You are on page 1of 4

Specifically improved durability of reinforced concrete structures

Specifically improved durability of come into use if the consultant or


reinforced concrete structures. architect expressly demands their use
for the purpose of securing the con-
by Dipl.-Ing. Rainer Böllinghaus, crete cover. For a long time, even in
managing director at Gebr. Seifert Europe, exactly defining the type of
GmbH, Europe's leading manufactu- spacer to be used was neglected, by
rer of rebar spacers. comparison to other products such as,
for instance, reinforcement, anchor
This article describes in detail efforts channels and fixing or lifting inserts.
in Europe, in particular in Germany
to optimise and standardise use of For a number of years, within the
rebar spacers with regard to increa- Spacer Project Group, whose mem-
sing the durability of reinforced con- bers consist of Germany's leading
crete components. construction associations, manufactu-
rers of prefabricated concrete compo-
Introduction nents, universities, manufacturers and
construction companies with renow-
It has long been recognised in Ingress of moisture to the reinforce- ned names such as Hochtief, Philip
Western Europe that the thickness and ment incurs corrosion which creates Holzmann, Dyckerhoff & Widmann,
surface cracking along the line of rein- Strabag Hoch- und Ingenieurbau,
sealing capability of the concrete forcement.
cover over the steel reinforcement has Europe's leading manufacturer of spa-
a deciding influence on the durability When the first industrially manufac- cers - Seifert, the University of Essen,
as well as on the level of fire protec- tured spacers were introduced, it see- the German Specialist Association for
tion of buildings constructed using med that a firm seating of the spacer Prefabricated Concrete Units, the
reinforced concrete or prestressed and the stress loading capability in a Institute for Steel Reinforcement and
concrete. In order to ensure the neces- horizontal or vertical direction as a many more have been occupied with
sary thickness of the concrete cover, result of formwork and reinforcement standardising spacers with regard to
spacers are required which are placed pressure were the most important cri- requirements, description, recom-
between the formwork and reinfor- teria for selection. This was initially mendation, inspection and quality
cing steel. more important than spacers of a con- control. Standardisation is in particu-
structionally superior design which lar intended to assist planners of sup-
The required concrete cover depends were thus more suited to the relevant porting frameworks whose responsi-
on the one hand on the diameter of the area of use. bility it is to select suitable spacers
reinforcing steel, on the other hand on with regard to performance class and,
direct influences from the surroun- Over the years, manufacturers such as if necessary, special requirements.
ding area of the reinforced concrete. Seifert have, after various testing, Also the manager at the building site,
In this respect it is of significance proved that an optimum product whose task it is to order and use the
whether a concrete part is, for design can prevent or reduce a host of spacers, as well as the consultant who
instance, on the inside of a building corrosive developments to a negli- has to check the installation of the
or on the outside, if this part of the gible level such as, for instance, car- spacers according to requirement by
construction is subject to periodic bonation (figure 1) or surrounding way of approval of the reinforcement.
damp penetration or if aggressive damp penetration through and along
chemicals come into contact with the the spacer. In contrast to an interna- DIN 1045 or the information sheet of
concrete. tional trend towards spacer construc- the German Concrete Association
tion becoming thinner, weaker and "Concrete Covering and Reinforce-
In order to at least partly fulfil a cor- simpler, Seifert in particular has put ment" already stipulates installing
rosion protection requirement, at the great emphasis on technical details reinforcement using a predefined
stage where this was initially recogni- right from the beginning. nominal measurement or installation
sed, wooden or concrete blocks were measurement of the concrete cover, in
made at the building site in order to such a way that the concrete cover in
ensure a distance, obviously adequate the finished building component is
but not yet exactly defined, between maintained with adequate safety. This
the reinforcement and the subsequent of course requires spacers which
concrete surface. Within a relatively ensure maintaining the concrete cover
short time however, it was understood before and during concrete work and
that the exact definition of the concre- which after completion do not impair
te cover in particular depends on the the usability and durability of the
Figure 1 Spacer with carbonation brake
reinforcement and the surroundings, building component.
and that the form and type of spacers In spite of the relative cheapness of
used are of significant importance in using spacers, they are still neglected
respect to the durability of reinforced in some countries, or merely thin pla-
concrete structures. stic wheels or unstable plastic chairs
For this reason, for every precisely In the process of almost 100 years point-type, line-shaped, or flat-sha-
defined instance of application, suita- development work, Seifert Research ped. Supports are installation compo-
ble spacers are to be installed in such has developed the largest spacer line nents which secure the top reinforce-
a way that they do not move or rotate world-wide for horizontal, vertical, ment in position, e.g. supporting
and so that they accept the forces top and bottom reinforcement as well cages, line-shaped or curved lattices,
acting on them during construction as for formwork (figure 3). This tried lattice supports or individual hystools
work in their designated position at all and tested line of spacers and special (figure 4). Supports for the top rein-
temperatures and with negligible products allows installation in all forcement can either stand on the
deformation. The spacers available on areas of use in insitu-cast and precast formwork or are stood into the bottom
the market generally consist of cement applications, taking individual condi- reinforcement. Position securing devi-
mortar, possibly reinforced with fib- tions into consideration such as envi- ces are installation components which
res, plastic (usually polyethylene) or ronmental influences, chemical secure the distance between the two
mortar set in reaction resin (figure 2). aggression, temperature deviations reinforcement layers in concrete walls
etc. and the respective technical requi- or individual reinforcement positions,
rements during construction. e.g. stirrup bolts, S-shaped hooks.

Terminology

The concrete cover is the concrete


Figure 2 Common concrete and plastic layer between a reinforcing bar and
spacers available on the market
the concrete surface. The minimum
Although spacers are unavoidable measurement of the concrete cover
inhomogenous units in concrete, they (minc) is the minimum sufficiently
must not significantly impair the sea- safe distance between the concrete
Figure 4 Supports for top reinforcement
ling qualities of the concrete cover in surface and the rebar. The nominal
the finished building component. The measurement of the concrete cover
Spacer requirements
widely held assumption that use of (nomc) is the sum of the minimum
concrete spacers leads to a kind of measurement and a lead measurement
Spacers vary in design, size, material,
"fusion" with the surrounding concre- (nomc = minc + ∆c).
types of application and in their cha-
te is a fallacy, as many tests have pro-
The lead measurement of the concrete racteristics when inside and outside
ved. Concrete spacers, as well as pla-
cover ∆c is intended to cover unavoi- concrete. Table 1 is a classification list
stic spacers, remain an inhomogenous
dable deviations in measurement due of spacers according to the type of
unit, whereas plastic spacers, due to
to bending and installing the reinfor- contact area.
their constructional design, give better
anchorage in concrete. Equally, com- cement, the type of spacers and instal-
plex testing has disproved the second ling them, production of the form- To begin with, one must differentiate
fallacy, namely that plastic spacers are work as well as placing and compac- between spot supporting single spa-
negatively acting foreign bodies. ting the concrete. The lead measure- cers and large-area supporting spacers
ment ∆c does not contain the unavoi- (figure 5).
The load-bearing capacity of spacers dable measuring errors during non-
depends on the material characteri- destructive verification measurement
stics and on the shape of the spacer as of the finished concrete component.
well as on the temperature at the res-
pective load. Material specific charac- The placing measurement nomcv of
teristics of concrete spacers are, for the reinforcement is the "spacer mea- Fig. 5 Point-type and area-type spacers
instance, that no deformation takes surement" of the concrete cover. It is
place under load, but that sudden bre- deduced from the nominal measure- With single spacers, generally at least
akage may occur. Furthermore, con- ments nomcl of the vertical bars and 4 spacers are used per m2. If the spa-
crete spacers have a tendency to beco- nomcq of the horizontal bars (stirrups). cers carry a heavy load or if in the
me porous, in particular at temperatu- It is usually the setpoint distance bet- case of thin reinforcement danger
res below freezing point, and to being ween the outer reinforcement bars and exists that the reinforcement may for
highly hygroscopic. Plastic spacers on concrete surface. The thickness or instance be trodden down between the
the other hand have a reduced tenden- height of the spacers is measured spacers, then more spacers must be
cy towards breakage, tend to not be used accordingly. In the case of area-
according to this setpoint distance. In
hygroscopic, but do tend towards type spacers or of line-shaped spacers
order to be able to differentiate from
deformation under load, in particular the distances between the spacers for
the required nominal measurements
at higher temperatures.
(setpoint measurements) the selected medium rebar diameter thicknesses
placing measurement (actual measu- should not exceed 70 cm. For bar dia-
rement) is described as nomcv. meters up to 6 mm Ø, a distance of 50
cm between the spacers should not be
Spacers are installation components exceeded.
which secure the required placing
measurement of the concrete cover
between the outer reinforcement bars
and the formwork. Spacers can be
Figure 3 Excerpt from the Seifert line
Table 1 mixed concrete usage (e.g. for reinfor-
Classification list of spacers cements carrying human loads; spa-
cers bearing a load when the form-
A C2 work is tensioned; for outside loads
which are temporarily stored on the
placed reinforcement etc.)

Standard requirements with regard to


B1 D1 inspection loads and permissible
deformation are described in detail in
Table 2 on the next page.

B2 D2

A Wheel-shaped C1 Line-shaped, not f.


C1 B1 Spot-support, C2 Line-shaped, f.
not fastened D1 Area-type, not f.
B2 Spot-supporting, D2 Area-type, fastened
fastened Figure 6 Testing of plastic spacers

If spacers are used in reinforced con-


To secure the concrete cover with building component, melting has no crete components which in a state of
regard to thickness and sealing capa- significant impact on the fire-resi- damp penetration are frequently sub-
bility, the spacers must have a suffi- stance capability of the building com- jected to temperature variations above
cient load-bearing capability and tilt ponent. and below freezing point with or with-
resistance depending on the respective out salt, then the spacers embedded in
load pressure and temperature effect, Performance classification the concrete must additionally be of a
if necessary, must be able to be ade- higher frost-resistance level. The resi-
quately fastened to the reinforcement The loads to which a spacer is subjec- stance capability counts as being ful-
bar and must have a minimum spring ted in practice may vary greatly accor- filled if, after due inspection no cracks
backlash so that after striking form- ding to the type of use. Thus, on brid- appear and only negligible chipping
work, the concrete layer next to the ge constructions with very heavy rein- has occurred.
surface is not pressed off. forcement and high concrete covers,
for instance, loads of 100 kg and more If spacers are installed in water-resi-
Furthermore, they should be formed per spacer are taken into account, stant reinforced concrete components
in such a way that they can only be whereas when reinforcing inside or in components which are intended
used for one placing measurement cv walls constructed when building to offer a high resistance to chemical
and so that the concrete completely apartments for instance, loads of only aggression, then the spacer must addi-
surrounds the spacer and does not 5 - 10 kg per spacer occur. On vertical tionally itself offer a high resistance to
segregate as a result of the spacer. The areas, the load capability depends on chemical aggression. Water penetrati-
following are of utmost importance: the type of formwork and reinforce- on of the spacer in the concrete may,
sufficient resistance to the alkaline ment. With columns, side areas of cei- according to the DBV (German Con-
content of the concrete, as well as the ling joists and stiffly braced walls it is crete Association) information sheet,
requirement that the spacer be made necessary to take into consideration not exceed the maximum permissible
of a material which itself is not corro- that the reinforcement cage, when the value as stated in DIN 1045.
sive and which does not cause further formwork is tensioned, puts a sub-
corrosion to the reinforcement and stantial load on individual spacers. In If spacers are used in reinforced con-
which damages neither freshly wor- such cases, with spacers for vertical crete components which are exposed
ked nor hardened concrete. The Insti- reinforcement, high loads are taken to higher temperature (e.g. outside
tute for Construction Technology in into account similar to those for hori- building components, containers in
Berlin verifies the unreserved accep- zontal reinforcement. industrial building concrete and fair-
tability of plastic spacers: "There are faced concrete), the DBV information
no reservations regarding the use of Minimum requirements are defined in sheet states that for the following
plastic spacers in concrete, reinforced two performance classes. alternating temperature loads, no
concrete and prestressed concrete in cracking and chipping in the area of
respect to fire protection, as long the No increased requirements exist for the spacer embedded in the concrete
plastic in question is not polyvinyl performance class L1 with regard to may occur. Tests have shown that
chloride.". load-bearing capability and tilt resi- microscopic cracks as a result of dif-
stance, e.g. for use in cases where the ferent temperature expansion rates in
In case of fire the following applies: in reinforcement is not subject to traffic plastic and concrete have no negative
the case of higher temperatures (e.g. a load. In contrast, for performance influence on the durability of buil-
fire) a plastic spacer may melt. As the class L2 increased demands are made dings. A mathematical example shows
thickness of the spacer is usually on load bearing capability and tilt that for a plastic spacer with an assu-
small in relation to the thickness of the resistance; standard spacers for site- med contact width of 1 cm only a very
minor change in volume results, even work against soft layers (e.g. insula- Summary
when the temperature varies in the ting boards), spacers with a larger The decisive criteria for selecting spa-
order of 50° C. Thus, in the case of contact area must be used (figure 9). cers should always be: fulfilment of
this temperature variation the said pla- the function "Guarantee of the requi-
stic spacer expands by only 0.035 mm red distance between formwork and
to 0.065 mm. The concrete cannot be reinforcement for ensuring the neces-
damaged by such diminutive expansi- sary concrete cover". If e.g. the load
on measurements as it is known that bearing capability of the individual
cracks in concrete below 0.25 mm in spacer is not sufficient, then either
width have no damaging effect. another spacer with a larger load bea-
Fig. 9 Spacer with larger contact area
ring capability should be selected or
If spacers are used in reinforced con- When reinforcing in vertical building the number of spacers per area should
crete which is intended as "designed components, spacers should be selec- be correspondingly increased in order
concrete" (fair-faced concrete), then ted so that after placing the fresh con- to distribute the load. A spacer which
the contact area on the formwork must crete beneath the spacers no damaging has to accept a high load necessarily
be as small as possible (figure 7) and voids occur. When arranging long requires a large contact area on the
the spacer may only be slightly pres- line-shaped spacers in the area of a formwork. The spacer will later on be
sed into the formwork. Furthermore, tension zone, cracks in the concrete, more or less visible in the concrete.
the spacer may only make a slight in particular in the area of the spacers, This fact has consequences in fair-
impression on the concrete surface. must be taken into account. For this faced concrete and must be taken into
reason, short line-shaped spacers consideration at the planning stage. A
should be used, with sufficient stagge- firm seating of the spacer is also of
ring to each other. Line-shaped spa- great importance. Even the most stable
cers in the pressure zone of building spacer cannot fulfil its function if it
components subject to flexing may changes its position when the concrete
only be installed parallel to the direc- is being poured. The ideal spacer for all
tion of tension, in the case of vertical areas of use under all conditions does
installation the usable height decrea- not yet exist. Selection of a spacer can
ses and an indenting effect with nega- therefore generally only be a compro-
Fig. 7 Praxifix spacer (pointed legs) tive concentration in tension additio- mise which takes the individual condi-
nally results. tions at hand into consideration.
Recommendations for selecting
spacers Table 2 Special thanks to Seifert Germany for
Standard requirements providing photos and test results.
As a rule, cement mortar spacers are,
Standard requirements with
with regard to stability of form, less
regard to inspection load Performance class L1 Performance class L2
sensitive to load and temperature and permissible deformation
variations than plastic spacers. They
Inspection loads
should be preferred for building com- - static short-time test 250 N1 1.000 N1
ponents with very high static and ther- - tilt resistance – 500 N
mal loads and in the case of high con- - creep test – 350 N2 / 175 N3
straining loads from the formwork Permissible deformation
(e.g. tunnel formwork). - nom cv ≤ 20 mm 1 mm 1 mm
- nom cv ≤ 20 mm 2 mm 2 mm
Firmly clipped spacers or single spa- 1
In the case of stiffly formed spacers, e.g. concrete spacers, the mean value of the measured bearing load must be doubled.
cers fastened with wire should always 2
Spot-supporting spacer
3
Line-shaped spacer
be fastened at the intersection of the
reinforcement (figure 8), as they can Table 3 contains recommendations according to building components and spacer type groups.
easily rotate when fixed to normal Ceilings, foundations,
Building component Supports Walls Beams floor slabs
reinforcement bars. Spacers which are
not fixed can move out of position Formwork vertical vertical horiz./vert. horizontal
when the formwork is cleaned and Reinforcement horizontal horiz./vert. horiz./vert. horizontal
thus become ineffective. Spacer type groups
A Wheels K1) K1) L L L L
B1 spot-supporting
not fastened
(block, trestle)
L L L K L K
spot-supporting (block, trestle)
B2 fastened J2) J2) J
) 2)
J J2) J
C1 line-shaped, not fastened L L L J L J
Figure 8 Spacer clipped on at C2 line-shaped, fastened J J K J K J
crosspoint of the reinforcement D1 area-supporting, not fastened L L L J L J
Spacers must be formed and fastened D2 area-supporting, fastened J J K J K J
in such a way that the placing measu- J recommended, K partially suitable, L unsuitable
rement is also maintained in the case
1) Caution, frequently insufficient tilt resistance when tensioning the formwork
of sectional weakening (e.g. by trape- 2) If tilting or pushing is not feasible
zium rails). In the case of concrete 3) With max. length (350 mm or < 2d or <1/4 x building component width)

You might also like