You are on page 1of 1

NORTH

KEY PLAN :

G F E D C B A QIBLA

FCU:-TFC-H-120 LM FCU:-TFC-H-120 LM FCU:-TFC-H-120 LM FCU:-TFC-H-120 LM


E1-L01-APT-109 E1-L01-APT-110 E1-L01-APT-101 E1-L01-APT-102
AIR FL:-588 L/s AIR FL:-588 L/s AIR FL:-588 L/s AIR FL:-588 L/s
BOU :- 2600 BOU :- 2600 BOU :2600 BOU :2600 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6

BALCONY BALCONY BALCONY BALCONY

KIT.
LIVING/DINING

KIT. KIT. KIT.

BEDROOM BEDROOM BEDROOM LIVING/DINING


LIVING/DINING BEDROOM
LIVING/DINING
FCU VALAVE PACKAGE
INSTALLATION DETAIL

PR.
PR. PR.
PR.

BATH BATH BATH


BATH WIC.
WIC.
WIC.
WIC.
109 110 101 102
1B-D 1B-B 1B-B 1B-D
109 102
110 101

FCU:-TFC-H-120 LM
DN KIT. E1-L01-APT-103
PR. SHAFT PR.

CORRIDOR
103

103
KIT. 108 AIR FL:-588 L/s
108 1B-C BOU :- 2550
1B-C
STAIRCASE E1-2 STAIRCASE E1-1
SHAFT
FCU:-TFC-H-120 LM UP UP
E1-L01-APT-108 REFUSE
AIR FL:-588 L/s ROOM
BOU :- 2590

LIVING/DINING
BTU METER
LIVING/DINING
INSTALLATION DETAIL

CORRIDOR
TELECOM
ELEC. ROOM
ROOM
MEP VOID LIFT E1-1
FIRE/SERVICE MEP
LIFT SHAFT
WIC. WIC.
BEDROOM MEP BEDROOM
SHAFT
WMC

BALCONY
LIFT LOBBY
BALCONY

104 BATH
1B-F
BATH

104
106 FCU:-TFC-H-140 LM 105
FCU:-TFC-H-90 LM
106 E1-L01-01 E1-L01-02 105
1B-E AIR FL:-625 L/s AIR FL:-360 L/s 1B-E
BOU :- 2500 BOU :- 2500
BATH BATH
LIVING/DINING
WIC. WIC.

CORRIDOR PR. BEDROOM


PR. PR.

107 LIVING/DINING
107

LIVING/DINING BEDROOM LIVING/DINING


ST-A BEDROOM

KIT. FCU:-TFC-H-120 LM
WIC. WIC.
E1-L01- APT-104 BATH
FCU:-TFC-M-85 KIT. FCU:-TFC-H-120 LM AIR FL:-588 L/s
FCU:-TFC-H-120 LM
E1-L01-APT-107 E1-L01- APT-105 BOU :- 2650
E1-L01- APT-106
AIR FL:-588 L/s
DRAWER

BATH KIT. AIR FL:-472 L/s AIR FL:-588 L/s KIT.


BOU :2550 BOU :- 2600
BOU :- 2590

TERRACE TERRACE TERRACE

DEYAAR DEVELOPMENTS PJSC

DEYAAR DEVLOPMENTS PJSC


THE MIDTOWN

SCHEDULE OF CHWP INSULATION RAMBOLL MIDDLE EAST LTD.

PIPE DIA PROPOSED THCKNESS Dubai, UAE


P.O. Box 116921
T: +971 4 3343616
INTERNAL F: +971 4 3343617
E-mail: ramboll-mea.com
FROM 20mm UPTO 40mm 19mm TUBE INSULATION.
FROM 50mm UPTO 100mm 25mm TUBE INSULATION.
FROM 125mm UPTO 300mm 25mm SHEET INSULATION.
EXTERNAL bh B E L H A S A
FROM 20mm UPTO 32mm 55mm THICKNESS
25mm TUBE INSULATION - 1st LAYER +
25mm SHEET INSULATION - 2nd LAYER
FROM 40mm UPTO 65mm 64mm THICKNESS MENASCO
32mm TUBE INSULATION - 1st LAYER + MECH. CONTRACTING (L.L.C.)
32mm SHEET INSULATION - 2nd LAYER P.O.BOX # 19086 Tel 04-2611164,7 Fax 04-2611696 DUBAI U.A.E
P.O.BOX # 65547 Tel 06-5351750 Fax 06-5351740 SHARJAH U.A.E
E-Mail-info@menascodubai.com Web site - www.Menascodubai.com
FOR 80mm 64mm THICKNESS
32mm TUBE INSULATION - 1st LAYER +
32mm SHEET INSULATION - 2nd LAYER E1 TYPE BUILDING - 3E
FOR 100mm 64mm THICKNESS 1st FLOOR PLAN
32mm SHEET INSULATION X 2 LAYERS AIR CONDITIONING LAYOUT
FROM 125mm UPTO 250mm 80mm THICKNESS
40mm SHEET INSULATION X 2 LAYERS A1
FROM 300mm UPTO 400mm 100mm THICKNESS
50mm SHEET INSULATION X 2 LAYERS
NOTE: CHW PIPE INSULATION COVERED WITH CANVAS CLOTH & FOSTER P-145-MMC-AB-MEP-MC-AC-Z2-008 04
IN RISER SHAFT & ROOF AREA