! Caution ! Caution
(1) Applying a voltage or current exceeding its maximum permissible value may (1) The recommended panel thickness is 0.8 to 5mm.
cause the unit to be damaged. (2) Do not install the unit in locations where it is exposed to direct sunlight;
(2) Always use the unit within the specified voltage range; otherwise, it may where ambient emperature or humidity doesn't meet the requirements below;
cause a fire, electric shock or personal/equipment damage. or where a drastic change in temperature may ause condensation.
Ambient temperature: 0 to 50 ℃
(3) For the purpose of functional improvement, the information written herein Ambient humidity: 35 to 85%
may be changed without prior notice. (3) Do not install the unit where it is exposed to dust, particles, chemicals harmful
(4) Information contained herein is considered accurate to the best of our to electric components, corrosive gases, etc.
knowledge. If you have any question or comment on the information, please (4) When this unit is installed inside other equipment, pay attention to the heat
contact us or our distributor. radiation and keep the heat inside the equipment 50℃ or below.
(5) Read this manual carefully and thoroughly before starting to operate the unit, (5) Do not install the unit where it is exposed to excessive vibration or shock.
and keep the manual available for future reference. (6) Install the unit horizontally; otherwise, ventilation will be adversely affected
and may result in deterioration.
Bottom
45
⑥LO
70 mm or more
Shift Key Shifts among the digits during the parameter setting.
⑥ Digital Zero control during normal measuring mode.
Scaling data pattern selection Set low layer values of the scaling data.
Select a parameter to
Mode Mode change.
Change the
Mode parameter selected.
Select the name of a parameter you want to change by pushing the Increment key.
Mode To change the selected parameter, use the Mode key to move from the menu selection mode to the value change mode.
Mode Use the Mode key to shift from the value change mode to the menu selection mode.
Use the Increment key to select the menu name of the parameter you want to change or return to measurement by pushing
or Enter the Enter key.
0 1 2 3 4 5 6 7 8 9 -
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z /
Round off display Rounding off the display to the nearest digits to eliminate display jitter. (e.g. Display only 0 or
S.WD 1 0 1/2/5/10 5 when set to 5.)
CLR Display color RED 1 RED/GREN Select the display color. (Not selectable for comparator output type)
Select the display brightness cutoff level. OFF = brightest >LV1>LV2>LV3>ON =
completely dark
Display brightness * It is possible to completely clear the displayed data with the display blank level set to ON.
BLNK cutoff OFF 0 OFF/LV1/LV2/LV3/ON Any displays such as the maximum value, etc. in “6 Memory Mode” described on page 8/10
are also cleared. Be careful that the operation of long pressing the Mode Key is still valid even
while the displayed data is cleared.
Digital Zero Select whether the Digital Zero data must be backed up or not when the power is removed.
DZ.BU backup OFF 0 OFF/ON
PS Pattern selection 1 0 1/2/4/8 Specify the pattern selection numbers activated for use.
LINE Linearization OFF 0 OFF/2/4/8/16 Select the calibration point numbers for linearization. OFF = No linearization
Tracking Zero time Select the calibration time for the Tracking Zero function. 000 = Disable
TR.T 000 0 000~999 * Please refer to 7.6 tracking Zero functions for an actual idea.
Tracking Zero Select the calibrated digits for the Tracking Zero function. (Invalid with TR.T set to 000)
TR.W range 01 0 01~99 * Please refer to 7.6 tracking Zero functions for an actual idea.
Select the stand-by time (in seconds) after the power startup.
Power ON delay * If the power-on delay time is set, operation progresses as follows: Segment check just after
P.ON time 0 0 0~9 power-on Delay time (WAIT display) Unit No. display (with the unit No. display setting
turned ON) Measurement.
Lockout protection Select the level of protection to prevent unwanted key operation. [lower] LV0<LV1<LV2<
PRO level LV.1 3 LV.0/LV.1/LV.2/LV.3 LV3 [higher]
Hardware Disable/enable the code display of built-in hardware unit types at the startup.
U-NO. configuration OFF 0 OFF/ON
15 *1 1 11/12/13/14/15 (voltage)
Input range Selects the input range. *Note that the input terminal changes depending on the input
RANG 24 *1 1 21/22/23/24 (small current) range.
26 *1 1 25/26 (large current)
Full-scale indicated
FSC value 9999 *2 2 -9999~+9999 Sets the relationship between an input signal and indicated value.
For the voltage measurement's 15 ranges, the full-scale input value becomes "9999"
Full-scale when an input is 700 V.
FIN input value 9999 *2 2 -9999~+9999 For the large-current measurement's 26 ranges, the full-scale input value becomes
"9999" when an input is 2 A.
OFS Offset indicated value 0 *2 2 -9999~+9999 * About a real way of thinking, please refer to 5.1 indication scaling setting examples.
OIN Offset input value 0 *2 2 -9999~+9999
Sets the high limit of the displayable range. (A value exceeding the digital limiter HI
DLHI Digital limiter HI 9999 0 -9999~+9999 setpoint is not updated and is held at the set value.)
Digital limiter LO Sets the low limit of the displayable range. (A value lower than the digital limiter LO
DLLO -9999 0 -9999~+9999 setpoint is not updated and is held at the set value.)
DP Decimal point None *2 2 Each digit Sets the decimal-point display position.
*1 It is set as the input range at the time of an order.
*2 It is set as the scaling display at the time of an order. It becomes an initial configuration when there is no specification.
Instruction Manual for MODEL 46DL2 UY-49203a 5/10
5 Setting Examples
5.1 Scaling Data Setting Example
Example 1( Voltage)
When the input signal varies between 0 to 700 V, corresponding indication values should be 0.0 to 700.0.
Indication value Input range (RANG) : 15
Full scale indication (FSC) : 7000
7000 Full scale input value (FIN) : 9999
Offset indication (OFS) : 0
Offset input (OIN) : 0
Digital limiter HI (DLHI) : 9999
Digital limiter LO (DLLO) : -9999
0 Decimal point (DP) : 10 1 digit
Input signal
0V 700V * The full-scale input value of the 15-range voltage measurement unit will be
9999 when the input signal is 700 V.
Example 2( Voltage)
When the voltage range of the input signal is 0 to 5 V, corresponding indication values should be 0.000 to 5.000.
Indication value Input range (RANG) : 13
Full scale indication (FSC) : 9999
9999 Full scale input value (FIN) : 5000
Offset indication (OFS) : 0
Offset input (OIN) : 0
Digital limiter HI (DLHI) : 9999
Digital limiter LO (DLLO) : -9999
Decimal point (DP) : 10 3 digit
0 Input signal * As the indication range (FSC-OFS=approx. 10,000) is larger than the actual
0V 5V
resolution (FIN-OIN=5,000), the indication will change in steps of more than
one.
Example 3( Voltage)
When the voltage range of the input signal is 0 to 10 V, corresponding indication values should be 0.000 to 5.000.
(display range : -2.000 to 3.000)
Input range (RANG) : 13
Indication value Full scale indication (FSC) : 5000
Full scale input value (FIN) : 9999
Offset indication (OFS) : 0
5000
Offset input (OIN) : 0
3000 Digital limiter HI (DLHI) : 3000
Digital limiter LO (DLLO) : -2000
Decimal point (DP) : 10 3 digit
Input signal
0 10V
-2000
Mode
or
The digit is moved, and the digit that
wants to change is selected.
Shift data setting
Increase a value.
Mode
Enter
Return to measurement
Instruction Manual for MODEL 46DL2 UY-49203a 7/10
Measurement operation
* Not displayed unless the value of the protect level parameter of the condition
data is PL0.
* Not displayed unless the linearization parameter of the condition data is enabled.
Mode
Correction Point 1 Input Data Setting
Mode Change the selected digit Select a digit to change
Change a value
Mode Save and return to measurement
Correction Point 1 Output Data Setting (setting method is the same as above)
Correction Point 2 Input Data Setting (setting method is the same as above)
Correction Point 2 Output Data Setting (setting method is the same as above)
Correction Point 16 Output Data Setting (setting method is the same as above)
* Not displayed when the value of the linearization parameter of the condition
data is smaller than 16.
Enter Return to measurement
For example, when the linearization function is OFF, and you wish to change the displayed value on the meter from 0
- 1000 to 0 - 1200, set N01.I (Correction Point 1 Input Data) and N01.O (Correction Point 1 Output Data) to 0, N02.I
(Correction Point 2 Input Data) to 1000, and N02.O (Correction Point 2 Output Data) to 1200.
In this case, the line between Correction Points 1 and 2 behaves according to the linearity correction setting. When the
value of the input data exceeds that at Correction Point 2, the behavior of the output data is no longer affected by the
setting (the value of the output data changes from 1200 to 1001). When more than two correction points are set, the
behavior of a line connecting two sequential correction points is different from that of the next two in sequence.
6 Memory mode
It is possible to display maximum value, minimum value, (maximum value - minimum value) and input value on the main monitor. Long pressing the Mode
Key results in displaying the maximum value. Press the Enter Key to return to normal display.
Measured maximum value, minimum value and (maximum value - minimum value) are always stored in memory (with the power turned on) and these data
values are cleared by long pressing the Mode Key. In addition, each of these maximum value, minimum value and (maximum value - minimum value) is
displayed in red, while the input value is displayed in green.
Measurement operation
Mode
Mode
The value in which minimum value is pulled from the
maximum value is displayed.( Red)
*The decimal point of 100 digits and 103 digits
turn on and off.
Mode
The input value is displayed.( Green)
*The decimal point of 102 digits and 103 digits turn on and off.
If the mode key is pushed, it becomes maximum value display.
Mode *The display changes sequentially.
Maximum →Mnimum →( MaximumーMnimum) →Input →Maximum
Mode It pushes long( About 3 seconds)
Enter
Display usually.
Enter Mode