• Hardware Reference Guide, 04-XX001-XX-en
Dimensions
NOTICE
CONTROLLER DAMAGE
Use the DIN rail end clip when you install the controller on a
vertical DIN rail.
Failure to follow these instructions can result in equipment
damage.
02-30032-02-en, March 2019 | 2
Connections
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power connected to this equipment before working on the equipment.
Failure to follow these instructions will result in death or serious injury.
02-30032-02-en, March 2019 | 3
Connections, continued
NOTICE
CONTROLLER DAMAGE
Before powering up the controller, ensure that the input power polarity is correct and that the voltage level meets the specifications of the
controller.
Failure to follow these instructions can result in equipment damage.
NOTICE
LOSS OF COMMUNICATION
Do not use a USB cable that exceeds 3 m (10 ft).
Failure to follow these instructions can result in loss of communication.
NOTICE
LOSS OF COMMUNICATION
• Ensure that the total length of the sensor bus does not exceed 61 m (200 ft).
• Use a Cat 5 or higher unshielded twisted pair cable with eight conductors (four twisted pairs), a cross-sectional area of 22 to 26 AWG
(0.34 to 0.14 mm2), and a rating that meets the requirements of the target environment.
Failure to follow these instructions can result in loss of communication.
02-30032-02-en, March 2019 | 4
Connections, continued
RP-C-12A-F-24V SXWRCF12A10001
RP-C-12B-F-24V SXWRCF12B10001
Specifications
AC input Operation environment Ub – Universal I/O
Nominal voltage Ambient temperature, operating Input rating
24 VAC 50/60 Hz 0 to 50 °C (32 to 122 °F) at normal operation 24 VDC , 2.4 mA
Power consumption -40 to +60 °C (-40 to +140 °F) for rooftop Voltage output rating
23 VA applications, horizontal installation only 0 to 10 VDC , 5 kohm (min.)
See section Installation Orientation Channels
DC input Restrictions. RP-C-12A: 8; -12B: 8; -12C: 4
Nominal voltage Humidity
24 to 30 VDC Maximum 95 % RH non-condensing DO – Relay outputs
Power consumption Relay contact rating
14 W Mechanical Pilot Duty (C300)
Ingress protection rating Min. current: 100 mA (5 VDC)
Port types IP 20 Resistive: 250 VAC / 30 VDC ,
USB device port Plastic flame rating 4 A (cos phi = 1)
Mini-B UL94-5VB Inductive: 250 VAC / 30 VDC ,
USB host port 4 A (cos phi = 0.4)
Type-A, 5 VDC, 0.5 A IP networking Channels
Ethernet port 1 and 2 IP address assignment methods RP-C-12A: 0; -12B: 3; -12C: 3
10/100BASE-TX RJ45 Static, DHCP, Auto-IP (address range
Sensor Bus 169.254.0.1 to 169.254.255.254, subnet DO – High power relay outputs
24 VDC, 2 W, RS-485 (RJ45) mask 255.255.0.0) Relay contact rating
Room Bus Pilot Duty (B300)
24 VDC, 3 W, RS-485 (RJ45) Regulatory compliance Normally Open, resistive: 250 VAC
EMC, safety, and environment / 24 VDC , 12 A (cos phi = 1)
Wireless connectivity FCC (ID: DVE-RPC24), ISED (IC: 24775- Normally Closed, inductive: 250 VAC
® ®
Bluetooth Low Energy (Bluetooth 5) RPC24), RCM, CE - RED 2014/53/EU, CE - / 24 VDC , 3 A (cos phi = 0.4)
2.402 to 2.480 GHz, max. 10 dBm output EMCD 2014/30/EU, CE - LVD 2014/35/EU, Channels
power, 100 m (328 ft) line-of-sight range WEEE 2012/19/EU, RoHS 2015/863/EU, RP-C-12A: 0; -12B: 1; -12C: 1
Antenna China RoHS SJ/T 11364-2014, UL 916 Listed
Integrated antenna products for the United States and Canada DO – Solid-state relay outputs
Approved external antenna (optional) (UL file E80146), UL 2043 (Approved for Output rating
Manufacturer: Linx Technologies, Model: plenum installations) 30 VAC / 30 VDC ,2A
ANT-2.4-WRT-MON-SMA, Gain: 0.8 dBi, Max. 4 A total load
Type: Monopole, Impedance: 50 ohm, Channels
Connector: SMA RP-C-12A: 4; -12B: 0; -12C: 4