INGENIERIA SKIM TANK

ESTACION TIGANA SUR

FECHA Rev. 1

ORDEN DE SERVICIO HOJAS DE DATOS VÁLVULA DE 28/02/2021 PAG 1 de 2

4400017196 EMERGENCIA CÓD. DOC.:

GPK-IFVI-TGS-INS-DS-026

INGENIERIA SKIM TANK


ESTACION TIGANA SUR

HOJAS DE DATOS VÁLVULA DE EMERGENCIA

GPK-IFVI-TGS-INS-DS-026

Registro de emisiones
Rev Fecha Elaboró Revisó Aprobó Descripción
A1 06/02/2021 F.S. D.A. A.M. Emitido para revisión interdisciplinaria
C1 06/02/2021 F.S. D.A. A.M. Emitido para revisión del cliente
0 28/02/2021 F.S. D.A. A.M. Aprobado
1 22/06/2021 F.S. D.A. A.M. Con Modificaciones Aprobado

Código YV: 3081-5DTSGETA-7008-008


Nº GEOPARK
GPK-IFVI-TGS-INS-DS-026
HOJAS DE DATOS VÁLVULA DE EMERGENCIA
No. Y&V:
3081-5DTSGETA-7008-008
Rev. No Fecha Descripción Preparó Revisó Aprobó
A1 6/02/2021 Emitido para revisión interdisciplinaria F.S. D.A. A.M.
C1 6/02/2021 Emitido para revisión del cliente F.S. D.A. A.M.
0 28/02/2021 Aprobado F.S. D.A. A.M.
1 22/06/2021 Con Modificaciones Aprobado F.S. D.A. A.M.
Cliente: GEOPARK Project No: 3081-5 Site: TIGANA SUR
Proyecto: INGENIERIA SKIM TANK ESTACION TIGANA SUR
Valve Information Valve Options or Other Information
1 Valve Quantity 1 for Vertical Cylinder Tank 52
General Information 53
2 G Project Location ESTACION TIGANA SUR
3 E Tank Number TGS-TK-101A
N
4 L Valve Tag Number JAC-ERV-101A-1
E
5 R P&ID Number GPK-IFVI-TGS-PRO-PID-005
6 A Engineer's Name
Tank Design Information per API 2000 7th Edition
7 Tank Type Vertical Cylinder
8 Dimensions D=12ft,H=40ft
T
9 A Tank Wetted Surface Area 1,131 ft²
10 N Environmental Factor 1
K
11 Tank MAWP 2,8 Nota 4 oz/in²
12
Pressure Parameter Information
13 Required Capacity 189228,34 SCFH (air)
14 Using API 2000 7th Ed
15
P
16 Calculated Flow
R
17 E
18 S
19 S
U
20
R
21 E
22
23 Pressure Setting 2 Nota 4 oz/in²
24 % of Tank MAWP 84,39 %
Vacuum Parameter Information
25
26
27 Calculated Flow
28 V
29 A
C
30 U
31 U
32 M Notes
33 1. Vendor must include 316SS nameplate engraved /stamped with tag number
34 and attached with either 316 SS riveting or wire
35 2. Vendor must verify all items including: sizing, construction materials,
Valve Design Information dimensions,Pressure Setting, accesories & devices according to process data.
36 Connection Size 12 inches 3. This data sheet is based on calculations supplied by vendor.
Flange Type & Rating API 4. This value should be verified by vendor of the emergency valve.
37 V
38 A Base and Arm 316 Stainless Steel
39 L Disk Cover Materials 316 Stainless Steel
V
40 Disk Seal Materials Viton ®
E
41
42 D
43 E Body Fastener Material S.S.
S
44 I Pallet Weight Material NA
45 G I.D. Tag Material 304 S.S.
N O
46 Max./Min. Design Temp -50 to 250 deg. F
R
47 Max./Min. Design Pressure -1 to 4 psig D
Valve Requirements E
48 Removable Seats / Seals Required R
I
49 Max. Leakage Rate 1.0 SCFH @ 90% Set Pressure
N
50 Certified Leak Test Required G
51 Self Draining / Drip Ring Required

2 de 2