Address. Jl. Hayam Wuruk 4 FX, Jakarta 10120 To. Date.

26 NOVEMBER 2020
Phone. (62-21) 385 0703, 386 1865, 351 7113, 345 1384
Fax. (62-21) 385 0702, 386 1865 Spec No.
Email. sales@trafoindonesia.com ; trafo@trafoindonesia.com
www.trafoindonesia.com
Address. Jl. Siliwangi, Tangerang (Factory I, II, III & IV) 7. ACCESSORIES : The transformer will be furnished with all necessary accessories as follow :

GENERAL ACCESSORIES SPECIAL ACCESSORIES


SPECIFICATION FOR TRANSFORMER √ HV Terminal √ Enclosure (Housing) IP 20
√ LV Terminal √ Digital Thermometer c/w Alarm & Trip Contact
1. TYPE AN : self cooled / indoor use / step-up / step-down / non encapsulated / Dry Non Resin distribution transformer - Anti Vibration Pad - Cooling Fans
√ Lifting lug
2. SERVICE CONDITION : The transformer will be installed at the altitudes below 1,000 meters √ Tapping Link
and the maximum ambient temperature does not exceed 40 o
C √ Connecting Rod
√ Brand Name
3. STANDARD : The transformer is designed, manufactured tested and tolerance in accordance with : √ Name Plate
ANSI C57.12-01 √ Earth Terminal
√ Skid Base (Pad Mounted)
4. RATING - Roller
4-1 Number of Phase : 3 phase 4-2 Frequency : 60 Hz
4-3 Primary Voltage : 0.48 kV 4-4 Secondary Voltage : 230 Volt
Winding Connection : DELTA Winding Connection : WYE
4-5 Rated Capacity (total) : 300 kVA No. Routine Test
Incase of double primary voltage, Capacity will be : 1 Transformer Turn Ratio, Polarity & Vector group test
at : - kV Rated Capacity : - kVA 2 Measurement of No load loss and Exciting current
at : - kV Rated Capacity : - kVA 3 Measurement of impedance and load loss
Incase of double secondary voltage, Capacity will be : 4 Separate source voltage withstand test (Applied potential test)
at : - V Rated Capacity : - kVA 5 Induced potential test
at : - V Rated Capacity : - kVA 6 Insulation resistance test
4-6 Additional Taps on High Voltage : +/- 5 % ( 3 Taps ) 7 Winding resistance measurement

5. POLARITY AND PHASOR RELATIONSHIP : The transformer will be subtractive polarity and phasor relationship will be : Dyn-11
Note : - Winding Cu-Cu
6. ELECTRIC PERFORMANCE :
Primary Voltage Secondary Voltage
6-1 Highest System Voltage : 0.6 kV : 0.25 kV
6-2 Impulse Test Voltage : 10 kV : - kV
6-3 Applied Test Voltage During 1 Minute : 3 kV : 2.5 kV
6-4 Induced Voltage Test : Apply 2 times of the rate voltage at 350 cycles per second for 18 second
6-5 Class of Winding Insulation : F
o
Temperature Rise The winding temperature rise measured by resistance method will not exceed : 90 C
6-6 Losses at Rated Voltage Primary Side : 0.48 kV Secondary Side : 0,23 kV
No Load Losses : 1,150 Watt
Load Losses ( at 110 °C ) : 4,150 Watt
Total Losses : 5,300 Watt
6-7 Efficiency at % Rated Capacity : 100 75 50 25 %
at P.F. = 1.0 : 98.26 98.48 98.56 98.16 %
at P.F. = 0.8 : 97.84 98.10 98.21 97.70 % Date of Approval :
6-9 Percent Impedance : 4.50 % PROPOSER :
6 - 10 Voltage Regulation at P.F. = 1.0 : 1.48 %
Voltage Regulation at P.F. = 0.8 : 3.71 % hp

P20-1271F - Af TP/V.11-03/19 (Rev./ Tgl. Form : 0/29-07-2019)