0 1 2 3 4 5 6 7 8 9

Power Supply
R R1
Y Y1
B B1
N N1
1 2 Control Supply
230V-L

Auto Feedback

Trip Feedback

Run Feedback
11
Q11
/1.0 14
3 4
230V-N 11
-F11 R12
/1.3 14
11
R11 21 21 31
/1.2 12 14 R11 R12 C11
/1.9
/1.2 24 /1.3 24 /1.8 34
STOP
1 3 5 12 11
-Q11 IPB12
11 14 /1.5
STOP -X1 1 2 3 4
/1.3

/1.8

I> I> I>


2 4 6 -X2 1
LPBS Digital Input To PLC Panel
PB11
STOP
1
R13
/1.6 -TB 1
4 -X3 1
1 3 5
-X2 2
C11 X1 1
/1.8 2 4 6 11 12 1 11 11 11 22
1 2
Q12 LPBS PLC
SS2 Q11 R12 R13 C11 C11

EXTERNAL
21
/1.0 /1.3 /1.6 /1.8 /1.8 21
14 11 4 14 14 12 IPB11 C11 PB12 START
/1.5 /1.8 24 START \STOP
X1 2 START
-TB 2
-X2 3 -X3 2
A1 A1 x1 x1 x1 x1 A1 A1
R11 R12 L11 L12 IPB11 IPB12 R13 C11
A2 A2 x2 x2 /1.6 x2 /1.8 x2 A2 A2
-X1 1 2 3
1 2 /1.0
3 4 /1.0
14 1 4 /1.4 1 4 /1.3
5 6 /1.1
12 11 /1.8 11 14 /1.8 11 14 /1.4
21 24 /1.9 21 24 /1.9 11 12 /1.5
11 14 /1.5
21 24 /1.7

External Trip
Trip
Auto/Manual

On Indication

Off Indication
(Green)
(Red)
Mode
31 34 /1.9

Trip Indication

Trip Indication
External
(Amber)

(Amber)
U V W
M
3~
PE Note:
1. Selection of MPCB (Qxx) and Contactor (Cxx) shall be as per Type-2 co-ordination.
2. Control supply MCB (Fxx) selection shall be done as per current requirement of contactor coil.
DOL Scheme with external trip
SFC Environmental Technologies Pvt. Ltd.
21st Floor, The Ambience Court, Hi-tech Busines Park, Plot No. 2, Sector 19D,
Vashi, Navi Mumbai-400705. INDIA.
Page 1 /1