All alarms in table should be ticked in output alarm configuration menu in Eltek web software.
Connection between rectifier alarm card and Base Band
This should be UTP cable connected to Base Band that controls L18 (usually BBy) on port 1 but this
should be communicated with integration engineer.
Connection of Krone alarm block and rectifier alarm card
Setting output alarms on Eltek
Set output alarm as on photos above. Alarm output 1 should have ticked only MAINS failure, Alarm
output 2 only HIGH TEMP etc. Click on each of 4 alarm output 1, 2, 3 and 4 and change it to NORMALLY
DEACTIVATED.
Programming Eltek input alarm card
Click on EDIT button to define input alarm. All 6 inputs should be renamed as on photo above, form
Hight Temp to Free Cool Fan. ONLY active alarms on site should be ENABLE (ticked like below). For only
active – enabled alarms status will be active, green – alarm free, red – alarm active. Above example is
where all 6 alarms are enabled – exist on site and they are alarm free, no active alarm.
Choose YES in Existing alarm column if alarm exist on site, choose NO if it is not present. Choose OK in
Alarm after this project if alarm is cleared and working after swap or NOK if not. If in column existing
alarm is chosen NO, then in alarm after should be chosen N/A.