Professional Documents
Culture Documents
Application note
8299_en_00 © PHOENIX CONTACT 2011-11-07
When using Inline terminals, observe the different tempera- Maximum ambient temperature in potentially explo-
ture specifications. sive areas according to UL 60079-15
Ambient tem- Example Location of Limit value for The maximum ambient temperature specified on the device
perature information together with the UL approval results from the UL standard
Storage/ -45°C ... Data sheet for areas in which an explosive atmosphere may typically
transport +85°C occur. A temperature range from -20°C to 60°C is assumed
Operation -25°C ... Data sheet Reliable and there.
+55°C permanent Thus, the specified, maximum upper limit of the temperature
function applies for explosion protection according to UL 60079-
15.
Acc. to 60°C Labeling on Explosion pro-
UL 60079-15 the Inline ter- tection accord- The test conditions mainly consider the maximum permissi-
(Ambient tem- minal (see ing to ble device surface temperature which is influenced directly
perature) Figure 1) UL 60079-15 by the ambient temperature. The device function or its ser-
vice life will not be taken into consideration for the UL ap-
proval tests.
The approval requirements are printed on the terminal in ac-
cordance with UL specifications.