GENERAL

L3 MAJOR ADVANTAGES
L2
L1
N
• Very small dimensions

• Simple installation

• Low voltage drop

• High short-circuit withstand

• Overload capacity + 20% - 2 hours

• Tailor-made end elements

• Degree of protection class IP68.IK10

• Low flammability
N
• Self-extinguishing insulation IEC-332
L1
L2
L3

• Fire resistant to IEC-331 (Low Voltage)

• Electrical continuity
E30-E90 finishing available

• Fire retardant bushings S30-S180; A90-H60

• Maintenance free

• ATEX
up to 10 kV

explosion proof •

All types have been tested


to international standards in
official laboratories. EMC
electro magnetic compatibility

E30
Manufactured MV-elements
are supplied with a test report.

I K 1 0
IP68.
electrical continuity

A90 H 6 0
degree of protection

fire proof bushings

CAST-RESIN INSULATED BUSWAY SYSTEMS

Review 6 d.d.09.06 Page A1


GENERAL

The busbars have been developed as a modern,


all-purpose means of efficient and safe transmission of elec-
trical energy. They have been in manufacture for more than
thirty-five years.

The system complies with all the requirements for


current ditribution at low and medium voltage.

The busbar consists of copper or aluminium conductors,


embedded in an enclosure of a fire retardant, selfextin-
guishing and homogeneous insulation mix based on epoxy
cast-resin with mineral fillers ensuring high mechanical
strength and chemical withstand.

Standard types are available for current ratings up to 6300 A


and voltage ratings up to 24kV. Systems for higher current
ratings or DC applications are possible.

The busbar line consists of a number of prefabricated


elements. The electrical joining of the conductors is
achieved by means of double fish plates and high tensile
steel bolts.

The junctions and the element ends are overcast with the
same insulation mix as used for the elements. In this way an
integral insulation enclosure to IP68.IK10 is guaranteed over
the full length of the busbar run. Strainght junctions and also
elbow junctions are available each facilitating installation
adjustments of 10-20 mm per standard junction.

Review 6 d.d.09.06 Page A2


APPLICATIONS / ELEMENT SHAPES

busbars are suitable for application in large


buildings, industrial plants, power stations, sub-stations
and large switchrooms, such as:

factory distribution of low and medium voltage power


rising mains with tee-offs to sub-distribution boards in
high rise buildings
transformer switchboard connections
main switchboard feeders to distribution panels
generator and large motor feeders
long lines with low voltage drop
400 Hz distribution systems

For special applications, please contact our factory or agent.

The busway system is available in a wide range of


standard element shapes, forms, lengths all of which are
fabricated to suit the typical project requirements.

straight elements
elbow elements, flat-flat and on edge
Z (double elbow) and T elements
flanged terminal elements
tap-off facilities and phase-transfer elements
thermal expansion compensation elements
tailor-made terminal elements for transformer
or generator and switchboard connection

Review 6 d.d.09.06 Page A3


TYPES / TESTS

The busbars can be supplied in the following standard


types:

For Low Voltage:


LA-LB series
Up to 1000 V AC 45-55 Hz
Three phase conductors and/or
protective earth / 50,100,150 % neutral

Applications:
Alu-conductors range up to 5250 Amps
Cu-conductors range up to 6500 Amps
Up to 1500 V DC
Applications up to 16,000 Amps

For Medium Voltage:


Type Current rating Voltage rating
SH-series up to 2000 A up to 7.2 kV
PH-series up to 4500 A up to 17.5 kV
MH-series up to 6300 A up to 24.0 kV
Other current ratings on request.

Type tests:
All technical data specified, such as current ratings and temperature
rise, insulation, resistance, voltage and short circuit withstand, have
been certified in accordance with international standards (IEC, VDE
or BS) by the independent testing stations K.E.M.A., LABORELEC,
LCIE. Assembled elements with cast junctions were submitted for
type testing.

Factory tests:
Prior to shipment, all elements are subjected to the following tests:
Low Voltage systems: insulation resistance measurement and volt-
age withstand Medium Voltage system: voltage withstand, insulation
resistance and partial discharge measurement

Test reports:
Copies of official certificates and works reports are sent on request for
Low Voltage. All M.V. elements are supplied with a works test report.

Review 6 d.d.09.06 Page A4


Technical Data
Low Voltage
Serie
I.E.C. 60.439-2 50Hz 1000V

Type 3-4-5 cond 6...10 cond In In cond. Icc R20 R 95 X Total weight *
BXH BXH norm 35 / 40°C 1sec dyn 3..5 cond 8..10
mm mm A A mm² kA kA m m m ~kg/m

ALUMINIUM AL AL AL AL AL
E single duct
LA04EA 104 x 80 500 520 160 12.0 ** 45 181.3 229.8 52.0 20.5
630 630 240 18.0 45 120.8 153.5 54.6 21.1

LA08EA 104 x 120 800 860 320 22.5 ** 75 91.5 115.0 31.5 30.6
1000 1050 480 33.5 75 61.9 77.0 33.6 31.7

LA12EA 104 x 160 1250 1400 720 40.0 90 42.7 51.4 24.4 42.4

LA16EA 104 x 200 1600 1750 960 53.0 120 33.2 38.5 19.2 53.1

D double duct

LA08DA 348 x 120 2000 2020 2 x 480 67.0 150 31.0 38.5 16.8 63.5

LA12DA 348 x 160 2500 2690 2 x 720 80.0 175 21.3 25.7 12.2 84.8

LA16DA 348 x 200 3150 3350 2 x 960 90.0 200 16.6 19.2 9.6 104.0

COPPER CU CU CU CU CU
E single duct
LA04EC 104 x 80 630 660 160 20.0 **65 109.9 142.3 52.0 24.9
735 200 25.0 **65 88.4 114.1 53.2 26.1
800 805 240 30.0 65 74.4 95.4 54.6 27.4

LA08EC 104 x 120 1000 1120 320 35.0 ** 105 56.4 71.3 31.5 39.4
1250 1355 480 50.0 105 39.0 48.0 33.6 44.5

LA12EC 104 x 160 1605 600 55.0 ** 145 32.1 38.2 23.6 57.7
1600 1750 720 65.0 145 27.5 32.1 24.4 61.5

LA16EC 104 x 200 2000 2000 800 65.0 **165 25.0 28.7 18.5 73.4
2220 960 75.0 165 21.3 24.1 19.2 78.5

D double duct
LA08DC 348 x 120 2000 2015 2 x 320 53.0 ** 175 28.2 35.6 15.7 78.8
2500 2440 2 x 480 80.0 175 19.5 24.0 16.8 88.9

LA12DC 348 x 160 2500 3080 2 x 600 80.0 ** 210 16.0 19.1 11.8 115.4
3150 3350 2 x 720 95.0 210 13.7 16.0 12.2 123.0

LA16DC 348 x 200 3830 2 x 800 95.0 ** 220 12.5 14.3 9.2 146.9
4000 4250 2 x 960 100.0 220 10.7 12.0 9.6 157.0

RST RST T SR
80 - 120 - 160 - 200

80 - 120 - 160 - 200


H

N N/A N N/A N/A N

B B B
104 104 140 104
Technical specifications may change without any further notice
* See p age G1 (point 2)
**Remark Peak value is not in relation to stated max. thermal value for the conductors of 4 and 5 mm.

Review 6 d.d.04.07 Page L 1


Technical Data
Low Voltage
Serie
I.E.C. 60.439-2 50Hz 1000V

Type 6 - 7 cond 8 - 9 cond In In cond. Icc R20 R 95 X Total weight *


BXH BXH norm 35 / 40 °C 1sec dyn 6 - 7 cond 8 - 9
mm mm A A mm² kA kA m m m ~kg/m

ALUMINIUM AL AL AL AL AL
E single duct
LB04EA 138 x 80 168 x 80 800 875 2 x 160 24 ** 85 90.6 114.9 26.0 27.0 32.7
1000 1050 2 x 240 37.5 85 60.4 76.8 27.3 27.9 33.9

LB08EA 138 x 120 168 x 120 1250 1400 2 x 320 45 ** 150 45.8 57.5 15.8 40.6 49.3
1600 1700 2 x 480 67 150 31.0 38.5 16.8 42.4 51.6

LB12EA 138 x 160 168 x 160 2000 2225 2 x 720 80 175 21.3 25.7 12.2 56.8 69.2

LB16EA 138 x 200 168 x 200 2500 2675 2 x 960 90 200 16.6 19.3 9.6 71.2 86.9

D double duct
LB08DA 416 x 120 476 x 120 3150 3250 4 x 480 100 220 15.5 19.2 8.4 84.7 103.2

LB12DA 416 x 160 476 x 160 4000 4255 4 x 720 120 260 10.7 12.8 6.1 113.6 138.4

LB16DA 416 x 200 476 x 200 5000 5120 4 x 960 135 290 8.3 9.6 4.8 142.5 173.8

COPPER CU CU CU CU CU
E single duct
LB04EC 138 x 80 168 x 80 1000 1100 2 x 160 30 ** 105 55.0 71.2 26.0 34.1 42.0
1250 1250 2 x 200 40 ** 105 44.2 57.1 26.6 36.2 44.7
1350 2 x 240 50 105 37.2 47.7 27.3 38.3 47.4

LB08EC 138 x 120 168 x 120 1600 1750 2 x 320 55 ** 175 28.2 35.7 15.8 54.8 67.8
2000 2000 2 x 400 65 ** 175 23.0 28.7 16.3 58.9 73.2
2150 2 x 480 80 175 19.5 24.0 16.8 63.0 78.6

LB12EC 138 x 160 168 x 160 2500 2600 2 x 600 85 ** 220 16.0 19.1 11.8 81.6 101.7
2800 2 x 720 100 220 13.7 16.1 12.2 87.8 109.8

LB16EC 138 x 200 168 x 200 3150 3200 2 x 800 100 ** 265 12.5 14.4 9.3 104.3 130.2
3375 2 x 960 120 265 10.7 12.1 9.6 112.6 140.9

D double duct
LB08DC 416 x 120 476 x 120 3845 4 x 400 100 ** 260 11.5 14.3 8.1 117.8 146.4
4000 4135 4 x 480 120 260 9.8 12.0 8.4 126.0 157.2

LB12DC 416 x 160 476 x 160 5000 5000 4 x 600 110 ** 280 8.0 9.5 5.9 163.2 203.4
5385 4 x 720 130 280 6.9 8.0 6.1 175.6 219.6

LB16DC 416 x 200 476 x 200 6000 6120 4 x 800 125 ** 330 6.3 7.2 4.6 208.7 260.4
6300 6475 4 x 960 150 330 5.3 6.0 3.0 225.1 281.8

RST T SR RST T SR RST T SR


80 - 120 - 160 - 200

80 - 120 - 160 - 200


H

N N/A N N N/A N N N/A N

B B B
138 - 168 138 - 168 140 138 - 168

Technical specifications may change without any further notice


* See p age G1 (point 2)
**Remark Peak value is not in relation to stated max. thermal value for the conductors of 4 and 5 mm.

Review 6 d.d.04.07 Page L 2


L.V.-SYSTEMS

The elements shown on pages L 4 till L 14 form the standardized


series of models for LV- applications.

Because of the existence of many models and the flexible


production methods- all casting mould models allow simple
length variations as well as asymmetrical shapes - together with
the standard straight and elbow junctions, the betobar-r system
can be envisaged easily by project engineers. The potential
length variation of min. 10 mm at each junction ensures the
electro-contractor a fast and safe installation.

Because unlimited dimensional projecting possibilities are not


always required for each connection, the LV- series is divided into
3 groups :

NORM is a series of elements with fixed dimensions.


Element code + N.

VARIO is the series of elements with large shape and


length variations. They are manufactured in
universal casting moulds, the delivery period is
longer than for the norm-series.
Element code + V.

SPECIAL is an unlimited series. The elements are made


in separate casting moulds. This group also
includes those elements, differing from norm
and vario series, but manufactured with exist-
ing casting moulds or combinations thereof.
Price and delivery conditions are given separ-
ately.
Element code + S.

EMP-EMI SCREENING : The group SPECIAL also includes


those versions of the VARIO-series, for which a special screen is
foreseen or will be foreseen by means of adapted casting
moulds.

We advise you to consult Eta-com or your betobar-r agent on


this matter.

We reserve the right to change, at any time and without prior warning the technical specification of any product illustrated in this
catalogue.

Review 6 d.d.09.06 Page L 3


NORM
STANDARD TERMINAL ELEMENTS LA LB

Norm - terminal elements CL S phase CL betobar-r

- All norm-terminal elements have fixed dimensions


and a fixed phase sequence.
Shape, length and drillings are fixed and cannot be
changed.

500
- The elements are symmetrical and therefore reversible
for adaptation of the phase sequence (rotation field).

- The elements are deliverable from stock or on extremely


short notice.

300
- Shunts / flexibles have to be adapted on site.

- Centre line of the element always has to be projected/


installed in the centre line of the middle S-phase.

Example : AHN R S T O

STANDARD TERMINAL ELEMENTS LA


LA 04 - 08

AYN
Is a universal terminal element.
Very suitable for introduction in
small connection compartments.
500

LA 04 - 08 - 12 - 16

AZN
Is a universal terminal element
500

with the smallest outer dimensions.


Very suitable for introduction in
small connection compartments.

Review 6 d.d.09.06 Page L 4


NORM
STANDARD TERMINAL ELEMENTS LA LB

LB
LB 08 12 16

AGN
Is a universal terminal element

500
500

500
with flange and cast-in nuts for
supports. Very suitable for
connection to railsystems and
transformers.

LB 08 12 16

AHN
Is a universal terminal element

500
500

500

with flange and cast-in nuts


for supports. Very suitable for
connection to switchboards,
top and/or bottom entry.

LB 08 12 16
AJN
Is a universal terminal element
with flange and cast-in nuts
for supports. Very suitable for
500

500

connection to switch-boards,
500

top and/or bottom entry.

Review 6 d.d.09.06 Page L 5


NORM + VARIO
STANDARD ELEMENTS LA LB

Straight element
RE V L = 4000mm max.
RE1 N L = 1000mm
RE2 N L = 2000mm
RE3 N L = 3000mm
RE4 N L = 4000mm

Brazed elbow element Bent elbow element


HL1 V L1 + L2 = max. 1000mm HB V L1 + L2 = max. 2000mm
HL2 V L1 + L2 = max. 2000mm HB1 N 325 + 325
HL1 N 325 + 325 HB1 N 650 + 350 / 350 + 650
HL1 N 650 + 350 HB2 N 500 + 1500
HL2 N 500 + 1500
L3

Brazed T- element Bent T- element


TL1 V L1 + L2 + L3 = max. 1000mm TB V L1 + L2 + L3 = max. 2000mm
TL2 V L1 + L2 + L3 = max. 2000mm

Review 6 d.d.09.06 Page L 6


NORM + VARIO
STANDARD ELEMENTS LA LB

L3

L3
Double elbow element right Double elbow element left
XR1 V L1 + L2 + L3 = max. 1000mm XL1 V L1 + L2 + L3 = max. 1000mm
XR2 V L1 + L2 + L3 = max. 2000mm XL2 V L1 + L2 + L3 = max. 2000mm
L2

Brazed Z- element Bent Z- element


ZL1 V L1 + L2 + L3 = max. 1000mm ZB1 V L1 + L2 + L3 = max. 1000mm
ZL2 V L1 + L2 + L3 = max. 2000mm ZB2 V L1 + L2 + L3 = max. 2000mm

Dimensions of expansion element

B' H' L'


LA04 341 166 530 3 4 5 cond.
LA08 341 206 530 3 4 5 cond.
LA12 341 246 530 3 4 5 cond.
LA16 341 286 530 3 4 5 cond.
H’

LB04 375 166 530 6 7 cond.


LB04 437 166 530 8 9 cond.
LB08 375 206 530 6 7 cond.
Expansion element LB08 437 206 530 8 9 cond.
EX N L = 1000mm fixed LB12 375 246 530 6 7 cond.
LB12 437 246 530 8 9 cond.
LB16 375 286 530 6 7 cond.
LB16 437 286 530 8 9 cond.

Review 6 d.d.07.07 Page L 7


VARIO
TERMINAL ELEMENTS LA LB

Straight

In PL* In PL* In PL*


AEV min max stand. APV min max stand. ACV min max stand.
L1 ** 1250 1000 L1 ** 1250 1000 L1 ** 1250 1000

P2 ** 1060 500 P2 ** 1060 500 P2 ** 1060 500

Hammerhead
L1

L1

L1

In PL* In PL* In PL*


AFV min max stand. AGV min max stand. AOV min max stand.
L1 ** 750 500 L1 ** 750 500 L1 ** 750 500

P2 ** 1000 500 P2 ** 1000 500 P2 ** 1000 500


L1

L1

L1

In PL* In PL* In PL*


AJV min max stand. AHV min max stand. AMV min max stand.
L1 ** 750 500 L1 ** 750 500 L1 ** 750 500

P2 ** 1000 500 P2 ** 1000 500 P2 ** 1000 500

* Price list
** Depends on the type and the number of conductors.

Review 6 d.d.09.06 Page L 8


VARIO
TERMINAL ELEMENTS LA LB
EXTENDED TERMINAL DISTANCE

Straight

AEVE min max ACVE min max


L1 1250 3000
L1 1250 3000
P2 ** 2700 P2 ** 2700

APVE min max


L1 1250 3000
P2 ** 2700

Hammerhead
L1
L1

P*** P***

AJVE max L1 min. AHVE max L1 min.


P2 2000 FIXED P2 2000 FIXED
225 + P*** 225 + P***
L1

P***

AMVE max L1min.


P2 2000 FIXED
225 + P***

The E (extended) elements are made especially for connections to dry transfos with large phase to phase dimensions.
** Depends on the type and the number of conductors.
*** P depends on type of betobar-r.

Review 6 d.d.09.06 Page L 9


VARIO
TERMINAL ELEMENTS LA LB

D -terminal elements

Standard Standard
DHD min max in PL* DHF min max in PL*
L1 ** 750 500 L1 ** 750 500
P2 280 1250 750 P2 280 1000 750
+2H +2H

L1
L1

Standard Standard
DJD min max in PL* DJF min max in PL*

L1 ** 750 500 L1 ** 750 500


P2 280 1250 750 P2 280 1000 750
+2H +2B
L1
L1

DMD min max Standard DMF min max


Standard
in PL* in PL*
L1 475 750 500 L1 ** 750 500
P2 280 1250 750 P2 280 1000 750
+2B +2B
L1
L1

Standard Standard
DGD min max in PL* DGF min max in PL*
L1 475 750 500 L1 ** 750 500
P2 280 1000 750 P2 280 1000 750
+2B +2B
L1
L1

* Price list
** Depends on the type and number of conductors.

Review 6 d.d.09.06 Page L 10


VARIO
TERMINAL ELEMENTS LA LB

U -terminal elements

Standard Standard
UHD min max in PL* UHF min max in PL*
L1 475 750 500 L1 475 750 500
O 815 1270 750 O 575 1270 750

L1
L1

Standard Standard
UJD min max in PL* UJF min max in PL*
L1 475 750 500 L1 475 750 500
O 835 1250 750 O 595 1250 750
L1
L1

Standard Standard
UMD min max UMF min max in PL*
in PL*
L1 475 750 500 L1 475 750 500
O 835 1250 750 O 595 1250 750
L1

L1

* Price list

Review 6 d.d.09.06 Page L 11


SPECIAL ELEMENTS LA LB

Special terminal elements

extra long
connection contacts
with collars

Special corner elements

>90º

Transfer element

Phase switch for correction of impedance


used with extremely long feeders

RST TSR

1/6 L
STR RTS
1/3 L
TRS SRT
1/3 L
RST TSR
1/6 L

RST TSR

Junctions
L 10 L Z L

+5
5
Z

st.26 st.27 Z
LA-LB
Straight junction Flat elbow junction
04 20
08 40
L

12 60
16 80

Review 6 d.d.09.06 Page L 12


TAKE-OFF FACILITIES
STANDARD JUNCTIONS LA LB

LA 250 A LB 400 A
400 A 630 A

min 210
min 210

2x50
180

3x45
L = max 4000

70
240

540
205
min 230

min 210

Fixed sets of contacts are available for all straight elements.

Up to 400 Amps available in standard


synthetic boxes. Please, indicate your
preferred manufacturer. Special versions
on request. .

- empty

- with fuses

- with circuit breaker / MCB / MCCB

Review 6 d.d.09.06 Page L 13


VARIO
SPRING SUPPORTS LA LB

The line of betobar-r busways has been split up in 9 weight classes, from “A” to “I”. Weight Class
71-89 kg A
According to the betobar-r type and the element length the class is laid down and the 89-113 kg B
spring type is defined. 113-142 kg C
The design of this spring support is such allowing a displacement of each individual element 142-179 kg D
179-225 kg E
of +40 mm and -10 mm. This range covers all normal indoor temperature conditions and the 225-283 kg F
thermal dilatation of the busway. For swift installation an adjustment range is available. 283-357 kg G
In case of special requests, contact our local representative. 357-450 kg H
450-567 kg I

Busway type Trunking Length mm


unit
Type In Number of
conductors 3000 mm 3500 mm 4000 mm
LB04 1100 A 6 A B B
LB04 7 A B C
LB04 8 B C C
LB04 9 B C C
LB04 1250 A 6 A B C
LB04 7 A B C
LB04 8 B C D
LB04 9 B C D
LB04 1350 A 6 B B C
LB04 7 B B C
LB04 8 C C D
LB04 9 C C D
LB08 1750 A 6 C D D
LB08 7 C D E
LB08 8 D E E
LB08 9 D E F
LB08 2000 A 6 C D E
LB08 7 D D E
LB08 8 D E F
LB08 9 E E F
LB08 2150 A 6 D D E
LB08 7 D E E
LB08 8 E F F
LB08 9 E F F
LB12 2600 A 6 E F F
Closed model LB12 7 E F F
LB12 8 F G G
LB12 9 F G G
LB12 2800 A 6 E F G
LB12 7 F F G
LB12 8 F G H
LB12 9 G G H
LB16 3200 A 6 F G G
LB16 7 F G H
LB16 8 G H H
LB16 9 G H I
LB16 3375 A 6 F G H
LB16 7 G G H
LB16 8 G H I
LB16 9 H H I

Busway type Trunking Length mm


unit
Type In Number of
conductors 3000 mm 3500 mm 4000 mm
LA08 1120 A 3 A B C
LA08 4 B B C
LA08 5 B C C
LA08 1355 A 3 B C C
LA08 4 B C D
LA08 5 C C D
LA12 1605 A 3 C D D
LA12 4 D D E
LA12 5 D E E
LA12 1750 A 3 C D E
LA12 4 D E E
LA12 5 D E F
LA16 2000 A 3 D E E
Open model LA16 4 E E F
LA16 5 E F F
LA16 2220 A 3 D E F
LA16 4 E F F
LA16 5 E F G

Review 6 d.d.03.07 Page L 14


MEDIUM VOLTAGE SYSTEMS

On pages M7 till M13, you find the standardized series


elements for MV-applications.

The large number of element shapes and the compact


dimensions of the system allow the engineer to design
MV-connections in betobar-r as simply as for LV-
versions.

The Eta-com project-engineers work out all MV-busducts


in detail, like connections, wall-bushings, supports.

There are 3 types of MV-systems

3,6 - 7,2 kV type SH


The most compact type, emanating from the Low Voltage
range, needs only supporting insulators in order to be
looked upon as an MV line.

3,6 - 17,5 kV type PH


The more elaborate compact model PH, suited for a maxi-
mum of 17,5 kV. This type can be manufactured with and
without self-supporting screening. The project situation
and the client's demands will be decisive.

3,6 - 24 kV type MH
This type is the only single-pole betobar-r system, thus
helping the flexibility while engineering the specific main
rail systems for this voltage. These lines are supplied with
a self-supporting screening.

Notes :

Up to 10 kV no protective screen has to be provided.


Eta-com advises such a screen for 12 kV and higher
voltage levels in areas with access to public or
unauthorised persons.

For outdoor or equal routings an additional


“weather screen” has to be provided for all systems.

All types can be applied for a lower voltage level than


specified.

A combined application of PH- and MH-type is


possible

We reserve the right to change, at any time and without prior warning the technical specification of any product illustrated in this
catalogue.

Review 6 d.d.09.06 Page M 6


STANDARD ELEMENTS SH

Type Ir Ur max. BxH Cu hxb mm


A kV mm RST
SH1 935

h
60x04

H
1040 60x05
1135 7,2 160x100 60x06

75
1295 60x08
1425 60x10
1540 60x12 Supporting insulator
SH2 1710 100x08
1880 7,2 160x140 100x10
2015 100x12
Support shoulder

Straight element
RE1 L= max. 1000mm
RE2 L= max. 2000mm
RE3 L= max. 3000mm
RE4 L= max. 4000mm
L2

Brazed corner element Bent corner element


HL1 L1+L2= max. 1000mm HB1 L1+L2= max. 1000mm
HL2 L1+L2= max. 2000mm HB2 L1+L2= max. 2000mm
L3

Brazed T- element Bent T- element


TL1 L1+L2+L3= max. 1000mm TB1 L1+L2+L3= max. 1000mm
TL2 L1+L2+L3= max. 2000mm TB2 L1+L2+L3= max. 2000mm

Technical specifications may change without any further notice.

Review 6 d.d.09.06 Page M 7


STANDARD ELEMENTS SH

L3

L3
Double elbow element right Double elbow element left
XR1 L1+L2+L3= max. 1000mm XL1 L1+L2+L3= max. 1000mm
XR2 L1+L2+L3= max. 2000mm XL2 L1+L2+L3= max. 2000mm
L2

Brazed Z- element Bent Z- element


ZL1 L1+L2+L3= max. 1000mm ZB1 L1+L2+L3= max. 1000mm
ZL2 L1+L2+L3= max. 2000mm ZB2 L1+L2+L3= max. 2000mm

B' x H' x L'


370 x 330 x 500
H’

Expansion element
EX1 L= 1000mm

Review 6 d.d.09.06 Page M 8


STANDARD TERMINAL ELEMENTS SH

Straight

Standard Standard Standard


L1 max in PL* L1 max. L1 max. in PL*
in PL*
AE1 1000mm 1000 AP1 1000mm 1000 AC1 1000mm 1000
AE2 2000mm 1000 AC2 2000mm 1000
AE3 3000mm 1000

Hammerhead
L1

L1

L1

Standard Standard Standard


L1 max. P2 max. in PL* L1 max. P2 max. L1 max. P2 max.
in PL* in PL*
AF1 700mm 1000mm 500 AG1 1000mm 1000mm 500 AO1 1000mm 1000mm 500
AG2 2000mm 1000mm 500 AO2 2000mm 1000mm 500
L1

L1
L1

Standard Standard Standard


L1 max. P2 max. in PL* L1 max. P2 max. in PL* L1 max. P2 max. in PL*
AJ1 1000mm 1000mm 500 AH1 700mm 1000mm 500 AM1 1000mm 1000mm 500
AJ2 2000mm 1000mm 500 AM2 2000mm 1000mm 500

* Price list

Review 6 d.d.09.06 Page M 9


STANDARD ELEMENTS PH

Type Ir Ur max. BxH Cu hxb mm

A kV mm RST
PH10 (PH1) 1690 100x04
1870 100x05
2030 17,5 300x140 100x06

H
2290 100x08
2520 100x10

75
PH12 2570 120x08
2820 17,5 322x170 120x10
3035 120x12 Supporting insulator
PH16 3215 160x08
3525 17,5 322x210 160x10
3785 160x12
PH20 3975 200x08
4360 200x10
4675 17,5 322x260 200x12
5050 200x15 Supporting shoulder
For st.28 elbow junction
5150 200x16 see p M12

Straight element
RE1 L= max. 1000mm
RE2 L= max. 2000mm
RE3 L= max. 3000mm
RE4 L= max. 4000mm

Bent corner element


HB1 L1+L2= max. 1000mm L1&L2 min. 420 mm
HB2 L1+L2= max. 2000mm
L2

L3

Brazed corner element Brazed T-element


HL1 L1+L2= max. 1000mm L2=fixed PH10 L1&L2 min. 375 mm TL2 L1+L2+L3= max. 2000mm PH10 L1&L2&L3 min. 375 mm
HL2 L1+L2= max. 2000mm )
PH12 L1&L2 min. 390 mm PH12 L1&L2&L3 min. 390 mm
PH16 L1&L2 min. 410 mm L3= fixed
PH16 L1&L2&L3 min. 410 mm
PH20 L1&L2 min. 435 mm PH20 L1&L2&L3 min. 435 mm

Technical specifications may change without any further notice.

Review 6 d.d.04.07 Page M 10


STANDARD ELEMENTS PH

L3

L3
Double elbow element right Double elbow element left
XR2 L1+L2+L3= max. 2000mm XL2 L1+L2+L3= max. 2000mm
L3= fixed PH1 L3=350 L3= fixed PH1 L3=350
PH1.2 L3=400 PH1.2 L3=400
PH1.2e L3=400 PH1.2e L3=400

H’

Bent Z- element Expansion element


ZB2 L1+L2+L3= max. 2000mm EX1 L= 1000mm fixed

Dimensions

PH10 12 450X430X500
PH16 460X600X500
PH20 495X470X570

Review 6 d.d.09.06 Page M 11


STANDARD TERMINAL ELEMENTS PH

Straight

Standard Standard
PH1 PH1.2 PH1 PH1.2 in PL*
in PL*
AC1 L1= max. 1000mm L1= max. 1000mm 1000 AE1 L1= max. 1000mm L1= max. 1000mm 1000

AC2 L1= max. 2000mm L1= max. 1500mm 1000 AE2 L1= max. 1500mm L1= max. 1500mm 1000

Hammerhead
L1

L1

Standard Standard
PH1 PH1.2 in PL* PH1 PH1.2 in PL*
AG1 L1= max. 1000mm L1= max. 1000mm 500
AJ1 L1= max. 1000mm L1= max. 1000mm 500

AG2 L1= max. 2000mm L1= max. 1500mm 500


AJ2 L1= max. 2000mm L1= max. 1500mm 500
L1

L1

Standard Standard
PH1 PH1.2 PH1 PH1.2 in PL*
in PL*
AM1 L1= max. 1000mm L1= max. 1000mm 500 AO1 L1= max. 1000mm L1= max. 1000mm 500

AM2 L1= max. 1500mm L1= max. 1500mm 500 AO2 L1= max. 1500mm L1= max. 1500mm 500

* Price list

Review 6 d.d.09.06 Page M 12


STANDARD JUNCTIONS

SH Z L Z L

10 5 5

Z
Z

5
L L
Z Z
SH1 30 SH1 95
L

L
SH2 50 SH2 95

st.26 st.27 st.28


Straight junction Flat elbow junction Bent elbow junction

PH Z L Z L

10
5 5

5
Z
Z

L L

Z Z
L

PH1 50 PH1 25
PH1.2 60 PH1.2 35
PH1.2e 80 PH1.2e 35

st.26 st.27 st.28


Straight junction Flat elbow junction Bent elbow junction

MH Z L Z L

10 5 5
Z

Z
5

L L

Z Z
L

MH1 30 MH1 25
MH2 50 MH2 25

st.26 st.27 st.28


Straight junction Flat elbow junction Bent elbow junction

Review 6 d.d.09.06 Page M 13


SPECIAL TERMINAL ELEMENTS PH

Special straight
L1

L1

SRA L1= max. 2000mm SRB L1= max. 2000mm

Special combi

Optional:
Creepage collar for
outdoor connection.

st.28 MH
L1

SRC L1= max. 2000mm

Review 6 d.d.09.06 Page M 14


GENERAL LOW VOLTAGE / MEDIUM VOLTAGE
DESIGN FUNDAMENTALS

1. IEC standard – Temperature limits


In accordance with the IEC standard the betobar-r nominal rated current are all based on a daily average
ambient temperature of 35ºC with daily peak of 40ºC. For LV the design temperature rise is defined to be 60ºC
for the conductors, at a power frequency of 50Hz, limiting the surface temperature to 90ºC. The MV system is
designed to limit the conductor temperature rise at 50ºC. If the operating conditions are different from the design
values, the maximum permissible load current has to be corrected by the factors in the table on page G2.

2. Weights
The weights of the betobar-r for the LV- types are the average weights as indicated in the tables on pages L1 and L2,
including the junction and the casting mix per system length of 2 m. For MV-types the supporting insulators and any
possible screening is included. If partitions for a full phase segregation are needed, they have to be added as extra
weight.

3. System impedance
The busduct resistance values (DC resistance) Rdc20 are based on a conductor temperature of 20°C and a power
frequency of 50Hz in accordance with the IEC standard. The Rac95 for LV and the Rac85 for MV are the values for
the conductor resistances at max. operating temperature. The reactance values (X) of the LB-types are based on the
standard phase sequence RST-TSR for a 3-phase system.
For other configurations, frequencies or extreme temperatures, please consult Eta-com B or your betobar-r agent.
All impedances have been calculated with physical values :
For copper :
Specific resistance at 20°C = 0.0175 .mm²/m conductivity 57 MS/m
Temperature coefficient = 0.00392 1/°C
Standard EN13601 (2002)

For aluminium :
Specific resistance at 20°C = 0.029 .mm²/m conductivity 35.4 MS/m
Temperature coefficient = 0.004 1/°C
Standard EN755-2 (1997)
4. Maximum voltage
PH series is designed for a maximum voltage of 17.5 kV. Rated voltage 12 kV is provided with self-supporting
safety screen, the called PH..S(creen) system.

5. Short circuit
LV MV Icc values in the technical data
lcw lk Symmetrical short circuit current (1 second effective value if no further indications)
lpk lp Asymmetrical (dynamic) short circuit current (peak value)
The betobar-r busbars type tested reports of the official and independent laboratories (mostly at KEMA and
Laborelec) defines the Icc rating.

For the MH- standard types the following dimensions apply :

For MH1 and MH2 : phase distance = 150 mm and 175 mm for full segregation, support-shoulder distance 600 mm
For MH.D : phase distance = 300 mm, support-shoulder distance 800 mm

Phase distance and support-shoulder distance can be chosen for each project taking into account the production
possibilities. Consult Eta-com or your betobar-r agent on this matter.

Review 6 d.d.09.06 Page G 1


GENERAL LOW VOLTAGE / MEDIUM VOLTAGE
DESIGN FUNDAMENTALS

6. Temperature correction factors


Current t0 for different ambient temperatures
Peak temperature ºC 20 25 30 35 40 45 50 55 60

Max. daily average ºC 15 20 25 30 35 40 45 50 55


temperature

Current rating 1.18 1.14 1.09 1.05 1.00 0.94 0.88 0.82 0.75
correction factor
NB For intermediate values the next higher temperature should be considered or for a more precise result the correction factor must
be interpolated

7. Correction factors 60 Hz
Current rating for a power frequency of 60 Hz

LA08 LA12 LA16 SH1 SH2 MH2 PH12


betobar-r type
LA04 LB08 LB12 LB16 MH1 PH1 MH.D MH2D e PH16 PH20

Cu height 30- 40 80 120 160 60 100 100 120 160 200

Current rating cor- 1.000 0.988 0.986 0.984 0.984 0.982 0.982 0.980 0.980 0.990
rection factor

8. Voltage drop calculation


Generally long busduct connections have to be checked for voltage drop with the following formula :
D U = 3 x Is x a x L x (Ra.cos j + X.sinj ) x 10-6 V.

whereby : DU = voltage drop (between phases) [Volts]


Is = Normal Full Load Current * [Amps]
a = current distribution factor see graph. below
L = total busduct length [m]
Rac = A.C. Resistance at operating temperature ** [mW /m]
cos j = power factor
X = reactance (mean value) [mW /m]
sin j = reactive factor (= 1 cosj²)
Notes :
* For distribution lines, the max. average load current which can be indicated as a % of the full load has to be used in
this calculation.
** The operating temperature is the sum of the ambient temperature and the temperature rise as a result of the load
current. For critical calculations Ra has to be corrected according to the tables (Ra20 or Ra85).
L L L
a=1 a= a=
0.5 0.25

L L L
a= a= a=
0.125 0.5 0.25

9. Phase sequence
Phase sequence in documentation and product documents :
is indicated as R S T
to be equal to R Y B
or L1 L2 L3
10. General
For all information or technical calculations, please consult Eta-com or your betobar-r agent.

Review 6 d.d.09.06 Page G 2


EXAMPLES FOR
LV TERMINATIONS

STANDARD FLEXIBLE TERMINATION


with bellow and laminated flexibles
1. betobar-r
2. Flange
3. Bellow
4. Flexibles
5. Switchgear or 2
connection box
3 1
6. Terminals
2
4 1

4
6

PANEL TERMINATION

Bottom entry :
with flexibles or shunts 2
and bottom plate 3

IP class to be determined 1
by customer 4

1. betobar-r
2. Flexibels
3. Terminals
4. Switchgear panel
5. Support

Review 6 d.d.09.06 Page V 1


EXAMPLES FOR TERMINATIONS
WITH BELLOW AND FLEXIBLES

1. betobar-r
2. Flange
3. Bellow or flat membrane 2 6
4. Flexibles
5. Connection box
6. Connection clamps
7. Switchgear 2

1
6

Review 6 d.d.09.06 Page V 2


EXAMPLES FOR TERMINATIONS
WITH ETA-COM STANDARD S-PROFILE BELLOW

60
+-30
75

Min. 10
Max. 30
5

30

Min. 10
Max. 40

Review 6 d.d.09.06 Page V 3


STANDARD FLEXIBLES

Max. usable contact


area

1 3

40
Code hxb
FLC 02510 25 x 10
b

FLC 04010 40 x 10

Eta-com recommends laminated press welded FLC 05005 50 x 05


flexibles for most of the terminations. FLC 05006 50 x 06
A stock of a standard range is kept available. FLC 05008 50 x 08
FLC 05010 50 x 10
1. Press-welded contact surfaces FLC 05012 50 x 12
on request: - cut to size
- tin-plated FLC 06005 60 x 05
- silver-plated FLC 06006 60 x 06
2. Drillings on request FLC 06008 60 x 08
see p R7 till R10 FLC 06010 60 x 10
3. Standard flexible FLC 06012 60 x 12
E-Cu laminations
foil 0.25 or 0.2 mm FLC 08005 80 x 05
FLC 08006 80 x 06
FLC 08008 80 x 08
FLC 08010 80 x 10
Remark : braided flexibles and Alu flexibles on request made to FLC 08012 80 x 12
size for each project
FLC 10005 100 x 05
FLC 10006 100 x 06
FLC 10008 100 x 08
FLC 10010 100 x 10
FLC 10012 100 x 12

FLC 12006 120 x 06


Standard size : FLC 12008 120 x 08
L = 370; L1 = 120; L2 = 100 FLC 12010 120 x 10
FLC 12012 120 x 12 *

Tolerance on b-dimension to DIN 46433


Tolerance on h-dimension can vary - 2 mm due to laminate size.

Technical specifications may change without any further notice.

Review 6 d.d.09.06 Page R 1


TERMINALS
STANDARD COLLARS LV - MV

LV
1000V LA - LB
40/60 max. 10 2x10 max.

20
h+10 18 34

min.5 h+20 28 44

h= 80/100/120/160
max. 12 3x12 max.

20
h+10
22 46

min.5 h+20
32 56

MV

7,2 - 12 kV 17,5 kV
SH PH
h= 60/80/100/120 max. 12 3x12 max.
17 5 kV
7 2 kV

12 kV
66

96
41

42 66
* min.20 h+30
58 82
74 98
* Beware of correct creepage path

Note : The dimensions of the collars can be changed without notice.

Review 6 d.d.09.06 Page R 2


STANDARD TERMINAL
DRILLING TO DIN 46206 STANDARD

Height 150 mm standard in price list : also available in 175 / 225 mm


Ø11 / 11 x 16.5
L.V.

1.1 1.8

= =

30
For 150 mm not standard available
15 Ø14 / 14 x 21
L.V.

Ø14 / 14 x 21

=
L.V.

= = = = = = =
1.2 1.9
= =

40

2 x 80
40 20

Ø14 / 14 x 21
L.V.

1.3
= =

50

M.V. 40 20

M.V. 40 20
L.V. Ø14 / 14 x 21
Ø14 / 14 x 21
L.V.

=
=
1.4 1.10
= =

60

2 x 100
=
M.V. 40 20

=
Ø14 / 14 x 21

=
L.V.

=
= = = =

1.5
=
80

M.V. 40 20

M.V. 40 20
Ø
L.V. / M.V.
Ø14 / 14 x 21
L.V. A max xL
16 M10 x 35
=

16 M12 x 40
L
=

24 M12 x 45
1.6
100

A
=

b
=

Protection washer
M.V. 40 20
Pressure washer
Ø14 / 14 x 21 DIN 6796
L.V.
=

Ø
L.V. / M.V.
A max xL
=

1.7
120

24 M10 x 45
=

24 M12 x 45
32 M12 x 55
b
=

48 M12 x 70
L
A

40 20
M.V. 74 Nm M12
43 Nm M10
Protection washer
Pressure washer
DIN 6796

Review 6 d.d.09.06 Page R 3


EXAMPLE FLEXIBLE WALL BUSHING UP TO S180
LV according to test reports on behalf of Eta-com

LOW VOLTAGE

1. Fireproof wall or floor

2. betobar-r frame only for S>60

3. Promatect plate 12mm (or similar)

4. Rockwool plate 50mm type 750

5. Pressing strip 30x5 or washer DIN 9021

6. Steelbolt M8x40 . washer . anchor (steel)

7.Fire protection coatings and mastic

2
40

3
40

B+160 x H+160
BxH

4
~180

2x12 60

*The fire resistance class is highly dependent on thickness and


quality of wall or floor.

Review 6 d.d.09.06 Page R 4


EXAMPLE FLEXIBLE WALL BUSHING TILL S180
Medium Voltage systems

SH PH

1. Fireproof wall or floor

2. betobar-r frames

3. Promatect plate 12mm (or similar)

4. Rockwool plate 50mm type 750

5. Pressing strip 30x5 or washer DIN 9021

6. Steelbolt M8x40 . washer . anchor (steel)

7. Fire protective coating and mastic

2
40

3
30
50

L**
B+240 x H+240
BxH

5
~180

2x12

60 3x50 min. 20

*The fire resistance class is highly dependent on thickness and


quality of wall or floor.
**L in 3 standard dimensions available 320 mm, 420 mm and 520 mm.

Review 6 d.d.09.06 Page R 5


DIMENSIONS JUNCTIONS

L1 B1 H1
mm mm mm
LA04 325 140 115
LA08 325 140 155
st.26 LA12 325 140 195
Straight junction LA16 325 140 235

LB04 325 175 115 6/7 conductors


LB08 325 175 155
LB12 325 175 195
H1

LB16 325 175 235

LB04 325 205 115 8/9 conductors


LB08 325 205 155
LB12 325 205 195
LB16 325 205 235

SH1 340 195 140


SH2 340 195 180
PH1 340 80 180
PH1.2 420 90 200
MH1 340 85 140
MH2 340 85 180

L1 B1 H1
st.27 mm mm mm
Flat elbow junction LA04 240 140 115
H1

LA08 280 140 155


LA12 320 140 195
LA16 360 140 235

LB04 240 175 115 6/7 conductors


LB08 280 175 155
LB12 320 175 195
LB16 360 175 235

LB04 240 205 115 8/9 conductors


LB08 280 205 155
LB12 320 205 195
LB16 360 205 235

SH1 270 195 135


SH2 310 195 175
PH1 310 80 175
PH1.2 370 90 195
MH1 270 85 135
st.28 MH2 310 85 175
Bent elbow junction
H1

L1 B1 H1
mm mm mm
SH1 380 195 135
SH2 380 195 175
PH1 225 80 175
PH1.2 280 90 195
H1

MH1 230 85 135


MH2 230 85 175

Technical specifications may change without any further notice.

Review 6 d.d.09.06 Page R 7


TEST REPORTS

Heat run test


Low Voltage betobar-r
Results Lab Report
Type S Ui In
mm² kV A
LA04 Cu 3x240+240+240 1 816 t = 60°C PDL 03-126-1
LA08 Cu 3x480+480+480 1 1380 t = 50°C PDL 03-126-1
LA12 Cu 3x720+720+720 1 1770 t = 50°C PDL 03-126-1
LA16 Cu 3x960+960+960 1 2200 t = 50°C PDL 03-126-1
LB04 Cu 3x480+480 1 1390 t = 50°C LCE 50929/039
LB08 Cu 3x960+960 1 2170 t = 50°C LCE 50929/039
LB12 Cu 3x1440+1440 1 2810 t = 50°C LCE 50929/039
LB16 Cu 3x1920+1920 1 3420 t = 50°C LCE 50929/039

Medium Voltage betobar-r


Results Lab Report
Type S Ur Ir
mm² kV A
SH1 Cu 3x720 7,2 1610 t = 50°C Kema 06-1174
SH2 Cu 3x1200 7,2 2050 t = 50°C Laborelec 41334/31 A
PH1 Cu 3x600 17,5 2100 t = 50°C Laborelec 34472/71
PH16 Cu 3x1920 17,5 3711 t = 50°C Kema 06-1172
PH20 Cu 3x2400 17,5 4675 t = 50°C Kema 04-1186

Partial discharges

kV pC

SH2 Cu 3x800 7.2 1665 7.9 10 KEMA 5205-72


PH1 Cu 3x1000 17.5 2400 17.4 10 KEMA 9251-73

Verification of fire resistance in building penetration


Low and Medium Voltage betobar-r
Results Lab Report
Type S Un kV In A
mm² 50 Hz 50 Hz
LV+MV all S60 S120 ULG EF/FV/1063E
LV+MV all S90 S120 ULG EF/FV/1063F
LV+MV all S90 S120 ULG EF/FV/1063G
LV all A60 H60 Statens
Provningsanstalt

Note :
From now on, LA-LB series for Low Voltage will fully replace the J-SL.0-1-2-3 series which are not shown in the
documentation anymore. However, these series can be produced on demand only for replacement or extensions of
existing installations. The test reports for the old series J-SL.0-1-2-3 will remain available on request.

Tec hnical specifications may change without any further notice.

Review 6 d.d.07.07 Page R 8


TEST REPORTS

Short-circuit resistance
Low Voltage betobar-r
Results Lab Report
Type S Un kV In A kA/1 s kA
mm² 50 Hz 50 Hz sym. asym.
LA04 Cu 3x240+240+240 1 816 30 121 PDL 03 126 1
LA08 Cu 3x480+480+480 1 1380 50 105 PDL 03 126 1
LA12 Cu 3x720+720+720 1 1770 65 143 PDL 03 126 1
LA16 Cu 3x960+960+960 1 2200 75 176 PDL 03 126 1
LB04 Cu 3x480+480+480 1 1390 45 95 Kema 212 92
LB08 Cu 3x960+960+960 1 2170 80 175 Kema 213 92
LB12 Cu 3x1440+1440 1 2810 90 200 Kema 214 92
LB16 Cu 3x1920+1920 1 3420 100 220 Kema 215 92
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A kA/1 s kA
mm² 50 Hz 50 Hz sym. asym.
SH1 Cu 3*720 7,2 1497 50 130 Kema 82 06
SH2 Cu 3x1200 7,2 2400 77 202 Kema 2998 78
PH1 Cu 3x1000 17,5 2400 95 205 Kema 1557 73
PH16 Cu 3x1920 17,5 3711 80 208 Kema 80 06
PH20 Cu 3x2400 17,5 5050 100 260 Kema 327 04

Thermal shock
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A Degree of
mm² 50 Hz 50 Hz protection
PH1 Cu 3x800 12 2175 No deterioration INIEX 70/76

Degree of protection
Low Voltage betobar-r
Results Lab Report
Type S Un kV In A Degree of
mm² 50 Hz 50 Hz protection
LA all 1 IP68 Kema 2071268 QUA/COM
LB all 1 IP68 Kema 2071268 QUA/COM
LV Take off box 1 IP55 Kema 200657.01 KRQ/COM
LV Take off box 1 IP67 Kema 2101518.01
LV Termination with bellow IP55 Kema 200657.01 KRQ/COM
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A Degree of
mm² 50 Hz 50 Hz protection
SH all 7,2 IP67 Kema 2071268 QUA/COM
PH all 17,5 IP67 Kema 2071268 QUA/COM
MH all 24 IP67 Kema 2071268 QUA/COM

Tec hnical specifications may change without any further notice.

Review 6 d.d.01.07 Page R 9


TEST REPORTS

Voltage tests
Low Voltage betobar-r
Results Lab Report
Type S Un kV In A kV kV
mm² 50 Hz 50 Hz 1 min 1.2/50 ms
LA04 Cu 3x240+240+240 1 816 3,5 12 PDL 03 126 1
LA08 Cu 3x480+480+480 1 1380 3,5 12 PDL 03 126 1
LA12 Cu 3x720+720+720 1 1770 3,5 12 PDL 03 126 1
LA16 Cu 3x960+960+960 1 2200 3,5 12 PDL 03 126 1
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A kV kV
mm² 50 Hz 50 Hz 1 min 1.2/50 ms
SH1 Cu 3x720 7,2 1497 38 95 Kema 06 1053
SH2 Cu 3x800 3,6 1665 27 45 Kema 5201 72
PH1 Cu 3x400 17,5 1690 38 95 Laborelec 42065/51
PH16 Cu 3x1920 17,5 3711 38 85 Kema 06 1051
MH2 Cu 3x800 24 2400 50 125 Laborelec 42066/51 4

Voltage duration tests


Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A kV
mm² 50 Hz 50 Hz 100 h
SH2 Cu 3x800 7,2 1665 13 Kema 5204 72

Leakage current
Medium Voltage betobar-r
Results Lab Report
Type S Ur kV Ir A mA
mm² 50 Hz 50 Hz
SH2 Cu 3x800 3,6 1665 0,06 @ 7,2 kV Kema 5205 72
PH1 Cu 3x1000 12 2400 0,28 @ 12 kV Kema 9251 73
MH1 Cu 3x1000 7,2 2410 0,10 @ 7,2 kV Kema 7335 72

Ex tests
betobar-r
Results Lab Report
Type S Un kV In A kA/1 s kA
mm² 50 Hz 50 Hz sym. asym.
LV/MV All 11 kV Eex mII T5 LCIE LCIE 07 ATEX 0003 U

Fire proof tests

Low Voltage betobar-r


Results Lab Report
Type S Un kV In A
mm² 50 Hz 50 Hz
LV all E120 ULG EF/FV/1063D

Tec hnical specifications may change without any further notice

Review 6 d.d.07.07 Page R 10


FINAL WORKS TESTS
ON ELEMENTS
MEDIUM VOLTAGE Ur > 1000 V

A. ELECTRICAL TESTS : VOLTAGE TEST AND PARTIAL DISCHARGE TEST

Tests between each conductor with all other conductors and supports earthed (dry)

Tests Test voltage Partial discharges

Standards IEC 60 IEC 270


Rated voltage

Types Ur Ur max * Ud 50 Hz 50 Hz q
at 50 Hz at 50 Hz 10 sec Ue at
kV kV/1 min. 1.7 Ur 1.1 Ur 1.1 Ur

3,6 10 6,12 3,96 20**


SH1 – SH2
7,2 20 12,24 7,92 20**

12 28 20,40 13,20 20**


PH10, 12, 16, 20
17,5 38 29,75 19,25 20**

MH1 – MH2 – MH.D 24 50 40,80 26,40 20**

* Ur level for work tests can be specified by customer. If not indicated, the test voltage will be according to
the rated voltage Ur equivalent to the operation voltage Us.
** Eta-com standard value. In accordance with IEC 62271 the customer can determine here a different value
for each project.

B. Dimensions
All dimensions are to be compared with the order sheet.

Result (yes/no) to be mentioned in final test report

C. Phase sequence
End- and phase switching elements : conductor connections are to be compared with the order sheet.

Result (yes/no) to be mentioned in final test report

D. Visual
The element and its workmanship are to be examined.

Result (yes/no) to be mentioned in final test report

Tests on site : The procedure of the tests to be executed on site is stipulated on page 33 from the MV Installation
Instructions.

Nomenclature M.V. : Us = Operation voltage, Ur = Rated voltage, Ud = Test voltage

Review 6 d.d.09.06 Page R 14


BUSWAY ROUTE PLANNER

Customer : Date :

Information required for quotation. Please, photocopy this form and attach to your inquiry.
In Un Freq. Temp. Project :
to t max.
o o
A V Hz C C Job nr :

Conductors 3P N PE + Line Length Outdoor U % Tap off’s


1/2 1/1
total In
Cu Al nr m m nr

Review 6 d.d.09.06 Page R 14


WORKS TEST REPORT L.V. PER ELEMENT SUMMARY
Project :
Client :
Ext. ref :
Int. ref :

A. IDENTIFICATION
Type :
Section. : Line nr. :
Nominal voltage Ui :
User voltage Ue :
Nominal current In :
User current Is :

B. TESTS AND STANDARDS


Visual inspection and dimensional control to ordersheet
Insulation resistance at 1 kV DC.
Power frequency (high potential) test at 5 kV / 1 min. to I.E.C. 60.439

ELEMENT EL-ID DATE ELEMENT EL-ID DATE ELEMENT EL-ID DATE

Note: For long lines and or split deliveries more than one report can be produced
C. RESULTS
Visual inspection and dimensions :
- All dimensions are according to ordersheet Yes / No
Electrical tests :
- All insulation values are more than 5 Gigaohm at 1 kV DC. Yes / No
- All elements withstand power frequency test at 5 kV / 1 min. Yes / No
- Terminal & phase switching elements: checked phase-sequence Yes / No

D. CONCLUSION
Tests : All elements comply with the requirements Yes / No
Packing : Material approved as ready for packing Yes / No
Shipment : Material approved as ready for shipment Yes / No
Remarks :................................................

Test engineer Company Date This document has been generated


automatically from data of our quality
ETA-COM B system and does not require a signature
Witness Company Date Signature

Serial Nr. :
Review 6
dd 20/10/2006
WORKS TEST REPORT M.V. PER ELEMENT
Project :
Client :
Ext. ref :
Int. ref :

A. IDENTIFICATION
Type :
Section. : Line nr. :
Nominal voltage Ur : Element nr. :
User voltage Us : Element form. :
Nominal current Ir :
User current Is :

B. VISUAL INSPECTION AND DIMENSIONAL CONTROL


Main dimensions L1 L2 / P2 L3 Ref.
Length(s) Ordersheet
Angle(s) Ordersheet
Cast-on accessories Type Number Position Ref.
Supports/Shoulders Ordersheet
Frames/Flanges Ordersheet
Terminals Drillings Phase distance Position Ref.
Junction(s) Eta-com standard
End element Ordersheet
Take offs Ordersheet
Appearance Conductors Insulation material Primary packing
Eta-com standard
Screen Type Appearance Position Ref.
Ordersheet

C. ELECTRICAL TESTS
- Power frequency test (HI-POT) to I.E.C. 60 and I.E.C. 270.
- Partial discharge measurements to I.E.C. 270 (P.D. level max. 20 pC. at 1,1 Umax = Eta-com std., or level defined by client at Order)
- Only for phase switching and expansion elements :
Insulation resistance measurement. All insulation resistance values are at least 10 Gigaohms at 5 kV. D.C.
Phase - sequence checked : . . . . . . . . . .

Power frequency test Partial discharges Remarks


Test set- Test voltage Time Results Rising voltage P.D. P.D. Results
up 50 Hz (sec.) Voltage Level
(Kv) 1,7 Ur Hold time 1,1 Ur
(kV) (sec.) (kV) (pC)

R-ST 60 10 <20
S-RT 60 10 <20
T-RS 60 10 <20

D. CONCLUSION
Tests : The element complies with the requirements Yes / No
Packing : Material approved as ready for packing Yes / No
Shipment : Material approved as ready for shipment Yes / No
Test engineer Company Date This document has been generated
ETA-COM B automatically from data of our quality
system and does not require a signature
Witness Company Date Signature

Serial Nr. :
Review 5
dd 20/10/2006
REFERENCE LIST
WORLDWIDE PROJECTS

Consultant
Place Project LV/MV Year
Engineering contractor

Algeria Arzew Sonatrach GP2Z Siemens Brussel MV 2001


Wilaya D’Llizi Sonatrach CPC Plant MV 1997

Aruba WEB Power Plant extension Siemens MV 2003


WEB Aruba ABB Rotterdam MV 1999

Austria Ös Telekom Vienna LV 2003


Vienna Telekom Austria Va Tech Elin EBG LV 2002
Klagenfurt University Klagenfurt Va Tech Elin EBG LV 2000
Salzburg Kaindl Siemens/Va Tech Elin EBG LV/MV 1999
Vienna Colt Va Tech Elin EBG LV 1999
Villach Landes Krankenhaus Va Tech Elin EBG LV 1998
Klagenfurt Landes Krankenhaus Va Tech Elin EBG LV 1998
Vienna Österreichische Nationalbank Va Tech Elin EBG LV 1996

Azerbaijan Yenikend Yenikend Hydro Power Station Pauwels International LV/MV 1999

Bangladesh Mymensing Powerplant MV 2005

Belgium Zelzate Sidmar Engineering Sidmar LV 2001


Olen Umicore GTI LV 2001
Antwerpen Fina Antwerp Olefins FAO/John Brown LV 1997
Antwerpen Fina Refinery ABB / Foster Wheeler LV/MV 1996
Gent P.P. “Nieuwe Vaart” ABB / Tractebel 1996
Brugge P.P. “Herdersbrug” Fabricom / Tractebel LV 1996
Geel Amoco Technipetrol LV 1995
Izegem Vandemoortele/SPE Twyver/Tractebel MV 1995
Meerhout Nike LV 1994
Antwerpen Agfa Gevaert LV 1994
Mechelen Kredietbank KBC ENI / ABE LV 1992
Leuven Gasthuisberg Hospital Inelec / Stabo LV 1992
Mechelen Procter & Gamble ABB LV

Brasil Petrobras P-50 offshore Siemens MV 2003

Chad Doba Doba GE Energy Products MV 2001

China Guangzhou Pumped Storage Power Station II Siemens Erlangen LV 1997


Hangzhou WWTP Hangzhou Siemens ANL LV/MV 1997
Korla - Shanshan Siemens Erlangen LV 1996

Denmark Hjorring Kraftvarmevoerk MV 1996


Offshore Maersk Giant ABB National Electric LV 1996

Egypt Sumed steelmill Sumed Egypt LV 2004


LNG train 2 LV/MV 2004
LNG plant LV/MV 2003
Ameriya Sidi Kerir Petrochemicals LV/MV 1997
Caïro (Helwan) EISCO Steel Mill Cegelec Belfort MV 1996
Caïro Caïro West Power Station ABB Schaltanlagen LV 1992

France Dunquerke ASP Forclum LV 2001


Paris Eiffel Tower – Repowering project Spie LV 1999
Donges Elf Antar Technip Lyon MV 1993
Epinal Papermill Golbey ABB Stromberg LV 1991

Germany Basell Polyoktins LV 2003


Trier Steel Mill LV 2003
Papermill WEPA LV 2003

d.d. 08.07 Rev. 3 - Worldwide 1


REFERENCE LIST
WORLDWIDE PROJECTS

Consultant
Place Project LV/MV Year
Engineering contractor

Frankfurt Deutsche Bundesbank DBB ESA Elektrotechnik LV 2001


Bonn European Transonic Windtunnel ETW Cologne MV 1992
Eisenhüttenstadt EKO - Stahlwerk LV 1996
Salzgitter Steel Mill PEINE WEPA LV 1991

Hungaria Procter & Gamble substation LV 2003

India Mumbai Offshore platform MV 2005


Neepco Agartala Gas Turbine Power Plant European Gas Turbines MV 1995
Gandhar Combined Cycle Power Station ABB Power Co Delhi LV 1993

Indonesia PLN Grati CCPP MV 1994


Riau-Sumatra PT Riau Andalan Pulp & Paper Siemens Germany MV 1993
Borneo Tambak Lorok CCPP Pertamina MV 1996
Jakarta PT W. Pertamina Hankam MV 1992

Iran NPC Bandar Imam MV 2003


EO/EG Plant Jaboun MV 2003
Yazd Nisco Alloy Steel Danielli LV/MV 1997

Iraq Al-Shemal General Company Electrical projects MV 2002

Ireland Belfast BBC Belfast Blackbourne Electrical LV 2003


Power Station Coolkaragh LV 2003

Israël Oil Refinery Plant L301 MV 2002

Italy Susa Pont Ventoux Hydro Power Station Carlo Gavazzi MV 2001

Kazachstan Tengiz Tengiz expansion LV 2003


Karachaganak Karachaganak Hydro Pauwels International LV/MV 1999
Tengiz KTL 2/3 Expansion project Bechtel LV 1998
Tengizchevroil
Tengiz KTL-Offplot Debottlenecking Bechtel MV 1997

Korea Songkhula GSP LV 2004

Luxembourg Worldcom GTI 2001

Lybia Dirmis II LV 1994


Tripoli Tripoli Central Hospital LV 1994

Malaysia FPSO-MSE offshore LV 2003


CA-CWP Platform Azeri LV 2003
LNG Tiga MV 2001
Kerteh Petlin LDPE Technip / Petronas LV/MV 2000
Grace Packaging ABB Australia LV 1995
Shell Berhad Pl M1 Samsung Heavy Industries LV 1995

Nigeria Bonny Island Refinery Pauwels LV 2003

Norway Navion Stavanger Aker Kvaerner MV 2006


Ekofisk offshore MV 2004
Norzink MV 2004
Sakhalin I Siemens AS LV 2003
Stortinget LV 2003
Hammerfest LNG plant LV 2003
Orlan Platform Oil & Gas Oslo

d.d. 08.07 Rev. 3 - Worldwide 2


REFERENCE LIST
WORLDWIDE PROJECTS

Consultant
Place Project LV/MV Year
Engineering contractor

Offshore Bideford Dolphin ABB Industry AS LV 1997


Offshore Heidrun Field Kvaerner Eng./ABB distribution MV/LV 1993
Norvegian Rig Consultants
Offshore Statfjord C Siemens AS LV 1993
Offshore Ekofisk 2/4 K Aker Electro LV 1993
Offshore Troll Platform Aker Engineering / ABB Distribution MV/LV 1992

Oman LNG Oman Pauwels MV 2003


Rusayl Oman Cement Project LV 1997
Nizwa Manah Power Project MV 1996

Pakistan Karachi FFC – Jordan LV/MV 1997

Palistinia Gaza Gaza Power Plant Alstom Power Sweden MV 2001

Poland Plewiska Uwplewiska MV 2001


Ostrow Umspannwerk Ostrow MV 1999
Opole Kraftwerk Opole MV 1995

Qatar Mesaieed Q-Chem LV 2000


Mesaieed Nodco Refinery Expansion LV/MV 2000
Ras Laffan Liquefied Natural Gas Co Siemens Advanced Eng. MV 1997
Mesaieed Qafco III Expansion Project LV/MV 1996

Russia Moscow Moscow City MV 2006


Sakhalin II offshore LV 2004
Piltun Field Sakhalin LV 2004
Moscow Moscow City Power Plant Alstom Power Sweden MV 2003

Saudi Arabia Shoaiba Shoaiba Power Plant stage II phase 2 Alstom MV 2005
Shoaiba Shoaiba Power Plant stage II phase 1 Alstom MV 2004
Shoaiba Shoaiba Power Plant Units 4 & 5 Alstom Germany MV 2002
Shoaiba Shoaiba Power Plant Units 1, 2 & 3 Alstom Germany MV 2000
Dammam Saad Hospital Alfanar LV 1998
Jubail Hunther Phase III LV 1998
Al Jubail 20 MIGD SWRO Plant LV/MV 1996
Al Jubail Saline Water Conversion Co Preussag Salzgitter LV/MV 1996
Bishah Cement Plant Siemens Erlangen LV 1995

Singapore The Esplanade – Theatres on the bay Busway Systems Engineering LV 2001

Sweden IBM Kista LV 2005


IBM Kaarstoe LV 2004

Syria Gas Turbine extension MV 2004


Deir-ez-zor Omar Power Station MV 2000

Taiwan Bi Hai MV 2004


Hannstar MV 2003
Liyutan Shihlin Hydropower Project LV/MV 1999

Thailand OCS 3 Thailand HAM Ferrostaal LV 2006


Aerosil Thailand Aerosil LV 2003
Krabi Krabi
Mae Moh ABB Mannheim LV/MV 1998
Monsanto MV 1994

The ABN Amro computer centre GTI Amsterdam LV 2006


Netherlands AMC Amsterdam GTI Amsterdam LV 2006

d.d. 08.07 Rev. 3 - Worldwide 3


REFERENCE LIST
WORLDWIDE PROJECTS

Consultant
Place Project LV/MV Year
Engineering contractor

Almelo Uranium Plant Urenco (DHV/AIB) LV 2003


Dordrecht Delrin Plant Dupont de Nemours / Siemens LV/MV 2002
Amsterdam Cisco Headoffice Cisco (Deerns) LV 2001
Delfzijl Akzo Delesto Saltplant Akzo Engineering LV/MV 2001
Rotterdam Eastman Chemicals Eastman (Fluor Daniels) LV 1999

Turkey Istanbul Pendik Nisasta Sanayi AS (PNS) 1995

U.A.E. Abu Dhabi DIFC Gate Village LV 2006


Abu Dhabi Habshan Gasco Switchgear & Instrumentation LV 2006
Abu Dhabi Nasser Tower LV 2006
Sharjah Saleh Bin Lahej LV 2006
Sharjah Bin Sabath Tower LV 2005
Sharjah Millennium Hotel LV 2002
Abu Dhabi Ruwais Borouge Petrochem. Switchgear & Instrumentation LV 2001
Abu Dhabi Ruwais Sulpher Handling Switchgear & Instrumentation LV 2000
Abu Dhabi OGD Project Phase II (ADNOC) Switchgear & Instrumentation LV 1999
Abu Dhabi ASAB Gas Development (ADNOC) Switchgear & Instrumentation LV 1998
Sharjah Al Ramtha Power Station GE Energy Products 1997
Abu Dhabi Taweelah Water Siemens Karlsruhe LV/MV 1996
Abu Dhabi Abu Dhabi National Oil Co (ADNOC) Bechtel LV 1996
BAB/Hamsham Gas
Ras Al Khaimah Union Cement Co MV 1995

United London BT Bletchley Fairbrother Ltd LV 2006


Kingdom Stratford Stratford Eye Switchgear & Instrumentation LV 2006
IDC Cardiff Switchgear & Instrumentation LV 2006
Warwick IBM Warwick Mitie Engineering LV 2006
Immingham Immingham CHP Foster Wheeler LV/MV 2003
London Canary Wharf N.G. Bailey/Delta Electrical LV 2002
London Empress State Building Gratte Brothers LV 2002
Cardiff IDC Cardiff Schneider Electric LV 2002
Hayes Middlesex Hayes Data Centre T. Clarke PLC/Deutsche Bank LV 2002
Swindon Compaq Data Center Emcor Drake & Scull LV 2002
London Redbus – Meridain Gate ABB LVS Ltd LV 2001
London Sovereign House ABB LVS Ltd LV 2001
Reading Green Park Haden Young Ltd LV 2001
Glasgow BT Glasgow Blackburn Starling LV 2000
London Royal Albert Hall Staveley Services LV 1999

d.d. 08.07 Rev. 3 - Worldwide 4