Professional Documents
Culture Documents
MAINTENANCE
MANUAL
TDA-110P
Aerosol Penetrometer
ii
1800103 Rev D Air Techniques Incorporated TDA-110P
Table of Contents
iii
TDA-110P Air Techniques International 1800103 Rev D
iv
1800103 Rev D Air Techniques Incorporated TDA-110P
v
1800103 Rev D Air Techniques Incorporated TDA-110P
1. Utility Requirements
Control Unit
Compressed Air - Clean, dry, compressed airflow rate of 10 SCFM at 80 psig (283 slpm @ 5.6 kg/cm2)
NOTE: Maintain the compressed air temperature between 60 and 90 degrees Fahrenheit (70 to 75 degrees is
recommended). It is highly recommended that a coalescing filter and pressure regulator be installed between the
plant airline and the air inlet.
Power –
Control Unit - Stable electrical power at 115 VAC, 50/60 Hz (a power line conditioner and surge
protection is recommended). 230 VAC, 50/60 Hz is optional.
NOTE: A dedicated power circuit is recommended for stable machine operation. Consult the manufacturer.
Aerosol Unit
Compressed Air - Clean, dry, compressed airflow rate of 10 SCFM at 80 psig (283 slpm @ 5.6 kg/cm2).
Three separate lines required.
NOTE: Maintain the compressed air temperature between 60 and 90 degrees Fahrenheit (70 to 75 degrees is
recommended). It is highly recommended that a coalescing filter and pressure regulator be installed between the
plant airline and the air inlet.
Blower Motor Power - Stable electrical power at 208-230/460 VAC, 3-Phase, 60 Hz.
NOTE: A dedicated power line is recommended for stable machine operation. Consult the manufacturer.
Ventilation - Exhaust the air with a duct capable or directing 500 cubic feet per minute at a resistance of
≤1 inch of water (see Section 5.2 - Exhaust Connection for details).
1
TDA-110P Air Techniques International 1800103 Rev D
2. Specifications
2.1. Physical Characteristics
Control Unit Size 24 in wide x 30 in deep x 72 in high
Weight 210 lbs.
2
1800103 Rev D Air Techniques Incorporated TDA-110P
3
TDA-110P Air Techniques International 1800103 Rev D
12 Resistance window
9 FAULT Indicator light
7 VF Display window
6 Function keys
4
1800103 Rev D Air Techniques Incorporated TDA-110P
(34) Chuck Pilot (36) Aerosol DWN Stream (35) Aerosol UP Stream (32) Resistance
UP Stream
(39) Generator Pilot (31) Chuck Supply (37) Damper Open (38) Damper Close (33) Resistance
DWN Stream
5
TDA-110P Air Techniques International 1800103 Rev D
20 AC Power Input
6
1800103 Rev D Air Techniques Incorporated TDA-110P
17. Exhaust Damper % Open Meter – displays position of exhaust damper in 0 -100 % open
19. Aerosol Generator ON/OFF switch – Turns on the aerosol generator pilot air pressure to enable the
aerosol generators.
20. AC Power Input – Recessed 3-prong, AC power inlet connector for control unit
21. Generator compressed air supply – Regulated compressed air supply for system aerosol generator
22 Electronic Enclosure
25 AC line Filter
23 Main PCBA
7
TDA-110P Air Techniques International 1800103 Rev D
26 Upstream Pressure
Transducer port - P2
27 Downstream
Pressure transducer
port - P1
22. Electronics Enclosure – contains the control relays and PCBA (printed circuit board assemblies)
23. Main PCBA – microprocessor circuit board. Location of operating program E-Prom and 8 bit
microprocessor
24. Main Power Relay (CR1) – maintains power to the control unit circuits, relays and valves after actuation
by the main Power ON switch
25. AC Line Filter –power input line conditioner to remove transient voltage fluctuations
26. Upstream Pressure Transducer Port P2 - Used to determine the filter pressure differential
27. Downstream Pressure Transducer Port P1 - Used to determine the filter pressure differential
28. Communication Port – A DB-9 female connector for RS-232 computer interface used for connection to a
PC serial port
29. User Interface Port - Used to interface with external control equipment
30. Main Pressure Input Port - Input for system compressed air supply
31. Chuck Supply– Compressed air used to raise test chuck to its open position
32. Resistance UP Stream - Used to determine the filter pressure differential
33. Resistance DWN Stream - Used to determine the filter pressure differential
34. Chuck Pilot - Compressed air used to lower test chuck to its closed position
35. Aerosol UP Stream – Sample line for measuring 100% aerosol challenge used for testing
36. Aerosol DWN Stream – Sample line for measuring aerosol challenge level penetrating through the filter
under test
8
1800103 Rev D Air Techniques Incorporated TDA-110P
21 Generator Supply
41 Virtual Impactor
40 Aerosol Generator
43 Flow Sensor
9
TDA-110P Air Techniques International 1800103 Rev D
10
1800103 Rev D Air Techniques Incorporated TDA-110P
11
TDA-110P Air Techniques International 1800103 Rev D
6. Initial Setup
1) Verify that all the input compressed air supplies are connected.
2) Plug the unit into the proper power source.
3) Fill both the 4Blite generators to the fill line (middle) with the oil specified in the
Factory Settings sheet (see Section 7 - Filling Methods).
NOTE: Over or under filling the generator will result in an unstable aerosol
source.
WARNING: If any liquids are used other than that which is specified on the
Factory Settings sheet, the generator will not function to specification.
4) Follow the Machine Startup Sequence (Section 8) until the Test menu (Section 9) is
reached. At this point the TDA-4Blite generators should be on and each of the
regulators located at the generators adjusted to 30 psi.
5) Check the system settings against the Factory Settings sheet included with this
manual.
6) Power the unit off by pressing the red push button.
7) Perform the test set up at this time (Section 12 – Setup Menu) to adjust user
specific testing parameters.
12
1800103 Rev D Air Techniques Incorporated TDA-110P
7. Filling Methods
7.1. Proper Fill Level
PAO Moil must always be used with this equipment.
ATI 4Blite Laskin aerosol generators tanks are
marked with a fill line at the center point of the
reservoir. The PAO oil level should always be
maintained within ± 0.25 inches of the fill line.
13
TDA-110P Air Techniques International 1800103 Rev D
.........
8.8. Initial Calibration
8.3. System Version After a system start the system must perform
the penetration calibration sequence (Section 11).
ATI 110P Ver n.n After this initial calibration is completed, the
machine will be ready for use and will display the
UNIT ID 9999 screen shown in Section 9.
14
1800103 Rev D Air Techniques Incorporated TDA-110P
9. Test Menu
After successful initialization, the TDA-110P will [P] Test % Penetration reading
be ready to test samples. [R] Test Resistance reading
[F] Test Flow reading
9.1. Start Cycle
At this point the machine is idle and can either If all three of the test parameters are within the
initiate a test, setup operating parameters (limits limits specified for the test the sample passes and
and timings), calibrate the LSC, or enter a standby the machine will return to the Start Cycle menu.
state.
If any of the test parameters are outside the
specified limits, the sample will be failed, the red fail
START CYCLE indicator will be illuminated, the display for the
failing parameter(s) will flash, and system will
STBY CAL SETUP display the Failed Check screen (See Section 9.5) if
the Failed Check option is enabled.
<SETUP> Enters the Setup Menu (Section 12).
<CAL> Enters the Calibration Sequence. Results of a test will remain on the displays until
(Section 11) the next operation is started.
<STBY> Enters into Standby Mode
<CLOSE> Close chuck to begin testing
9.5. Failed Check
The Failed Check is used to confirm a failed
9.2. Test Loading test. This check is optional and may be bypassed if
The system is waiting the designated load time
the Failed Lockout dipswitch is set or if the unit is in
prior to testing.
the Automatic Testing mode. (See Appendix A for
setting locations.)
** LOADING **
** FAILED **
CONT
9.3. Testing
Test readings are displayed for the total sample <CONT> Returns to Start Cycle
time in approximately one-second intervals. The
chuck will automatically open at the end of the test
cycle if the sample time has been set. 9.6. Calibration Prompt
This prompt will appear if the “Cycles to
** TESTING ** Calibration” setup option has been selected
(Section 12.14) and the specified number of test
cycles has been reached.
[P] Test % Penetration reading Cal Penetration?
[R] Test Resistance reading
[F] Test Flow reading YES NO
NOTE: If the sample time is disabled, the
test continues until either chuck switch <YES> Enter the penetration calibration
is pressed to end the test. process (See Section 11.7)
<NO> Skip the calibration and return to the
9.4. Test End Start Cycle menu. If the calibration is
At the completion of the test the last sample skipped, the prompt will not appear
parameter readings will be displayed on the until the number of cycles is reached
operator panel and the success or failure of the test again.
indicated by the operator panel status lights. The
displayed values are:
9.7.
15
TDA-110P Air Techniques International 1800103 Rev D
STANDBY
CONT
WAIT
16
1800103 Rev D Air Techniques Incorporated TDA-110P
Insert Filter
and Close
17
TDA-110P Air Techniques International 1800103 Rev D
* CALIBRATING *
0 SETTING
WAIT
18
1800103 Rev D Air Techniques Incorporated TDA-110P
19
TDA-110P Air Techniques International 1800103 Rev D
<ENBL> Enable the alarm function. When <ENTER> Accepts the setting and enters the next
pressed, “ENBL” changes to “DSBL” Setup menu screen
and the digits of the limit are displayed.
<ENTER> Accepts the setting and enters the next 12.6. Test Flow Tolerance Variable
Setup menu screen (Alarm Point)
Flow Tol = ± 99 cfm
12.5. Minimum Resistance Variable
UP DWN DSBL ENTER
(Alarm point)
Res Min = 999.9 mmH2O 99 Alarm activated at test flow readings +/-
this value (Range: 1 – 10)
UP DWN DSBL ENTER <UP> Increases the variable
<DWN> Decreases the variable
999.9 Alarm activated at readings less than <DSBL> Disable the alarm function. When
this set point (Range: 0 – 250 mmH2O) pressed, “DSBL” changes to “ENBL”
<UP> Increases the variable and the digits are replaced by dashes
<DWN> Decreases the variable (“-“).
<DSBL> Disable the alarm function. <ENBL> Enable the alarm function. When
When pressed, “DSBL” changes to pressed, “ENBL” changes to “DSBL”
“ENBL” and the digits are replaced by and the digits of the limit are displayed.
dashes (“-“). <ENTER> Accepts the setting and enters the next
<ENBL> Enable the alarm function. When Setup menu screen
pressed, “ENBL” changes to “DSBL”
and the digits of the limit are displayed.
<ENTER> Accepts the setting and enters the next
12.7. Load Time Variable Setup menu screen
The load time variable is the time from when the
chuck is closed to when the unit begins to measure 12.9. Sample Time Variable
the properties of the sample. This time is used to The sample time variable is the length of time the
establish a stabile aerosol flow. test is sampled in one-second intervals. The unit
displays the test results at approximately one second
Load Time = 99 sec intervals during the testing.
20
1800103 Rev D Air Techniques Incorporated TDA-110P
99.9 Open Time in seconds. (Range 0 to 60) <DSBL> Disables the alarm function
<UP> Increases the variable. <SET > Activates the alarm function
<DWN> Decreases the variable. <ENTER> Accepts the setting and enters the next
<ENTER> Accepts the setting and enters the next Setup menu screen.
Setup menu screen.
12.13. Set Date and Time
12.11. Cycles to Calibration Set/Enter screen
Sets the number of test cycles that must be This screen allows the user to select whether
completed between prompts for system recalibration they want to change the date/time recorded in the
(See Section 9.6). When the specified number of machine or proceed to the next screen.
tests has been completed, the system will prompt the
operator to recalibrate the penetration. This same
interval is used to update the temperature and mm/dd/yy hh:mm
barometric pressure if the ”Auto” selection is made
SET ENTER
for flow compensation is selected. (Section 12)
mm Month (1 to 12)
Cycles to Cal = 9999 CTS dd Day of Month (1 to last day of month)
yy Last two digits of year. (The first two
UP DWN DSBL ENTER digits are assumed to be “20”.)
hh Hour of the day using the 24 hour clock.
9999 (Range 1 – 9999) (0 to 23)
<DSBL> disables the function mm Minutes in the hour. (0 to 59)
<UP> Increases the variable <SET> Enters the date/time setting mode
<DWN> Decreases the variable below.
<DSBL> Disable the alarm function. When <ENTER> Accepts the setting and enters the next
pressed, “DSBL” changes to “ENBL” Setup menu screen.
and the digits are replaced by dashes Date/Time Setting Mode
(“-“). In the date/time set mode, each group of digits
<ENBL> Enable the alarm function. When (month, day, year, etc.) is incremented or
pressed, “ENBL” changes to “DSBL” decremented in turn by the <UP> and <DWN>
and the digits of the limit are displayed. buttons. Pressing the <CONT> button will advance
<ENTER> Accepts the setting and enters the next to the next group of digits.
Setup menu screen
mm/dd/yy hh:mm
12.12. Concentration Reference Alarm
After the Penetration Setup menu, the test UP DWN CONT
aerosol concentration in mg/m3 is displayed. A
concentration error will occur if the concentration falls <UP> Increases the variable
outside of the concentration alarm point window. <DWN> Decreases the variable
(See Section 15.15 – Gravimetric Setup in the <CONT> Advance to the next group of digits.
Maintenance section) After the minutes group, returns to the
Set/Enter Screen.
21
TDA-110P Air Techniques International 1800103 Rev D
13. Maintenance
22
1800103 Rev D Air Techniques Incorporated TDA-110P
Exit Maintenance?
14. Maintenance Menu Structure
Yes No
14.1. Maintenance Menus
The menu structure within the Maintenance A B C D
portion of the TDA-100P operating program is laid
out in a loop. Using the <Next> and/or <Prev> keys <Yes> Exits Maintenance and restarts the unit.
allows navigation through the loop until arriving <No> Returns to Maintenance entry menu
again at the entry point. Selecting <CONT> enters
the feature displayed in the topmost row.
The top level Maintenance features are Maint: Res Offset
“Gravimetric”, “Res Offset”, “Flow Balance”, “LSC
Check”, “LSC Offset”, “View Sensor”, “Cal Sensor”, Prev Next Cont Back
“ID”, “Console” & “Security”. After “Security” the
menu loops back to “Gravimetric”. A B C D
<Prev> Returns to Gravimetric selection
The 100P will enter maintenance mode in three
circumstances: <Next> Proceeds to Flow Balance selection
1. In response to an error such as an LSC failure <Cont> Enters Res Offset
that requires use of maintenance mode to test
<Back> Prompts for Maintenance exit
and recalibrate the system.
2. If the internal memory becomes corrupted. This
will require that all the maintenance calibration Maint: Flow Balance
routines be performed to restore the machine to
an operational state. Prev Next Cont Back
3. After a restart of the machine. To enter A B C D
maintenance mode after a restart, wait until the
System Version is displayed, and then press <Prev> Returns to Res Offset selection
and hold the leftmost function key, ‘A’, until the <Next> Proceeds to LSC Check selection
display changes or a short beep is heard.
<Cont> Enters Flow Balance
4. To re-initialize ALL values stored in the units
battery-backed RAM substitute the rightmost <Back> Prompts for Maintenance exit
function key, ‘D’, for the ‘A’ key called out in
step 3 above.
* Please note that once this initialization has Maint: LSC Check
been performed the previous values cannot be
recovered. Prev Next Cont Back
23
TDA-110P Air Techniques International 1800103 Rev D
24
1800103 Rev D Air Techniques Incorporated TDA-110P
A B C D
Gravimetric Test “AvgFlow = ##.#” is the average sample flow
present during the Gravimetric test period.
Enter Exit
<Cont> proceeds to the next step
A B C D
<Enter> Enters Gravimetric test routine
Loading Complete
<Exit> Returns to Maintenance entry menu.
TotFlow = ###.# Cont
A B C D
Wait
“TotFlow = ###.#” is the total volume of sample flow
30 seconds remaining that passed through the pre-weighed media during
30 second countdown begins before entry into the Gravimetric test period. Record this number.
Gravimetric test <Cont> proceeds to the next step
Determine the amount of weight increase for the
media used during the gravimetric test by
Close Chuck to Start subtracting the starting weight from the ending
weight measured after completion of “Loading”
Exit
Ending weight – starting weight = weight increase
A B C D Divide the weight increase by the recorded TotFlow
Weigh a sample of high efficiency media large value. The result obtained is the aerosol
enough to completely fill the test fixture opening concentration expressed as weight of aerosol (ug)
and record the weight. No sample air flow should per volume of air (l).
be able to pass through the test fixture without Weight increase ÷ TotFlow = concentration in ug/l
passing through the media.
Place the weighed media in the test fixture.
With the media in place depress both actuator
switches at the same time to initiate the Gravimetric
test.
25
TDA-110P Air Techniques International 1800103 Rev D
Exit
Con. = ### ug/l
A B C D
UP DWN ENTER
Make sure that nothing is in the test fixture.
A B C D Depress both actuator switches at the same time to
initiate the completion of this routine.
“Con. = ### ug/l” is calculated using the values
obtained during the gravimetric test. After a loading period, the microprocessor will
adjust the sensitivity of the LSC to obtain the
<UP> Increases the displayed Conc. value required voltage level. At the end of this adjustment
<DWN> Decreases the displayed Conc. Value the display will briefly show the 100% voltage level.
The Sample/Clear valve then changes to the clear
<ENTER> Accepts the entered Conc. Value as the position to provide the LSC with particle free air.
calculated aerosol concentration and continues to After a short delay the Clear 0 baseline voltage
the next step. (stray light) will be stored to memory and briefly
displayed.
The operating program then immediately returns to
Hi Con. = ### ug/l the top level Maintenance entry menu.
UP DWN ENTER 14.3. Res Offset
A B C D Maint: Res Offset
“Hi Con. = ### ug/l” is the upper concentration limit Prev Next Cont Back
for the “Con Check” variable.
A B C D
<UP> Increases the concentration limit
<Prev> Proceeds to Maintenance entry menu
<DWN> Decreases the concentration limit
<Next> Proceeds to Flow Balance selection
<ENTER>Accepts the value displayed as the upper
concentration limit and continues to the next step <Cont> Enters Res Offset menu
The calculated “Hi Con” value displayed will be the <Back> Prompts for Maintenance exit
valued entered for “Con” + 20%. This value may be
increased or decreased at the discretion of the end-
user.
UP DWN ENTER
A B C D
“Lo Con. = ### ug/l” is the lower concentration limit
of the “Con Check” variable.
26
1800103 Rev D Air Techniques Incorporated TDA-110P
A B C D ON OFF EXIT
Prev Next Cont Back <Exit> Returns to the Maintenance entry menu
The menu is used to observe the LSC operating
A B C D voltages for basic troubleshooting purposes.
This routine is used to correct for air flow resistance
differentials between the sample flow path and the
clear airflow path. This is done to minimize LSC Check - Close
response lag in the mass flow meter.
<Prev> Returns to Gravimetric selection EXIT
27
TDA-110P Air Techniques International 1800103 Rev D
A B C D
“LSC Voltage = #.####” displays the voltage output
signal for the LSC.
<ON>/<OFF> Enable/Disables the Sample/Clear
solenoid valve.
<ON> Sample valve is enabled. The displayed
voltage represents the signal generated by the
100% sample of the available aerosol
concentration.
<OFF> Sample valve is disabled. The displayed
voltage represents the signal generated by
sampling particle free air through the 0 Reference
filter. This is the “straylight” voltage.
<Exit> Returns to the Maintenance entry menu
14.6. LSC Offset
Maint: LSC Offset
A B C D
Used to access and set the LSC Offset variable.
The value is used to correct for signal shifts in the
LSC output caused by DC power variations during
operation.
<Prev> Returns to LSC Check selection
<Next> Proceeds to View Sensor selection
<Cont> Enters LSC Offset menu
<Exit> Returns to the Maintenance entry menu
Note: Under most applications this variable is more
easily and accurately set using Console mode
access.
A B C D
“LSC Offset - -###” displays the stored LSC
Offset value. A display of “------“indicates a
disabled state.
<Set> Enters LSC Offset adjustment routine.
<Dsbl>/<Enbl> Enables or disables the LSC Offset
feature.
<Dsbl> indicates the feature is enabled and
pressing the key will disable the LSC Offset.
28
1800103 Rev D Air Techniques Incorporated TDA-110P
A B C D
The TDA-100P will sample for a period of time to Selecting Pressure
stabilize and record the LSC output signal in this
sampling state. Prev Next Cont Back
A B C D
Remove Filter <Prev> Proceeds to LSC sensor output
<Next> Proceeds to Flow senor output
CONT
<Cont> Enters Pressure sensor output
A B C D
<Back> Returns to the Maintenance entry menu
<CONT> Used as an acknowledgement that the
previously installed filter has been
removed and the LSC inet port tubing Voltage = #.#### V
connections restored. The
Sample/Clear valve will de-energize at Exit
the appearance of this screen.
A B C D
“Voltage = #.### V” displays the output signal being
Finding Zero received from the differential pressure transducer.
<Exit> Returns to the initial View Sensor menu,
“Selecting Pressure”.
A B C D
The TDA-100P will sample for a period of time to
stabilize and record the LSC output signal in this Selecting Flow
sampling state before returning to the Maintenance
Prev Next Cont Back
entry menu.
A B C D
<Prev> Proceeds to Pressure sensor output
<Next> Proceeds to Aux Flow senor output
<Cont> Enters Flow sensor output
<Back> Returns to the Maintenance entry menu
29
TDA-110P Air Techniques International 1800103 Rev D
Voltage = #.#### V
Prev Next Cont Back <Exit> Returns to the initial View Sensor menu,
“Selecting Pressure”.
A B C D
This feature is currently not used and is
intended for future applications. Selecting Baro Pres
<Prev> Proceeds to Flow sensor output Prev Next Cont Back
<Next> Proceeds to Temp senor output
A B C D
<Cont> Enters Aux Flow sensor output
<Prev> Proceeds to Temp sensor output
<Back> Returns to the Maintenance entry menu
<Next> Proceeds to LSC senor output
<Cont> Enters Baro Pres output
Voltage = #.#### V <Back> Returns to the Maintenance entry menu.
Exit
30
1800103 Rev D Air Techniques Incorporated TDA-110P
Selecting LSC
14.8. Cal Sensor
Prev Next Cont Back
Maint: Cal Sensor
A B C D
Prev Next Cont Back
<Prev> Proceeds to Baro Pres sensor output
<Next> Proceeds to Pressure senor output A B C D
<Cont> Enters LSC sensor output WARNING: The screens associated steps within
this section are used to verify and/or calibrate the
<Back> Returns to the Maintenance entry menu sensors used during the operation of the TDA-
100P. Known calibration standards, specific
supplies and fixtures may be required and should
DAC = ##, LSC=#.#### be readily available
Only Trained and Authorized personnel should
Up Dwn Samp Exit access these features. Improper or partial
completion of the steps outlined will render the
A B C D TDA-100P inoperable until successful completion.
The View LSC screen is intended as the primary <Prev> Returns to View Sensor selection
working maintenance interface for light scattering
chamber. Using this screen, all necessary output is <Next> Proceeds to ID selection
available to enable optical alignment, PMT
<Cont> Enters Cal Sensor menu
alignment & troubleshooting as well as leak testing.
<Back> Returns to the Maintenance entry menu.
The test fixture should be closed at this time.
Closure may be accomplished using either manual
actuators or an EXT Start signal sent to the User
Port. Selecting Pressure
“DAC = ##” displays the stored gain sensitivity Prev Next Cont Back
setting for the LSC photomultiplier tube
“LSC = #.####” displays the output voltage from the A B C D
light scattering chamber under its current <Prev> Proceeds to Gravimetric test.
conditions. See Section 14.2
<Up> Increases the DAC value by one at each <Next> Proceeds to Flow calibration menu
press. Changes made using this feature are not
retained upon exit. <Cont> Enters Pressure sensor calibration
<Dwn> Decreases the DAC value by one at each <Back> Returns to the Maintenance entry menu
press. Changes made using this feature are not
retained upon exit.
<Samp>/<Cler> Enable/Disables the Sample/Clear Pressure Check?
solenoid valve.
Yes No
<Samp> Sample valve is disabled. The displayed
voltage represents the signal generated by A B C D
sampling particle free air through the 0 Reference
<Yes> enters a pressure verification menu.
filter. This is the “straylight” voltage.
<No> Proceeds to Pressure sensor calibration.
<Cler> Sample valve is enabled. The displayed
voltage represents the signal generated by the
100% sample of the available aerosol
concentration.
<Exit> Returns to the initial View Sensor menu,
“Selecting Pressure”.
31
TDA-110P Air Techniques International 1800103 Rev D
Set for – 0 - WC
A B C D YES NO DEFAULT
<CONT> enters a pressure verification routine. NOTE: Loading “Default” values is not
recommended except in extreme circumstances.
Always be prepared to select <Yes> and set up the
pressure transducer with a NIST traceable pressure
Pressure #.#### calibrator.
Exit
Set for – 0 - WC
A B C D
“Pressure #.###” displays the output signal CONT
being received from the pressure sensor in mm/H2O
A B C D
calculated using the conversion constant stored in
memory. Disconnect both lines from the pressure transducer
so that the transducer inlets are bleeding to
Close any open bleed valves on the pressure
atmosphere (0” water column).
calibrator/source and slowly apply pressure to the
pressure transducer inlet port labeled P2. Attach a pressure calibrator and pressure source in
series with the transducer inlet port labeled P2
Allow the pressure to stabilize at 10, 40 & 80
(uppermost). The pressure calibrator/source should
mm/H2O and compare the TDA-100P pressure to
not be sourcing pressure to the transducer at this
the pressure calibrator displayed pressure. The
stage.
TDA-100P pressure must correspond to the
pressure calibrator display within ± 0.5 mm/H2O at <CONT> enters a pressure verification routine.
all three (3) pressure set points.
Record - 0 - #.####
<Exit> Proceeds to the Pressure Setup menu
ENTER
Pressure Setup A B C D
“Pressure #.###” displays the output signal
Exit Enter being received from the pressure transducer as
voltage.
A B C D
<ENTER> Stores the transducer output signal at
<Exit> Returns to Cal Sensor entry menu.
atmospheric pressure memory.
<Enter> Proceeds to pressure sensor calibration.
If all pressure set point readings in the pressure
check menu were acceptable, restore the pressure
transducer tubing connections and press ‘C’
<EXIT>.
If any pressures set point readings in the pressure
check menu were unacceptable, press ‘D’
<ENTER>.
32
1800103 Rev D Air Techniques Incorporated TDA-110P
<ENTER> Records the transducer output signal at <CONT> Continues to the flow meter zero output
the applied pressure to memory. signal display screen.
<Exit> Returns to the initial View Sensor menu,
NOTE: It is important that the exact value displayed
“Selecting Pressure”.
on the pressure calibrator in mm/H2O be noted at
the moment <ENTER> is pressed. This value is At this step the blower should be OFF to prevent
required for the next step. any air currents from being detected..
33
TDA-110P Air Techniques International 1800103 Rev D
<VOL> Proceeds to the Volumetric based <UP> Increases the displayed flow calibration
calibration routine using cubic feet per minute (cfm). voltage.
<DWN> Decreases the displayed flow calibration
voltage.
VOLUMETRIC CALIBRATION
<ENTER> Stores the entered value to memory.
When Flow = ### cfm
Duct Dia. = #.##”
UP DN ENTER
UP DWN ENTER
A B C D
<UP> Increases the displayed flow calibration value A B C D
in cfm. 330 CFM default for Accuvalve “Duct Dia. = #.####” displays the diameter to be
used for calculating the cross-sectional area
<DWN> Decreases the displayed flow calibration
(inches).
value in cfm.
<UP> Increases the displayed duct diameter.
<ENTER> Stores the entered value to memory.
<DWN> Decreases the displayed duct diameter.
Flow Volts = #.####
<ENTER> Stores the entered value to memory and
UP DWN ENTER returns to CAL SENSOR menu.
14.10. Auxiliary (LOW) Flow Sensor
A B C D
Setup
“Flow Volts = #.####” displays a user entered Ref “Flow2” Input on PCBA
Flow voltage (5.00VDC typical) from a NIST
Feature used to enter Flow Sensor calibration
Traceable calibration sheet.
data for the auxiliary flow sensor.
<UP> Increases the displayed flow calibration
Note – if the flow sensor has been calibrated by its
voltage.
manufacturer then this procedure is not required.
<DWN> Decreases the displayed flow calibration
voltage. Selecting Aux Flow
<ENTER> Stores the entered value to memory and Prev Next Cont Back
returns to CAL SENSOR menu.
VELOCITY CALIBRATION A B C D
<Prev> Proceeds to Flow sensor calibration
When Flow = ####.# fpm
<Next> Proceeds to Temp senor calibration
UP DN ENTER <Cont> Enters Aux Flow sensor calibration
A B C D <Back> Returns to the Maintenance entry menu
<UP> Increases the displayed flow calibration point Enable Aux Flow Sens
in feet per minute.
<DWN> Decreases the displayed flow calibration YES NO
point in feet per minute.
A B C D
<ENTER> Stores the entered value to memory.
<Yes> Enters Aux Flow sensor calibration
<No> Returns to the Maintenance entry menu
Flow Volts = #.####
UP DWN ENTER
A B C D
“Flow Volts = #.####” displays a user entered Ref
Flow voltage (5.00VDC typical) from a NIST
Traceable calibration sheet.
34
1800103 Rev D Air Techniques Incorporated TDA-110P
VOLUMETRIC CALIBRATION
Adj Aux Flow to Zero
When Flow = ### cfm
CONT EXIT
UP DN ENTER
A B C D
<CONT> Continues to the flow meter zero output A B C D
signal display screen.
<UP> Increases the displayed flow calibration value
<Exit> Returns to the initial View Sensor menu, in cfm.
“Selecting Pressure”.
<DWN> Decreases the displayed flow calibration
At this step the blower should be OFF and cap the value in cfm.
probe to eliminate any air currents from being
<ENTER> Stores the entered value to memory.
detected.
Flow Volts = #.####
Flow Zero = #.####
UP DWN ENTER
SET EXIT
A B C D
A B C D
“Flow Volts = #.####” displays a user entered Ref
“Flow Zero = #.####” V” displays the flow meter
Flow voltage (5.00VDC typical) from a NIST
signal being received with no air flow through the
Traceable calibration sheet..
sensor.
<UP> Increases the displayed flow calibration
<SET> Stores the displayed voltage to memory.
voltage.
<Exit> Returns to the initial View Sensor menu,
<DWN> Decreases the displayed flow calibration
“Selecting Pressure”.
voltage.
Select Cal Type <ENTER> Stores the entered value to memory and
returns to CAL SENSOR menu.
VEL VOL
VELOCITY CALIBRATION
A B C D
When Flow = ####.# fpm
<VEL> Proceeds to the Velocity based calibration
routine using feet per minute and the cross- UP DN ENTER
sectional area where the sensor is installed.
A B C D
<VOL> Proceeds to the Volume based calibration
routine using cubic feet per minute. <UP> Increases the displayed flow calibration point
in feet per minute. 250 FPM for TSI
<DWN> Decreases the displayed flow calibration
point in feet per minute.
<ENTER> Stores the entered value to memory.
UP DWN ENTER
A B C D
“Flow Volts = #.####” displays a user entered Ref
Flow voltage (5.00VDC typical) from a NIST
Traceable calibration sheet.
<UP> Increases the displayed flow calibration
voltage.
<DWN> Decreases the displayed flow calibration
voltage.
35
TDA-110P Air Techniques International 1800103 Rev D
A B C D
.Selecting Temp
<Cont> Returns to the Maintenance entry menu.
Prev Next Cont Back Calibration of the barometric pressure sensor is
performed at the manufacturing level. No post-
A B C D
manufacturing calibration is possible
<Prev> Proceeds to Aux Flow sensor calibration
<Next> Proceeds to Baro Pres sensor calibration.
Selecting LSC
<Cont> Enters Temp output calibration
<Back> Returns to the Maintenance entry menu. Prev Next Cont Back
A B C D
36
1800103 Rev D Air Techniques Incorporated TDA-110P
14.12. Console
Console ID 9999
37
TDA-110P Air Techniques International 1800103 Rev D
38
1800103 Rev D Air Techniques Incorporated TDA-110P
Figure 10
NOTE: Make sure that when separating these two
pieces, the Light Barrel is on the bottom and the
Cone is lifted upward (See Figure 6).
WARNING – Failure to do this will cause the
lens to fall out damaging it.
Figure 9 - Phototube
D. Turn on the unit power and enter the Main
Maintenance menu LSC Check (Section 5.3).
Turn off the aerosol to obtain the low reading.
E. Rotate the phototube housing until the highest
reading is achieved.
F. Tighten the wing nut.
NOTE: Follow the aligning procedure if any other
changes were made to the LSC assembly.
16.2. Cleaning
A. Remove the power from the unit.
B. Remove the LSC from the unit.
Figure 11
NOTE: Do not remove the Light Assembly screw or
loosen the Light End Plate screws during cleaning.
C. Remove the three thumbnuts and the F. Wipe the outer lens on the Light Barrel with a
Photomultiplier Tube Elbow (See Figure 5). clean, lint free cloth to eliminate all foreign
D. Remove the three screws securing the Lens matter.
End Plate to the Sample Cone. NOTE: Do not disturb the rubber aperture.
E. Remove the three screws securing the Light G. Wipe the lens and Lens End Plate with a clean,
Barrel to the Sample Cone. lint free cloth to eliminate all foreign matter.
H. Inspect the inside of the Sample Cone and
remove any buildup or foreign matter.
NOTE: Any lint or foreign matter left in the Cone or
on the lenses will decrease the sensitivity of the
LSC.
I. Reverse this procedure to reassemble the LSC
and to reinstall it into the unit.
39
TDA-110P Air Techniques International 1800103 Rev D
16.3. Aligning
A. Turn on the unit power and enter the Main
Maintenance menu LSC Check. Turn off the
aerosol to obtain the low reading.
B. If the Light Assembly was removed, loosen and
move in and out until the lowest reading is
displayed. Tighten the screw.
NOTE: If the Light Assembly is started from the full
in position and pulled out, the reading will start high,
drop, then increase and drop again when the
assembly is in the out position. The low point of the
first drop is the correct setting.
C. If the Light End Plate was moved, loosen the
thumbscrews and realign the plate even with
the barrel. Tighten the screws.
D. Loosen the thumbscrews on the Photomultiplier
Tube Elbow and adjust for the lowest reading.
Tighten the screws.
Figure 12
E. Repeat the Light Assembly adjustment
procedure for the lowest reading.
40
Appendix A. Dip Switch Settings
UNIT_ID A numeric identifier that can be used to distinguish one TDA-110P from another. This number
is included in the result output string reported at the serial port.
PENMAX Maximum allowed penetration during a test. An alarm will be raised if this limit is exceeded.
PENMAX_ON “Y” if maximum penetration limit is enabled; if “N” the upper limit will not be tested.
PENMIN Minimum allowed penetration during a test. An alarm will be raised if the sample penetration
falls below this limit.
PEN_LO_ON “Y” if minimum penetration limit is enabled; if “N” the upper limit will not be tested.
RESMAX Maximum allowed resistance during a test. An alarm will be raised if this limit is exceeded.
RESMAX_ON “Y” if maximum resistance limit is enabled; if “N” the upper limit will not be tested.
RESMIN Minimum allowed resistance during a test. An alarm will be raised if the sample resistance falls
below this limit.
RESMIN_ON “Y” if minimum resistance limit is enabled; if “N” the upper limit will not be tested.
FLOW_TOL Allowable variation tolerance of the sample flow during testing in LPM.
FLOW_TOL_ON “Y” if flow tolerance limit is enabled; if “N” the limits will not be tested.
CYC_TO_CAL Number of test cycles performed between mandatory recalibrations.
CYC_TO_CAL_ON “Y” if the mandatory calibration based on test count is enforced.
LOAD_TIME Delay time (in seconds) allowed for aerosol loading and stabilization.
LOAD_TIME_ON “Y” if load time will be used. If “N”, load time will be ignored.
SAMP_TIME Sample testing time (in seconds).
SAMP_TIME_ON “Y” if sample testing is limited to the value of “SAMP_TIME”. If “N”, testing will run continuously
until an alarm limit is exceeded or the chuck is opened by the operator.
EXT_LOAD_TIME Extended load time (in seconds). Extended load time is used on the first test after calibration
and after a limit error.
Parameters below this line will only appear if the trace level (TLEVEL) parameter is > 1 (one). These
parameters are normally set during the calibration process and should not be changed manually without a
thorough understanding of the impact on test results.
RES_OFF Provides an end-user feature to shift the displayed pressure differential by a fixed amount due
to sample path variations occurring in non-encapsulating test fixtures. Default setting is 0.
RES_OFF_ON “N” disables the resistance offset. Default setting is N (Disabled).
ZERO_OFF An offset in Analog to Digital converter counts that is be applied to the LSC reading, at each
test cycle, during calculation of the % Penetration. Default setting of -120.
ZERO_OFF_ON “N” disables the zero offset. Default setting is N (Disabled)
CAL_100 100% LSC Reading from gravimetric calibration
FLOWCON Flow calibration slope constant
FLOWZERO Zero flow output level for flow sensor (in counts)
GRAVCON LSC slope constant created during gravimetric calibration
GRAVHI Upper response limit of the 100% penetration reading (set during gravimetric routine).
GRAVLO Lower response limit of the 100% penetration reading (set during gravimetric routine).
LSC_DAC LSC DAC (Gain) Setting
RESCON Pressure (resistance) calibration slope constant.
TLEVEL Trace Level determines the amount of diagnostic information displayed through the serial port.
Available levels are 0, 1, and 3, representing minimal, normal and maximum amounts of output.
Default value of 0 to match legacy output content.
QZT Quick Zero Tolerance is a factor applied to the LSC reading returned at the start of each test
cycle to determine if the LSC state has recovered from the previous test. 0=Off. Default value
of 6.
For operating revisions ≥1.17
BPSENSTYPE Specifies the type of barometric pressure sensor installed.
0=None (Default), 1 = MPX4105A, 2= MPX5100A
FLOWSENSTYPE Specifies the mass flow meter installed.
A=Alicat (Default), T=Teledyne Hastings
For operating revisions ≥2.0
ALT100PCT “N” disables the non-encapsulating feature (Default). Default setting is N (Disabled). “Y”
enables non-encapsulating feature utilizing an optional dedicated valve for obtaining 100%
during daily ‘PenCal’ routine.
42
1800103 Rev D Air Techniques Incorporated TDA-110P
43
TDA-110P Air Techniques International 1800103 Rev D
This message occurs when the selected number of tests Enter <YES> to enter the
between calibrations has been reached. (See “Cycles to Cal” for penetration calibration
information about this setting.) This prompt allows the user to enter procedure (See section 11.7.)
Cal Penetration? the penetration calibration procedure or to skip the calibration. Enter <NO> to return to the
Whether the calibration is performed or not, this prompt will not Start Menu (Section 8.3) without
reappear until the number of tests between calibrations count is calibration.
reached again.
LSC PROBLEM
- RUN MAINTEN No LSC output or LSC output less than 30% of initial reading Check LSC LED
– RESET
Check generator level
CON SYSTEM Check drip jar
ERROR Check for proper dilution air
Penetration reading exceeded maximum available span
- RUN MAINTEN Check nozzle pressure
– RESET Clean LSC and run gravimetric
test
Check generator level
Check drip jar
CON TO HI
Check for proper dilution air
- RUN MAINTEN Concentration check higher than Hi setting from gravimetric test
Check nozzle pressure
– RESET
Clean LSC and run gravimetric
test
44
1800103 Rev D Air Techniques Incorporated TDA-110P
CHECK FLOW
Check vacuum pressure
CTRL
System flow is outside of set flow tolerance Readjust flow rate
TURN POWER
Check test flow filters
OFF
CHECK
VACUUM Check vacuum system
The system has lost vacuum or signal from the mass flow meter
TURN MAIN Check mass flow meter cabling
POWER OFF
SYSTEM Turn power off, wait two minutes
ERROR and turn power on
General system fault
TURN POWER If problem persists contact
OFF manufacturer
Verify adequate pressure supply
of 10 cfm @ 80 psig to unit.
CHECK
Verify incoming compressed air
SYSTEM AIR
System pressure switch has not actuated. supply line has a min 0.375” ID
TURN MAIN
(9.5 mm).
POWER OFF
Check system pressure switch
operation.
45
Appendix E. Remote Mode Operation
In remote mode, the TDA110P can be controlled from an external computer through a combination of the
user interface port and commands sent and received through the serial port. The remote mode is selected by
DIP switch 2 (two) and 4 (four) (See Appendix A). The program trace level (TLEVEL parameter) should also be
set to level 1 for remote operation (See Appendix B)
When the machine is restarted in this mode:
1) The machine will wait for air.
2) The check level prompt is bypassed.
3) The system warm-up will proceed.
4) Personnel will be required to either enter or bypass barometric pressure and ambient temperature
selection.
5) The message “Insert Filter; and Close” will print on the VF display. Personnel will be required to
close the test fixture locally or through an HMI, and an external start signal sent through the user
interface port.
6) The sample flow rate is then adjusted using the “Flow Adjustment “ valve located on the front panel
and accepted using the ‘D’ function key on the control panel.
7) The machine will enter an LSC calibration cycle. In the calibration cycle:
a. The machine will remain busy.
b. The message “!Close Chuck” will be sent to the serial port, while the message “Clear
Chuck & Close” will print on the VF display. In response to this, the chuck should be
closed, and an external start signal sent to the machine through the user interface port.
c. Upon receipt of the external start, a 100% calibration will be performed.
d. At the end of the 100% calibration, two messages will be sent to the serial port. The first:
“ PENCAL: LSC_100% = nnnnnn” will display the penetration calibration constants. The
second: “PENCAL: Res Tare = nnnnnn” will display the resistance tare value.
The numbers in the above strings will not occupy a fixed number of digits; they will be as
large as needed to represent the values.
e. A 0 (zero) baseline routine will be performed with no external intervention required.
f. At the end of the calibration process, the “Ready” contact at the User Interface port will
become active.
Note: The calibration beginning from step 7 will also be entered if a “PENCAL” command is sent to the
RS-232 port using the console command protocol (See) or the number of cycles specified by the
“Cycles to Cal” variable is exceeded.
Other operational features of the machine can be controlled through parameter setting commands available
as described in the Console Commands section of this manual (See).
The RS-232 printed statements listed above are the minimum that will be printed during these stages of unit
operation. As greater levels of program trace output are enabled there may be significantly more data
available at the RS-232 port.
Appendix F. USE
ER INTERF
FACE Circu
uit Example
Appendix G. 4B Lite Aerosol Generator
Generator Description
The generators used on the ATI 110P Penetrometer are based on a modified Laskin III-A
nozzle used in conjunction with a virtual impactor. The particle size distribution produced by
this combination is characterized as 0.185 CMD ± 0.020 micron with a standard deviation of <
1.6.
Generator Maintenance
1. If clean, dry, compressed air is used with this unit, little maintenance should be
required.
2. Inspect and drain the compressed air filter/regulator daily, or more often, as required.
3. Yearly, under daily operation, drain all liquid and flush with a solvent to remove any
residue from the unit.
Package the unit in a triple wall carton with a minimum of 3 inches of loose packing fill on all
sides.
48
Appendix H. PAO-4 Safety Data Sheet
2. Hazard Identification
GHS Labeling:
Symbol:
US OSHA/HCS Status: Hazardous under OSHA Hazard Communication Standard Revised in 2012
49
3. Composition/Information on Ingredients
4. First Aid
Inhalation: If inhaled, move to fresh air. If victim has stopped breathing give artificial respiration,
preferably, mouth to mouth. Contact a physician immediately.
Eyes: Flush with large amounts of cold water for at least 15 minutes. Do not let victim rub eyes.
If irritation develops, contact a physician immediately.
Ingestion: Do not induce vomiting. If victim is conscious and able to swallow, promptly have victim
drink water to dilute. Do not give sodium bicarbonate, fruit juices or vinegar. Never give
anything by mouth if victim is unconscious or having convulsions. Contact a physician
immediately.
Skin: Wash affected area with soap and water. Remove contaminated clothing. Launder
contaminated clothing before re-use.
Most important symptoms and hazardous effects: Local necrosis as evidenced by delayed onset of
pain and tissue damage a few hours after exposure.
Indication of immediate medical attention and special treatment needed: If ingested, material may
be aspirated into the lungs and cause chemical pneumonitis. Treat appropriately.
5. Fire-fighting Measures
Suitable extinguishing media: Carbon dioxide, Dry chemical, Foam, Water spray
Specific protective equipment and precautions for fire fighters: Use water spray, dry chemical,
foam or carbon dioxide. Water may be ineffective but should be used to keep fire exposed containers
cool. If a spill or a leak has not ignited, use water spray to disperse the vapors. Water spray may be
used to flush spills away from fire.
Perform only those firefighting procedures for which you have been trained. Firefighters should wear
self-contained breathing apparatus in the positive pressure mode with a full face piece where there is a
possibility of exposure to smoke, fumes or hazardous decomposition products.
Flammability Properties:
50
6. Accidental Release Measures
Environmental Precautions: Do not allow spilled material to enter sewers or streams. If spills are
likely to enter any drain, waterway or groundwater, contact the
appropriate governmental agency.
Methods and materials for containment: Add dry material to absorb (if large spill, dike to contain).
Using recommended protective equipment, pick up bulk of
spill and containerize for recovery or disposal. Flush area
with water to remove residues.
Precautions for safe handling: Read label for instructions in use of product. Prevent small spills and
leakage to avoid slip hazard. Material can accumulate static charges which may cause an electrical
spark (ignition source).
Conditions for safe storage: Store in closed containers in a cool, dry well ventilated area. Maintain
closure of bungs. Store at temperatures between 5oC and 50oC. Do not reuse container. Avoid
container damage while storing.
Empty containers retain residue (liquid and/or vapor) and can be dangerous. Do not pressurize, cut,
weld, bronze, solder, drill, grind or expose such containers to heat, flame, sparks, static electricity or
other sources of ignition; they may explode and cause injury or death. Do not attempt to refill
containers since residue is difficult to remove. Empty drums should be completely drained, properly
bunged and returned to a drum reconditioner. All containers should be disposed of in an
environmentally safe manner in accordance with governmental regulations.
Appropriate engineering controls: Proper protection and controls is dependent upon the potential
exposure conditions. No special requirements are needed under ordinary conditions where adequate
ventilation is available.
Respiratory protection: Needed when airborne contaminant concentrations are at a level which cannot
protect worker health. Then an approved respirator must be used. Selection of the respirator is
dependent upon regulatory conditions.
For high airborne concentrations, use an approved supplied-air respirator, operated in positive pressure
mode.
51
Eye protection: No eye protection is needed under conditions of normal use. If there is a possibility
that the product can be splashed into the eyes, then safety glasses with side shields or chemical goggles
are required. Contact lenses should also not be worn if the product could be splashed into the eyes.
Hand protection: No gloves are required for single, short duration exposures. For
prolonged or repeated exposures, wear rubber gloves.
Body protection: If product use involves single, short duration exposures, then no additional protective
wear for covering the skin is required. For prolonged or repeated exposures to the skin, wear
impervious, protective clothing including rubber safety shoes to avoid skin contact.
Inhalation Toxicity: Practically non-irritating. LC50 > 5 mg/l Based on testing of similar products
Oral Toxicity (Rabbits): LD 50 > 15 g/kg Practically non-irritating
Skin Irritation (Rabbits): Practically non-irritating. Primary irritation score 1.3 (Scale 0-8)
52
Dermal Toxicity (Rabbits): LD50 > 5 g/kg. Practically non-irritating
Eye Irritation (Rabbits): Practically non-irritating. Eye irritation score: 2.0 at 1 hour, 2.0 at 24
hours (Scale 0-110)
Aspiration Toxicity: May be fatal if swallowed and enters airways. Substances known to cause
human aspiration toxicity hazards or to be regarded as if they cause human
aspiration toxicity hazard.
Chronic Exposure Target Organ Effects: No data is available to indicate product present at greater
than 1% is a chronic health hazard.
Carcinogenicity: This product present at a level of 0.1% or higher is not considered to be carcinogenic
under IARC.
Persistence and degradability: Biodegradability of this material is greater than or equal to 20%. This
material is inherently biodegradable.
Disposal methods: Product can be disposed of by burning in an enclosed, controlled burner for fuel
value or disposal by supervised incineration. Such burning may be limited by the
controlling authority. In addition, the product is suitable for processing by an
approved recycling facility or can be disposed of at any licensed waste disposal
site.
Precaution for disposal: All recovered material should be packaged, labeled, transported and
disposed or reclaimed in conformance with Good Engineering Practices.
Comply with all applicable governmental regulations. Avoid land filling of
liquids. Reclaim where possible.
53
14. Transport Information
California Proposition 65
This product contains no listed substances known to the State of California to cause cancer, birth
defects, or other reproductive harm, at levels which would require a warning under the statute.
References and Sources: Information contained in this safety data sheet is based on Air Techniques
International owned data and public sources deemed valid or acceptable.
The absence of data elements required by ANSI or 2001/58/EC indicates
that no data meeting these requirements is available.
Disclaimer: This document has been prepared in good faith and from information provided to us by
our suppliers and other sources considered to be reliable. No warranty, express or implied is given. The
buyer is responsible to evaluate all available information when using this product for any particular
use. The buyer is also responsible for complying with all Federal, State, Provincial, and Local Laws
and regulations when using this product.
54
Appendix I. Blower Motor
55
Appendix J. Flow Sensor Operation and Service Manual
The flow sensor manufacturer’s installation, operating and service instructions are
included in this addendum. Please follow the manufacturer’s recommended
instructions for service and operation.
Appendix K. Manual Revision
Date Revision
Base Manual version September 2006 A
Limited release firmware manual September 2007 B
Updated to include operating code &
design revisions incurred since 2007 December 2012 C
Rev B release
Updated PAO SDS. Altered content
October 2015 D
to reflect Oct 2015 build
57