Project : MRF, Akenpally Consultants : Semac Date : 15 Jan 2014 DG Model : SGM 2625 PH Prime : 2625 kVA, 415 V Standby : 2887 kVA, 415 V Alternator Make : STAMFORD Alternator Model : PI734G
Generator Rating (in MVA) 2.625
Generator Voltage (in V) 415 Subtranscient Reactance (xd'') in % 15.5 Generator Reactance @ Base MVA 5.90 No. of Generator in Parallel 1.00 Equivalent Reactance 5.90 Short Circuit MVA 16.94
Total Short Circuit Current (in kA) 23.56
Fault Level Calcualtions
DG Vendor : Sterling Wilson Powergen - Chennai
Project : MRF, Akenpally Consultants : Semac Date : 15 Jan 2014 DG Model : 4012-46TAG0A Prime : 1250 kVA, 415 V Standby : 1375 kVA, 415 V Alternator Make : Stamford Alternator Model : PI734A
Generator Rating (in MVA) 1.25
Generator Voltage (in V) 415 Subtranscient Reactance (xd'') in % 14 Generator Reactance @ Base MVA 11.20 No. of Generator in Parallel 1.00 Equivalent Reactance 11.20 Short Circuit MVA 8.93 Total Short Circuit Current (in kA) 12.42
Total Short Circuit Current (in KA) for above no.of DG set in 35.98 Parallel MVA V % Ohm DG Ohm MVA