Conductors in Parallel
Exception No. 4: Under the supervision of a licensed electrical instrument cases shall not be smaller than 3.5 mm2 (2.0 mm
engineer, grounded neutral conductors in sizes 30 mm2 and dia.) copper or 5.5 mm2 (2.6 mm dia.) aluminum.
larger shall be permitted to be run in parallel for existing
installations. What are the conductors(min. size)for circuit wires having a
circuit rating of 15A?- 2.0 mm2
Conductors in Parallel. Aluminum, copper-clad aluminum, or
copper conductors of size 50 mm2 and larger, comprising Minimum size of copper conductor voltage rating 15001-
each phase, polarity, neutral, or grounded circuit conductor, 28000 volts? - 38 mm2
shall be permitted to be connected in parallel (electrically
joined at both ends). Multiconductor flat cable 22 mm2 or larger shall be permitted
to employ an external ridge on the grounded conductor.
Grounding electrode conductors smaller than 14 mm2 shall be
in rigid metal conduit, intermediate metal conduit, rigid non- Connected to Rod, Pipe, or Plate Electrodes. Where
metallic conduit, electrical metallic tubing, or cable armor. connected to rod, pipe, or plate electrodes, that portion of
the grounding electrode conductor that is the sole
Connected to a Concrete-Encased Electrode. Where connection to the grounding electrode shall not be required
connected to a concrete-encased electrode as in that to be larger than 14 mm2 copper wire or 22 mm2 aluminum
portion of the grounding electrode conductor that is the sole wire.
connection to the grounding electrode shall not be required
to be larger than 22 mm2 copper wire. Loads for structural additions to an existing dwelling unit or
for a previously unwired portion of an existing dwelling unit,
An insulated grounded conductor of 14 mm2 or smaller shall either of which exceeds 46.5 m2 (500 ft2), shall be calculated
be identified by a continuous white or gray outer finish or by in accordance with Lighting load for specified occupancies
three continuous white stripes on other than green insulation and other laods - all occupancies.
along its entire length.
Common Grounding Electrode Conductor Size. The common
Grounding conductors not an integral part of a cable grounding electrode conductor shall not be smaller than 80
assembly shall not be smaller than 14 mm2 copper or 22 mm2 mm2 copper or 125 mm2 aluminum.
aluminum.
The size of the system bonding jumper for a system that
Insulated Fittings. Where raceways containing ungrounded supplies a Class 1, Class 2, or Class 3 circuit, and is derived
conductors 22 mm2 or larger enter a cabinet, box enclosure, from a transformer rated not more than 1000 volt-amperes,
or raceway, the conductors shall be protected by a shall not be smaller than the derived phase conductors and
substantial fitting providing a smoothly rounded insulating shall not be smaller than 2.0 mm2 (1.6 mm dia.) copper or 3.5
surface, unless the conductors are separated from the fitting mm2 (2.0 mm dia.) aluminum.
or raceway by substantial insulating material that is securely
fastened in place. Where the dc system consist of a 3-wire balancer set or a
balancer winding with overcurrent protection, the grounding
Size — Equipment Bonding Jumper on Load Side of Service. electrode conductor shall not be smaller than the largest
The equipment bonding jumper on the load side of the conductor supplied by the system, and not smaller than 8.0
service overcurrent devices shall be sized, as a minimum, but mm2 (3.2 mm dia.) copper or 14 mm2 aluminum.
shall not be required to be larger than the largest
ungrounded circuit conductors supplying the equipment and
shall not be smaller than 2.0 mm2 (1.6 mm dia.).