WALK CIRCUIT PROTECTION

BATHROOM CIRCUIT VOLTS


IN LOAD DESCRIPTION QUANTITY VOLTS AMPERE SIZE OF WIRE SIZE OF CONDUIT
NUMBER AMPERE
CLOSET AT AF P
BEDROOM 2 BEDROOM 3 BEDROOM 1
2 - 2.0mm² TW
KITCHEN DINING ROOM LIVING ROOM MEDIA ROOM 1 LIGHTING OUTLET 25 2500 230 10.87 15 50 2 16mmØ PVC
WALK IN WALK IN COPPER WIRE
CLOSET CLOSET
2 - 2.0mm² TW
2 LIGHTING OUTLET 23 2300 230 10 15 50 2 16mmØ PVC
COPPER WIRE
BATHROOM
2 - 2.0mm² TW Ka
DOWN DOWN 3 LIGHTING OUTLET 23 2300 230 10 15 50 2 16mmØ PVC ru
COPPER WIRE
ha
CONVENIENCE 2 - 3.5mm² TW ta
WALK IN WALK IN CLOSET 4 9 3240 230 14.09 20 50 2 16mmØ PVC n
CLOSET STORAGE/ OUTLET COPPER WIRE Ro
MECHANIC ad
CONVENIENCE 2 - 3.5mm² TW
ROOM 5 5 1800 230 7.83 20 50 2 16mmØ PVC

ve
OUTLET COPPER WIRE

rA
bo
BATHROOM CONVENIENCE 2 - 3.5mm² TW

Ar
GARAGE 6 7 2520 230 10.96 20 50 2 16mmØ PVC Ac
OUTLET COPPER WIRE a cia

St.
UP UP
GUEST ROOM MASTER'S BEDROOM BATHROOM CONVENIENCE 2 - 3.5mm² TW St
7 .

s
LOCKER 6 2160 230 9.39 20 50 2 16mmØ PVC

Batanga
OUTLET COPPER WIRE
CONVENIENCE 2 - 3.5mm² TW
8 7 2520 230 10.96 20 50 2 16mmØ PVC
OUTLET COPPER WIRE
2 - 3.5mm² TW
9 1.5 HP ACU 1 2300 230 10 30 50 2 16mmØ PVC
COPPER WIRE

10 1.5 HP ACU 2300 230 10 30 50


2 - 3.5mm² TW
16mmØ PVC
SITE
1 2
COPPER WIRE
2 - 3.5mm² TW
11 1.5 HP ACU 1 2300 230 10 30 50 2 16mmØ PVC
COPPER WIRE
3RD FLOOR 2ND FLOOR GROUND FLOOR 2 - 3.5mm² TW
12 1.5 HP ACU 1 2300 230 10 30 50 2 16mmØ PVC
FLOOR PLAN FLOOR PLAN FLOOR PLAN COPPER WIRE
2 - 3.5mm² TW
13 1.5 HP ACU 1 2300 230 10 30 50 2 16mmØ PVC
COPPER WIRE
2 - 3.5mm² TW
14 SPARE - 3680 230 16 20 50 2 16mmØ PVC
COPPER WIRE
ACU ACU
VICINITY MAP
11 12

ACU

9
SCHEDULE OF LOADS
4

7 5
8
DOWN DOWN

SPECIFICATION
CONVENIENCE OUTLET 1. ALL ELECTRICAL WORKS SHALL BE EXECUTED WITH
10
UP UP
PROVISION OF THE LATEST PHILIPPINE ELECTRICAL
2-38mm² THWN IN 35mmØ RMC
ACU
AIR CONDITIONING UNIT 1-PC 8mm² THWN CODE, LAWS AND ORDINANCES OF THE MUNICIPALITY,
ACU

13 SERVICE ENTRNCE: 125/600V, 3


WIRE
M AND RULES AND REGULATIONS OF THE LOCAL POWER
PIN LIGHT COMPANY.
ACU
2. POWER SERVICE TO THE BUILDING SHALL BE 230V,
COMPACT FLUORESCENT 125AT/2P
SINGLE PHASE AND 60 HERTZ SUPPLY.
LAMP
3. ADEQUATE AND EFFECTIVE GROUNDING EQUIPMENT
SQUARE FLUORESCENT 15AT/2P 15AT/2P
SHALL BE PROVIDED.
LAMP 1 2 4. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL
3RD FLOOR 2ND FLOOR GROUND FLOOR
POWER LAYOUT POWER LAYOUT POWER LAYOUT 40 W / 20 W FLUORESCENT BE NEW AND OF APPROVED TYPE FOR THE LOCATION
3 15AT/2P 20AT/2P
4
LAMP AND PURPOSE.
5 20AT/2P 20AT/2P
6 5. SMALLEST CONDUCTOR FOR LIGHTING SYSTEM SHALL
WALL FLUORESCENT LAMP BE #14 AWG(2.0mm²) AND THE SMALLEST RACEWAY
S3w S3wHI SJ
S3w
A A C C

SHALL BE 15mmØ.
J J

7 20AT/2P 20AT/2P
8
S
1 HOME RUN CIRCUIT 6. NO BRANCH CIRCUIT SHALL HAVE A LOAD OF MORE
S
H I

B
SAB
9 30AT/2P 30AT/2P
10 THAN 80% OF ITS RATING.
S S S S A S ONE WAY SWITCH
30AT/2P 30AT/2P
7. MOUNTING HEIGHTS SHALL BE AS FOLLOWING:
H I
S
D D
11 12 A. LIGHT CONTROL SWITCHES - 1.40m ABOVE FLOOR
3
S
N S3wNO
1
S
S3w 3 WAY SWITCH FINISHED
DOWN J

2 S3wH S3wI
DOWN C SCD 13 30AT/2P 20AT/2P
14 B. CONVENIENCE OUTLET - 0.30m ABOVE FLOOR
N S
F F
O

LIGHTING PANEL BOX FINISHED


C. SPECIAL PURPOSE OUTLET - AS REQUIRED BY THE
L E

S
S SM S3wNO S S

A
POWER PANEL BOX
EQUIPMENT
S S3w S
L E
D. PANEL BOARDS - 140m ABOVE FLOOR FINISHED
8. ALL ELECTRICAL WORKS SHALL BE DONE UNDER
G

SFG S SE
UP UP
S S

L E
ELECTRICAL LEGEND DIRECT SUPERVISION OF DULY LICENSED
M M
SKL ELECTRICAL ENGINEER OR MASTER ELECTRICIAN.
S

S3w K RISER DIAGRAM

GENERAL NOTES AND SPECIFICATIONS

3RD FLOOR 2ND FLOOR GROUND FLOOR


LIGHTING LAYOUT LIGHTING LAYOUT LIGHTING LAYOUT

CONTRACTOR'S LOGO NAME OF PROJECT NAME OF OWNER SHEET CONTENT DESIGNED BY: CHECKED BY: NAME OF PEE PRC REG NO. SHEET NO.

FLOOR PLAN
CHEYSHEL MAE GERANTA EISEN JAYLORD C. CO ENGR. DAGANIO PTR NO.

ADDRESS OF OWNER
LIGHTING LAYOUT
POWER LAYOUT
RISER DIAGRAM
DRAWN BY: DATE ISSUED
E1
SCHEDULE OF LOADS

B6 L12 VILLA SAMANTHA SUBDIVISION


LAWA MEYCAUAYAN BULACAN
VICINITY MAP
LEGEND
GENERAL NOTES AND SPECIFICATIONS
EISEN JAYLORD C. CO TIN. 1