PICTURES KONGSBERG FIELD STATION CHECKLIST

ITEM FIELD STATION TYPE LOCATION Comment


Fuse#4 in WU2 on terminal X21 is lifted- plastic terminal connector hanging in the cabinet needs to replaced
with a terminal secure in rail DIN provided-Wires under U7 need to be routed properly( inside wire way )
1 FS 31 FS-240C-R1 CENTRE BOW THRUSTERFS
1 31 (pictures FS31)

Wires need to be routed properly( inside wire way )-Fuse #2 in WU2 on Terminal X21 is lifted-Fuse #9 in WU6
2 FS45 FS-400C-R1 GEN SPACE ROOM 108 on Terminal X61 is lifted-Fuse #2 in WU5 on Terminal X51 is lifted-(FS45 PICTURES)

Fuse #5,6 in WU6 on Terminal X61 are lifted-Various cables are crossing over modules,they need to be
properly routed in wireway provided,-plastic terminal connector hanging in the cabinet needs to replaced with
3 FS46 FS-400C-R1 GEN SPACE ROOM 108 a terminal secure in rail DIN provided(FS46 Pictures)

Fuse #5 in WU5 on Terminal X51 is lifted-Fuse #3,4,5,6 on Terminal X61 are lifted-Fuse #2 in WU2 on
4 FS47 FS-400C-R1 Drilling DRIVE ROOM Terminal X21 is lifted-Wire tag#w9521 is loose inside the enclosure-(FS47 Picture)

IS THIS CABINET A SPARE ONE ?NO POWER: VARIOUS FUSES LIFTED -LOOSE SPBUS P2
5 FS48 FS-400C-R1 GEN SPACE ROOM 108 CONNECTORS HANGING IN THE ENCLOSURE-(FS48 Pictures)

Fuse#4 on WU2 in X21 lifted-wire on top of U9 need to be routed properly-fuse#4 on WU3 in X31 lifted-plastic
6 FS33 FS-240C-R1 STBD BOW THUSTER 3 terminal connector hanging in the cabinet needs to replaced with a terminal secure in rail DIN provided

7 FS49 FS-400C-R1 GEN EL ROOM 108 OK

Loose connector needs to be secured-plastic terminal connector hanging in the cabinet needs to replaced with a
8 FS50 FS-400C-R1 GEN EL ROOM 108 terminal secure in rail DIN provided-

Loose connector needs to be secured-plastic terminal connector hanging in the cabinet needs to replaced with a
9 FS51 FS-400C-R1 U-DECK ROOM 108 terminal secure in rail DIN provided-

Fuse #1,4 in WU3 on Terminal X31 are lifted-Fuse #4 in WU2 on Terminal X21 is lifted-plastic terminal
connector hanging in the cabinet needs to replaced with a terminal secure in rail DIN provided-Wires above U9
need to be routed properly( inside wire way )-Ground wire under U2 needs to be terminated-loose SPBUS
10 FS32 FS-240C-R1 PORT BOW TH2 terminal need to be secured in wireway-Breaker feeding Q1,Q2,Q3,Q4 is mounted backward.

Various cables are crossing over modules,they need to be properly routed in wireway provided-Fuse #2 in WU2
11 FS41 FS-400C-R1 DRILL SWITCH GEAR ROOM on Terminal X21 is lifted

Fuse#2 in WU2 on Terminal X21 is lifted-fuses1,2,3,4,5,6 on WU6 in X61 lifted,SPBUS connectors are hanging
12 FS43 FS-400C-R1 ECR inside the cabinet

13 FS44 FS-400C-R1 ECR Fuse#2 in WU2 on Terminal X21 is lifted-Wires need to be routed properly( inside wire way )

14 FS37 FS-400C-R1 MAIN SWITCH ROOM PORT Fuse#2 in WU2 on Terminal X21 is lifted-Wires need to be routed properly( inside wire way )

15 FS38 FS-400C-R1 MAIN SWITCH ROOM PORT Wires need to be routed properly( inside wire way )-
Fuse#2 in WU2 on Terminal X21 is lifted-fuses2,3,4,5,6 on WU6 in X61 lifted,Wires need to be routed
16 FS39 FS-400C-R1 MAIN SWITCH ROOM CENTER properly( inside wire way )

Fuse#2 in WU2 on Terminal X21 is lifted-fuses1,2,3,4,5,6 on WU6 in X61 lifted,SPBUS connectors are hanging
17 FS40 FS-400C-R1 MAIN SWITCH ROOM CENTER inside the cabinet

18 PDU MAIN SWITCH ROOM STBD Proper labelling needs to be made

19 FS42 FS-400C-R1 MAIN SWITCH ROOM STBD Fuse#2 in WU2 on Terminal X21 is lifted-

plastic terminal connector hanging in the cabinet needs to replaced with a terminal secure in rail DIN
20 FS34 FS-240C-R1 PORT STERN TH4 provided-C0nnectors need to be secured

plastic terminal connector hanging in the cabinet needs to replaced with a terminal secure in rail DIN
21 FS36 FS-240C-R1 PORT STERN TH6 provided-

22 NDU A2 ROOM 108 U-DECK Enclosure needs to be clean

23 NDU A3 MAIN SWITCH ROOM PORT ok

24 DPC-1 ECR ROOM Connector hanging inside enclosure,enclosure needs to be clean

plastic terminal connector hanging in the cabinet needs to replaced with a terminal secure in rail DIN
25 FS35 FS-400C-R1 STBD STERN THRUSTER provided-Wires need to be routed properly( inside wire way )

26 AFT SPBUS BOOST CABINET EMERG. DIESEL ROOM 108 UPPER DOOR has lock broken-WIRE IN THE CABINET NEED TO BE ROUTED PROPERLY

27 STBD SPBUS BOOST CABINET EMERG. DIESEL ROOM 108 WIRE IN THE CABINET NEED TO BE ROUTED PROPERLY

28 PDU PDU01A ROOM 108 U-DECK BREAKERS NEED PROPER LABELS

29 ISOLATION BOX ECR ROOM OK