You are on page 1of 9

4.

11 Temperature Switches and Alarm Alarm Damper or


Valve

Thermostats TSH

TS TC
TT
B. G. LIPTÁK (1982, 1995) L. W. MOORE, B. ADLER (2003)

Flow Sheet Symbol

Types: A. Electronic Switches


A1. Input From Transmitter
A2. Input From Sensor in the Field
B. Electromechanical Switches
C. Thermostats
C1. Electrical/Electronic
C2. Pneumatic

Range: A1: Depends on sensor/transmitter range


A2: Depends on sensor, from −328 to 4172°F (−200 to 2300°C)
B: From 0 to 75°F (−8 to 24°C) up to 50 to 650°F (10 to 343°C) spans are standard;
the maximum range is from −50 to 1100°F (−46 to 593°C)
C: Room thermostat set points are adjustable from 45 to 85°F (7 to 29°C) for heating
and from 55 to 105°F (13 to 40°C) for cooling services

Cost: A: $150 to $600


B: Bimetallic spring elements cost only a few dollars; general purpose temperature
switches are $150; industrial-quality, indicating, explosion-proof temperature
switches with thermowells cost $300 to $500
C: Conventional room thermostats cost from $50 to about $100; programmable
microprocessor-based energy-saver thermostats cost $200 to $400

Inaccuracy: B: 0.5 to 2% of span


C: Traditional thermostats are usually uncalibrated and their set point error can vary
from 0.5 to 3% and is not guaranteed. The microprocessor-based programmable
thermostats are repeatable within 1°F (0.6°C).

Repeatability of Actuation: A: 0.5% of span for analog, 0.05% for digital

Partial List of Suppliers: Acromag (A1, A2) (www.acromag.com)


Allen-Bradley (B) (www.ab.com)
Ametek Drexelbrook (B) (www.drexelbrook.com)
API (A1, A2) (www.api-usa.com)
Applications Engineering Ltd. (B) (www.appeng.co.uk)
ASCO (B) (www.ascovalve.com)
Ashcroft (B) (www.dresserinstruments.com)
Barksdale/Crane (B) (www.barksdale.com)
Custom Control Sensors (B) (www.ccsduslsnap.com)
Dallas Semiconductor/Maxim (B) (www.para.maxim-ic.com)
Dresser Instruments (B) (www.dresserinstruments.com)
Eurotherm/Action Instruments/Invensys (A1, A2) (www.actionio.com)
Eurotherm/Barber Coleman (A1, A2, C) (www.eurotherm.com)
Fluid Components (B) (www.fluidcomponents.com)
Foxboro Co. (A1) (www.foxboro.com)
Hi-Stat Div. Stoneridge (B) (www.histat.com/histat/temp-sw.htm)
Honeywell (B) (www.thermalswitch.com)
Honeywell (C) (www.content.honeywell.com/yourhome/ptc-thermostats/thermostat.ht)

657
© 2003 by Béla Lipták
658 Temperature Measurement

Honeywell Sensing and Control (A1, A2) (www.honeywell.com/sensing)


Jumo (B) (www.jumoprocesscontrol.com)
Kobold (B) (www.coboldusa.com)
Mercoid/Dwyer (B) (www.dwyer-inst.com)
Moore Industries-International, Inc. (A1, A2) (www.miinet.com)
Neo-Dyn (B) (www.neodyn.com)
Omega Engineering (A1, A2, B) (www.omega.com)
Powers Controls (B, C) (www.powerscontrols.com)
Robertshaw/Invensys (C) (www.robertshaw.com/cli-fam-robTherm.html)
Rochester/Ametek (A1, A2) (www.rochester.com)
Rosemount Inc. Div. of Emerson (A1) (www.rosemount.com)
SOR (B) (www.sorinc.com/productsTemp.stm)
Staefa/Siemens Building Automation (C) (www.sbt.siemens.com/hvp/Components/
catalog/thermostats.asp)
Therm-O-Disc/Emerson (B) (www.thermodisc.com)
Thermo Electric (B) (www.thermo-electric-direct.com)
United Electric (B) (www.ueonline.com)
White Rogers (C) (www.whiterogers.com)

INTRODUCTION rising (high) or falling (low) temperature. The set point is the
temperature that actuates the switch to open or close an
The terms thermostat and temperature switch are somewhat electric circuit. The set point accuracy defines the band within
interchangeable. Temperature switches are on-off devices, which repetitive actuations will occur. Differential or dead
while thermostats are narrow (frequently fixed) proportional band is the difference between the set point and reactuation
band controllers. Their common characteristic is that mea- point. For example, if a high temperature switch is set to
surement, set point, and control functions are all combined actuate (close) at 100°F (38°C) on rising temperature, it will
into a single instrument. close at that point. When the temperature drops, it will not
A thermostat is a device that controls the temperature in open again until the temperature has fallen to 95°F (35°C).
an enclosed space and can be electrical/electronic or pneu- In this case, the differential is 5°F (2.8°C). Tolerance is the
matic. It functions either as a proportional-only controller or repeatable accuracy of the reactuation point.
as an on-off switch with a dead-band. Temperature switches utilize a wide variety of technolo-
Figure 4.11a illustrates some of the terminology used in gies depending on their applications in commercial products,
connection with temperature switches. The temperature range industrial equipment, process control, and even aerospace.
within which the actuation point can be set is referred to as They also vary in sophistication from simple snap disc mod-
adjustable range. The switch may actuate at its set point on els typically used in coffee makers up through very sophis-
ticated models. An alternate name for them is limit alarms.
They can accept temperature sensor inputs from thermocou-
ples (TCs) or resistance temperature detectors (RTDs) and
High Temperature Switch Low Temperature Switch
(Detects Temperature Rise) (Detects Temperature Decrease) provide multiple alarms at different settings or serve both
Accuracy Tolerance alarm and equipment shutdown functions. This section will
Reactivation
discuss both industrial and commercial switches as well as
Set Point Point personal comfort (heating, ventilation, and air conditioning
[HVAC]) thermostats.

ELECTRONIC TEMPERATURE SWITCHES


Adjustable
Differential Range Differential There are two types of electronic temperature switches (some
suppliers also call them limit alarms), which are differenti-
ated by the source of their input signals. If the temperature
of interest is detected by a temperature transmitter, the high
or low temperature switch detects a transmitter output signal
Reactivation Set Point
Point
of 4–20 mA or 1–5 V DC. If a transmitter is not available,
Accuracy
a local process temperature sensor is connected directly to
Tolerance
the electronic high or low temperature switch (limit alarm),
FIG. 4.11a which is preferably mounted near the sensing point. Both
Temperature switch terminology. types will be discussed.

© 2003 by Béla Lipták


4.11 Temperature Switches and Thermostats 659

Input from Transmitter

Temperature transmitters with 4–20 mA output signals are


often connected to a programmable logic controller or dis-
tributed control system for monitoring, alarming, and control.
However, there are often requirements to have a backup
device for monitoring the same signal for redundant alarming
and emergency equipment shutdown. It makes economical
sense to locate this device near the equipment being moni-
tored so that shutdown commands need not be wired all the
way from the control room.
This type of temperature switch uses an analog circuitry
and typically has either one or two trip points that are screw-
driver adjusted and provide relay outputs. These analog
switches require a signal source and a continuity-measuring
device to set the trip points. Such an analog temperature
switch is shown in Figure 4.11b. Indicating models are also
available, which indicate both the detected temperature and FIG. 4.11c
the set point for switch actuation. Trip point repeatability as Configurable and indicating digital electronic switch operating off
a percent of input span varies from 0.5 to 0.05% of span, as the output signal of a transmitter. (Courtesy of Moore Industries-
a function of whether the device is an inexpensive analog International, Inc.)
model or a more accurate digital one. Some models are also
provided with an adjustable dead band, which is a range,
through which the input can change without causing a state Input Directly from Sensor
change in the switch position.
High-end digital temperature switches are field-configurable These direct connected temperature switches also range from
for trip point, dead band, time delay, and latching options less sophisticated analog designs to the more sophisticated
(Figure 4.11c). Others also incorporate an indicating display, field-configurable digital models. For the analog switches,
which is scalable in various engineering units, or provide the type of sensor input must be specified while the digital
excitation power for the temperature transmitter and retrans- models can be field-configured for a variety of sensors. This
mits the received input signal as an isolated 4–20 mA output includes eight types of TCs and a number of RTDs, including
signal. These temperature switches are available with 1 to 4 two-, three-, or four-wire circuitry and platinum, nickel, or
relays. copper elements.
These switches also accept direct resistance input or mil-
livolt signals. A valuable feature of these sensor input devices
is their ability to perform sensor diagnostics. One model pro-
vides a relay output in the event of a sensor failure while
inhibiting the other alarm/shutdown outputs. The benefit is
that a nuisance shutdown of a piece of machinery or a process
may be avoided and yet the user knows that a sensor must
be replaced to maintain monitoring.
If the same temperature, which is detected by the tem-
perature switch, is also needed for control, recording or other
reasons, some of these direct-connected devices are able to
also act as transmitters and output a 4–20 mA signal (Figure
4.11d). This way, in addition to the temperature switch, the
functions of indication and transmission are also provided by
the same unit.

Installation Considerations

In The Control Room If a temperature transmitter output is


already being sent to the control room, it is logical to also
FIG. 4.11b mount the temperature switch there. For direct sensor input,
Analog electronic switch operating off the output signal of a trans- better performance is obtained by installing the instrument
mitter. (Courtesy of Moore Industries-International, Inc.) close to the sensor, in order to reduce the effects of electrical

© 2003 by Béla Lipták


660 Temperature Measurement

dates that there be no open contacts, and alarm devices must


have hermetically sealed relays or use solid-state switching
to meet this requirement.
Because temperature switches are often installed to pro-
tect critical processes, a false or nuisance trip can be very
costly. Frequently the cause of these nuisance trips is RFI
generated by walkie-talkies, which are used in most plant
locations. Therefore, it is important to specify that the switch
must include RFI immunity. (Immunity to 10 V/m according
to the SAMA specification 33.1 is considered acceptable.)

Availability and Reliability

Often, a temperature switch will have the critical role of


guaranteeing a safe shutdown. Safety Instrumented Systems
standards (including ANSI/ISA 84.01, IEC 61508, and IEC
FIG. 4.11d 61511) provide guidance and thereby assure the availability
Direct connected configurable electronic temperature switch with and reliability of the devices that are used in safety related
display and retransmission capability. (Courtesy of Moore Industries- applications.
International, Inc.)
Availability means that the device will be able to perform
the assigned task when it is called upon to do so. For example,
noise (electromagnetic interference and radio frequency the probability that an alarm switch or limit device will sense
interference [RFI]) and the errors introduced by extension a dangerously high temperature and will trip an emergency
cables. shutdown valve when the tripping occurs is referred to as its
For the installation of high temperature switches, the Probability of Failure On Demand.
recommended practice is to connect them in parallel with the Reliability refers to the likelihood of the device suffering
rest of the control system, recorder, or logger. Most input a nuisance failure and thereby causing a false trip. This factor
circuits to these devices use a 250-Ω input resistor that con- is referred to as its Mean Time To Fail spurious. These stan-
verts the 4–20 mA signal into a 1–5 V DC signal. By con- dards contain equations for the calculation of the reliability
necting the alarm trip in parallel, it can then monitor this of the complete loop. These calculations are performed by
same 1–5 V DC signal and either device can be removed inserting numerical values for the availability and reliability
from service without affecting the operation of the other. of each device in a loop. Only a few suppliers can provide
While most models can be surface mounted, the (DIN) the data required to calculate the reliability of such loops.
rail mounting style is the most effective, because the elec- When a third party tests and evaluates an instrument, it pub-
tronic switch units simply clip on a standard DIN rail elim- lishes a report known as a Failure Modes Effects, Diagnostic
inating the need for drilling and tapping screw holes. Analysis. That report contains all the required data for the
calculations in the standards. Documented reliability does
Field Mounting Local mounting is recommended for all not have to increase costs, because higher reliability often
direct connected temperature switches in order to minimize results in reduced maintenance costs.
the signal degradation caused by the long wiring runs back to
a control room. When a high temperature switch also initiates
equipment shutdown, wiring costs can be reduced by installing ELECTROMECHANICAL TEMPERATURE SWITCHES
the alarm/shutdown switch near the protected equipment.
When installing any electrical or electronic equipment in Temperature switches are used to energize and deenergize
the field, the instrument enclosures must meet both environ- electric circuits as a function of the relationship between the
mental and safety concerns. If explosive vapors or dust are process, temperature, and a predetermined set point. The set
present continuously in the area, the enclosure must be a point error on the best electro-mechanical switches is about
Class 1, Division 1 explosion proof enclosure, which would ± 0.5% of span, but that error can rise substantially as the
be needed to meet Class 1, Division 1 requirements of agen- switch cost and quality drops. The sensing elements are
cies like (FM) and (CSA). mostly the elastic types including filled and bimetallic ele-
If these vapors or dusts are only present under abnormal ments. The electric switching assemblies are either snap-
conditions, the enclosures must meet the much less rigorous acting mechanical micro-switches or mercury switches. The
requirements of Class 1, Division 2. Note that both the instru- latter contain no mechanical moving parts and must be mounted
ment and the enclosure enter into the consideration. Often a on a vibration-free level surface.
Division 2 enclosure can also meet (NEMA) 4X requirements Many applications from furnace protection to local fan
for watertight and corrosion resistance. Division 2 also man- controls may not require sophisticated electronic temperature

© 2003 by Béla Lipták


4.11 Temperature Switches and Thermostats 661

switches, and in such applications bimetallic or filled bulb switches inside them may require certification to meet haz-
type switches are used. The lower cost versions are provided ardous area classifications from certification agencies such
only with factory set fixed set points and fixed differentials, as FM, CSA, or Underwriters’ Laboratories.
while the more expensive ones can be indicating and have In some designs, the control mechanism is an integral part
adjustable differentials and calibrated, externally adjustable of the explosion-proof case, while in others it can be removed
set points and setting scales. in the field for maintenance. As noted earlier, the set point
should be externally adjustable so that the explosion-proof
Features Required for Industrial Applications case does not need to be opened in order to change the set
point. For added convenience of the operator, some switches
Temperature switch elements should be selected with service also provide continuous process temperature indication.
life and maximum operating temperature in mind. Most elas- Another optional feature is push-button reset, which must be
tic elements will have a service life of close to a million manually operated before the circuit will be restored to its
cycles if the cycle time is not less than 5 s. The service life original state after an automatic operation. This manual reset
is related to the amount of current required to switch and the encourages the operator to verify the safety of the system
frequency of switching. By increasing the dead-band, the before restarting.
frequency of switching is reduced and the life of the switch
increases. Similarly, increasing the margin between the switch
rating and the actual current flow handled will also increase THERMOSTATS
switch life. For example, a device that is switching 4 A should
have a 10-A and not a 5-A rating. Conventional thermostats are usually uncalibrated devices
Selection of the adjustable range for a specific installation and their manufacturers usually do not guarantee their accu-
should consider both the set point actuation accuracy and the racy. This is a limitation, because it is possible to have some
life factor. For greatest accuracy, the set point should fall in thermostats with as much as 5 to 10°F (3 to 6°C) error in
the upper half of the range, but for longest service life it their measurement. In the last decades a new generation of
should be in the lower half. The usually acceptable compro- thermostats has been introduced that guarantee to limit their
mise is to locate the set point in the middle third of the range. error to 1°F (0.6°C) or less.
It is desirable to have an external calibrated knob pro-
vided on the temperature switch for set point adjustment. Electromechanical Designs
Uncalibrated or internal set point adjustments are generally
undesirable on industrial installations. The fixed differential There is little difference between a two-position thermostat
temperature switches are furnished with a single adjustment and a temperature switch. The temperature-sensing elements
for set point. These units are factory-set with differentials in the thermostats shown in Figure 4.11e are bimetallic
that range from 0.5 to 1% of span. On double-adjustment- springs. In the design shown on the left, the gap between
type designs, both set points and reactuation points can be contacts is almost zero and the movement of the bimetallic
independently adjusted. The maximum differential in such element directly opens and closes the load contact. In the
designs is the range of the switch, while the minimum varies design shown in the center a positive gap is provided, serving
between 2 and 8% of span. Temperature switches with dual to reduce wear on control equipment. The gap is produced by
control are also available. Here, two independent switches toggle action and is adjustable by adjusting the spring tension.
mounted in the same housing are responding to the same In slow processes with long cycle periods, such as in
process temperature in opening or closing two independent domestic thermostats, anticipation is provided through the
circuits. use of a negative gap (right of Figure 4.11e). In this thermo-
stat, when the heater in a room is turned on, a small internal
heater within the thermostat is also actuated. This causes the
Safety Considerations bimetallic spring to turn off the room heater before the room
The electrical rating of temperature switches at a 115 V oper- temperature reaches the temperature inside the thermostat.
ating level varies from 0.3 to 10 A on AC or DC circuits.
Generally, the dual control and the fixed differential switches
have lower ratings, and the double-adjustment-type units have
higher ratings. The available circuit arrangements are very
flexible. Some of the standard arrangements include single- +G
pole–single-throw, single-pole–double-throw, and double-
−G
pole–double-throw designs, but units are available with up to
four poles. Positive Gap
Zero Gap Negative Gap
There are basically three standard case designs: general
purpose (NEMA 1), weather-resistant (NEMA 2 and 3), and FIG. 4.11e
explosion-proof (NEMA 7) cases. These enclosures and the Design variations of two-position electromechanical thermostats.

© 2003 by Béla Lipták


662 Temperature Measurement

Setpoint Scale This Thermostat Is Called a Fixed


Sets the Normal Value Proportional Band Design Because the
Distances A and B Are Fixed. A Standard
Manual Setpoint Response Is to Give a 2.5 PSIG (17kPa)
Adjustment °F 50 60 70 80 °F Change in Output Signal for Each °F
°C 10 15 20 25 °C Change in Measurement.
0.01" (0.25 mm)
Diameter
Restriction
A B
INCR.

20 PSIG (140 kPa)


As the Temperature Rises the Bimetallic
Air Supply
Element Moves to the Right, Increasing
the Back Pressure on the Nozzle and
Thereby Raising the Thermostat Output
Low Volume
Signal (this Is called Direct Action).
(1 SCFH or
0.028 m3/hr)
Output
Bimetallic Signal to
Element Flapper 0.015" (0.375 mm) Dampers or
Diameter Nozzle to Control
Valves

FIG. 4.11f
Direct-acting pneumatic-bimetallic thermostat with manual set point and fixed proportional band. This is a low-volume design since output
air flow is limited because there are no relays.

Pneumatic Designs This controller, having a fixed proportional band of 5%


is very sensitive, has a small “offset,” and, as its gain is fixed,
Pneumatic-Bimetallic The next level of sophistication is to cannot be tuned.
replace the completely on-off action (with or without adjust-
able gap) of the thermostat with a small amount of throttling. Offset Error Let us examine the consequences of these
In such throttling thermostats, the room temperature has to
characteristics separately. A sensitive controller is suited for
move away from set point by a degree or two before the
the control of very slow, large-capacity processors. Temper-
heating (or cooling) valve (damper) is fully opened. One
ature control in the HVAC industry usually fits that descrip-
simple way of achieving such throttling action is by letting
tion. Therefore, thermostats with fixed, high gains can give
the bimetallic spring move a flapper in front of a nozzle
acceptable results, if space temperature can change only very
(Figure 4.11f), thereby causing the pneumatic output pres-
slowly. On the other hand, such thermostats cannot control
sure of the thermostat to change with temperature.
spaces with fast dynamics (short time constants) and will
cycle or lose control when applied to such service.
Throttling Thermostats are distinguished from other control-
The offset inherent in all proportional controllers is not
lers in that they provide proportional action only and that their
proportional band (gain) is narrow and fixed. A conventional a serious drawback because the resulting error is small, due
room thermostat might have a set point range of 55 to 85°F (13 to the narrowness of the proportional band. Using our earlier
to 29°C) and a fixed sensitivity (gain) of 2.5 PSI/°F (0.3 bar/°C). example and assuming that the thermostat output is set at
Assuming that this thermostat operates a control valve having 11 PSIG (0.76 bar) when the error is zero (thermostat on
a 9 to 13 PSIG (0.6 to 0.9 bar) spring range, we can convert set point), we can calculate the maximum error due to offset.
the fixed sensitivity of 2.5 PSI/°F into a percent proportional When there is no error, the control valve is 50% open
band value that is better understood by instrument engineers. (output is 11 PSIG, or 0.76 bar). As the load changes, an
Sensitivity (or gain) is stated as the ratio between a change error must be allowed to develop in order for the valve
in measurement and a change in the corresponding controller opening to change. Assuming that the valve has been cor-
output. A 1°F (0.56°C) change in measurement is 3.3% of rectly sized and is large enough to handle all expected loads,
the measurement range of 30°F (55 to 85°F, or 13 to 29°C), the maximum error due to offset will be that deviation from
while the 2.5 PSI change in controller output is 62% of the set point that is required to move the valve from half to full
controller output range of 4 PSI (9 to 13 PSIG). If a 3.3% opening. This 2 PSIG (0.14 bar) change in thermostat output
change in input results in a 62% change in output, that is a will occur when the deviation from set point is 0.8°F
gain of 62/3.3 = 19. Converting this typical thermostat gain (0.4°C).
to proportional band, we get: Therefore, this is the size of the permanent offset error
for a gain of 19:1. There is an inverse linear relationship
100 100 between gain and offset error, such that if the gain is cut in
P= = = 5.3% 4.11(1)
G 19 half, the offset error will be doubled.

© 2003 by Béla Lipták


4.11 Temperature Switches and Thermostats 663

From the above discussion it might be concluded that the Heating Cooling
conventional room thermostat is a good selection for the Load Load
HVAC-type applications and that more expensive instru- Conventional Control
100% 100%
ments, such as PID controllers, would not necessarily ZEB Control
improve the overall performance.
Resulting Saving
Design Features Application engineers can choose from a
fairly large variety of design features when specifying ther-
0% Room
mostats, because they cannot only be electromechanical, 0%
pneumatic, or electronic, but can also be (1) indicating or 55 65 75 85 95 Temperature
Zeb (°F)
blind, (2) direct or reverse acting, (3) can automatically switch (Adjustable)
their actions in response to a pneumatic or electronic signal,
(4) can have bimetallic, filled, or electronic sensing elements, FIG. 4.11h
(5) can have local or remote set points, or (6) have their set Zero energy band control.
points under key, concealed, or externally adjustable.

Advanced Features If the set point of a pneumatic thermo- Limited Control Range These thermostats allow the occu-
stat is adjusted remotely by an air signal, each 1 PSIG (0.07 bar) pant of an office to move the set point to any value desired,
change in set point pressure will move the set point by an but will disregard any setting that exceeds the limit value.
adjustable preset amount. The range of this adjustment is For example, in heating applications, the limit could be 74°F
usually from 0.15 to 1.4°F (0.1 to 0.8°C) per 1 PSI (0.07 bar). (23°C). In this case, the space temperature will be limited to
If the set point is to change as a function of the time of day, a maximum of 74°F, regardless of the setting by the occupant.
a timer can automatically operate a solenoid and thereby Similar limit values can be set for cooling.
switch the set point signal.
Some of the more recently developed and more advanced Zero Energy Band Control A recent addition to the avail-
thermostat features include the following: able thermostat choices is the zero energy band (ZEB) design.
The idea behind ZEB control is to conserve energy by not
Adjustable Gains or Proportional Bands Another term used using any when the room is comfortable. As illustrated by
to describe the sensitivity of thermostats is throttling range. Figure 4.11h, the conventional thermostat wastes energy by
As shown in Figure 4.11g, it refers to the amount of temper- continuing to use energy when the area’s temperature is
ature change that is required to change the thermostat output already comfortable. The comfort gap, or ZEB, is adjustable
from 3 to 13 PSIG (0.2 to 0.9 bar). The throttling range is and can be varied to match the nature of the particular space
usually adjustable from 2 to 10°F (1 to 5°C). involved.
Dual Set Points These thermostats will switch their settings ZEB control can be accomplished in one of two ways. The
in response to a change in the air supply pressure. Both set single set point and single output approach is illustrated on the
points can be manually adjusted, with the day setting made by left side of Figure 4.11i. Here the cooling valve fails closed
external thumbwheel and the night setting concealed internally. and is shown to have an 8 to 11 PSIG (0.55 to 0.76 bar) spring
range, while the heating valve is selected to fail open and has
a 2 to 5 PSIG (0.14 to 0.34 bar) range. Therefore, between 5
Thermostat
Output (PSIG)
and 8 PSIG (0.34 and 0.55) both valves are closed, and no pay
energy is expended while the thermostat output is within this
range. The throttling range is usually adjustable from 5 to 25°F
13 (3 to 13°C). Thus, if the ZEB is 30% of the throttling range,
it can be varied from a gap size of 1.5°F (0.85°C) to 7.5°F
(4.2°C) by changing the throttling range (or gain).

Split Range Control While the split-range approach is a little


less expensive than the dual set point scheme (shown on the
right of Figure 4.11i), it is also less flexible and more restrictive.
3 The two basic limitations of the split-range approach are:
Temperature
Throttling (°F) 1. The gap width can only be adjusted by changing the
Range thermostat gain; maximum gap width is limited by the
minimum gain setting of the unit.
FIG. 4.11g 2. In this design, the heating valve must fail open; this is
Definitions of throttling range for pneumatic thermostats. undesirable from an energy conservation point of view.

© 2003 by Béla Lipták


664 Temperature Measurement

Dual Output
Pressure from
Thermostat
Output Pressure
(PSIG)
of Single Full Heating Full Cooling
Thermostat 13
Gain = 0.75 PSI/°F
(PSIG)
12
Cooling Valve Open 11
11
10
10 9 Zero
9 8 Energy
Cooling Valve Closed
8 7 Band
7 6
6 Heating
Valve Closed 5
5
4
4 Heating
Valve 3
3
Open 2 Cooling
2 Heat
1 Off Off
1 Space Space
0 Temperature 0 Temperature
67 71 75 79 °F
Heat ZEB Cool °F 64 66 68 70 72 74 76 78 80 82

Single Set Point Split-Range System Dual Set Point System

FIG. 4.11i
Implementation of zero energy band control.

These limitations are removed when a dual set point, dual Programmable setback models with 24-hour or 7-day
output thermostat is used. Here both valves can fail closed programs
and the band width is independently adjustable from the
thermostat gain. The gains of the heating and cooling ther-
mostats are also independently adjustable. In Figure 4.11i, RECENT ADVANCES
the heating thermostat is reverse-acting and the cooling ther-
mostat is direct-acting. Microprocessor-based units continue to incorporate new fea-
tures. These are programmable devices with memory and
Electrical/Electronic Designs communication capability. They can be monitored and reset
by central computers using pairs of telephone wires as the
The most common is the low voltage unit that uses communication link. Microprocessor-based units can be pro-
external interposing relays to control heating and/or vided with continuously recharged backup batteries and with
cooling equipment (typically 24 V AC) accurate electronic room temperature sensors. They can also
Line voltage units that directly control AC circuits (120 operate without a host computer (in the stand alone mode).
or 240 V AC) In this case the user manually programs the thermostat to
Heating only or heating/cooling models maintain various room temperatures as a function of the time
Digital or analog indication of room temperature of day and other considerations.
Bimetallic, filled system or electronic sensing elements In 2000, the first residential gateway for the HVAC indus-
Direct or reverse acting try’s new open communications standard for residential envi-
Local or remote set point ronmental control was introduced. This gateway enables
Local set points may be external or internal and may secure, remote access to residential HVAC systems via touch-
be key protected tone telephone, standard phone line, and pass code. Some
Limited control range thermostats allow the occupant systems offer either dial in or dial out functions. Owners can
of an office to move the set point to any value call in to check the temperature, change the status of their
desired, but will disregard any setting that exceeds HVAC system, and perform other thermostat-related func-
the limit value. For example, in heating applications, tions. These telephone access modules enable monitoring of
the limit could be 74°F (23°C). In this case, the the building’s temperature and its heating/cooling equipment.
space temperature will be limited to a maximum of It can report when a furnace filter needs replacing or an
74°F, regardless of the setting by the occupant. Sim- electronic air cleaner’s cells need cleaning. And it can call
ilar limit values can be set for cooling. up to three phone numbers to immediately alert the owner,

© 2003 by Béla Lipták


4.11 Temperature Switches and Thermostats 665

contractor, or others of problems, such as freezing tempera- Hashemian, H.M., et al., “Assuring Accurate Temperature Measurement,”
tures or an extended power outage. InTech, October 1989.
Jutila, J.M., “Temperature Instrumentation,” Instrumentation Technology,
February 1980.
Krigman, A., “Guide to Selecting Temperature Switches,” InTech, June
Bibliography 1984.
Lipták, B.G., “Reducing the Operating Costs of Buildings by the Use of
Computers,” ASHRAE Transactions, Vol. 83, Part I, 1977.
Air-Conditioning and Refrigeration Institute Standard: 750–76, “Thermo-
static Refrigerant Expansion Valves,” Atlanta, GA, 1976. National Electric Manufacturers’ Association Standard: DC3–1972, “Res-
American Gas Association Standard: Z21.23–1975, “Gas Appliance Ther- idential Controls: Low Voltage Room Thermostats,” Rosslyn, VA,
mostats,” Washington, D.C., 1975. 1972.
American Society of Heating, Refrigerating and Air-Conditioning Engineers National Electric Manufacturers’ Association Standard: DC13–1973, “Res-
Standard: 17–75 (ANSI: B60.1–1975), “Method of Testing for Capac- idential Controls: Integrally Mounted Thermostats for Electric Heat-
ity Rating of Thermostatic Refrigerant Expansion Valves,” Atlanta, ers,” Rosslyn, VA, 1973.
GA, 1975. Plumb, H.H., “Temperature: Its Measure and Control in Science and Indus-
American Society of Testing and Materials Standard: B106–68, “Standard try,” 5th Symposium on Temperature, National Bureau of Standards,
Method of Test for Flexibility of Thermostat Metals,” West Consho- American Institute of Physics, Instrumentation, Systems, and Automa-
hocken, PA, 1972. tion Society, 1971.
American Society of Testing and Materials Standard: B389–65, “Standard Spethmann, D.H., “Importance of Control in Energy Conservation,”
Method of Test of Thermal Deflection Rate of Spiral and Helical Coils ASHRAE Journal, February 1975.
of Thermostat Metal,” West Conshohocken, PA, 1975. Roots, W.K., Fundamentals of Temperature Control, New York: Academic
“Automatic Control,” in ASHRAE Handbook and Product Directory, Atlanta, Press, 1969.
GA: American Society of Heating, Refrigerating and Air-Conditioning Underwriters’ Laboratories Standard: UL-521 (ANSI: Z220.1–1971), “Stan-
Engineers,1980, chap. 34. dard for Fire-Detection Thermostats,” Northbrook, IL, 1971.
Eckman, D.P., Automatic Process Controls, New York: John Wiley & Sons, Ween, S., “Liquid-in-glass Thermometers, Still Well and Indicating,” Paper
1958. #91–0308, Instrumentation, Systems, and Automation Society Confer-
“Filled-Systems Thermometers,” Measurements and Controls, September 1991. ence, Toronto, 1991.

© 2003 by Béla Lipták

You might also like