Professional Documents
Culture Documents
May 2009
Systems Operation
Testing and Adjusting
Disassembly and
Assembly
SR4B Generator
SAFETY.CAT.COM
i01658146
Table of Contents
Systems Operation Section
General Information ................................................ 4
Component Descriptions ........................................ 5
Generator Operation ............................................. 12
Lead Connections ................................................. 20
Glossary ................................................................ 24
Index Section
Index ..................................................................... 75
4 SENR5359-11
Systems Operation Section
General Information
SMCS Code: 4450
g00609958
Illustration 3
SR4B Generator
(1) Generator terminal strip
(2) Main armature (stator)
(3) Main field (rotor)
(4) Rotor shaft
(5) Permanent magnet pilot exciter (PMPE)
(6) Exciter
g00611770 (7) Bearing
Illustration 1 (8) Fan
Generator Set
The SR4B generator has the following characteristics:
i01152505
Component Descriptions
SMCS Code: 4450
g00611832
Illustration 4
PMPE Type Components
(1) Rectifiers (5) Exciter field (stator) (8) Main field (rotor)
(2) Pilot exciter field (permanent magnet) (6) Bearing with a sleeve for 3500 Engine (9) Rotor shaft
(3) Pilot exciter armature (PM armature) Family only (10) Fan
(4) Exciter armature (rotor) (7) Main armature (stator)
6 SENR5359-11
Systems Operation Section
g00611839
Illustration 5
PMPE Type Components with a Pilot Exciter
(1) Rectifiers (5) Pilot exciter field (permanent magnet) (9) Rotor shaft
(2) Exciter field (stator) (6) Bearing (10) Fan
(3) Exciter armature (rotor) (7) Main armature (stator)
(4) Pilot exciter armature (PM armature) (8) Main field (rotor)
SENR5359-11 7
Systems Operation Section
g00611845
Illustration 6
SE Type Components with Inboard Bearing
(1) Rectifiers (4) Bearing (7) Rotor shaft
(2) Exciter field (stator) (5) Main armature (stator) (8) Fan
(3) Exciter armature (rotor) (6) Main field (rotor)
8 SENR5359-11
Systems Operation Section
g00611851
Illustration 7
SE Type Components (Outboard Bearing)
(1) Bearing (4) Rectifiers (7) Rotor shaft
(2) Exciter armature (rotor) (5) Main field (rotor) (8) Fan
(3) Exciter field (stator) (6) Main armature (stator)
SENR5359-11 9
Systems Operation Section
g00611856
Illustration 8
Two-Bearing Generator (PMPE Type Components)
(1) Rectifiers (5) Exciter field (stator) (8) Main field (rotor)
(2) Pilot exciter field (permanent magnet) (6) Bearing with a sleeve for 3500 Engine (9) Rotor shaft
(3) Pilot exciter armature (PM armature) Family only (10) Fan
(4) Exciter armature (rotor) (7) Main armature (stator)
g00626058
Illustration 9
SR4B generator that is used with a 3406E engine
(1) Rectifiers (4) Bearing (7) Fan
(2) Exciter armature (rotor) (5) Main armature (stator) (8) Rotor shaft
(3) Exciter field (stator) (6) Main field (rotor)
10 SENR5359-11
Systems Operation Section
g00611866
Illustration 11
RFA Components (PMPE Type)
(1) Pilot exciter field (permanent magnet)
(2) Exciter armature (rotor)
(3) Bearing
(4) Main field (rotor)
(5) Rotor shaft
(6) Rectifiers
g00609975
Illustration 10
PMPE Generator Wiring Diagram
(CR1 - CR6) Diodes
(CR7) Varistor
(L1) Exciter field (stator)
(L2) Exciter armature (rotor)
(L3) Main field (rotor)
(L4) Main armature (stator) g00611892
(L5) Pilot exciter armature Illustration 12
(PM) Permanent magnet Main Armature (Stator (L4))
(R5) Resistor
(RFA) Rotating field assembly
(TR1) Optional Voltage droop transformer
The generator main armature is stationary and
(T0, T1, T2, T3, T7, T8, T9) Generator Terminals and/or Generator the generator main armature contains the stator
leads windings.
SENR5359-11 11
Systems Operation Section
g00611914 g00611961
Illustration 13 Illustration 16
g00611951
Illustration 14
Exciter Armature (Rotor (L2))
g00610186
Illustration 17
Two Diode Rectifier Block
g00611956
Illustration 15
Exciter Field (Stator (L1))
12 SENR5359-11
Systems Operation Section
i01149466
Generator Operation
SMCS Code: 4450
g00610236
Illustration 18
Three Diode Rectifier Block
(1) Positive rectifier block
(2) Negative rectifier block
g00609958
Illustration 20
SR4B Generator
(1) Generator terminal strip
(2) Main armature (Stator)
(3) Main field (Rotor)
(4) Rotor shaft
(5) Permanent magnet pilot exciter
(6) Exciter
(7) Bearing
(8) Fan
Permanent Magnet Pilot Excited Permanent magnet pilot excited generators receive
power for the voltage regulator from a pilot exciter.
(PMPE) Generator Self-excited generators receive power for the
voltage regulator from the main armature. The
pilot exciter consists of permanent magnet (PM)
and Pilot Exciter Armature (L5). The pilot exciter
operates independently from the generator output
voltage. Constant excitation during a large load
application is possible. Constant excitation is
possible because the irregularities that occur in the
generator output voltage are not fed back into the
exciter. The irregularities that occur in the generator
output voltage are caused by load conditions. The
independent operation also allows the generator to
sustain excessive currents for short periods of time.
Illustration 21
g00609975 The DC output from the bridge rectifier is carried
PMPE Generator Wiring Diagram to main field (L3) by conductors which are routed
through a passage in the generator shaft. Current
(CR1 - CR6) Diodes
(CR7) Varistor through the main field creates the magnetic field of
(L1) Exciter field (stator) the generator. As the main field rotates, the main field
(L2) Exciter armature (rotor) induces a three-phase AC voltage in main armature
(L3) Main field (rotor) (L4). This voltage is sent to the following terminals:
(L4) Main armature (stator)
(L5) Pilot exciter armature
T0, T1, T2, and T3. These terminals are connections
(PM) Permanent magnet for the load.
(R5) Resistor
(RFA) Rotating field assembly To keep the output voltage constant with changing
(TR1) Optional Voltage droop transformer loads, it is necessary to control the exciter current.
(T0, T1, T2, T3, T7, T8, T9) Generator terminals and/or Generator
leads This control is the function of the voltage regulator.
The voltage regulator senses the generator output
voltage at the following wires: “20”, “22”, and “24”.
The regulator sends current to the exciter through
wires “F1” and “F2”. The amount of current is
dependent on the sensed voltage. The current is
drawn from the pilot exciter and the armature (wires
“11”, “12”, and “13”). Regardless of the generator's
type (PMPE generator or self-excited generator),
changing the exciter current has the same effect on
the generator's operation. See the topic Self-Excited
Generators for a description of generator operation
when the exciter current changes.
14 SENR5359-11
Systems Operation Section
Note: For more information on voltage regulation, Self-excited generators receive the power for
see the appropriate voltage regulator service manual. excitation from the generator armature (the generator
output). When the engine starts turning the Rotating
PMPE generators provide the magnetism for start-up Field Assembly (RFA), the residual magnetism in
of the generator. A Permanent Magnet (PM) supplies exciter field (L1) causes a small amount of AC voltage
the initial magnetism that is required at start-up. to be generated in exciter armature (L2). Induced
Flashing the field is not required for start-up of the voltage causes current to flow. This current is present
generator. in the exciter armature. The AC is then rectified by
a three-phase full-wave bridge rectifier circuit. This
rectifier circuit is made of the following diodes: CR1,
Self-Excited (SE) Generators CR2, CR3, CR4, CR5, and CR6. Direct current then
flows through main field (L3). The flow of DC through
the main field creates a magnetic field. This magnetic
field adds to the existing residual magnetism of the
main field. As the main field rotates, an AC voltage
is induced into main armature (L4) which appears
as a three-phase AC voltage at the following output
terminals: T0, T1, T2, and T3. The voltage regulator
taps the AC output through wires: “20”, “22”, and “24”.
During start-up, this tapped output is sensed by the
voltage regulator. The voltage regulator senses the
output as a low-voltage output condition. Therefore,
the voltage regulator output to the exciter field is
increased so that the generator output will continue
to increase up to the rated voltage.
When the voltage regulator senses an increase in Three-diode rectifier block – The three-diode
output voltage, the voltage regulator will decrease rectifier block contains three diodes. Two different
the DC voltage to the exciter. This will result in a blocks are required. One block is positive and the
decrease in generator output voltage. other block is negative.
Residual magnetism is necessary for start-up of the Six-diode rectifier block – The six-diode rectifier
self-excited generator. The main field coils are wound block contains six diodes. One block is required.
on magnetic steel which retains a small amount of
magnetism after shutdown. After time and certain Rectifying the current creates heat. The rotating
conditions, the residual magnetism may decrease. rectifier blocks are fastened to heat sinks. These heat
The residual magnetism will then be insufficient to sinks spread the heat. These heat sinks also allow
start the generating process. If this occurs, refer to the rotating rectifier blocks to operate at a cooler
Testing And Adjusting Section, “Exciter Field - Flash”. temperature.
g00610163 g00610186
Illustration 23 Illustration 24
Rectifier Circuit Two-diode rectifier block
(CR1 - CR6) Diodes
(CR7) Varistor
(L2) Exciter armature (rotor)
(L3) Main field (rotor)
(R5) Resistor
g00610236
Illustration 27
Three-diode rectifier blocks
(1) Positive rectifier block
(2) Negative rectifier block
g00610202
Illustration 26
The wiring of the three two-diode rectifier blocks
(1) “L2” (wire passage)
(2) Heat sink assembly
(3) Three two-diode rectifier blocks
(4) “L3” (wire passage)
(5) R5
(6) CR7
g00610322
Illustration 30
Six-Diode Rectifier Block
g00610241
Illustration 29
The wiring of the three-diode rectifier blocks
(1) Positive rectifier block
(2) Negative rectifier block
(3) “L3” (two-wire passage)
(4) Heat sink assembly
(5) R5
(6) “L2” (three-wire passage)
(7) CR7
g00610335
Illustration 32
Six-Diode Rectifier Block Location (Outboard Bearing)
(1) Exciter
(2) Six-Diode Rectifier Block
(3) Disc
(4) Main Field
Space Heaters
g00610379
Illustration 34
Varistor (CR7)
g00610396
Illustration 36
Space Heater Connection Diagram
g00611486
Illustration 38
Six Lead Wye Connection Diagram
SENR5359-11 21
Systems Operation Section
g00611596
Illustration 40
Ten Lead Wye Connection Diagram (Low Voltage)
Table 4
g00611584
Illustration 39
Ten Lead Wye Connection Diagram (High Voltage)
Table 3
Connect T4 - 22
and T7
T2 T2 -
Connect T5 - 24
and T8
T3 T3 -
Connect T6, T9 - 20
T0 Neutral -
22 SENR5359-11
Systems Operation Section
Twelve Lead Wye Connection (High Twelve Lead Wye Connection (Low
Voltage) Voltage)
g00611603 g00611608
Illustration 41 Illustration 42
Twelve Lead Wye Connection Diagram (High Voltage) Twelve Lead Wye Connection Diagram (Low Voltage)
Table 5 Table 6
TWELVE LEAD WYE CONNECTIONS (HIGH TWELVE LEAD WYE CONNECTIONS (LOW
VOLTAGE) VOLTAGE)
Generator Lead Line Lead Regulator Generator Lead Line Lead Regulator
Load Lead
T1 T1 - Connect T1 and T7 T1 22
Connect T4 and T7 - 22 Connect T2 and T8 T2 24
T2 T2 - Connect T3 and T9 T3 20
Connect T5 and T8 - 24 Connect T4, T5, T6, T10, Neutral -
T11, and T12
T3 T3 -
Connect T6 and T9 - 20
Connect T10, T11, Neutral -
and T12
SENR5359-11 23
Systems Operation Section
g00611618 g00611504
Illustration 43 Illustration 44
Six Lead Delta Connection Diagram Twelve Lead Delta Connection Diagram
Table 7 Table 8
Depending on the connections that are made Direct Current (DC) – Direct current is current flow
between the load and the generator line leads, that moves in only one direction in a given circuit.
single-phase voltages and/or three-phase voltages
are possible. For more information, refer to Operation Damping – Damping refers to decreasing the
and Maintenance Manual, LEKQ7119, “Engine Data amplitude of a signal.
Sheet”. Refer to Connection Diagrams, SENR4794.
De-energized – A de-energized input refers to
stopping the current that is going to a component.
i01731631
Anode – An anode is the positive end of a diode or Excitation – Excitation is controlled direct current
an anode is the positive end of a rectifier. (DC) that is used to make a magnetic field.
Blocking Rectifier – A blocking rectifier permits Energized – An energized input refers to activating
direct current flow in only one direction. a device.
Bolted – A bolted device uses a bolt to hold two or Electrostatic Charge – Electrostatic charge is
more parts together. electricity that is caused by induced voltage and
stored charge.
Bridge – A bridge is a circuit that is used to measure
small quantities of current, voltage, or resistance. Exciter – An exciter supplies direct current (DC) to
the field windings of the generator.
Bridge Rectifier – A bridge rectifier is a circuit that
is used to change alternating current (AC) to direct Field – A field is a magnetic line of force that
current (DC). surrounds a conductor. This force is caused by
current flow in the conductor.
Buildup – A buildup is a gradual increase in voltage.
Field Windings – Field windings are many turns of
Cathode – A cathode is the negative end of a diode wire that are wrapped around an iron core. When
or a cathode is the negative end of a rectifier. direct current (DC) flows through the field windings,
a magnetic field is produced. This magnetic field is
Capacitance – Capacitance is the ability to store comparable to the magnetic field of a bar magnet.
an electrical charge.
Flashing – Flashing is a process of putting direct
Capacitor – A capacitor is a device that will store current from an external source into the field
an electrical charge. windings. This process causes the generator to
produce an output voltage.
Circuit Breaker – A circuit breaker is an automatic
switch that is used to open a circuit. Flux – Flux is magnetic lines of force.
Circulating Current – Circulating current is the flow Full-Wave Rectifier – A full-wave rectifier changes
of current between two or more generators that are the positive phase and the negative phase of
working in parallel. Circulating current is also the flow alternating current to direct current.
of current between two or more generators that are
parallel with a utility line. Gain – Gain relates to the relationship between input
magnitude and output magnitude.
Conduct – Conducting relates to allowing the flow of
current. Gate – A gate is an electronic part of a controlled
rectifier (thyristor).
Continuity – Continuity provides a path for current
flow. Generate – This refers to the process of making
electricity.
Control – A control is a device that controls another
device. A control is also a circuit that controls a Grounded – A device is grounded by making
device. a connection to ground. A device could also be
grounded by making a connection to a component
that is connected to ground.
SENR5359-11 25
Systems Operation Section
Humidity – Humidity is the water content that is Phase Winding – A phase winding is a group of
present in the air. generator stator coils. Electric power for one phase
of the load is induced in the phase winding.
Impedance – Impedance is the resistance to
alternating current. Polarity – Polarity is the positive characteristics or
the negative characteristics of two poles.
Impulse Modulation – Impulse modulation changes
the following characteristics of a wave: amplitude, Pulsating – Pulsating relates to the characteristics
frequency, and phase. This is accomplished by of current that are similar to mechanical vibration.
impressing one wave on another wave that has
constant properties. Radio Suppression – Radio suppression reduces
the amplitude of radio frequency interference.
Induce – This refers to the transfer of power from
one device to another device. The transfer is done Reciprocating – Reciprocating motion is motion
via a magnetic field or via an electric field. that first moves in a straight line in one direction. The
direction of this motion then varies by 180 degrees.
Interference – Interference is an unwanted mixture
of electrical signals. Interference is usually associated Rectifier – A rectifier is a diode circuit that converts
with electrical noise. alternating current (AC) to direct current (DC).
Make sure the testing equipment is designed for Personal injury or death can result from high volt-
and correctly operated for high voltage and cur- age.
rent tests being made.
When power generation equipment must be in op-
When servicing or repairing electric power gener- eration to make tests and/or adjustments, high
ation equipment: voltage and current are present.
• Make sure the unit is off-line (disconnected Improper test equipment can fail and present a
from utility and/or other generators power high voltage shock hazard to its user.
service) , and either locked out or tagged DO
NOT OPERATE. Make sure the testing equipment is designed for
and correctly operated for high voltage and cur-
• Remove all fuses. rent tests being made.
Table 9 i01155184
Problem List
Table 10
The generator set functional test is a simplified test 6. The measured voltages of Step 4 should be at
that can be performed in order to determine if the least 85 VAC. With a 10% increase in generator
generator is functional. The final test should be on set speed, the voltages of Step 5 should show
the complete generator set while the generator is an increase of 10%. With a 10% decrease in
under load. The generator set functional test will generator set speed, the voltages of Step 5 should
determine if a phase voltage is being generated. show a decrease of 10%.
The generator set functional test will also determine
if the phase voltages are balanced. In addition, this Note: If the engine speed cannot be adjusted to half
test will determine if the phase voltages change with of the rated speed, a 6 VDC battery can be used.
engine speed. The 6 VDC battery would be connected to wires F1+
and F2- in Step 2.
The generator set functional test consists of the
following steps:
i02440023
TOOLS NEEDED
NOTICE
Do not operate the generator set at a speed that is Part Number Tool Quantity
higher than one-half of the rated speed. 6V-7070 Digital 1
Multimeter
Higher speeds under these test conditions can cause
damage to the system. 243-3134(1) Tester Group 1
(1) Or equivalent.
Personal injury or death can result from improper Do not connect generator to a utility electrical dis-
troubleshooting and repair procedures. tribution system unless it is isolated from the sys-
tem. Electrical feedback into the distribution sys-
The following troubleshooting and repair proce- tem can occur and could cause personal injury or
dures should only be performed by qualified per- death.
sonnel familiar with this equipment.
Open and secure main distribution system switch,
or if the connection is permanent, install a double
throw transfer switch to prevent electrical feed-
back. Some generators are specifically approved
Personal injury or death can result from high volt- by a utility to run in parallel with the distribution
age. system and isolation may not be required. Always
check with your utility as to the applicable circum-
When power generation equipment must be in op- stances.
eration to make tests and/or adjustments, high
voltage and current are present.
Procedure
Improper test equipment can fail and present a
high voltage shock hazard to its user. The two following procedures test the ability of the
normal state of two different varistors. The following
Make sure the testing equipment is designed for procedures are to be used for the 9Y-9412 Varistor
and correctly operated for high voltage and cur- (CR7) and the 4P-6009 Varistor (CR7. Determine
rent tests being made. which varistor is being used in your application, then
use the appropriate procedure. If any meter reading
When servicing or repairing electric power gener- does not fall within the given ranges, replace the
ation equipment: varistor (CR7).
NOTICE
Do not over torque. Applying torques greater than the
listed torques may cause damage to the components.
32 SENR5359-11
Testing and Adjusting Section
6. Install leads. Apply the following torques. • Varistor mounting to heat sink - 8.1 N·m
(72 lb in) to 16.3 N·m (144 lb in)
• Terminal connections - 1.4 N·m (12 lb in) to
1.7 N·m (15 lb in) Note: If the varistor (CR7) is found to be faulty, the
varistor (CR7) most likely failed due to a transient
• Varistor mounting to heat sink - 8.1 N·m voltage surge on the main rotor. Varistor failure is not
(72 lb in) to 16.3 N·m (144 lb in) usually a component failure. Root causes of varistor
(CR7) failure include:
Note: If the varistor (CR7) is found to be faulty, then
the varistor (CR7) most likely failed due to a transient • Incorrect paralleling or loss of synchronism
voltage surge on the main rotor. Varistor failure is not
usually a component failure. Root causes of varistor • Reverse VAR or reverse power event
(CR7) failure include:
• High ambient temperature (or other application
• Incorrect paralleling or loss of synchronism error)
Personal injury or death can result from improper • Make sure all batteries are disconnected.
troubleshooting and repair procedures.
• Make sure all capacitors are discharged.
The following troubleshooting and repair proce-
dures should only be performed by qualified per-
sonnel familiar with this equipment.
Shut off engine and remove key before perform-
ing maintenance or repair work. Failure to do so
may result in personal injury due to inadvertant
machine operation.
Note: A shorted diode can cause damage to the Note: Do not apply voltage to the varistor (CR7)
exciter rotor. If a diode is shorted, check the exciter for greater than 3 seconds..
rotor. Refer to the Testing and Adjusting, “Winding -
Test” and Testing and Adjusting, “Insulation - Test”. 5. Megohmmeter readings should be between 450
Perform these tests. VDC and 600 VDC.
Note: For a failed rectifier block, refer to the “Diode • If the readings are greater than 600 VDC, the
Block Troubleshooting Guide”, Table 15. The “Diode varistor (CR7) is OPEN.
Block Troubleshooting Guide” consists of a list of
items to consider when troubleshooting a failed diode • If the readings are less than 450 VDC, the
block and/or external varistor (CR7). The purpose of varistor (CR7) is SHORTED or DEGRADED.
this list is to find a cause for the diode block and/or
varistor (CR7) failure which may be external to the Note: Do not over torque. Applying torques greater
exciter system. The purpose of this list is NOT to than the listed torques may cause damage to the
troubleshoot “no voltage output” from the generator. components.
• Terminal connections - 2.35 N·m (20.8 lb in) to • Terminal connections - 2.35 N·m (20.8 lb in) to
3.36 N·m (29.7 lb in) 3.36 N·m (29.7 lb in)
• 9Y-0916 Rectifier Assembly (mounting to Note: If the varistor (CR7) is found to be defective,
heatsink) - 4.07 N·m (36 lb in) to 5.54 N·m the varistor (CR7) most likely failed due to a transient
(49 lb in) voltage surge on the main rotor winding. Varistor
failure is not usually a component failure. Root
NOTICE causes of varistor (CR7) failure include:
Do not over-torque. Applying torques greater than the
listed torques may cause damage to the components. • Incorrect paralleling or loss of synchronism
• Reverse VAR or reverse power event
SENR5359-11 35
Testing and Adjusting Section
• Loss of main rotor field due to voltage regulator 1. Set the digital multimeter on the diode range.
failure, diode rectifier failure, or other events Remove all leads from the rectifier block.
• High ambient temperature (or other application 2. To test the negative rectifier block, follow these
error) steps:
• Large sudden load application a. Place the red test lead on the negative “-”
terminal. Place the black test lead on the
following rectifier terminals: “AC1”(3), “AC2”(4),
Three Diode Rectifier Block and “AC3”(5). All readings on the meter should
be between 0.4 and 1.0.
Table 15
Diode Block Troubleshooting Guide
Check For Measurement OK/Failed
Diode checks? Diode short or open.
Internal varistor (CR7) OK or Failed.
External varistor (CR7) check - A shorted external varistor can cause diode block
OK or Failed? failure due to overcurrent.
A failed diode block can cause the external varistor
to fail due to the loss of the main rotor circuit,
overheat, and then become an open circuit.
ALL faults and alarms (both Was the unit in stable operation, starting up,
logged and active)? shutting down, or paralleling (trying to match
voltage and frequency before shutting the
breaker)?
Confirm that every engine shutdown or voltage
regulator shutdown will open the main generator
output breaker. How much time does it take to get
the breaker open?
Confirm kVAR or Power factor set point for voltage
regulator(s).
Check set point and correct operation of reverse
VAR and reverse kW relays.
Check set point and correct operation of minimum
excitation limiter.
Check set point and correct operation of maximum
excitation limiter.
Check set point and correct operation of loss of
field protection.
Table 16
TOOLS NEEDED
Part Number Tool Quantity
Digital
6V-7070 1
Multimeter
40 SENR5359-11
Testing and Adjusting Section
i01699697
Insulation - Test
Personal injury or death can result from electro-
SMCS Code: 4453-081; 4454-081; 4457-081; cution.
4470-081
The megohmmeter is applying a high voltage to
the circuit.
• moisture (water)
• dust
• grease
• other foreign matter within the generator
This deterioration reduces the resistance of the
insulation. This test will measure the resistance of
the winding insulation.
Illustration 54
g00874841 Note: For information on generator cleaning, refer to
PMPE Generator Wiring Diagram Special Instruction, SEHS9124.
(CR1-C6)Diodes
When generators have not been used for a period
(CR7) Varistor of time, moisture can accumulate. Therefore, the
(L1) Exciter Field (Stator) insulation test should be performed on generators
(L2) Exciter Armature (Rotor) that have been idle. If moisture is known to exist,
(L3) Main Field (Rotor) the windings must be dried prior to testing. Refer to
(L4) Main Armature (Stator)
Testing And Adjusting, “Generator - Dry”.
(L5) Pilot Exciter Armature
The winding needs to be reconditioned or the winding
(PM) Permanent Magnet needs to be replaced in the following cases:
(RFA) Rotating Field Assembly
(CT1) Optional Voltage Droop Transformer • The measured insulation resistance falls below the
(T0, T1, T2, T3, T7, T8, T9) Generator terminals specified amount. The cleanup procedure does not
correct the discrepancy.
Table 17
TOOLS NEEDED
• The measured insulation resistance falls below the
specified amount. The drying procedure does not
Part Number Tool Quantity correct the discrepancy.
142-5055 Insulation Tester 1
Megohmmeter
SENR5359-11 41
Testing and Adjusting Section
The specified insulation resistance is an approximate 4. Measure the resistance of the exciter field winding
value. It can be possible to operate the generator with insulation to ground. The insulation resistance
less than the specified value. However, a generator must be a minimum of 0.25 megohm (250000
that has a low winding insulation resistance will be ohms).
more likely to have a failure.
Exciter Armature (Rotor L2)
1. Isolate exciter armature (L2) from the rectifier
Personal injury or death can result from improper circuit. Disconnect the three wires of the exciter
troubleshooting and repair procedures. armature from the rectifier blocks.
The following troubleshooting and repair proce- 2. Connect one test lead of the insulation tester
dures should only be performed by qualified per- (megohmmeter) to the rotor shaft.
sonnel familiar with this equipment.
3. Connect one test lead of the insulation tester
(megohmmeter) to any one exciter field lead.
The insulation test gives accurate results only when
the generator windings are free of moisture and the 4. The insulation resistance must be a minimum of
generator windings are at room temperature. 0.25 megohm (250000 ohms).
Each winding must have a minimum insulation
resistance of one megohm. Pilot Exciter Armature L5
1. Isolate pilot exciter armature (L5) from the voltage
Main Armature (Stator L4) regulator. Disconnect wires 26, 28, and 30 of the
pilot exciter from the termination points. These
1. Remove the load from the generator by either wires are usually fused. These wires connect to a
opening the line circuit breaker or the load terminal strip or these wires connect to the voltage
connections to (T1), (T2), (T3), and (T0). Prevent regulator.
these wires from coming into contact with each
other and prevent these wires from contacting 2. Connect one test lead of the insulation tester
ground. (megohmmeter) to the generator enclosure
(ground).
2. Isolate main armature (L4) from the voltage
regulator by disconnecting wires 20, 22, and 24. If 3. Connect the other test lead of the insulation tester
generator lead (T0) is connected to the generator (megohmmeter) to any one lead of the pilot exciter
frame or ground, open the connection. armature.
3. Connect one test lead of the insulation tester 4. The insulation resistance must be a minimum of
(megohmmeter) to the generator enclosure 0.25 megohm (250000 ohms).
(ground).
i01699710
Generator - Dry
SMCS Code: 4450-569
NOTICE
Do not operate the generator if the windings are wet. If
the generator is operated when the windings are wet,
damage can occur due to insulation breakdown.
Table 18
Self-Circulating Air Method
TOOLS NEEDED
Run the engine and disconnect the generator load.
Part Number Tool Quantity
This will help circulate air. Operate the generator
6V-7070 Digital 1 space heaters.
Multimeter
SENR5359-11 43
Testing and Adjusting Section
NOTICE
Controlled Current Method Do not exceed the rated phase current that is listed on
the generator nameplate. Exceeding the rated phase
current will easily damage the generator windings.
Table 19 i01699714
g00614361
Illustration 59
Lead To Lead Connection (Generators with medium voltage or
less)
(1) Plated washer
g00614345 Table 20
Illustration 58
Terminal Strip Lead Connections TOOLS NEEDED
(1) Generator leads Part Number Tool Quantity
(2) Terminal strip (Bus Bar)
(3) Plated washer 5N-4685 Varnished cambric 1
electric tape
Attach the generator leads (1) to terminal strip (2) 15000 volt rating
in the following manner: 105 °C (221.0 °F) rating
5N-4686 Black vinyl plastic 1
1. When more than one lead attaches to the bus electrical tape
bar, place the leads on each side of the bus bar. −40 °C (−40.0 °F) to
Use flat plated washer (3) under the bolt head and 80 °C (176.0 °F) rating
under the nut.
When connecting the generator leads together or
2. After connecting the leads to the bus bar, group all when connecting generator leads to a load lead, use
generator phase leads together. Tie these leads the following procedure:
together.
1. Fasten the generator leads together by using flat
Ensure that there is a minimum clearance of 25 mm plated washer (1) under the bolt head and under
(1.0 inch) between uninsulated connections (phase the nut.
to phase and phase to ground).
2. Apply two layers of varnished cambric high voltage
tape. When the tape is being wrapped, the tape
must be overlapped. The tape must be overlapped
50% of the width of the tape. Taping must extend
length “B” onto the lead wire insulation. Length “B”
is equal to 25 mm (1.0 inch).
i01699728
NOTICE
Exciter Field - Flash Do not flash permanent magnet pilot excited (PMPE)
generators. Damage to the generator set can occur.
SMCS Code: 4470
Illustration 60
g00874825
Dynamic Flashing (Running
Wiring Diagram of the Self-Excited Generator
Engine)
(CR1-C6) Diodes
(CR7) Varistor
(L1) Exciter field (stator)
(L2) Exciter armature (rotor)
(L3) Main field (rotor)
(L4) Main armature (stator)
(RFA) Rotating field assembly
(CT1) Optional Voltage Droop Transformer
(T0, T1, T2, T3, T7, T8, T9) Generator terminals
Table 22
TOOLS NEEDED
Part Number Tool Quantity
6V-7070 Digital 1
Multimeter
9P-5153 Diode 1
(MR-504)
Dynamic 1
Flashing Circuit
NOTICE
Do not hold the flashing circuit's test leads on the ter-
minals longer than necessary. This can cause the volt-
age to become too high. Excessive voltage can cause
damage to the generator and can cause damage to
the flashing circuit.
Removal Procedure
Remove The Exciter Field and Remove
The Exciter Armature Illustration 64
g00619563
Terminal Strip
“F1” and “F2” first terminate at a terminal strip.
(1) Wires “F1” and “F2”
g00619571
Illustration 65
Two-Diode Rectifier Blocks (Three Pieces)
g00619559
Illustration 63
Voltage Regulator
“F1” and “F2” first terminate at a voltage regulator.
48 SENR5359-11
Disassembly and Assembly Section
g00619585 g00619592
Illustration 66 Illustration 68
Three-Diode Rectifier Block (One Piece) Generator with Outboard PM Pilot Exciter
(4) Bolts
(5) Mounting Assembly
(6) Retainer
g00619588
Illustration 67
Six-Diode Rectifier Block (One Piece)
(2) Screws
(3) Mounting Assembly
g00619613 g00619644
Illustration 70 Illustration 72
Shroud and Exciter Field Generator with Outboard PM Pilot Exciter
(10) Shroud (16) Bolt
(11) Exciter Field (17) Exciter Field
(12) Bolts
8. On generators with an outboard PM pilot exciter,
6. If equipped, remove four bolts (12) which fasten perform the following procedure:
shroud (10) and exciter field (11) to the generator.
Remove shroud (10) (if equipped) and exciter field a. Remove four bolts (16) which fasten exciter
(11) from the generator. field (17) to the generator.
g00620388
Illustration 71
Retainer and Exciter Armature
g00619666
(13) Exciter Armature Illustration 73
(14) Retainer Generator with Outboard PM Pilot Exciter
(15) Bolts
(18) Exciter Armature
(19) Spacer
7. Four bolts (15) and a retainer (14) are used to
fasten the exciter armature (13) to the rotor shaft. 9. On generators with an outboard PM pilot exciter,
Remove the four bolts and remove the retainer. perform the following procedure:
While the retainer is being removed, carefully
pass the generator leads through the retainer's a. Carefully slide spacer (19) off the rotor shaft.
opening. Remove exciter armature (13) from the
rotor shaft. b. As the spacer is slid off the rotor shaft, ensure
that the spacer clears the exciter leads.
g00619669
Illustration 74
Generator with Inboard PM Pilot Exciter
(20) Pilot Exciter Armature
(21) Pilot Exciter Field
(22) Spacer
(23) Bolts
1. On generators with an inboard PM pilot exciter, 3. On generators with an outboard PM pilot exciter,
perform the following procedure: perform the following procedure:
g00619644
g00619669 Illustration 77
Illustration 75
Generator with Inboard PM Pilot Exciter
a. Place exciter field (17) on the generator.
(20) Pilot Exciter Armature
(21) Pilot Exciter Field
(22) Spacer
b. Use four bolts (16) to fasten the exciter field
(23) Bolts to the generator.
SENR5359-11 51
Disassembly and Assembly Section
4. Slide exciter armature (13) on the rotor shaft. 7. Use four bolts (12) to attach shroud (10) (if
equipped) and exciter field (11) to the generator.
g00620388
Illustration 78
g00619603
Retainer and Exciter Armature Illustration 80
(13) Exciter Armature Generator with Outboard PM Pilot Exciter
(14) Retainer (7) Bolts
(15) Bolts (8) Rotating Pilot Exciter Field
(9) Stationary Pilot Exciter Armature
5. A retainer (14) is used to fasten the exciter
armature (13 ) to the generator. Carefully pass the 8. On generators with an outboard PM pilot exciter,
generator leads through the retainer's opening. perform the following procedure:
6. Use four bolts (15) to fasten the retainer to the a. Place stationary pilot exciter armature (9) and
generator. rotating pilot exciter field (8) on the generator.
Note: When the exciter armature (13) is installed, the b. Use four bolts to attach the stationary pilot
bolts (15) must be properly tightened. exciter armature (9) and rotating pilot exciter
field (8) to the generator.
Apply 9S-3263 Thread Lock to the bolts (15)
before the bolts are installed. Refer to Table 23 for 9. On generators with an outboard PM pilot exciter,
information regarding bolt torque. perform the following procedure:
Table 23
BOLT TORQUE
Bolt Size Torque
5/16 inch 35.4 N·m (26.11 lb ft)
3/8 inch 55.8 N·m (41.16 lb ft)
g00619592
Illustration 81
Generator with Outboard PM Pilot Exciter
(4) Bolts
(5) Mounting Assembly
(6) Retainer
End By:
i01161961
Generator - Remove
SMCS Code: 4450-011
Removal Procedure
g00619102
Illustration 84
Generator Terminal Box with a Typical 400 Frame
g00619076
Illustration 82
(1) Stationary pilot exciter armature
(2) Rotating pilot exciter field
g00619124
Illustration 86
Terminal Strips
g00619180
Illustration 88
Generator Terminal Box (Typical 600 Frame)
g00619154
Illustration 87
Terminal Strips (Control Panel interior)
g00619203 g00619206
Illustration 91 Illustration 93
Generator support (7) Screen
(8) Shield
(4) Support Beam
(9) Bolts
g00619261
Illustration 94
g00621148 (10) Bolts
Illustration 92
(11) Bolts
Generator ground strap
(5) Ground strap 11. Remove bolts (11) which fasten the fan and the
(6) Bolt coupling plate to the engine flywheel.
7. Remove bolt (6) that attaches ground strap (5) to 12. Remove bolts (10) which fasten the generator
the generator. housing to the flywheel housing.
SENR5359-11 55
Disassembly and Assembly Section
i01159488
Generator - Install
SMCS Code: 4450-012
Installation Procedure
All Generator Sets Except 3500 Engine
Family
Table 24
TOOLS NEEDED
Illustration 95
g00619267 Part Number Tool Quantity
(12) Bolts 8S-2328 Dial Indicator 1
(13) Coupling Plate Group
g00616707
Illustration 97
(1) Flywheel Pilot Bore
(2) Surface
g00295967
Illustration 98
(3) Dial Indicator Group
(4) Crankshaft Pulley
56 SENR5359-11
Disassembly and Assembly Section
2. In order to manually rotate the engine, remove 4. Install a full shim pack (5) and plate assembly (6)
the timing pointer's cover from the engine's on the generator with bolts (7). Tighten the bolts
flywheel housing. Install dial indicator group (3). to the torques that are shown in Table 25.
Refer to Illustration 98. The tip of the indicator
must touch the face of crankshaft pulley (4). Use Table 25
a bar between the flywheel and the flywheel REQUIRED TORQUE
housing in order to push the crankshaft toward
the flywheel. This will remove all the end play. Put Engine Torque
the dial indicator in the ZERO position. Move the D379, G379, D398, G398, 505 ± 45 N·m
crankshaft to the most forward position. Make a D399, G399 (372.0 ± 33.0 lb ft)
record of the total indicator reading (TIR). The TIR
is the end play of the crankshaft. All other engines Standard torque
g00616727
Illustration 99
(5) Shim Pack
g00295970
Illustration 101
(8) Guide Bolt
NOTICE
Do not run the generator set unless the plate assembly
has the correct clearance. If the plate assembly does
not have the correct clearance, damage can occur to
the engine and/or generator.
g00295967 g00616719
Illustration 103 Illustration 105
(11) Bolts
8. Install dial indicator group (3) in order to measure (12) Generator supports
crankshaft end play at crankshaft pulley (4).
In order to remove all end play, place a bar 11. Install all bolts (11) which fasten generator
between the flywheel and the flywheel housing. supports (12) to the base. Do not tighten. Align
Push the crankshaft toward the flywheel. Put the the generator to the engine. Go to the following
dial indicator in the ZERO position. Move the alignment procedure which corresponds to the
crankshaft to the most forward position and make particular generator set.
a record of the total indicator reading (TIR). Do not
use force to hold the crankshaft in position. The
TIR is the end play of the crankshaft.
g00616727
Illustration 104
Table 27
PARTS NEEDED
Part Number Part Quantity
5N-4479 Shim 6
5N-4478 Plate Assembly 1
Table 28
TOOLS NEEDED
g00616707
Illustration 106
(1) Flywheel Pilot Bore
(2) Surface
8S-2328 Dial Indicator 1
Group
g00617579
Illustration 107
(1) Dial indicator
g00617602
Illustration 108
(1) Straight edge (2) Flywheel (3) Flywheel housing
g00617618
Illustration 110
g00617620
Illustration 111
(7) Straight edge (8) End ring (9) Drive coupling
6. Move the rotor assembly to the rearmost position. 7. Take a standard set of seventeen 5N-4478 flex
Before proceeding, ensure that the air gap is plates. Bolt the plates together by using the
equal between the rotor assembly and the stator. flywheel mounting holes. The bolts should be
Position straight edge (7) across the diameter of tight, but not tightened to the final torque. Measure
end ring (8). See Illustration 111. the thickness of the plates in two locations along
the border.
a. Measure the distance from the top of straight
edge (7) to the mounting surface (H) of end ring a. Calculate the average of the two
(8). Record this value on “Line H” of Table 26. measurements. Record this value on
“Line K” of Table 26.
b. Measure the distance from the top of straight
edge (7) to the mounting surface (I) of drive 8. In order to determine the number of shims that
coupling (9). Record the value on “Line I” of are required to provide proper axial alignment,
Table 26. perform the calculation that is shown on “Line L” of
Table 26 (J - B - E - G - K = L). Record this value
c. Subtract “Line H” from “Line I”. Record this on “Line L” of Table 26.
value on “Line J” of Table 26 (I - H = J).
a. Divide the value of “Line L” by 0.8 mm
Note: Attachment of the straight edge (ferrous (0.032 inch). Record this new value on “Line M”
material) can be accomplished by using two magnetic of Table 26. The value that is shown on “Line M”
bases from the dial indicator. is the total number of shims. This value should
be rounded up to the nearest whole number.
SENR5359-11 63
Disassembly and Assembly Section
g00617618
Illustration 114
g00617698
Illustration 115
(11) Fan bolts
13. Install fan bolts (11) into the flywheel. Tighten the
fan bolts to standard torque.
g00617679
Illustration 113
(10) Bolts
14. Place a dial indicator on the vertical surface of Align Generator Sets With No Supports
the crankshaft throw cheek. Place another dial At The Flywheel Housing
indicator on the vertical surface of the heat sink
assembly. Refer to Step 12. Push the crankshaft
forward in order to determine the amount of end
play. The amount of crankshaft end play that is
shown on the dial indicator should be 0.178 mm
(0.0070 inch) to 0.635 mm (0.0250 inch). The
amount of heat sink end play that is shown on the
dial indicator should be 0.076 mm (0.0030 inch) to
0.635 mm (0.0250 inch).
Generator Alignment
Note: For the alignment procedure for two-bearing
close coupled generators, see Special Instruction,
SEHS7073, “Alignment Of Two Bearing Generators”.
g00616477
Illustration 118
(1) Base
(2) Generator support
(3) Shims
SENR5359-11 65
Disassembly and Assembly Section
(2) Bolts
g00616490
Illustration 119
Generator Set With Supports At The Flywheel Housing g00295996
Illustration 121
(1) Base (3) Support
(4) Bolt
1. If base (1) of the electric set is fastened to a (5) Shims
foundation, loosen all bolts that connect the base
to the foundation. Loosen all bolts that fasten the 4. While the generator is supported by a crane,
engine supports and generator supports to the loosen all bolts (2) that fasten the generator to the
base. flywheel housing. Tighten alternate bolts to the
final torque.
2. Ensure that there is enough clearance between
the bolts and the bolt holes in the base, engine 5. Check the clearance between the base and
supports and generator supports at all locations. the engine and generator supports at all four
locations. Check the clearance over the entire
3. Check the clearance between the base and the length of the supports. This is especially important
foundation at all mounting locations. Shims should on generators with long supports (3). Shims
be used in order to prevent the deflection of (5) should be installed until all of the mounting
the base as the bolts that connect the base to surfaces are flat and parallel.
the foundation are tightened. When there is no
deflection in the base, tighten all bolts that connect 6. Tighten all bolts that fasten the engine supports
the base to the foundation to the final torque. and the generator supports to the base to half of
the final torque. Loosen all bolts (2) that fasten
the generator to the flywheel housing. Measure
the gap between the generator and the flywheel
housing. Visually ensure that the bolts (2) are
centered in the clearance holes.
66 SENR5359-11
Disassembly and Assembly Section
i01158402
g00295997
Illustration 122
Rotor - Remove and Install
7. The gaps at locations (E), (G), (F), and (H) should
be more than 0.03 mm (0.0012 inch) and less SMCS Code: 4457-010
than 0.13 mm (0.005 inch). If the gaps at locations
(E) and (G) are not correct, adjust the number of Removal Procedure
shims under each generator support. If the gaps
at locations (F) and (H) are not correct, loosen the Start By:
bolts in the generator supports. Move the rear of
the generator to the right or left accordingly. a. Remove the generator. Refer to Disassembly and
Assembly, “Generator - Remove”.
8. After a correction has been made to the thickness
in the shims, tighten the generator support's bolts b. Remove the exciter field and remove the exciter
to half of the final torque 450 N·m (332.0 lb ft). armature. Refer to Disassembly and Assembly,
Check the gap at locations (E), (G), (F), and (H). “Exciter - Remove and Install”.
Repeat this procedure until the gap measurements
are 0.13 mm (0.005 inch) or less. Begin with Step
6.
g00615990
Illustration 124
(1) Bolts
(2) Coupling plate
g00616519
Illustration 123
(1) Base 1. Remove bolts (1) which fasten coupling plate
(2) Support (2) to the rotor. Remove the coupling plate. The
(3) Bolt coupling plate assembly can be a single solid plate
or the coupling plate assembly can be numerous
flexible plates.
SENR5359-11 67
Disassembly and Assembly Section
g00615994
Illustration 125
(3) Shims
(4) Fan
g00616057
g00616040 Illustration 129
Illustration 126
800 frame generator
400 Frame Generator
g00616101
Illustration 132
400 Frame Single Bearing Generator
(8) Protective strip
(9) Drive coupling
g00624626
Illustration 130
(5) Bolts
g00616108
Illustration 133
800 Frame Two-Bearing Generator
(9) Drive coupling
NOTICE
During removal of the generator, the rotor assembly
must not contact the stator assembly. If the rotor as-
sembly contacts the stator assembly, the windings can
be damaged.
g00616086
Illustration 131 8. Put protective strips (8) of cardboard, plastic or
800 Frame Two-Bearing Generator curved sheet metal between the rotor assembly
(6) Bolts and the stator assembly. The pieces should be as
(7) Drive end housing long as the rotor assembly. These pieces protect
the rotor and these pieces protect the stator from
7. For two-bearing generators, bolts (6) which fasten damage during rotor removal.
drive end housing (7) to the generator must be
removed. The drive end housing remains with the For two-bearing generators, put a mark on drive
rotor shaft. Remove the bolts. end housing (7) and the generator housing. This
will ensure proper alignment during installation.
Installation Procedure
Start By:
g00616086
Illustration 135
(6) Bolts
(7) Drive end housing
g00615990
Illustration 138
i02966183
a. Remove the exciter field and remove the exciter 3. If the generator end housing is equipped with
armature. Refer to Disassembly and Assembly, retaining bars (2), remove the four bolts that fasten
“Exciter - Remove and Install” and Disassembly the retaining bars to the generator end housing.
and Assembly, “Rotor - Remove and Install”. Remove the retaining bars.
Table 29
TOOLS NEEDED
Part Number Tool Quantity
1H-3107 Push-Puller 1
1H-3108 Push-Puller Leg 2
1H-3110 Bearing Pulling 1
Attachment
g00615797
Illustration 141
Bearing Cap
(3) Bearing Cap
g00615803
Illustration 142
(4) End housing
(5) Bolts
g00615814
Note: The weight of end housing (4) varies with the Illustration 144
size of the generator. Larger end housings require (1) Bolts
the use of a hoist.
1. The generator bearing is retained in the generator
5. Attach a hoist to end housing (4). Remove bolts (5) end housing. On the inside of the generator end
that fasten end housing (4) to the generator. Use housing, a bearing cap retains the bearing.
a pry bar to separate the end housing from the
generator. Some end housings have provisions Remove bolts (1) which fasten the bearing cap to
which allow the use of forcing screws. Lift the end the generator end housing. Pry the bearing cap
housing from the generator and remove the end out of the generator end housing. The bearing cap
housing from the generator. remains with the rotor shaft. If a bearing lube line is
attached to the bearing cap, remove the lube line.
g00615809
Illustration 143
(6) Tooling g00615816
Illustration 145
(2) End Housing
6. Attach tooling (6). Remove the bearing. (3) Bolts
Two-Bearing Generator
Note: On two-bearing generators, there is a bearing
on each end of the generator. To install the bearing
on the drive end of the generator, use the following
procedure.
i02463125
Coupling - Remove
SMCS Code: 4456-011
Removal Procedure
Start By:
g00615824
Illustration 147 a. Remove the generator. See the topic Disassembly
Replaceable bearing wear sleeve (inside view of end housing) and Assembly, “Generator - Remove”.
(5) Bearing wear sleeve
Installation Procedure
To install the bearing that is located at the exciter end
of the generator, use the following procedure.
g00615513
Illustration 149
i02966210
Coupling - Install
SMCS Code: 4456-012
g00615500
Illustration 151
Installation Procedure A Coupling with a stop fixture attached.
Table 31
3. Attach the stop fixture to the coupling.
TOOLS NEEDED
Tool Quantity
Stop Fixture. Refer to Illustration 150. 1
g00615513
Illustration 152
g00615518
Illustration 153
Index
B I
E R
General Information........................................... 4, 27 S
Generator - Align ................................................... 64
Generator Alignment.......................................... 64 Service Tools ......................................................... 27
Generator - Dry...................................................... 42 Systems Operation Section ..................................... 4
Drying Methods.................................................. 42
Generator - Install.................................................. 55
Installation Procedure ........................................ 55 T
Generator - Remove.............................................. 52
Removal Procedure ........................................... 52 Table of Contents..................................................... 3
Generator Operation.............................................. 12 Testing and Adjusting ............................................ 27
Generator Circuit Protection .............................. 18 Testing and Adjusting Section ............................... 27
Permanent Magnet Pilot Excited (PMPE) Troubleshooting..................................................... 28
Generator ......................................................... 13 Problem List ....................................................... 29
Rectifier Circuits................................................. 15 Visual Checks .................................................... 29
Self-Excited (SE) Generators............................. 14
Space Heaters ................................................... 19
Generator Set - Test .............................................. 29 V
Glossary ................................................................ 24
Varistor - Test......................................................... 30
Procedure .......................................................... 31
W
Winding - Test........................................................ 39
©2009 Caterpillar Cat, Caterpillar, their respective logos, “Caterpillar Yellow” and the Power edge Printed in U.S.A.
All Rights Reserved trade dress, as well as corporate and product identity used herein, are trademarks
of Caterpillar and may not be used without permission.