1. Software
2. Alarms Commissioning steps
1. Software required
Plugged the USB cable between PC and Eltek controller (this cable is provided also with the
equipment).
Start the Power Suite program and connect to the equipment.
You'll be promted with the following window...
Then select Access – Login and input 0003 as passoword, this gives you service access.
Select Alarms overview, here you have 4 tabbed menus (Summary, Configuration, Outputs, Logical
Groups), on the Configuration tab we will discard some Mains related events (by default Eltek
generates the mains alarm for multiple events)
We will drag and drop the mains events from Mains alarm to Not Assigned like this:
Continue to drag and drop events until only Mains Fail-Major Alarm remains.
Next we will select the Outputs tab, on coontrol unit will be selected Smart Pack
All checked boxes will be unchecked in order to define (check) our alarms like this:
For this unit the wiring will be made for normal open. On the IO Monitor unit you can select normal
open or normal closed by wiring the alarms.