Power Supply
R R1
Y Y1
B B1
N N1
1 2 Control Supply
230V-L
Auto Feedback
Trip Feedback
Run Feedback
11
Q11
/1.0 14
3 4
230V-N 11
-F11 R12
/1.3 14
11
R11 21 21 31
/1.2 12 14 R11 R12 C11
/1.9
/1.2 24 /1.3 24 /1.8 34
STOP
1 3 5 12 11
-Q11 IPB12
11 14 /1.5
STOP -X1 1 2 3 4
/1.3
/1.8
EXTERNAL
21
/1.0 /1.3 /1.6 /1.8 /1.8 21
14 11 4 14 14 12 IPB11 C11 PB12 START
/1.5 /1.8 24 START \STOP
X1 2 START
-TB 2
-X2 3 -X3 2
A1 A1 x1 x1 x1 x1 A1 A1
R11 R12 L11 L12 IPB11 IPB12 R13 C11
A2 A2 x2 x2 /1.6 x2 /1.8 x2 A2 A2
-X1 1 2 3
1 2 /1.0
3 4 /1.0
14 1 4 /1.4 1 4 /1.3
5 6 /1.1
12 11 /1.8 11 14 /1.8 11 14 /1.4
21 24 /1.9 21 24 /1.9 11 12 /1.5
11 14 /1.5
21 24 /1.7
External Trip
Trip
Auto/Manual
On Indication
Off Indication
(Green)
(Red)
Mode
31 34 /1.9
Trip Indication
Trip Indication
External
(Amber)
(Amber)
U V W
M
3~
PE Note:
1. Selection of MPCB (Qxx) and Contactor (Cxx) shall be as per Type-2 co-ordination.
2. Control supply MCB (Fxx) selection shall be done as per current requirement of contactor coil.
DOL Scheme with external trip