Installation Sheet 02-30033-02-en, March 2019 | 1

RP-C-16A Model
SmartX IP Controller
Regulatory Compliance and Safety Information
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this material.
Read these instructions and all information relevant for this product carefully before trying to install it. See the list of technical literature.
The technical literature and declarations of conformity can be accessed on the Schneider Electric Exchange website, ecobuilding.schneider-
electric.com. Contact your local Schneider Electric sales office for hard copy of documentation or for additional information.

Technical Literature
• Hardware Reference Guide, 04-XX001-XX-en

Recommended Installation Location


The controller is intended for fan coil, ceiling systems, and other applications. The controller is typically installed next to or inside the fan coil
equipment. The controller can be equipped with optional covers to reduce access to the screw terminals and wires.

Dimensions

Installing the Device on a DIN Rail


Installation Orientation Restrictions
NOTICE
CONTROLLER DAMAGE
Use the DIN rail end clip when you install the controller on a
vertical DIN rail.
Failure to follow these instructions can result in equipment
damage.
02-30033-02-en, March 2019 | 2

Installing the Device on a Flat Surface

Installing and Removing the Optional Covers

Connections

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power connected to this equipment before working on the equipment.
Failure to follow these instructions will result in death or serious injury.
02-30033-02-en, March 2019 | 3

Connections, continued

NOTICE
CONTROLLER DAMAGE
Before powering up the controller, ensure that the input power voltage level meets the specifications of the controller.
Failure to follow these instructions can result in equipment damage.

NOTICE
LOSS OF COMMUNICATION
Do not use a USB cable that exceeds 3 m (10 ft).
Failure to follow these instructions can result in loss of communication.

NOTICE
LOSS OF COMMUNICATION
• Ensure that the total length of the sensor bus does not exceed 61 m (200 ft).
• Use a Cat 5 or higher unshielded twisted pair cable with eight conductors (four twisted pairs), a cross-sectional area of 22 to 26 AWG
(0.34 to 0.14 mm2), and a rating that meets the requirements of the target environment.
Failure to follow these instructions can result in loss of communication.

Product Part number


Wiring
For information on wiring, including connection diagrams, rating of Optional covers SXWRPCCOV10001
and location of fuses (circuit breakers), and cable specifications,
see the Hardware Reference Guide. DIN-rail end clip, 25 pieces SXWDINEND10001

Part Numbers
Product Part number

RP-C-16A-F-230V SXWRCF16A10002
02-30033-02-en, March 2019 | 4

Specifications
AC input Approved external antenna (optional) Voltage output rating
Nominal voltage Manufacturer: Linx Technologies, Model: 0 to 10 VDC , 5 kohm (min.)
230 VAC 50/60 Hz ANT-2.4-WRT-MON-SMA, Gain: 0.8 dBi, Channels
Power consumption Type: Monopole, Impedance: 50 ohm, 8
65 VA Connector: SMA
DO – Relay outputs
AC output Operation environment Relay contact rating
Type Ambient temperature, operating Pilot Duty (C300)
Isolated output 0 to 50 °C (32 to 122 °F) Min. current: 100 mA (5 VDC)
Nominal voltage See section Installation Orientation Resistive: 250 VAC / 30 VDC ,
24 VAC 50/60 Hz Restrictions. 4 A (cos phi = 1)
Power rating Humidity Inductive: 250 VAC / 30 VDC ,
19 VA Maximum 95 % RH non-condensing 4 A (cos phi = 0.4)
Overvoltage category Channels
III Mechanical 3
Pollution degree Ingress protection rating
2 IP 20 DO – High power relay outputs
Plastic flame rating Relay contact rating
Port types UL94-5VB Pilot Duty (B300)
USB device port Normally Open, resistive: 250 VAC
Mini-B IP networking / 24 VDC , 12 A (cos phi = 1)
USB host port IP address assignment methods Normally Closed, inductive: 250 VAC
Type-A, 5 VDC, 0.5 A Static, DHCP, Auto-IP (address range / 24 VDC , 3 A (cos phi = 0.4)
Ethernet port 1 and 2 169.254.0.1 to 169.254.255.254, subnet Channels
10/100BASE-TX RJ45 mask 255.255.0.0) 1
Sensor Bus Regulatory compliance
24 VDC, 2 W, RS-485 (RJ45) DO – Solid-state relay outputs
EMC, safety, and environment Output rating
Room Bus RCM, CE - RED 2014/53/EU, CE - EMCD
24 VDC, 3 W, RS-485 (RJ45) 30 VAC / 30 VDC ,2A
2014/30/EU, CE - LVD 2014/35/EU, WEEE Max. 4 A total load
Wireless connectivity 2012/19/EU, RoHS 2015/863/EU, China Channels
Bluetooth® Low Energy (Bluetooth® 5) RoHS SJ/T 11364-2014, eu.bac certified 4
2.402 to 2.480 GHz, max. 10 dBm output product (pending)
power, 100 m (328 ft) line-of-sight range Ub – Universal I/O
Antenna Input rating
Integrated antenna 24 VDC , 2.4 mA

© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.