Professional Documents
Culture Documents
Catalog Ocs
Catalog Ocs
PAGE
Introduction___________________________________________________ 1
Installation____________________________________________________ 2
a) Introduction
b) Setup Location
c) Installation Preparation
Installation Diagram____________________________________________ 5
Operation_____________________________________________________ 7
a) Introduction
b) Description
c) Operating
Maintenance___________________________________________________ 10
a) Introduction
b) Maintenance Instructions
Trouble shooting________________________________________________12
a) Introduction
b) Problems, Possible Cause, Remedy
Equipment_____________________________________________________14
Appendix______________________________________________________ 19
Abbreviations__________________________________________________ 20
Glossary of Terms______________________________________________ 21
Conversions___________________________________________________ 25
This manual is designed to assist on the maintenance and operating procedures of
high pressure test units brought to you by Open and Close Equipment. All test
units are designed to provide a safe and an efficient way to test the blowout
preventers.
OPERATION: Instructions and illustrations for the proper use of the test
unit.
1
OPEN AND CLOSE
EQUIPMENT, INC.
www.bopenandclose.com
Email: sales@bopenandclose.com
a) INTRODUCTION
b) SETUP LOCATION
The unit should be installed in a firm and leveled area with adequate air flow and
water supply.
Sufficient lighting and drainage for vented or liquid fluid. The location should not
interrupt other operations. And should be isolated in a secure area, in case of any
failure.
c) INSTALLATION PREPARATION
Before the start of any test, check the equipment thoroughly for any damage. In high
pressure testing all components must be in a perfect condition to prevent an
accident.
1. Check that air lubricator (Item 6) is full of SAE 10W Lubricating oil.
3. Check that rupture disk (Item 15) is installed and that opening is NOT plugged.
o Check that the ink well is full and pen operates. (Check maintenance section
if it´s not operated properly).
o Check that the clock is wound by using key provided enclosed with the
recorder.
2
2) Initial Hookup
2. Connect water supply hose or pipe to customer water supply connection see
equipment specifications.
NOTE: For testing of self-contained units that include a reservoir, either a light
weight SAE 10W Oil or water can be used. Fill to approximately 8” from the top.
3. Connect air supply hose or pipe to customer air supply connection (item1); (see
Installation Data sheet and Equipment Specifications).
1. Open test outlet valve (Item 13) and bleeder valve (Item 14).
3. Open air supply valve (Item5) ONLY on low pressure pump (Item 10).
4. Purge lines with water to remove air and then close bleeder valve (Item14).
5. When pressure reaches 3,000 PSI, open air supply valve (Item 8) to high
pressure pump (Item11).
b. Read air regulator pressure gauge for pressure setting of the regulator.
c. Set at required testing pressure.
8. Observe that recorder (Item 17) is tracking the same pressure as the test
pressure gauge (Item16). If adjustments are required (see maintenance section).
11. Repair any leaks. If leaks are in high pressure tubing connections, (See
maintenance section).
3 2
4) Test Hook-Up
2. Connect high pressure hose to high pressure test connection (Item 3) (see
equipment specifications).
3. Optional: Connect bleeder hose to bleeder line connection (Item 4) Run other end
of hose to nearest drain and safely secure.
4. Open air supply valve (Item 5 ) only to low pressure pump (Item 10).
6. Purge high pressure test hose to remove air and close air supply valve (Item 5)
THE HIGH PRESSURE UNIT IS USED FOR HIGH PRESSURE – LOW FLOW. IT IS
NOT A VOLUME PUMP ASSEMBLY. USING IT TO FILL THE TEST CAVITY WILL
ONLY DELAY TESTING.
10. Purge entire test circuit to remove air then close air supply valve (Item 5).
3 4
5
RAM PREVENTER
2
TEST UNIT MODEL No. No. OF PUMPS Min air supply req’d
PSI CFM
OCS15RA 2 90 112
OCS10RA 2 90 112
OCS20RA 2 90 112
OCS30RA 2 90 133
Note: - You should ensure that the air supply is CLEAN and DRY.
•Excessive moister and contaminants can cause operational problems
2. Test Unit (see equipment section) Equal to or greater than test pressure
5. High Pressure Test Hose or Tubing Equal to rated working pressure of test
(see equipment section) Unit
NOTES:
a) INTRODUCTION
High pressure hydrostatic tests must be conducted with an approved test procedure.
The test procedures should be developed by your own company or a standard accepted
test producer such as that outlined in API RP53 Section 7A can be used. All test
procedures must specify, in detail, the test criteria such as; test pressure, test duration,
acceptable test results, and a blank data sheet to record the test results.
b) DESCRIPTION
The high pressure test unit assembly uses the air supply to power the air motor of
one low and one high pressure pump to build up the high pressures for testing. The low
pressure pump (Item 10) is a double acting, 60:1 ratio pump which is capable of a
maximum 7,500 PSI output. The high pressure pump (Item 11) is a bidirectional 200:1
ratio pump. Passes through the air supply valve (Item 5), then flows through a
lubricator (Item 6) and is impregnate with 10W oil. The air supply is then routed
through an air pressure relieving regulator equipped with a pressure gauge (Item 7) The
regulator serves as the system’s test pressure controller. The air regulator contains a
diaphragm pressure side to connects to the outlet port of the regulator so that, as
pressure increases, the diaphragm compresses the adjusting spring. An equilibrium
state is maintained between the load exerted by the adjusting spring and the load from
the regulated pressure. The load exerted by the adjusting spring controls the valve
position to maintain the desired regulated pressure.
The open air supply valve (Item 5) starts up the low pressure pump and pulls the water
supply trough a strainer (Item 9) located in the low pressure pump suction line. This
fluid suction line enters the fluid end of the low pressure pump. The flow in the air
supply line to the high pressure pump is controlled by the opening of the air supply
valve (item 8). When the air supply valve is opened to start up the high pressure pump.
The fluid end pressurizes the fluid discharge from the low pressure pump. Both the
upstream and discharge lines of the high pressure pump contain check valves (Item12)
to prevent backflow of the high pressure fluid. When the backpressure fluid force
discharge by the pumps equals the regulated air pressure force into the high pressure
air motor, the pumps will stall out.
The pumps discharge line is directed through the test outlet valve (item 13) and controls
the high pressure flow through the high pressure test connection (Item 3) to the
equipment being tested. An additional vent or bleeder line is provided with a bleeder
valve (Item 14) to control the release of the system fluid and pressure. A rupture disk
(Item15) serves to protect the test unit assembly against over pressurizing. The rupture
pressure of these discs will vary according to the working pressure rated of the test
unit.
7 2
The pressure in the test line is monitored through a tube connection to a test
pressure gauge (Item 16). Units equipped with a test pressure recorder
(Item 17) connect to this tubing for indication of test pressures on the
recording chart.
NOTE: Preventer and valves that have been tested with water should be
purge with oil after testing.
c) OPERATING
1. Test Start-Up
o Open the air supply valve (Item 5) to the low pressure pump (Item 10).
o When test pressure reaches 3,000 PSI, open the air supply valve
(Item 8) to the high pressure pump (Item11).
o The test unit should automatically stall out at the required test
pressure as set in the installation section. If not, adjust the air regulator
(Item 8) to desired test pressure.
o After pressure stabilizes, close the air supply valves (Items 5, 8) and
test outlet valve (Item 13).
2) Test
o Observe the test pressure gauge (Item 16), or recorder chart (Item 17),
if so equipped, for any pressure losses. If there is a constant drop in
pressure, there is a leak in the test circuit.
3) Test Rig-Down
10
16
17
11
12
7 13
1
5 12
3
15
2
4 14
9
SCHEMATIC
TYPICAL HIGH PRESSURE TEST UNIT
Item Description
6 Air Lubricator
9 Suction Strainer
10
14
10 Low Pressure Pump
4 9
11 High Pressure Pump
15 13 12 12
12 Check Valves 11
2
13 Test Outlet Valve
14 Bleeder Valve
Air Supply Pressure
Regulated Air Pressure
15 Rupture Disc
Water Supply Pressure
Intermediate Pressure
16 Test Pressure Gauge
High Pressure
17 Test Pressure Recorder
9
OPEN AND CLOSE
EQUIPMENT, INC.
www.bopenandclose.com
Email: sales@bopenandclose.com
a) INTRODUCTION
All high pressure hose lines should be double checked that pressures have been
relieved before attempting maintenance.
b) MAINTENANCE INSTRUCTIONS
The following instruction are categorized by component maintenance. The item numbers
refer to the illustrations located in the operation section.
2. Strainers (Item 9)
o On a regular basis remove strainer elements and wash with warm water or
kerosene.
o Use a torque wrench when tightening gland nuts on high pressure fittings and
valves to stop leaks.
o Over tightening may cause seat damage. Torque requirements are:
1. Valve stem glands – 85 ft-lbs.
2. Tubing connection glands -55-ft-lbs.
1) Pen
1. Press forefinger over end of pen box to start ink flow through pen. This
should cause pressure to build up and ink to flow through capillary.
2) Clogged Pen
o Pull pen box off of open arm and soak in water or alcohol.
o Insert a cleaner wire up the capillary hole and into the box reservoir.
o Reinstall the pen box by pushing the pen all the way on the pen arm until
the top of the pen arm touches the capillary.
o Remove the connecting link from its bearing point by rotating the retainer
clip on the end of the connecting link to allow the bearing pin to slip out of
its bearing hole on the calibration arm.
o Position the pen arm so that the pen rests on the fine line near the center of
the chart. If It:
4) Loosen the clamp screw at the upper end of the pen arm and adjust the length.
5) Tighten the clamp screws and reconnect the link to the calibration arm.
9) Reservoir
o The fluid reservoir should be checked regularly, drained and cleaned. Fill to
approximately 8” from the top with a light weight SAE 10W oil or water.
NOTE:
Never use fuel oil, kerosene or salt water in the reservoir.
11
OPEN AND CLOSE
EQUIPMENT, INC.
www.bopenandclose.com
Email: sales@bopenandclose.com
o All repairs to the unit should be performed while the unit is removed from service.
o To ensure safety the repairs should be done in pairs so there is a backup in case
of an emergency.
o All high pressure hose lines should be double checked that pressures have
been relieved before attempting maintenance.
TEST UNITS
MODEL NUMBER IDENTIFICATION SYSTEM
OC S 15 R A
S Skid Mounted
14
Approximate
Maximum Pressure Weight
MODEL
(PSI)
Lbs. kgs
OCS10RA 10,000 430 195
OCS15RA 15,000 430 195
OCS20RA 20,000 430 195
OCS30RA 30,000 445 202
15
4
3 5
16
Item Description Qty Item Description Qty
5 Needle Valve 9/16”, 20,000 PSI, 316 SS 2 25.a 1”, 160 PSI, Air Regulator 1
6 Nipple 9/16” x 6” 20,000 PSI, 316 SS 4 25.b 1”, 160 PSI, Air Lubricator 1
14 Needle Valve 1/4”, 20,000 PSI, 316 SS 1 35 Street Conn. 9/16” 316 SS, LP 4
17
18
OPEN AND CLOSE
EQUIPMENT, INC.
www.bopenandclose.com
Email: sales@bopenandclose.com
19
ADJ – Adjust INC/DEC – Increase/Decrease. The control
function that regulates the pressure to be applied
AMB – Ambient to the annular valve on the BOP stack
HZ – Hertz. Preferred terminology for cycles per second, VDC – Volts Direct Current. An electrical
the frequency of an electrical wavelength current that flows in one direction only
20
Ambient Temperature: The temperature of the all encompassing atmosphere within a given area.
Accumulator: A vessel containing both hydraulic fluid and gas stored under pressure as a source
of fluid power to operate opening and closing of blowout preventer rams and annular preventer
elements. Accumulators supply energy for connectors and valves remotely controlled.
Accumulator Unit: The assembly of pumps, valves, lines, accumulators, and other items necessary
to open and close the blowout preventer equipment.
Accumulator Bank Isolator Valve: The opening and closing device located upstream of the
accumulators in the accumulator piping which stops flow of fluids and pressure in the piping.
Accumulator Relief Valve: The automatic device located in the accumulator piping that opens
when the preset pressure limit has been reached so as to release the excess pressure and protect
the accumulator.
Air Breather: A device permitting air movement between the atmosphere and the component in
which it is installed.
Air Pressure Switch Bypass Valve: The opening and closing device located in the air supply line
which blocks air flow in one line to be redirected through another. In open position, air flow is not
routed through the air pressure switch for automatic shutoff thereby allowing the air pumps to
continue to run.
Air Pump Suction Valve: The opening and closing device located in the piping line that draws fluid
from the reservoir into the fluid end of the pump when the air motor is operating.
Air Regulator: The adjusting device to vary the amount of air pressure entering as to the amount
to be discharged down the piping lines.
Air Supply Valve: The opening and closing device in the connecting line of the compressed air
routed to flow into the accumulator system lines as a power source for components.
Ampere: The unit used for measuring the quantity of an electric current flow. One ampere
represents a flow of one coulomb per second.
Annular: A large valve, usually installed above the ram preventers, that forms a seal in the space
between the pipe and wellbore or on the wellbore itself. The space around a pipe in a wellbore, the
outer wall of which may be the wall of either the borehole or the casting.
Annular Regulator: The device located in the annular manifold header to enable adjustment of
pressure levels which will flow past to control the amount of closure of the annular preventer.
Blowout Preventer: The equipment installed at the wellhead to enable the driller to prevent
damage at the surface while restoring the balance between the pressure exerted by the column of
drilling fluid and formation pressure. The BOP allows the well to be sealed to confine the well fluids
and prevent the escape of pressure either in the annular space between the casting and drill pipe or
in an open hole. The blowout preventer is located beneath the rig at the land’s surface on land rigs
or at the water’s surface on jack-up or platform rigs and on the seafloor for floating offshore rigs.
BOP Stack: The assembly of well control equipment including preventers, spools, valves and
nipples connected to the top of the casing head.
Baffle: A partition plate inside the reservoir to prevent unbalancing by sudden weight shifting of the
hydraulic fluid.
Bleeder Valve: An opening and closing device for removal of pressurized fluid.
Blowout: An uncontrolled flow of gas, oil, or other well fluids into the atmosphere. A blowout, or
gusher, occurs when formation pressure exceeds the pressure applied to it by the column of drilling
fluid.
Chain guard: The metal enclosure surrounding the electric pump driving chain to protect and
contain an oil lubricate for the chain.
Check Valve: A valve that permits flow in only one direction.
Choke: A variable diameter orifice installed in a line through which high pressure well fluids can be
restricted or released at a controlled rate. Chokes also control the rate of flow of the drilling mud
out of the hole when the wells is closed in with the blowout preventer and a kick is being circulated
out of the hole.
Circuit Breaker: An electrical switching device able to carry an electrical current and automatically
break the current to interrupt the electrical circuit if adverse conditions such as shorts or overloads
occur.
Conductivity: The capability of a material to carry an electrical charge. Usually expressed as a
percentage of copper conductivity (copper being one hundred 100 percent). Conductivity is
expressed for a standard configuration of conductor.
Conductor: The substance or body capable of transmitting electricity, heat, light, or sound.
21 Contact Block: The conductor located in the electric panels which bring together the electrical
connections of the operation pushbuttons with those of the operator valves.
Continuity: The uninterrupted flow of current in a conductor.
Control Manifold: The system of valves and piping used to control the flow of pressured hydraulic
fluid to operate the various components of the blowout preventer stack.
Corrosion Inhibitor: Any substance which slows or prevents the chemical reactions of corrosion.
Cylinder: A device which converts fluid or air power into linear mechanical force and motion. It
consists of a movable element such as a piston and piston rod, plunger rod, plunger or ram,
operating within a cylindrical chamber.
Discharge Check Valve: The device located in the expelling line of a pump (air or electric) which
allows fluid to flow out only and thereby prevents a back flow of fluid into the pump.
Drain Port: The plugged openings on the lower side portions of the reservoir which can be opened to
empty or release the hydraulic fluid, and through which the reservoir can be cleaned.
Dust Cap: The screw on covering for the electric panel connector receptacles which protect the
electrical contacts from foreign matter and moisture.
Electric Pump Suction Valve: The opening and closing device located in the piping line that draws
fluid from the reservoir into the pump inlet when the motor is operating.
Element (Filter): The substance of porous nature which retains foreign particles that pass through
the containing chamber to serrate and clean the gas or liquid flow.
Fill Port: The plugged opening in the top of the fluid reservoir through which hydraulic oil is added.
Filter (Air): Apparatus used to clean air flow of dirt, moisture and other contaminants.
Filter (Hydraulic): A device whose function is the retention of insoluble contaminants from a fluid.
Filter (Air): Apparatus used to clean air flow of dirt, moisture and other contaminants.
Filter (Hydraulic): A device whose function is the retention of insoluble contaminants from a fluid.
Flow Rate: The volume, mass, or weight of a fluid passing through any conductor, such as pipe or
tubing, per unit of time.
Flow meter: A device which indicates either flow rate, total flow, or a combination of both, that
travels through a conductor such as pipe or tubing.
Fluid: A substance that flows and yields to any force tending to change its shape. Liquids and gases
are fluids. The accumulator system pressurizes fluid to be sued as a source of power to open and
closed valves and rams on the BOP stack.
Full Load Current: The amount of current used by an electrical circuit when that circuit is operating
at its designed or rated maximum capacity.
Function: The term given to the duty of operating the control valves of the accumulator system. The
action performed by the control valves when operating the ram preventers or gate valves.
Gage: A standard method of specifying the physical size of a conductor (wire) diameter based on the
circular mil system. 1 mil equals .001. The higher the number, the smaller the diameter.
Gauge: An instrument for measuring fluid pressure that usually registers the difference between
atmospheric pressure and the pressure of the fluid by indicating the effect of such pressures on a
measuring element (as a column of liquid, a bourdon tube, a weighted piston, a diaphragm, or other
pressure-sensitive devices).
Gland: The cavity of a stuffing box.
Ground: An electrical term meaning to connect to the earth, or another large conducting body to
serve as earth, thus making a complete electrical circuit. The conducting connection of a circuit to
the earth.
Hydrostatic: Relating to liquids at rest and the pressures they exert.
Indicating Light: The bulbs of the electric control panels that shine to point out which electrical
contacts have made a circuit. The electric panel bulbs make circuit contacts through pressure
switches, transducers, and solenoid valves to demonstrate activation.
Inspection Port: The plugged openings on the sides of the fluid reservoir which can be opened to
view the interior fluid level and return lines from the relief, bleeder, control valves, and regulators.
Insulation: A non-conductive material usually surrounding or separating the current-carrying parts
from each other or from the core.
Kick: The increase in pit volume caused by the entrance of formation liquids or gas in the wellbore.
Without corrective measures, this condition can result in a blowout.
Kill Line: A high-pressure fluid line connecting the mud pump and the wellhead at some point below
a blowout preventer. This line allows heavy drilling fluids to be pumped into the well or annulus with
the blowout preventer closed to control a threatened blowout.
Lubricator (Air): A device which adds controlled or metered amount of a substance into the air line of
a fluid power system to prevent or lessen friction.
Manifold Bleeder Valve: The opening and closing device in the piping that connects the manifold
header and the reservoir, and which can be opened to release the fluid pressure and vent it back into
the reservoir. 22
Manifold Header: The piping system which serves to divide a flow through several possible
outlets. The 4-Way control valve inlets connect to the piping so that high pressure fluid is
available to pass through any or all of the valves.
Manifold Regulator: The device located in the manifold header which can vary the amount of
pressure that enters and exits its chamber. The manifold regulator controls the pressure level of
the fluid flowing through and out the 4-way control valves.
Manifold Regulator Bypass Valve: The opening and closing device which blocks flow in one line
to be redirected through another. This valve is located in the manifold piping so that in the open
position the high pressure fluid does not flow through the regulator in the manifold header,
thereby allowing higher pressure fluid to be available to the 4-way control valves.
Manifold Relief Valve: The automatic opening device located on the manifold header that opens
when the preset pressure limit has been reached so any excess pressure is released, thereby
protecting the manifold header.
Meter: An instrument, operated by an electrical signal, that indicates a measurement of pressure.
Meter Circuit Board: Printed circuit board used with the electrical meters to provide the circuits
necessary for calibration of the meter.
Micron: (A millionth of a meter or about 0.00004 inch). The measuring unit of the porosity of
filter elements.
Mil: A measurement used in determining the area of wire. The area of a circle one 1/thousandth
inch in diameter.
Motor Starter: Automatic device which starts or stops the electric motor driving the duplex or
triplex pump which works in conjunction with the automatic electrical pressure switch for
pressure limits of pump start-up and shutoff.
Needle Valve: A shutoff (2-Way) valve that incorporates a needle point to allow fine adjustment in
flow.
Ohm: A unit of electrical resistance, the resistance of a circuit in which a potential difference of
one volt produces a current of one ampere.
Ohmmeter: The measuring instrument which indicates resistance in ohms.
Petcock: The small faucet or valve used to release compression or drain moisture accumulated in
the anterior chamber of the lubricator.
Phase (3-Phase Motor): A particular stage or point of advancement in an electrical cycle. The
fractional part of the period through which the time has advanced, measured from some arbitrary
point usually expressed in electrical degrees where 360º represents one cycle.
Pipe Rack: The connecting pipelines between the control valve outlets and the BOP stack
preventers which carry the high pressure operating fluid. The lines of pipe are laid together and
are often covered with grating to create a walkway.
Potable: A liquid that is suitable for drinking.
Pressure Switch (Air): The automatic device to start and stop the air pump operation when the
preset pressure limits are reached.
Pressure Switch (Electric): An electrical switch, operated by fluid pressure, which automatically
starts and stops the electrical pump when the preset pressures are reached.
Pressure Transmitter: Device which sends a pressure signal to be converted and calibrated to
register the equal pressure reading on a gauge. The air output pressure is proportional to the
hydraulic input pressure.
Pump (Air): A device that increases the pressure on a fluid or raises it to a higher level by being
compressed in a chamber by a piston operated with an air pressure motor.
Pump (Electric): A device that increases the pressure on a fluid and moves it to a higher level
using compression force from a chamber and piston that is driven by an electric motor.
Pushbutton/Indicating Light: The control valve operates with bulbs on the electrical remote
panel which change and indicate the position of the control valves.
Ram: The closing and sealing component on a blowout preventer. One of three types blind, pipe,
or shear – may be installed in several preventers, mounted in a stack on top of the wellbore. Blind
rams, when closed, form a seal on a hole that has no drill pipe in it; pipe rams, when closed, seal
around the pipe; shear rams cut through drill pipe and then form a seal.
Recorder: An automatic device that reads and records pressure outputs continually on a revolving
chart to provide continuous evidence of pressures.
Regulator: A device that varies and controls the amount of pressure of a liquid or gas that passes
through its chambers.
Relay: An electrical device to automatically control the operation of another device in another
circuit by passing on an electric current.
Relay Socket: A device used to interconnect a relay with its circuitry and which allows quick and
23 easy removal of the relay without special tools.
Reservoir: The container for storage of liquid. The reservoir houses hydraulic fluid at atmospheric
pressure as the supply for fluid power.
Resistance: The property of an electrical circuit which determines for a given current, the rate at
which electrical energy is converted into heat and has a value such that the current squared,
multiplied by the resistance, gives the power converted.
Rupture Disk: A device whose breaking strength (the point at which it physically comes apart) works
to relieve pressure in the system. The rupture disk is contained as a safety device for the test unit
system.
Solenoid Valve: The opening/closing device which is activated by an electrical signal to control liquid
or gas pressured flow to be sent to open or close the 4-way control valves. The valve position is
controlled by an electromagnetic bar, enclosed by a coil.
Solenoid Valve Box: The explosion proof enclosure, located on the accumulator unit, which contains
the electrically powered actuators for the remote control electrical panel. The box is wired to the
electrical supply, and houses solenoid valves, pressure switches and transducers.
Span Adjustment: The control to vary the space between the electrical contact points in the electrical
pressure switch.
Strainer: A porous material which retains contaminants passing through a line along with the gas or
liquid flow.
Suction Strainer: The porous element, located in a “Y” shaped fitting of the pump suction lines, which
cleans the hydraulic fluid or air of contaminants before entering the pumps.
Surge Damper: The one quart capacity bladder accumulator used to absorb the shock and waves
caused by an initial flow of high pressure fluid. Located in the downstream line of the annular
regulator.
Swivel Joint: A connecting device, joining parts so that each can pivot freely. Swivel joints are used at
the end of the pipe rack to see connections to the control valve outlets and to the BOP stack.
Terminal Strip: Grouped electrical conductor endings where screw connections are made.
Transducer: The device located in the solenoid valve box which is actuated by hydraulic pressure and
converts the force to an electrical force for indication on a meter. The electrical output signal is in
proportion to the hydraulic input pressure.
Unit/Remote Selector: The valve located on the manifold header whose ports allow flow into the
annular regulator. The valve position determines the source of flow supply and subsequently controls
the location of operation.
Valve, Float: A device that is positioned as either open or closed, depending on the position of a lever
connected to a buoyant material sitting in the fluid to be monitored.
Valve, Manipulator: A control device having three positions, giving four direction selections for flow
which alternately pressurizes and vents the pressure outlets. The manipulator style valve vents all
pressure outlets when placed in the center position.
Valve, Selector: A control device having three positions, giving four directions selections for flow
which alternately pressurizes and vents the pressure outlets. The selector style valve blocks all
pressure points if placed in the center position.
Valve, Poppet: The opening and closing device in a line of flow which restricts flow by lowering a
piston type plunger into the valve passageway.
Valve, Precharge: The device located on the accumulator bladder ports which open and close for the
nitrogen pressure contained.
Valve, Relief: A valve that opens at a preset pressure to relieve excessive pressures within a vessel or
line whose primary function is to limit system pressure.
Valve, Shutoff: A valve which operates fully open or fully closed to control the flow through the lines.
Valve, Shuttle: A connective valve which selects one of two or more circuits because flow or pressure
changes between the circuits.
Viscosity: A measure of the internal friction or the resistance of a fluid to flow.
Volt: A unit of electromotive force.
Watt: A unit of electrical power; the power of one ampere of current pushed by one volt of
electromotive force.
Zero Adjustment: The control to move the meter gauge indicator for resetting calibration accuracy.
Control used to make the meter read 0 by applying an offset voltage to the meter to offset any positive
voltage present at the meter, even though there is no pressure at the input of the transducer.
24
LENGTH CONVERSION AREA CONVERSIONS
TO CONVERT TO:
Celsius ºC = 5/9 (ºF - 32)
Fahrenheit ºF = 9/5 ºC + 32
Kelvin ºK = ºC + 273.15
Rankin ºR = ºF + 459.67
25
POWER AND FLOW CONVERSION PRESSURE CONVERSIONS
To Convert To Multiply To Convert To Multiply
Unit (1) Unit (2) Unit (1) by: Unit (1) Unit (2) Unit (1) by:
Hp hp. (metric) 1.014 PSI Atm. 0.06804
hp watts 745.7 PSI ft. H2O 2.307
hp ft. lbs./min. 33,000.0 PSI kgs./sq. cm. .07031
hp BTUs/min. 42.44 Atm. ft. H2O 33.90
BTU ft. lbs. 778.26 Atm. PSI 14.70
BTUs/min. hp. 0.02356 Atm. kgs./sq. cm. 1.0333
BTUs/min. watts 17.57 ft. H2O Atm. 0.02950
watt hp. .001341 ft. H2O PSI 0.4335
watt BTU/min. 0.05692 kgs./sq. cm. PSI 14.22
watt ft. lbs./min. 44.26
kw/hr. ft. lbs. 2.655x10(6)
kw/hr. BTU 3415
gpm cfm .13368
gpm liters/min. 3.7848
l/m gpm .26418
l/m cfm .035316
cfm gpm 7.48
cfm liters/min. 28.32
ft. lbs./min. hp. 3.030x10(-5)
ft. lbs./min. BTU/min. .001286