L3 MAJOR ADVANTAGES
L2
L1
N
• Very small dimensions
• Simple installation
• Low flammability
N
• Self-extinguishing insulation IEC-332
L1
L2
L3
• Electrical continuity
E30-E90 finishing available
• Maintenance free
• ATEX
up to 10 kV
explosion proof •
E30
Manufactured MV-elements
are supplied with a test report.
I K 1 0
IP68.
electrical continuity
A90 H 6 0
degree of protection
The junctions and the element ends are overcast with the
same insulation mix as used for the elements. In this way an
integral insulation enclosure to IP68.IK10 is guaranteed over
the full length of the busbar run. Strainght junctions and also
elbow junctions are available each facilitating installation
adjustments of 10-20 mm per standard junction.
straight elements
elbow elements, flat-flat and on edge
Z (double elbow) and T elements
flanged terminal elements
tap-off facilities and phase-transfer elements
thermal expansion compensation elements
tailor-made terminal elements for transformer
or generator and switchboard connection
Applications:
Alu-conductors range up to 5250 Amps
Cu-conductors range up to 6500 Amps
Up to 1500 V DC
Applications up to 16,000 Amps
Type tests:
All technical data specified, such as current ratings and temperature
rise, insulation, resistance, voltage and short circuit withstand, have
been certified in accordance with international standards (IEC, VDE
or BS) by the independent testing stations K.E.M.A., LABORELEC,
LCIE. Assembled elements with cast junctions were submitted for
type testing.
Factory tests:
Prior to shipment, all elements are subjected to the following tests:
Low Voltage systems: insulation resistance measurement and volt-
age withstand Medium Voltage system: voltage withstand, insulation
resistance and partial discharge measurement
Test reports:
Copies of official certificates and works reports are sent on request for
Low Voltage. All M.V. elements are supplied with a works test report.
Type 3-4-5 cond 6...10 cond In In cond. Icc R20 R 95 X Total weight *
BXH BXH norm 35 / 40°C 1sec dyn 3..5 cond 8..10
mm mm A A mm² kA kA m m m ~kg/m
ALUMINIUM AL AL AL AL AL
E single duct
LA04EA 104 x 80 500 520 160 12.0 ** 45 181.3 229.8 52.0 20.5
630 630 240 18.0 45 120.8 153.5 54.6 21.1
LA08EA 104 x 120 800 860 320 22.5 ** 75 91.5 115.0 31.5 30.6
1000 1050 480 33.5 75 61.9 77.0 33.6 31.7
LA12EA 104 x 160 1250 1400 720 40.0 90 42.7 51.4 24.4 42.4
LA16EA 104 x 200 1600 1750 960 53.0 120 33.2 38.5 19.2 53.1
D double duct
LA08DA 348 x 120 2000 2020 2 x 480 67.0 150 31.0 38.5 16.8 63.5
LA12DA 348 x 160 2500 2690 2 x 720 80.0 175 21.3 25.7 12.2 84.8
LA16DA 348 x 200 3150 3350 2 x 960 90.0 200 16.6 19.2 9.6 104.0
COPPER CU CU CU CU CU
E single duct
LA04EC 104 x 80 630 660 160 20.0 **65 109.9 142.3 52.0 24.9
735 200 25.0 **65 88.4 114.1 53.2 26.1
800 805 240 30.0 65 74.4 95.4 54.6 27.4
LA08EC 104 x 120 1000 1120 320 35.0 ** 105 56.4 71.3 31.5 39.4
1250 1355 480 50.0 105 39.0 48.0 33.6 44.5
LA12EC 104 x 160 1605 600 55.0 ** 145 32.1 38.2 23.6 57.7
1600 1750 720 65.0 145 27.5 32.1 24.4 61.5
LA16EC 104 x 200 2000 2000 800 65.0 **165 25.0 28.7 18.5 73.4
2220 960 75.0 165 21.3 24.1 19.2 78.5
D double duct
LA08DC 348 x 120 2000 2015 2 x 320 53.0 ** 175 28.2 35.6 15.7 78.8
2500 2440 2 x 480 80.0 175 19.5 24.0 16.8 88.9
LA12DC 348 x 160 2500 3080 2 x 600 80.0 ** 210 16.0 19.1 11.8 115.4
3150 3350 2 x 720 95.0 210 13.7 16.0 12.2 123.0
LA16DC 348 x 200 3830 2 x 800 95.0 ** 220 12.5 14.3 9.2 146.9
4000 4250 2 x 960 100.0 220 10.7 12.0 9.6 157.0
RST RST T SR
80 - 120 - 160 - 200
B B B
104 104 140 104
Technical specifications may change without any further notice
* See p age G1 (point 2)
**Remark Peak value is not in relation to stated max. thermal value for the conductors of 4 and 5 mm.
ALUMINIUM AL AL AL AL AL
E single duct
LB04EA 138 x 80 168 x 80 800 875 2 x 160 24 ** 85 90.6 114.9 26.0 27.0 32.7
1000 1050 2 x 240 37.5 85 60.4 76.8 27.3 27.9 33.9
LB08EA 138 x 120 168 x 120 1250 1400 2 x 320 45 ** 150 45.8 57.5 15.8 40.6 49.3
1600 1700 2 x 480 67 150 31.0 38.5 16.8 42.4 51.6
LB12EA 138 x 160 168 x 160 2000 2225 2 x 720 80 175 21.3 25.7 12.2 56.8 69.2
LB16EA 138 x 200 168 x 200 2500 2675 2 x 960 90 200 16.6 19.3 9.6 71.2 86.9
D double duct
LB08DA 416 x 120 476 x 120 3150 3250 4 x 480 100 220 15.5 19.2 8.4 84.7 103.2
LB12DA 416 x 160 476 x 160 4000 4255 4 x 720 120 260 10.7 12.8 6.1 113.6 138.4
LB16DA 416 x 200 476 x 200 5000 5120 4 x 960 135 290 8.3 9.6 4.8 142.5 173.8
COPPER CU CU CU CU CU
E single duct
LB04EC 138 x 80 168 x 80 1000 1100 2 x 160 30 ** 105 55.0 71.2 26.0 34.1 42.0
1250 1250 2 x 200 40 ** 105 44.2 57.1 26.6 36.2 44.7
1350 2 x 240 50 105 37.2 47.7 27.3 38.3 47.4
LB08EC 138 x 120 168 x 120 1600 1750 2 x 320 55 ** 175 28.2 35.7 15.8 54.8 67.8
2000 2000 2 x 400 65 ** 175 23.0 28.7 16.3 58.9 73.2
2150 2 x 480 80 175 19.5 24.0 16.8 63.0 78.6
LB12EC 138 x 160 168 x 160 2500 2600 2 x 600 85 ** 220 16.0 19.1 11.8 81.6 101.7
2800 2 x 720 100 220 13.7 16.1 12.2 87.8 109.8
LB16EC 138 x 200 168 x 200 3150 3200 2 x 800 100 ** 265 12.5 14.4 9.3 104.3 130.2
3375 2 x 960 120 265 10.7 12.1 9.6 112.6 140.9
D double duct
LB08DC 416 x 120 476 x 120 3845 4 x 400 100 ** 260 11.5 14.3 8.1 117.8 146.4
4000 4135 4 x 480 120 260 9.8 12.0 8.4 126.0 157.2
LB12DC 416 x 160 476 x 160 5000 5000 4 x 600 110 ** 280 8.0 9.5 5.9 163.2 203.4
5385 4 x 720 130 280 6.9 8.0 6.1 175.6 219.6
LB16DC 416 x 200 476 x 200 6000 6120 4 x 800 125 ** 330 6.3 7.2 4.6 208.7 260.4
6300 6475 4 x 960 150 330 5.3 6.0 3.0 225.1 281.8
B B B
138 - 168 138 - 168 140 138 - 168
We reserve the right to change, at any time and without prior warning the technical specification of any product illustrated in this
catalogue.
500
- The elements are symmetrical and therefore reversible
for adaptation of the phase sequence (rotation field).
300
- Shunts / flexibles have to be adapted on site.
Example : AHN R S T O
AYN
Is a universal terminal element.
Very suitable for introduction in
small connection compartments.
500
LA 04 - 08 - 12 - 16
AZN
Is a universal terminal element
500
LB
LB 08 12 16
AGN
Is a universal terminal element
500
500
500
with flange and cast-in nuts for
supports. Very suitable for
connection to railsystems and
transformers.
LB 08 12 16
AHN
Is a universal terminal element
500
500
500
LB 08 12 16
AJN
Is a universal terminal element
with flange and cast-in nuts
for supports. Very suitable for
500
500
connection to switch-boards,
500
Straight element
RE V L = 4000mm max.
RE1 N L = 1000mm
RE2 N L = 2000mm
RE3 N L = 3000mm
RE4 N L = 4000mm
L3
L3
Double elbow element right Double elbow element left
XR1 V L1 + L2 + L3 = max. 1000mm XL1 V L1 + L2 + L3 = max. 1000mm
XR2 V L1 + L2 + L3 = max. 2000mm XL2 V L1 + L2 + L3 = max. 2000mm
L2
Straight
Hammerhead
L1
L1
L1
L1
L1
* Price list
** Depends on the type and the number of conductors.
Straight
Hammerhead
L1
L1
P*** P***
P***
The E (extended) elements are made especially for connections to dry transfos with large phase to phase dimensions.
** Depends on the type and the number of conductors.
*** P depends on type of betobar-r.
D -terminal elements
Standard Standard
DHD min max in PL* DHF min max in PL*
L1 ** 750 500 L1 ** 750 500
P2 280 1250 750 P2 280 1000 750
+2H +2H
L1
L1
Standard Standard
DJD min max in PL* DJF min max in PL*
Standard Standard
DGD min max in PL* DGF min max in PL*
L1 475 750 500 L1 ** 750 500
P2 280 1000 750 P2 280 1000 750
+2B +2B
L1
L1
* Price list
** Depends on the type and number of conductors.
U -terminal elements
Standard Standard
UHD min max in PL* UHF min max in PL*
L1 475 750 500 L1 475 750 500
O 815 1270 750 O 575 1270 750
L1
L1
Standard Standard
UJD min max in PL* UJF min max in PL*
L1 475 750 500 L1 475 750 500
O 835 1250 750 O 595 1250 750
L1
L1
Standard Standard
UMD min max UMF min max in PL*
in PL*
L1 475 750 500 L1 475 750 500
O 835 1250 750 O 595 1250 750
L1
L1
* Price list
extra long
connection contacts
with collars
>90º
Transfer element
RST TSR
1/6 L
STR RTS
1/3 L
TRS SRT
1/3 L
RST TSR
1/6 L
RST TSR
Junctions
L 10 L Z L
+5
5
Z
st.26 st.27 Z
LA-LB
Straight junction Flat elbow junction
04 20
08 40
L
12 60
16 80
LA 250 A LB 400 A
400 A 630 A
min 210
min 210
2x50
180
3x45
L = max 4000
70
240
540
205
min 230
min 210
- empty
- with fuses
The line of betobar-r busways has been split up in 9 weight classes, from “A” to “I”. Weight Class
71-89 kg A
According to the betobar-r type and the element length the class is laid down and the 89-113 kg B
spring type is defined. 113-142 kg C
The design of this spring support is such allowing a displacement of each individual element 142-179 kg D
179-225 kg E
of +40 mm and -10 mm. This range covers all normal indoor temperature conditions and the 225-283 kg F
thermal dilatation of the busway. For swift installation an adjustment range is available. 283-357 kg G
In case of special requests, contact our local representative. 357-450 kg H
450-567 kg I
3,6 - 24 kV type MH
This type is the only single-pole betobar-r system, thus
helping the flexibility while engineering the specific main
rail systems for this voltage. These lines are supplied with
a self-supporting screening.
Notes :
We reserve the right to change, at any time and without prior warning the technical specification of any product illustrated in this
catalogue.
h
60x04
H
1040 60x05
1135 7,2 160x100 60x06
75
1295 60x08
1425 60x10
1540 60x12 Supporting insulator
SH2 1710 100x08
1880 7,2 160x140 100x10
2015 100x12
Support shoulder
Straight element
RE1 L= max. 1000mm
RE2 L= max. 2000mm
RE3 L= max. 3000mm
RE4 L= max. 4000mm
L2
L3
L3
Double elbow element right Double elbow element left
XR1 L1+L2+L3= max. 1000mm XL1 L1+L2+L3= max. 1000mm
XR2 L1+L2+L3= max. 2000mm XL2 L1+L2+L3= max. 2000mm
L2
Expansion element
EX1 L= 1000mm
Straight
Hammerhead
L1
L1
L1
L1
L1
* Price list
A kV mm RST
PH10 (PH1) 1690 100x04
1870 100x05
2030 17,5 300x140 100x06
H
2290 100x08
2520 100x10
75
PH12 2570 120x08
2820 17,5 322x170 120x10
3035 120x12 Supporting insulator
PH16 3215 160x08
3525 17,5 322x210 160x10
3785 160x12
PH20 3975 200x08
4360 200x10
4675 17,5 322x260 200x12
5050 200x15 Supporting shoulder
For st.28 elbow junction
5150 200x16 see p M12
Straight element
RE1 L= max. 1000mm
RE2 L= max. 2000mm
RE3 L= max. 3000mm
RE4 L= max. 4000mm
L3
L3
L3
Double elbow element right Double elbow element left
XR2 L1+L2+L3= max. 2000mm XL2 L1+L2+L3= max. 2000mm
L3= fixed PH1 L3=350 L3= fixed PH1 L3=350
PH1.2 L3=400 PH1.2 L3=400
PH1.2e L3=400 PH1.2e L3=400
H’
Dimensions
PH10 12 450X430X500
PH16 460X600X500
PH20 495X470X570
Straight
Standard Standard
PH1 PH1.2 PH1 PH1.2 in PL*
in PL*
AC1 L1= max. 1000mm L1= max. 1000mm 1000 AE1 L1= max. 1000mm L1= max. 1000mm 1000
AC2 L1= max. 2000mm L1= max. 1500mm 1000 AE2 L1= max. 1500mm L1= max. 1500mm 1000
Hammerhead
L1
L1
Standard Standard
PH1 PH1.2 in PL* PH1 PH1.2 in PL*
AG1 L1= max. 1000mm L1= max. 1000mm 500
AJ1 L1= max. 1000mm L1= max. 1000mm 500
L1
Standard Standard
PH1 PH1.2 PH1 PH1.2 in PL*
in PL*
AM1 L1= max. 1000mm L1= max. 1000mm 500 AO1 L1= max. 1000mm L1= max. 1000mm 500
AM2 L1= max. 1500mm L1= max. 1500mm 500 AO2 L1= max. 1500mm L1= max. 1500mm 500
* Price list
SH Z L Z L
10 5 5
Z
Z
5
L L
Z Z
SH1 30 SH1 95
L
L
SH2 50 SH2 95
PH Z L Z L
10
5 5
5
Z
Z
L L
Z Z
L
PH1 50 PH1 25
PH1.2 60 PH1.2 35
PH1.2e 80 PH1.2e 35
MH Z L Z L
10 5 5
Z
Z
5
L L
Z Z
L
MH1 30 MH1 25
MH2 50 MH2 25
Special straight
L1
L1
Special combi
Optional:
Creepage collar for
outdoor connection.
st.28 MH
L1
2. Weights
The weights of the betobar-r for the LV- types are the average weights as indicated in the tables on pages L1 and L2,
including the junction and the casting mix per system length of 2 m. For MV-types the supporting insulators and any
possible screening is included. If partitions for a full phase segregation are needed, they have to be added as extra
weight.
3. System impedance
The busduct resistance values (DC resistance) Rdc20 are based on a conductor temperature of 20°C and a power
frequency of 50Hz in accordance with the IEC standard. The Rac95 for LV and the Rac85 for MV are the values for
the conductor resistances at max. operating temperature. The reactance values (X) of the LB-types are based on the
standard phase sequence RST-TSR for a 3-phase system.
For other configurations, frequencies or extreme temperatures, please consult Eta-com B or your betobar-r agent.
All impedances have been calculated with physical values :
For copper :
Specific resistance at 20°C = 0.0175 .mm²/m conductivity 57 MS/m
Temperature coefficient = 0.00392 1/°C
Standard EN13601 (2002)
For aluminium :
Specific resistance at 20°C = 0.029 .mm²/m conductivity 35.4 MS/m
Temperature coefficient = 0.004 1/°C
Standard EN755-2 (1997)
4. Maximum voltage
PH series is designed for a maximum voltage of 17.5 kV. Rated voltage 12 kV is provided with self-supporting
safety screen, the called PH..S(creen) system.
5. Short circuit
LV MV Icc values in the technical data
lcw lk Symmetrical short circuit current (1 second effective value if no further indications)
lpk lp Asymmetrical (dynamic) short circuit current (peak value)
The betobar-r busbars type tested reports of the official and independent laboratories (mostly at KEMA and
Laborelec) defines the Icc rating.
For MH1 and MH2 : phase distance = 150 mm and 175 mm for full segregation, support-shoulder distance 600 mm
For MH.D : phase distance = 300 mm, support-shoulder distance 800 mm
Phase distance and support-shoulder distance can be chosen for each project taking into account the production
possibilities. Consult Eta-com or your betobar-r agent on this matter.
Current rating 1.18 1.14 1.09 1.05 1.00 0.94 0.88 0.82 0.75
correction factor
NB For intermediate values the next higher temperature should be considered or for a more precise result the correction factor must
be interpolated
7. Correction factors 60 Hz
Current rating for a power frequency of 60 Hz
Current rating cor- 1.000 0.988 0.986 0.984 0.984 0.982 0.982 0.980 0.980 0.990
rection factor
L L L
a= a= a=
0.125 0.5 0.25
9. Phase sequence
Phase sequence in documentation and product documents :
is indicated as R S T
to be equal to R Y B
or L1 L2 L3
10. General
For all information or technical calculations, please consult Eta-com or your betobar-r agent.
4
6
PANEL TERMINATION
Bottom entry :
with flexibles or shunts 2
and bottom plate 3
IP class to be determined 1
by customer 4
1. betobar-r
2. Flexibels
3. Terminals
4. Switchgear panel
5. Support
1. betobar-r
2. Flange
3. Bellow or flat membrane 2 6
4. Flexibles
5. Connection box
6. Connection clamps
7. Switchgear 2
1
6
60
+-30
75
Min. 10
Max. 30
5
30
Min. 10
Max. 40
1 3
40
Code hxb
FLC 02510 25 x 10
b
FLC 04010 40 x 10
LV
1000V LA - LB
40/60 max. 10 2x10 max.
20
h+10 18 34
min.5 h+20 28 44
h= 80/100/120/160
max. 12 3x12 max.
20
h+10
22 46
min.5 h+20
32 56
MV
7,2 - 12 kV 17,5 kV
SH PH
h= 60/80/100/120 max. 12 3x12 max.
17 5 kV
7 2 kV
12 kV
66
96
41
42 66
* min.20 h+30
58 82
74 98
* Beware of correct creepage path
1.1 1.8
= =
30
For 150 mm not standard available
15 Ø14 / 14 x 21
L.V.
Ø14 / 14 x 21
=
L.V.
= = = = = = =
1.2 1.9
= =
40
2 x 80
40 20
Ø14 / 14 x 21
L.V.
1.3
= =
50
M.V. 40 20
M.V. 40 20
L.V. Ø14 / 14 x 21
Ø14 / 14 x 21
L.V.
=
=
1.4 1.10
= =
60
2 x 100
=
M.V. 40 20
=
Ø14 / 14 x 21
=
L.V.
=
= = = =
1.5
=
80
M.V. 40 20
M.V. 40 20
Ø
L.V. / M.V.
Ø14 / 14 x 21
L.V. A max xL
16 M10 x 35
=
16 M12 x 40
L
=
24 M12 x 45
1.6
100
A
=
b
=
Protection washer
M.V. 40 20
Pressure washer
Ø14 / 14 x 21 DIN 6796
L.V.
=
Ø
L.V. / M.V.
A max xL
=
1.7
120
24 M10 x 45
=
24 M12 x 45
32 M12 x 55
b
=
48 M12 x 70
L
A
40 20
M.V. 74 Nm M12
43 Nm M10
Protection washer
Pressure washer
DIN 6796
LOW VOLTAGE
2
40
3
40
B+160 x H+160
BxH
4
~180
2x12 60
SH PH
2. betobar-r frames
2
40
3
30
50
L**
B+240 x H+240
BxH
5
~180
2x12
60 3x50 min. 20
L1 B1 H1
mm mm mm
LA04 325 140 115
LA08 325 140 155
st.26 LA12 325 140 195
Straight junction LA16 325 140 235
L1 B1 H1
st.27 mm mm mm
Flat elbow junction LA04 240 140 115
H1
L1 B1 H1
mm mm mm
SH1 380 195 135
SH2 380 195 175
PH1 225 80 175
PH1.2 280 90 195
H1
Partial discharges
kV pC
Note :
From now on, LA-LB series for Low Voltage will fully replace the J-SL.0-1-2-3 series which are not shown in the
documentation anymore. However, these series can be produced on demand only for replacement or extensions of
existing installations. The test reports for the old series J-SL.0-1-2-3 will remain available on request.
Short-circuit resistance
Low Voltage betobar-r
Results Lab Report
Type S Un kV In A kA/1 s kA
mm² 50 Hz 50 Hz sym. asym.
LA04 Cu 3x240+240+240 1 816 30 121 PDL 03 126 1
LA08 Cu 3x480+480+480 1 1380 50 105 PDL 03 126 1
LA12 Cu 3x720+720+720 1 1770 65 143 PDL 03 126 1
LA16 Cu 3x960+960+960 1 2200 75 176 PDL 03 126 1
LB04 Cu 3x480+480+480 1 1390 45 95 Kema 212 92
LB08 Cu 3x960+960+960 1 2170 80 175 Kema 213 92
LB12 Cu 3x1440+1440 1 2810 90 200 Kema 214 92
LB16 Cu 3x1920+1920 1 3420 100 220 Kema 215 92
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A kA/1 s kA
mm² 50 Hz 50 Hz sym. asym.
SH1 Cu 3*720 7,2 1497 50 130 Kema 82 06
SH2 Cu 3x1200 7,2 2400 77 202 Kema 2998 78
PH1 Cu 3x1000 17,5 2400 95 205 Kema 1557 73
PH16 Cu 3x1920 17,5 3711 80 208 Kema 80 06
PH20 Cu 3x2400 17,5 5050 100 260 Kema 327 04
Thermal shock
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A Degree of
mm² 50 Hz 50 Hz protection
PH1 Cu 3x800 12 2175 No deterioration INIEX 70/76
Degree of protection
Low Voltage betobar-r
Results Lab Report
Type S Un kV In A Degree of
mm² 50 Hz 50 Hz protection
LA all 1 IP68 Kema 2071268 QUA/COM
LB all 1 IP68 Kema 2071268 QUA/COM
LV Take off box 1 IP55 Kema 200657.01 KRQ/COM
LV Take off box 1 IP67 Kema 2101518.01
LV Termination with bellow IP55 Kema 200657.01 KRQ/COM
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A Degree of
mm² 50 Hz 50 Hz protection
SH all 7,2 IP67 Kema 2071268 QUA/COM
PH all 17,5 IP67 Kema 2071268 QUA/COM
MH all 24 IP67 Kema 2071268 QUA/COM
Voltage tests
Low Voltage betobar-r
Results Lab Report
Type S Un kV In A kV kV
mm² 50 Hz 50 Hz 1 min 1.2/50 ms
LA04 Cu 3x240+240+240 1 816 3,5 12 PDL 03 126 1
LA08 Cu 3x480+480+480 1 1380 3,5 12 PDL 03 126 1
LA12 Cu 3x720+720+720 1 1770 3,5 12 PDL 03 126 1
LA16 Cu 3x960+960+960 1 2200 3,5 12 PDL 03 126 1
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A kV kV
mm² 50 Hz 50 Hz 1 min 1.2/50 ms
SH1 Cu 3x720 7,2 1497 38 95 Kema 06 1053
SH2 Cu 3x800 3,6 1665 27 45 Kema 5201 72
PH1 Cu 3x400 17,5 1690 38 95 Laborelec 42065/51
PH16 Cu 3x1920 17,5 3711 38 85 Kema 06 1051
MH2 Cu 3x800 24 2400 50 125 Laborelec 42066/51 4
Leakage current
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A mA
mm² 50 Hz 50 Hz
SH2 Cu 3x800 3,6 1665 0,06 @ 7,2 kV Kema 5205 72
PH1 Cu 3x1000 12 2400 0,28 @ 12 kV Kema 9251 73
MH1 Cu 3x1000 7,2 2410 0,10 @ 7,2 kV Kema 7335 72
Ex tests
betobar-r
Results Lab Report
Type S Un kV In A kA/1 s kA
mm² 50 Hz 50 Hz sym. asym.
LV/MV All 11 kV Eex mII T5 LCIE LCIE 07 ATEX 0003 U
Tests between each conductor with all other conductors and supports earthed (dry)
Types Ur Ur max * Ud 50 Hz 50 Hz q
at 50 Hz at 50 Hz 10 sec Ue at
kV kV/1 min. 1.7 Ur 1.1 Ur 1.1 Ur
* Ur level for work tests can be specified by customer. If not indicated, the test voltage will be according to
the rated voltage Ur equivalent to the operation voltage Us.
** Eta-com standard value. In accordance with IEC 62271 the customer can determine here a different value
for each project.
B. Dimensions
All dimensions are to be compared with the order sheet.
C. Phase sequence
End- and phase switching elements : conductor connections are to be compared with the order sheet.
D. Visual
The element and its workmanship are to be examined.
Tests on site : The procedure of the tests to be executed on site is stipulated on page 33 from the MV Installation
Instructions.
Customer : Date :
Information required for quotation. Please, photocopy this form and attach to your inquiry.
In Un Freq. Temp. Project :
to t max.
o o
A V Hz C C Job nr :
A. IDENTIFICATION
Type :
Section. : Line nr. :
Nominal voltage Ui :
User voltage Ue :
Nominal current In :
User current Is :
Note: For long lines and or split deliveries more than one report can be produced
C. RESULTS
Visual inspection and dimensions :
- All dimensions are according to ordersheet Yes / No
Electrical tests :
- All insulation values are more than 5 Gigaohm at 1 kV DC. Yes / No
- All elements withstand power frequency test at 5 kV / 1 min. Yes / No
- Terminal & phase switching elements: checked phase-sequence Yes / No
D. CONCLUSION
Tests : All elements comply with the requirements Yes / No
Packing : Material approved as ready for packing Yes / No
Shipment : Material approved as ready for shipment Yes / No
Remarks :................................................
Serial Nr. :
Review 6
dd 20/10/2006
WORKS TEST REPORT M.V. PER ELEMENT
Project :
Client :
Ext. ref :
Int. ref :
A. IDENTIFICATION
Type :
Section. : Line nr. :
Nominal voltage Ur : Element nr. :
User voltage Us : Element form. :
Nominal current Ir :
User current Is :
C. ELECTRICAL TESTS
- Power frequency test (HI-POT) to I.E.C. 60 and I.E.C. 270.
- Partial discharge measurements to I.E.C. 270 (P.D. level max. 20 pC. at 1,1 Umax = Eta-com std., or level defined by client at Order)
- Only for phase switching and expansion elements :
Insulation resistance measurement. All insulation resistance values are at least 10 Gigaohms at 5 kV. D.C.
Phase - sequence checked : . . . . . . . . . .
R-ST 60 10 <20
S-RT 60 10 <20
T-RS 60 10 <20
D. CONCLUSION
Tests : The element complies with the requirements Yes / No
Packing : Material approved as ready for packing Yes / No
Shipment : Material approved as ready for shipment Yes / No
Test engineer Company Date This document has been generated
ETA-COM B automatically from data of our quality
system and does not require a signature
Witness Company Date Signature
Serial Nr. :
Review 5
dd 20/10/2006
REFERENCE LIST
WORLDWIDE PROJECTS
Consultant
Place Project LV/MV Year
Engineering contractor
Azerbaijan Yenikend Yenikend Hydro Power Station Pauwels International LV/MV 1999
Consultant
Place Project LV/MV Year
Engineering contractor
Italy Susa Pont Ventoux Hydro Power Station Carlo Gavazzi MV 2001
Consultant
Place Project LV/MV Year
Engineering contractor
Saudi Arabia Shoaiba Shoaiba Power Plant stage II phase 2 Alstom MV 2005
Shoaiba Shoaiba Power Plant stage II phase 1 Alstom MV 2004
Shoaiba Shoaiba Power Plant Units 4 & 5 Alstom Germany MV 2002
Shoaiba Shoaiba Power Plant Units 1, 2 & 3 Alstom Germany MV 2000
Dammam Saad Hospital Alfanar LV 1998
Jubail Hunther Phase III LV 1998
Al Jubail 20 MIGD SWRO Plant LV/MV 1996
Al Jubail Saline Water Conversion Co Preussag Salzgitter LV/MV 1996
Bishah Cement Plant Siemens Erlangen LV 1995
Singapore The Esplanade – Theatres on the bay Busway Systems Engineering LV 2001
Consultant
Place Project LV/MV Year
Engineering contractor