You are on page 1of 4

Fault Level Calcualtions

DG Vendor : Sterling Wilson Powergen - Chennai


Project : MRF, Akenpally
Consultants : Semac
Date : 15 Jan 2014
DG Model : SGM 2625 PH
Prime : 2625 kVA, 415 V
Standby : 2887 kVA, 415 V
Alternator Make : STAMFORD
Alternator Model : PI734G

Generator Rating (in MVA) 2.625


Generator Voltage (in V) 415
Subtranscient Reactance (xd'') in % 15.5
Generator Reactance @ Base MVA 5.90
No. of Generator in Parallel 1.00
Equivalent Reactance 5.90
Short Circuit MVA 16.94

Total Short Circuit Current (in kA) 23.56

Fault Level Calcualtions

DG Vendor : Sterling Wilson Powergen - Chennai


Project : MRF, Akenpally
Consultants : Semac
Date : 15 Jan 2014
DG Model : 4012-46TAG0A
Prime : 1250 kVA, 415 V
Standby : 1375 kVA, 415 V
Alternator Make : Stamford
Alternator Model : PI734A

Generator Rating (in MVA) 1.25


Generator Voltage (in V) 415
Subtranscient Reactance (xd'') in % 14
Generator Reactance @ Base MVA 11.20
No. of Generator in Parallel 1.00
Equivalent Reactance 11.20
Short Circuit MVA 8.93
Total Short Circuit Current (in kA) 12.42

Total Short Circuit Current (in KA) for above no.of DG set in 35.98
Parallel
MVA
V
%
Ohm
DG
Ohm
MVA

kA

MVA
V
%
Ohm
DG
Ohm
MVA
kA

kA