You are on page 1of 16

UNIVERSITY OF BATANGAS

COLLEGE OF ENGINEERING
MECHANICAL ENGINEERING DEPARTMENT

DESIGN OF AIR CONDITIONING SYSTEM FOR INTERNET CAFE

IN PARTIAL FULFILLMENT OF THE


REQUIREMENTS FOR THE SUBJECT
ME20 – AIR CONDITIONING AND VENTILATION SYSTEMS

SUBMITTED BY:
DIMACULANGAN, ROCKWELL D.
1401879
HOLGADO, RALF VINCENT M.
1701319
AMUL, RAJIV GABRIEL M.
1402969
DELA CRUZ, KENN JAY
1702352
CUENCA, CEDERICK D.
1701596

SUBMITTED TO:
ENGR. KELVIN M. MARANAN, ME
INSTRUCTOR

DECEMBER 2019
I. INTRODUCTION

Air conditioning is the process of treating air, to control simultaneously its

temperature, humidity, cleanliness and distribution to meet the requirements

of the space to be conditioned.

The purpose of air conditioning is to control the temperature, humidity,

filtration, and air movement of the indoor environment. The atmospheric air

always contains moisture in the form of water vapor, but the maximum

amount of water vapor that may be contained in the air depends on its

temperature and so the higher the temperature, the more water vapor that can

be contained in it. At high temperatures and moisture content levels,

extreme discomfort is experienced as the evaporation of moisture from the

body into the atmosphere by the process of perspiration becomes difficult.

The term “humidity ratio” indicates the mass of water vapor present per

kilogram of dry air, whereas the term “relative humidity” is the ratio between

the actual moisture content of the air and the moisture content of the air

required for saturation at the same temperature. The purpose of comfort

conditioning is solely to provide a comfortable environment for the majority of

occupants. Humans are reasonably tolerant to humidity and may be

comfortable from a range of between 55% and 20% relative humidity at

normal comfort temperatures.

In air conditioning, the humidification of air to increase the moisture

content is achieved by the use of a humidifier, and in reverse, the moisture

content of the air is reduced by a dehumidification process. The independent

control of the air temperature by heating and cooling processes and of relative

humidity by the humidifying and dehumidifying processes constitutes full air


conditioning, but this control is not always exercised. The more often used

vapor compression refrigeration equipment is capable of cooling and then

dehumidifying.

Ventilation systems deliver conditioned air to occupied spaces. Depending

on the building type, ventilation air may be comprised of 100% outside air,

such as in a laboratory building, or some mixture of re-circulated interior air

and outside air.

The ventilation system or air-handling unit of a home is frequently referred

to as the HVAC system. The HVAC system consists of the mechanical and

functional components of duct work, air filter, air conditioning, and heating

unit. The primary functions of the HVAC system are cooling, heating, and

humidification; maintenance of overall comfort, odor control; and maintenance

of oxygen and carbon dioxide levels at acceptable concentrations. HVAC

systems in some homes are installed to service zones. As the number and

size of zones increase, so does the cost of ventilation. A zone is typically

defined by the presence of a thermostat.

Understanding HVAC functioning is critical to indoor air quality

evaluations. HVAC systems for commercial and industrial operations often

have an outside air intake on the top or side of a building that brings outdoor

air inside. The outdoor air is then mixed with recirculated air from the

occupied area. The mixed air usually passes through a filter to remove gross

contaminants. This filtered air then passes through a fan, which creates a

positive pressure, forcing the air through coils that either cool or heat. A drain

pan beneath the coils collects water that condenses on the cooling coil. Air

leaving the coil may be humidified or dehumidified depending on the


circumstances. The supplied air then travels from the distribution box through

small ducts to terminal ducts and diffusers and from there into the rooms. The

supplied air migrates throughout the room and eventually enters an air return

vent, also called a plenum, where it is recirculated or exhausted outdoors.


II. DESIGN OF AIR CONDITIONING UNIT

A. INTRODUCTION

When selecting the proper type of conditioning system to be used for the

space chosen, factors should be considered to make sure the comfort of the

occupants. The dimension (length, width, height) of the room should be

measured and also the components of the walls, if there are any insulation

present, along with the installed windows (single or double-glazed) or doors.

Sunlit areas of windows and walls are to be examined. Depending on the type

of room to be conditioned, elements like the appliances, lighting, and products

that produces heat should also be acknowledged to compute the heat loss

within the room. Aside from looking at the number of people occupying the

room and what activities they do, infiltration of air from outside should be also

dealt with.

The group had decided to use split-type air conditioning system. This type

of system consists of an outdoor and indoor unit. The outside unit composed

of the the condenser, the compressor, and the fan while the inside has the

cooling coil, blower and air filter.

A great advantage of this type of cooling system is the reduction of noise.

Systems like window-type cooling system produce noise since the

compressor installed with other components in the wall, unlike in split-type

where these components are located outside the room, thus reducing the

noise produced. Also, this type of air conditioning system requires lesser

space compared to other types and is recommended since small holes (for
wiring and tubing) are needed.

B. COMPONENTS OF COOLING LOAD

Date: November 21, 2019


Time Used: 2pm
Design Condition
Outdoor Indoor
Relative Humidity 88% 88%
Dry Bulb Temperature 30 C° 24 C°
Wet Bulb Temperature
Schedule of Lighting
Start End
Lights on
 Ceiling Lights 8:00 am 12:00 am
 Neon 8:00 am 12:00 am
Lights off
 Ceiling Lights 12:00 am 8:00 am
 Neon 12:00 am 8:00 am
Number of Occupants
(Main Game Room)
78

Infiltration Rate
3HRS

THINGS MATERIAL R (m2-K/W)


Lights
 Ceiling CFL Bulb (20 watts)
 Neon Mount Acrylic
 Base Nickel-plated brass

Blinds Fabric 0.083


Computer Table Laminate
Gaming Chair
Computer
BUILDING MATERIALS

Windows
 W1-W13 Single Glass

Composite Wall
 Concrete block Concrete block 0.18
 Air Space Fir Negligible
 Thermal Insulation Mineral Fiber (90 mm) 1.94
 Air Space Atmospheric Air (Vertical) 0.12
 Gypsum Board Gypsum Board (16 mm) 0.10

Floor Sand and gravel aggregate


Air space 0.11
Insulation mineral fiber, 75mm 1.94
Fiber board 0.23
Concrete block 0.18
Ceiling (disregarding the metal Plywood 10mm 0.10
frames) Gypsum Board (16mm) 0.10
Insulation fiber glass 130mm

Sources for Outdoor and Indoor Conditions:


http://ashrae-meteo.info/index.php?lat=14.58&lng=120.98&place=%27%27&wmo=984250

BUILDING MATERIAL DIAGRAM


FLOOR PLAN
TOP VIEW

SIDE VIEW

FRONT VIEW
CALCULATIONS

SENSIBLE HEAT GAINS PRESENT


8AM
to=30oc
ti=24oc

Composite Wall MATERIAL R


 NORTH WEST Outside air 0.029
A=6 x 2.74 m Concrete block 0.18
( No sunlight infiltrating ) Mineral Fiber (90 mm) 1.94
Inside air 0.12
Gypsum Board (16 mm) 0.10
RT= 2.369 m2k/w
U= 0.4221 w/m2k

QstNW=UA[ to-ti ]

QstNW=0.4221w/m2k(6x2.74)m2[30-24]

QstNW=41.6359 W

Composite Wall MATERIAL R


 NORTH EAST Outside air 0.029
A=18 x 2.74 m Concrete block 0.18
CLTD= 15 Mineral Fiber (90 mm) 1.94
Inside air 0.12
Gypsum Board (16 mm) 0.10
RT= 2.369 m2k/w
U= 0.4221 w/m2k

QsoNE=UA[ CLTD + (25-ti) + (to-29) ]

QsoNE=0.4221w/m2k(18x2.74)m2[ 15 +(25-24)k +(30-29)k ]

QsoNE=353.9055 W

Composite Wall MATERIAL R


 SOUTH EAST (1) Outside air 0.029
A=0.25 x 2.74 m Concrete block 0.18
Mineral Fiber (90 mm) 1.94
Inside air 0.12
Gypsum Board (16 mm) 0.10
RT= 2.369 m2k/w
U=
0.4221 w/m2k
GLASS Single glass
A= 4.75 x 2.74m
U= 5.9 at summer
QstSE=UA[ to-ti ]wall + UA[to-ti] glass

QstSE=0.4221w/m2k(0.25x2.74)m2[30-24]K + 5.9w/m2k(4.75x 2.74)m2[30-24]K

QstSE=462.4658 W

Composite Wall MATERIAL R


 SOUTH EAST (2) Outside air 0.029
A=0.25 x 2.74 m Concrete block 0.18
Mineral Fiber (90 mm) 1.94
Inside air 0.12
Gypsum Board (16 mm) 0.10
RT= 2.369 m2k/w
U=
0.4221 w/m2k
GLASS Single glass
A= 0.75 x 2.74m
U= 5.9 at summer

QstSE=UA[ to-ti ]wall + UA[to-ti] glass

QstSE=0.4221w/m2k(0.25x2.74)m2[30-24]K + 5.9w/m2k(O.75x 2.74)m2[30-24]K

QstSE=74.4818 W

Composite Wall MATERIAL R


(FOUNDATION)X3 Outside air 0.029
 SOUTH WEST Concrete block 0.18
AX3=0.75 x 2.74 m Mineral Fiber (90 mm) 1.94
Inside air 0.12
Gypsum Board (16 mm) 0.10
RT= 2.369 m2k/w
U=
0.4221 w/m2k
GLASS Single glass
A= 17.25 x 2.74m
U= 5.9 at summer

QsiSW=UA[ to-ti ]wall + UA[to-ti] glass

QstSW=0.4221w/m2k(0.75x2.74)m2[30-24]K+5.9w/m2k(17.25x 2.74)m2[30-24]K

QstSW=1678.3855 W
 Ceiling MATERIAL R
A=6x 18m Outside air 0.029
Plywood 10mm 0.10
Gypsum Board (16mm) 0.10
Insulation fiber glass 130mm .13m(27.7)=3.061
Inside air 0.16
Rt=
3.45m2k/w
U=0.2899w/m2k

Qstceiling=UA[ to-ti ]

Qstceiling=0.2899w/m2k(18x6)m2[30-24]

Qstceiling=187.8261 W

 Floor Air space in 0.11


A=6x 18m Insulation mineral fiber, 75mm 1.94
Fiber board 0.23
Concrete block 0.18
Air space out 0.29
Rt= 2.75m2k/w
Ut=0.3636w/m2k
Qstfloor=UA[ to-ti ]

Qstfloor=0.3636w/m2k(18x6)m2[30-24]

Qstfloor=235.6128 W

THROUGH INFILTRATION

Qsi=1.23q(to-ti)

q=HLWG/3600 x (Nc)

G=1.5 two outside walls

Nc= a+bv+c (average)

Nc= 0.20 + 0.015(3.33m/s) + 0.014 =0.26395

q=(2.74m x 18m x 6m)/3600 x 0.26395 = 0.02169699

Qsi=1.239(.02169699)(30-24)

Qsi=0.1613 W
HEAT FROM OCCUPANTS

OFFICE TYPE =150 w

Where qp= 150w(0.55)= 82.5W

Where hrs after each entry into space is 3hrs and 6hrs is total hours in space

So CLF =0.67

No=78 persons

Qsc=qp(No)(CLF)

Qsc= 82.5w(78)(0.67)

Qsc=4311.45W

HEAT GAIN FROM ELECTRIC LIGHTS

Computer=

LED bulbs=
LATENT HEAT GAINS PRESENT

OFFICE TYPE =150 w

Where 150w(0.55)= 82.5W

Qp= 150w-82.5w =67.5

CLF =1

No=78 persons

Qlc=qp(No)(CLF)

Qlc= 67.5w(78)(1)

Qlc=5265W
TOTAL HEAT

QT=QS +QL

QS QL
QstNW=41.6359 W Qlc=5265W
QsoNE=353.9055 W
QstSE=462.4658 W TOTAL =
QstSE=74.4818 W
QstSW=1678.3855 W
Qstceiling=187.8261 W
Qstfloor=235.6128 W
Qsi=0.1613 W
Qsc=4311.45W
Computer=
LED bulbs=
TOTAL =

QT=QS +QL
SPECIFICATIONS OF AIRCON THAT WILL BE USED

CONCLUSION

You might also like