaction with oxygen
is show below, in practice around 3 ppm DEHA is needed per ppm oxygen.
Carbohydrazide
Carbohydrazide is a 'combined form' of hydrazine. It was designed to minimise exposure to
hydrazine vapours during handling. Carbohydrazide and its reaction products will add no
dissolved solids to the water. Carbohydrazide can be used as an oxygen scavenger and
metal passivator at both high (230 °C) and low (65 °C) temperatures. Carbohydrazide can
be applied to boilers up to 170 bar (2500 psi).
49
Water Treatment Manual
The reaction with oxygen is:
In the boiler, hydrazine is one of the thermal degradation products of carbohydrazide, and
for this reason it cannot be used for steam humidification or where FDA approval is required.
Tannins
Certain alkaline tannin solutions have a good oxygen absorbing ability, with approximately 6
ppm of certain tannin extracts being required to remove 1 ppm of dissolved oxygen at pH 12.
This figure compares favourably with the concentration of 8 ppm of sodium sulphite required
to remove 1 ppm of dissolved oxygen. However, the stoichiometry of the `tannin' reaction
with oxygen is complex, and the use of tannins is at best empirical.
Erythorbic acid
Another effective oxygen scavenger and metal passivator, it is the only non-volatile
scavenger which can be used for spray attemperation. It does not add measurable solids to
the boiler water, is non-volatile, and will not jeopardise steam purity. Erythorbic acid can be
used in boilers up to 122 bar (1800 psi). Erythorbic acid is also on the FDA list of Generally
Recognised as Safe Substances (GRAS).
As with hydrazine, a small amount of ammonia is produced in the boiler. Erythorbic acid is
not recommended for boiler lay-up. Good corrosion control requires a high boiler water pH
value since the magnetite film is at its most stable when the pH value is between 10.5 and
11.5. These pH conditions will normally be achieved by the methods used for scale control.
pH control
In low and medium pressure boilers it is usual to maintain a level of free OH alkalinity to aid
in the prevention of corrosion of steel. The recommended level of free OH alkalinity is
dependent on boiler pressure and heat flux and can be found in the literature e.g. BS 2486
1997 and TUV regulations.
These control methods are based on the hydrolysis of tri-sodium phosphate (TSP) and di-
sodium phosphate (DSP) in the boiler water.
50
Water Treatment Manual
Na3PO4 (<3:1). This is achieved by the equilibrium reaction above. The congruent phosphate
approach utilises mixtures of TSP and DSP to further ensure the absence of free OH
alkalinity and usually run with a Na:PO4 ratio of <2.8.
Other variations on this approach may be encountered in the industry. Control charts such
as the in Figure 43 are used to check whether the water chemistry is correct e.g. if the water
analysis lies in the control box then free OH alkalinity should not be present.
Hide-out
In high pressure water-tube boiler it is sometimes observed that the concentration of soluble
salts, notably phosphate salts, do not rise in line with other salts and when the boiler load
reduces their concentrations suddenly rise. This is phenomena termed ‘hide-out’ and is due
to the reduced solubility of sodium phosphate at temperatures above 250 °C. As load and
temperature at heat transfer surfaces increases then some of the sodium phosphate will
precipitate and measured PO4 reserves will fall. When load and temperature reduce the PO4
salts resolubilise and the reserve is seen to increase. When phosphate hide-out occurs there
is a risk of permanent scale deposition and/or localised evolution of free caustic which in turn
could lead to severe corrosion.
51
Water Treatment Manual
Apart from the loss of metal which will necessitate costly replacement of pipe-work and may
shutdown a part of the plant, the products of corrosion will deposit in traps and strainers.
Some of these corrosion products will be returned to the boiler with the condensate and will
deposit as scale. Above 41 bar (600 psig) iron and copper produced by corrosion, if returned
to the boiler, can be particularly damaging, and causing 'hot spots' leading to tube failure.
Every effort should therefore be made to minimise pick up in the condensate and feed
system. Suggested limits on iron and copper oxides in feedwater to boilers operating at
pressures above 41 bar (600 psig) are less than 0.03 ppm total iron and copper.
52
Water Treatment Manual
1.11.2 Neutralising amines
These are steam volatile, alkaline compounds with the basic formula RNH2 where R denotes
an organic molecule. When applied to the boiler feed-water or direct to the boiler drum these
materials volatilise, pass into the steam system and condensed with the condensate water.
They react with carbonic acid in the condensate water to form an alkaline amine carbonate:
This action neutralises the CO2 present and elevates the pH of the condensate water thus
providing good protection against corrosion. The alkalinity (basicity) of neutralising amines
varies, for example Cyclohexylamine is a much stronger base than Morpholine.
For example at 10 bar Cyclohexylamine has a V/L ratio of 4. This means that 75% of the
amine is available as a vapour and 25% as a liquid. Under the same conditions Morpholine
has a V/L ratio of 0.5 which means that 50% of this amine is present as a liquid i.e.
Morpholine condenses more readily. A range of temperatures and pressures are
encountered in a typical condensate system and therefore it is usual to apply these inhibitors
as mixtures to give best protection of the entire condensate system.
For example, Cyclohexylamine is more volatile than Morpholine and will reach to long
condensate pipe-runs. Morpholine will condense more quickly and protect the earlier, hotter
parts of the condensate system.
Mechanical conditions such as poor trapping and draining of lines, and air ingress may also
need to be corrected.
The correct choice of corrosion inhibitor depends on the boiler system, plant lay-out,
operating conditions and feedwater composition. In general volatile neutralising amines are
better with low make-up, low feedwater alkalinity and good oxygen control. Filming inhibitors
53
Water Treatment Manual
usually give more economical protection with high make-up, air ingress, high feedwater
alkalinity or where the system is operated intermittently. In some cases a combination of
treatment is required.
The protective film is generally stable but extreme pH conditions (high or low) can upset
stability and cause the film to be stripped off. Caution must be exercised when applying
filming amines as they act to clean off any loose iron oxide present in the condensate pipe-
work. If this happens to a great extent the blockages of steam traps and valves may occur.
Because of this it is usual to build up the dose rate slowly. Overdosing can case the filming
amine to accumulate as a sticky mass ‘gunk balls’ which again can cause problems in steam
traps, valves etc. The primary filming amines are very viscous and difficult to apply and have
therefore been superseded by neutralising amine blends in the majority of applications.
1. At least 30 minutes before the boiler is to come off-line make addition of the
treatment chemicals. The chemicals must be well distributed in the boiler water. If the
boiler is on low load then natural circulation will effect mixing. If an auxiliary boiler is
incorporated and is to also go off-line then ensure that treated water circulates
through this system.
2. The boiler should then be filled to the top of the drum and/or auxiliary boiler blanking
off outlets as necessary to avoid flooding steam lines or the superheater. A simple
header device (Figure 44) can be used to verify that the boiler is full and as a check
for leakage.
3. The boiler water should be tested every week to check that oxygen scavenger and
alkalinity levels are being maintained. Extra treatment can be added via the header
arrangement or via a by-pass feeder.
54
Water Treatment Manual
DEHA or hydrazine 100 – 200 ppm or
Sodium sulphite 200 – 400 ppm
Alkalinity 100 – 300 ppm
(pH 9,5 – 10,5)
1. At least 30 minutes before the boiler is to come off-line make addition of the
treatment chemicals. The chemicals must be well distributed in the boiler water. If the
boiler is on low load then natural circulation will effect mixing. If an auxiliary boiler is
incorporated and is to also go off-line then ensure that treated water circulates
through this system.
2. The boiler should then be filled to the top of the drum and/or auxiliary boiler blanking
off outlets as necessary to avoid flooding steam lines or the superheater. A simple
header device (Figure 44) can be used to verify that the boiler is full and as a check
for leakage.
3. The boiler water should be tested every 2-3 weeks to check that nitrite levels and pH
are being maintained. Extra treatment can be added via the header arrangement or
via a by-pass feeder.
55
Water Treatment Manual
pH 9,5 – 10,5
Dry lay-up
1. After the boiler has cooled it should be drained completely, ensuring water is
removed from all low spots.
2. The internal surfaces of the boiler should be thoroughly dried using warm air
circulation.
3. Trays of silica gel (or quick lime) should be placed in the boiler drum and headers to
mop up any moisture. As a rule of thumb, allow 5 kg silica gel per tonne/hr steaming
capacity. Alternatively, a vapour phase inhibitor (neutralising amines) may be used.
4. Seal the boiler carefully, blanking off all openings through which air or steam might
enter. Inspect the moisture absorbent every 8 weeks and replace as required.
Boiler start-up
Ensure that all of the moisture absorbent is removed, fill up boiler with good quality
evaporated water and make initial additions of treatment chemicals. The boiler can then be
brought on-line as usual.
Many different types of contaminants can be found in the waterside of a boiler system.
These can originate from impurities naturally found in or added to the water or from
extraneous materials which have gained entrance due to faulty, worn or defective equipment
associated with the system. This contamination can be in the form of hardness scale, oil,
metallic oxides, sludge and various combinations of these as well as other miscellaneous
materials. The procedure(s) required to clean the system will therefore depend on the nature
and condition of the substances to be removed.
The best initial approach to chemical cleaning is to inspect the fouled system as thoroughly
as possible to determine the nature and extent of contamination. If possible, samples of the
offending materials should be taken for examination and if necessary sent in for laboratory
analyses. Once the results of this preliminary investigation and/or lab analysis are known,
the appropriate cleaning procedure or procedures can be determined and implemented as
follows.
Boil-out
Boil-out procedures are commonly used for pre-commission cleaning of new systems to
remove preservatives, mill scale and other contaminants of construction, subsequent to
major system repairs, prior to returning to service and for the removal of trace amounts of oil
contamination.
Mechanically remove as much oily matter and as many other loose contaminants as
possible.
56
Water Treatment Manual
Degreasing
For removal of light to heavy contamination resulting from ingress of oil due to defective
machinery, equipment seals, or bunker or cargo tank heating coils.
Determine the source of oil contamination and take appropriate steps to eliminate the
problem prior to initiating the cleaning operation.
If deposits are covered with an oily or greasy film, degrease as outlined in the cleaning
manual.
Subsequent to degreasing or, if not required, construct a circuit for recirculating the acid
cleaning solution through the boiler, being certain to by-pass all sections of the system
containing non-ferrous metals. Ensure this circuit is vented at its highest point to allow the
release of gases produced during the cleaning process.
57
Water Treatment Manual
Steam users
Exhaust
Dosing point
Aux. 3
Exhaust boilers
boilers Condensa
te return
Dosing point
2
Evaporator/
R.O Hotwell
system Dosing point
1
Figure 45: Typical dosage point locations
Dosing point 1
Dosing into the hotwell is common, and can be used for non-volatile chemicals. Sulphite,
alkalinity and scale inhibitors can be dosed here. Neutralising amines and oxygen
scavengers based on DEHA, hydrazine or carbohydrazide should not be dosed here as
there will be some vaporization in the hotwell. The dosage point should be below the water
level, preferably close to a water inlet that can provide some mixing.
Dosing point 2
This is the preferred point for volatile oxygen scavengers and neutralising amines. This will
provide protection from dissolved oxygen as early as possible in the system, avoiding
excessive vaporisation in the hotwell.
Dosing point 3
This dosage point is used where separate dosing to multiple boilers is necessary. Scale
inhibitors and some combined treatment are sometimes dosed here. Keep in mind that when
dosing on the pressure side of the feed water pump, the metering pump need to be
designed for pumping against a higher pressure.
58
Water Treatment Manual
1.14.2 Sampling and monitoring
Because of the constantly changing load on a boiler, daily monitoring of the chemical levels
is important to make sure that the system is in good condition. For a small system sampling
is typically taken from the boilers and the condensate return. More complex system would
require samples from the feed water as well.
All sampling points should have a sample cooler to ensure the sample is at a temperature of
20-25°C when sampled. This is important because it will prevent flashing of the volatile
components like the amines and DEHA, yielding lower results than actual when sampling.
Additionally, this will prevent burn incidents of the personnel.
When sampling, there should always be used clean sampling bottles. A good practice could
be to have pre-labelled bottles so that the same bottle is used for the condensate each time.
Trace amounts of boiler water from last sample may very well ‘ruin’ a condensate sample if
bottles are mixed. Ideally, the bottle should be flushed with the water to be sampled a few
times before the samples are collected.
Cleanliness is important when analysing the water. Dirty hands and working benches may
contaminate the samples. As an example, human sweat contains app. 6000 ppm chlorides,
so there is not much needed to contaminate a condensate sample with chloride.
59
Water Treatment Manual
Sensible heat - is that heat which when added to water causes a change in temperature of
the water.
Latent heat - is that heat which causes a change in state, e.g. the vapour produced from
boiling water is steam and the amount of heat needed to change water into steam at the
same temperature is known as the latent heat of evaporation.
Latent heat is not constant and is reduced as the pressure of steam above the water
increases, for example:
The latent heat of steam at atmospheric pressure is 2257.5 kJ/kg (970.6 BTU/lb).
At 6.9 bar (100 psi), latent heat of steam is 2050.5 kJ/kg (881.6 BTU/lb).
While the value of the latent heat becomes less as the pressure rises the value of the
sensible heat increases so there is a steady increase in total heat up to pressures of around
27.6 bar (400 psi) after which the total heat begins to fall off.
1.15.2 Steam
Saturated Steam - is steam without entrained or condensed moisture and without
superheat. It is an ideal condition rarely obtained in the steam space in a boiler as there is
always some entrainment of water. Saturated steam in a pipeline develops moisture content
due to condensation caused by heat losses due to radiation.
Dry Steam - is steam containing no moisture. It should be noted that all superheated steam
is dry.
Superheat - When steam is formed and all the water was evaporated, the addition of heat
will raise the steam temperature. This further increase in heat is known as superheat of
steam. Superheaters must be fitted externally to the boiler in order to raise the steam
temperature at any given steam pressure.
Dryness fraction - is the ratio, weight of saturated steam to total weight of 'steam'. It is
sometimes expressed as a percentage. For example a 'Dryness Fraction' of 0.9 means that
in 1 kg of steam there is a 0.9 kg of saturated steam and 0.1 kg of moisture. As a
60
Water Treatment Manual
percentage this would be expressed at '90% Dry'. A conventional boiler without a
superheater may give steam of dryness fraction about 0.97, i.e. it contains 3.0% of un-
evaporated water as droplets.
Dry saturated steam - is a term that may be encountered in practice. It is simply a double
assurance that the steam is dry and not superheated, i.e. it is true saturated steam.
There are two possible zeros on which boiler pressures can be based:
a) Zero is taken as the pressure in a perfect vacuum. On this basis boiler pressures are
expressed as 'x' bara/psia.
b) Zero is taken as atmospheric pressure. Upon this basis boiler pressures are
expressed as 'x' gauge pressure which in practice is contracted to barg/psig. Zero
barg = 1 bara = atmospheric pressure.
The heat in the steam can be obtained from steam tables. In the case of petroleum fuel oils
and natural gas the published data for their calorific or heat value is sufficiently accurate for
most practical purposes. In order to arrive at the ratio, the weight of fuel used and the total
steam output from the boiler must be known. The thermal efficiency may be expressed in the
gross or net calorific value of the fuel.
Overall efficiency - is used in Power Houses. It is the percentage of heat in the fuel which
leaves the Power House in the form of mechanical or electrical energy. Two factors are thus
taken into account:
Historically, Power House overall efficiencies may be from 30% to 35% and modern CHP
systems can yield overall efficiencies of 55%.
61
Water Treatment Manual
water, the class of fuel burnt, the boiler pressure, and the amount of superheat. All variables
except the calorific value of the fuel can be eliminated by the use of this method:
This evaporation can of course vary with the class of fuel in use and the efficiency of
combustion. It does give an excellent standard provided the fuel and combustion conditions
are stated.
Superheated steam at any given pressure has more energy than saturated steam at the
same pressure and this increase in energy is in the form of sensible heat. The total heat of
saturated steam at a pressure of 'P' is more than the total heat of saturated steam at
pressure (P-p). If dry saturated steam at pressure 'P' is passed through a valve and reduced
in pressure to (P-p) there is no loss of heat and the steam at the lower pressure (P-p)
becomes superheated.
Superheated steam is admitted into a vessel into which water is sprayed in sufficient
quantity to reduce the superheat. Condensate or de-mineralised water should be
used since this form of de-superheating involves the evaporation of water. The use of
raw or treated water may lead to deposition of solids in the de-superheater or further
along the system.
The superheated steam is passed through "U" tubes or a coil in the water/steam
drum of the boiler.
The superheated steam is passed through "U" tubes or a coil in a vessel filled with
boiler water and connected to the water and steam sides of the boiler. The term
'Attemperator' is usually applied to this type of de-superheater.
62
Water Treatment Manual
De-superheating is commonly practiced on turbine driven ships to provide lower temperature
steam for the astern turbine when manoeuvring. This eliminates the danger of superheated
steam reaching the condenser.
1.15.8 Reheat
When superheated steam does work in a turbine, there is an intermediate range of
conditions where superheat and part of the total heat at the saturation has been lost.
Although the steam pressure within this range is substantially reduced, a good deal of useful
work can be obtained if the steam continues to expand. However, the efficiency of the power
unit can be increased if at this stage the steam is superheated again before being used
further.
This superheating of steam which has already done some work is known as reheat. Reheat,
unlike superheat, does not increase steam pressure but only its temperature. Its advantages
show best with a large installation, and it is not usually practiced with small boilers.
Normally, in land practice, the steam is led from the machine at the end of the high pressure
stage into a re-heater section in the boiler. The re-heater will not differ in essential design
from the superheater but will be situated in a cooler part of the boiler. After reheat, the steam
is fed back to the inlet of the intermediate stage of the power unit. With the very high
pressure boilers now being built (above 138 bar) two stages of reheat may be employed. In
marine practice the initial superheat given is frequently appreciably greater than that
required by the engine or turbine. Before reaching the engine or turbine inlet, the
superheated steam passes through a heat exchanger of more or less conventional design,
where the excess superheat is transferred to the steam passing from the high pressure
stage to the intermediate stage. This heat exchanger is also known as a re-heater.
63
Water Treatment Manual
BTU/lb MJ/kg
Gas oil 19,500 45.36
Medium fuel oil 18,900 43.96
Heavy fuel oil 18,760 43.63
Residual fuel oil 18,300 42.56
Anthracite coal 14,500 33.73
Bituminous COAL 8,000-13,000 18.61-30.24
Coke 11,000-13,500 25.59-31.40
Low grade coal, washed slurry or 3,000-8,000 6.98-18.61
washery fines
Town gas 375-550 0.87-1.28
Natural gas 1,025-1,049 2.38-2.44
Commercial butane 3,270 7.61
Commercial propane 2,500 5.81
Table 5: Typical calorific values of fuels
E = CV x B
2260 100
Where neither steam output nor water consumption are measured, it is possible to estimate
the evaporation from the fuel consumption, provided data on fuel CV and boiler efficiency
are available. A well-known fuel efficiency organisation has published data on the average
boiler efficiency for various types. A selection of the data is reproduced below, together with
E values calculated by the above formula for coal and oil having, respectively, CV of 25.59
and 41.89 MJ/kg (11,000 and 18,000 BTU/lb). These are useful in calculating approximately
the evaporation, and hence the likely off-take of chemical treatment - where specific data for
CV and B are lacking for a particular plant. An example is given later.
64
Water Treatment Manual
Boiler Type Coal Oil
B E B E
% kg/kg % kg/kg
Lancashire without economisers 57.3 6.5 63.8 12.0
Lancashire with economisers 65.6 7.5 72.9 13.6
Economic 68.3 7.75 77.0 14.2
Cross-tube Vertical 48.8 5.5 62.0 11.5
Smoke-tube Vertical 58.4 6.65 62.0 11.5
Water Tube 70.2 8.0 70.3 13.2
Example: A compact water tube boiler has been surveyed and the manual gives normal
maximum evaporation as 3200 kg/hr.
A check on fuel ordering shows that 3 tonnes of coal per working day of 10
hours is used.
The average oil-fired economic boiler works closer to the maximum attainable efficiency, and
for this class not more than 5% increase is allowable on the table values.
65
Water Treatment Manual
kg/hr calculated from table
Most modern boilers use modulating control which will provide improvement in the last 3
figures given above.
Spray carryover
This term is used to describe the carryover of fine particles of spray or mist with the steam,
due to the ejection of small drops of water into the steam space when steam bubbles arrive
at the surface and burst. It is a function of the surface tension at the steam/water interface
and some carryover of this kind takes place in all boilers. It can be minimised by correct
design, i.e. attention to the rate of steam release per unit area of water surface, etc. All
boilers will exhibit the type of carry over to some extent.
Foaming
More accurately referred to as 'carryover due to foaming', this phenomenon arises from the
development of a stable foam upon the surface of a boiler water so that some of it is torn off
by the escaping steam and is carried into the steam and condensate system. In severe
cases the whole of the steam space within the boiler drum or shell may become filled with
foam, which can then pass 'en masse' into the steam system. This can lead to dangerous
problems with float type level control switches as false water levels may be detected. The
causes of foaming are not entirely understood but it is associated with absorption of
dissolved salts and suspended solids onto the films of water which are the walls of individual
66
Water Treatment Manual
bubbles, so that small bubbles, instead of coalescing to form larger ones, repel one another.
High alkalinity and/or TDS levels are associated with this type of carryover. It is thought that
the principal function of an antifoam material is to prevent this absorption into bubble films.
Priming
This describes the ejection of comparatively large masses of water into the steam space,
owing to 'spouting' or 'surging' of the boiler water. This spouting or surging may be due to a
number of factors, mainly connected with the rate of steam release and the ease with which
steam and water pass from one section of the boiler to another, and with which steam and
water separate. Priming mainly occurs when steam demand is high and/or variable and is
frequently associated with the too rapid opening of steam supply valves.
Antifoams
Foaming can be minimised by the application of suitable antifoams. When fully dispersed in
the boiler water the antifoam will be present in the steam bubble skin. Here it acts on the
surface of the bubbles. Its presence there weakens the film causing it to rupture easily and
foaming is reduced.
67
Water Treatment Manual
2.1 Introduction
Marine diesel engines are used primarily to provide ships propulsion and electrical power.
Contrary to their name they do not usually burn diesel fuel but heavy fuel oil that is heated
and cleaned by centrifugal filtration. Large quantities of waste-heat are evolved from the
combustion processes. Some of the energy from this waste-heat is recovered and used to
produce steam via exhaust gas boiler systems. The majority of the heat produced by
combustion must be dissipated to prevent overheating and failure of the engines moving
parts such as the pistons, valves and associated seals. This heat dissipation is carried out
by the incorporation of a water cooling circuit into the engine design which provides cooling
for the combustion chamber and cylinder head. The engine cooling circuit is designed to be
a ‘closed cooling system’, i.e. the make-up is normally less than 5% of the system capacity
per week.
68
Water Treatment Manual
69
Water Treatment Manual
Calcium carbonate
Calcium carbonate scale appears as a pale cream. yellow deposit and is formed by the
thermal decomposition of calcium bicarbonate at heat transfer surfaces:
Magnesium silicate:
Magnesium Silicate scale is a rough textured, tan to off-white deposit found in cooling
circuits where sufficient amounts of Magnesium are present in conjunction with adequate
amounts of silicate ions with a deficiency of OH Alkalinity.
H2SiO3 → H+ + HSiO3-
Silicate deposits are also a risk where silicate additives are used to as corrosion protection
for aluminium metal in the cooling circuit. The corrosion mechanism relies on the silicate
forming a protective film in the metal surface and the silicate is maintained in solution by
maintaining a relatively high pH in the cooling circuit (9.5 - 10.5). If this pH is reduced due to
ingress of shore-water or sea-water then the silicate will precipitate in the bulk of the cooling
water (as magnesium or calcium silicate) and cause gross fouling of the cooling circuit.
70
Water Treatment Manual
It is vital when operating a silicate treatment regime for cooling circuits containing aluminium
that the system under consideration should be made up with evaporated or softened water
to prevent this problem.
Hematite (Fe2O3)
This type of red/brown iron oxide deposit is found because of active corrosion occurring
somewhere within the cooling system.
Copper
The presence of copper deposits in a cooling system presents a very serious corrosion risk
because of the initiation of galvanic corrosion mechanisms with steel. The steel in the
cooling system is anodic to the copper and rapid loss of metal will occur. It is usual to
incorporate specific copper corrosion inhibitors in the formulation of cooling system corrosion
inhibitors
Figure 50: Calcium carbonate scale deposition on valve seat / typical iron oxide deposition
71
Water Treatment Manual
The corrosion mechanism pertaining to each metal are different and need to be considered
before selecting the proprietary corrosion inhibitor to give best protection.
Anodic and cathodic sites are formed on the metal surface by numerous mechanisms such
as surface stresses, presence of deposits, grain boundaries, impurities or connection to
other metals of differing nobility.
72
Water Treatment Manual
Once there is an anode and cathode in existence then, with reference to the corrosion cell
above, the corrosion process will commence and can be represented as an electrochemical
reaction:
At the Anode:
At the Cathode:
The variables pH, temperature and the concentration of oxygen affect the rate of corrosion.
As temperature and/or oxygen levels rise the corrosion rate accelerates.
pH is inversely related to corrosion rate. This is why alkaline conditions are maintained in
steam boiler systems and closed cooling circuits.
Oxygen reacts with iron to give ferric oxide (rust) Fe2O3 which will not protect the metal from
further attack and metal is continuously dissolved.
4Fe + 3 O2 → 2Fe2O3
Haematite (ferric Oxide)
Oxygen corrosion is usually observed as localised pitting on a metal surface often with large
tubercles of iron oxide covering the pit.
73
Water Treatment Manual
combines with the chromium and iron to form a highly adherent and protective oxide film. If
this film is ruptured in an oxidising environment then the oxide film is rapidly re-formed.
Therefore the corrosion resistance of stainless steels is reduced in deaerated waters, which
is the opposite to normal steels. The presence of chlorides and other strong ‘de-passivating’
ions can seriously reduce the corrosion resistance of stainless steels. The main drawback of
more widespread use of stainless steels is extra cost and susceptibility to stress corrosion
cracking in the presence of high chloride levels especially at elevated temperatures.
In the engine cooling circuit, like in steam boiler systems, this corrosion mechanism can be
exacerbated by localised boiling and the formation of high concentrations of OH ions at the
metal surface. This will lead to aggressive corrosion and rapid failure.
Zinc is the principle metal used to protect steel as a galvanised coating. Here the zinc is
anodic to the iron and preferentially corrodes at a slow rate thus protecting the steel. Zinc
corrodes at a rate somewhere between that of iron and copper in most natural waters.
Attack will occur in the absence of oxygen as with aluminium. Zinc is also an amphoteric
metal and is corroded at high and low pH.
74
Water Treatment Manual
2.4.2 pH/alkalinity
As previously discussed the corrosion rates of metals with respect to pH can vary depending
on their electrochemical nature. For example the corrosion rate of steel is greatly increased
in acid conditions as they prevent the formation of a protective oxide layer. Corrosion rate of
mild steel reduces as pH rises up to around 13 because of the reducing solubility of iron
oxide in this range. Copper behaves in a similar manner. Aluminium and zinc because of
their amphoteric nature exhibit increased corrosion rates at extremes of pH. The following
diagrams show the general influence of pH on the corrosion rates of metals.
75
Water Treatment Manual
Figure 54: Aluminium pipe from engine circuit with corrosion damage due to high pH
Stress corrosion cracking due to chlorides is a phenomena mostly associated with stainless
steels. Here the chloride ions are just the right size to enter the atomic matrix of the metal
and their concentration accelerates corrosion and causes the propagation of cracks in the
metal. Catastrophic failure is often the outcome of such corrosion mechanisms.
76
Water Treatment Manual
2.4.4 Galvanic corrosion
This relatively common form of corrosion occurs when two dissimilar metals are connected
and exposed to an aqueous environment. One metal becomes anodic and the other
cathodic thus setting up what is termed a ‘galvanic cell’. The anodic metal will exhibit
corrosion in preference to the cathodic one. The most common example of this type of
corrosion is when copper and mild steel are connected in water. The mild steel becomes
anodic because it will give up electrons more readily than copper and subsequently
corrodes.
Figure 56 shows the Galvanic Series of common metals and alloys. The closer the metals
are together in the series the less the corrosion rate and vice versa.
The rate of corrosion at the anode is very much related to the relative surface areas of the
anodic and cathodic metals.
77
Water Treatment Manual
Aluminum alloy 2024
Cadmium
Aluminum alloy 1100
Zinc
Magnesium and magnesium alloys
Active or anodic end of series
2.4.5 Cavitation
Cavitation can be described as the instantaneous formation and collapse of vapour bubbles
in a liquid that is subject to rapid, intense localised pressure changes. In essence this is
localised boiling without a temperature increase. Cavitation damage occurs when this
phenomena act at the metal surface and the hydrodynamic forces created by the collapsing
vapour bubbles create microscopic ‘torpedoes’ of water. These torpedoes can have
velocities of up to 500m/s and on impact with the metal surface dislodge the protective oxide
coating and deform the metal itself. Cavitation is common in feed-pumps on steam boiler
systems and is becoming more common in engine cooling systems as engine manufacturers
move to produce more compact high efficiency diesel engines with smaller, more compact
cooling circuits where the risk of localised boiling is increased.
78
Water Treatment Manual
Corrosion inhibitors are classified on how they affect the corrosion cell and are placed in
three categories:
79
Water Treatment Manual
Anodic inhibitors
Cathodic inhibitors
Combination inhibitors/organic inhibitors
Chromate Carbonate
Nitrite Polyphosphate
Orthophosphate Phosphonates
Bicarbonate Zinc
Silicate
Molybdate
Nitrite (NO2-)
Nitrites are by far the most common corrosion inhibitor used in engine cooling systems and
prove to be excellent corrosion inhibitors for mild steels.
Nitrites oxidise mild steel surfaces to form an extremely thin and highly tenacious layer of
corrosion product. Because of the relatively high dose rates required, nitrites are used
primarily in closed systems for economic reasons. Hydrocarbons and glycols do not affect
the performance of nitrite.
Silicates
Silicates (SiO32-) react with dissolved metal ions at the anode. The resultant metal
ion/silicate complex forms a gel that deposits on anodic sites. The gel forms a thin, adherent
layer that is relatively unaffected by pH in comparison to other commonly used inhibitors.
The inhibiting properties of silicates increase with increasing temperature and pH. Silicates
are normally used to inhibit aluminium corrosion at elevated pH (9.5 - 10.5). This pH range is
critical to maintain the silicate in solution and prevent gross precipitation.
80
Water Treatment Manual
It must be noted that in this environment, if localised boiling causes cavitation and
concentration mechanisms, then extremely rapid corrosion of the aluminium will occur as the
protective oxide layer is destroyed and the metal is dissolved by the high pH conditions.
Orthophosphate
Orthophosphate (PO4) forms an insoluble complex with dissolved ferric ions, such as Fe2+
that deposit at anodic sites. Ferric orthophosphate is more adherent and less pH sensitive
than other anodic inhibitors. The film forms more effectively in a pH range of 6.5 - 7.0.
Typical minimum dose rate in neutral waters are around 10ppm.
Polyphosphate
Polyphosphates will form complexes with calcium, zinc and other divalent ions to form
positively charged colloidal particles. These migrate to the cathodic sites and precipitate to
form a corrosion inhibitor film. Polyphosphates required the presence of calcium to function,
typically a minimum of 50ppm. Extremes of pH can upset the stability of the inhibitor film as
with zinc hydroxide. Additionally reversion to orthophosphate will occur with time and
temperature.
Zinc
Zinc ions are positively charged and are therefore attracted to the cathodic site of the
corrosion cell. The soluble zinc ions react with the free OH ions surrounding the cathode to
form a stable film of zinc hydroxide (Zn(OH)2). This protective film is susceptible to changes
in pH. If the pH is acidic then the film will dissolve and not re-form and if the water conditions
are too alkaline the zinc hydroxide will precipitate in the bulk of solution rather than at the
cathodic site. Typical pH limits for the application of corrosion inhibitors based on zinc are
7.4 - 8.2.
Phosphonates
These materials were initially introduced into water treatment as scale inhibitors to replace
polyphosphates. They have been shown to exhibit adsorption onto the metal surface by the
P-O group especially in alkaline, hard waters. Phosphonates are normally used in
conjunction with other inhibitor types to achieve best corrosion performance.
81
Water Treatment Manual
82
Water Treatment Manual
Typical evidence of this situation is a loss of nitrite reserve but a stable or increasing trend in
system conductivity as the nitrate formed still contributes to conductivity.
The incidence of microbiological fouling in engine cooling circuits is low due to the high
temperatures and pH levels typically encountered. If microbiological fouling is uncovered
then a proprietary biocide should be applied to kill the troublesome bacteria and prevent re-
growth
83
Water Treatment Manual
Figure 62: Typical plate exchanger and shell and tube exchanger layouts
84
Water Treatment Manual
2.9.2 Microbiological fouling
The main problem associated with sea-water cooling circuits is fouling due to presence of
micro-organisms found naturally in sea-water.
The two main problematic organisms are the Mussel (Mytilus Edulis) and the Barnacle
(Balanus Balanoides)
These are common, shelled, filter feeding forms of marine life found world-wide - Australia,
New Zealand, India, Japan, Europe, North America and South America. They can grow up
to 10 cm in length and 5 cm in diameter and cause severe fouling where sea-water is used
as a coolant. These species are very common throughout the world and their spawning
periods will vary depending on the prevalent conditions. Spawning activity occurs when
water temperatures rise above 10-15°C. This means that most deep-sea vessels are
susceptible to contamination and fouling.
Fully grown mussels and barnacles can be eliminated by filters and strainers; however it is
the freshly spawned species (veligers) that cause problems. These veligers start life in a
microscopic size and can easily find their way into the cooling circuit. Once in the system
pipe-work they attach themselves to surfaces using strong elastic threads of protein
(Byssus). Once attached, they can readily feed and grow. As their size and numbers
increase, fouling and blockage of waterways takes place.
85
Water Treatment Manual
2.9.3 Control of fouling
As the problem species are live, micro-organisms they can theoretically be killed using a
variety of biocide additives or the installation of Marine Growth Protection Systems (MGPS).
Chlorine has been used, but it is found that fully grown species can require 0.2 - 1.0ppm free
chlorine for a period of up to 10 days which often impractical on a sea-going vessel.
Additionally fully developed mussels and barnacles can detect the presence of chlorine as
an irritant and will ‘close up’ and secrete a mucous seal that is impervious to the biocide.
The best approach is to eliminate the mussels and barnacles when they are in their most
vulnerable state (as veligers) and prevent them from attaching and growing. This can be
accomplished by the routine application of a proprietary biocide and anti-foulant.
86
Water Treatment Manual
Aluminium alloyed anodes
Aluminium alloyed anodes are used in conjunction with copper alloyed anodes to prevent
corrosion throughout ferrous pipe work.
87