Cool Partners have developed an Air Purger, the CPA, that has proven to be highly efficient while
being very simple to operate.The Air Purger utilize the lowest temperature and the highest pressure
available in the system to acheive the highest possible degree of separation between the air and the
refrigerant.

In our experience – air, water and oil are the cause of most problems in refrigeration systems.

Symptoms include:

Loosing capacity over the years
Capacity problems during the summer
http://www.coolpartners.dk/efficiency/air­purger­cpa­10/ 2/3
3/13/2017 Air Purger (CPA­10) | Cool Partners

Increased power consumption
Higher service/maintenance costs
Oil decomposing
Unexplained behavior…

What happens with air in the system?

Occupies condenser surface 
= higher condensing pressures
Blocking drainage of liquid
Chemical reactions take place 
= oxidation of oil and metals
Control problems due to air pockets 
(e.g. HP float valves)

As a consequence…

A 1°C increase in condensing pressure means approx…

1% lower cooling capacity
3% Lower COP
3.1% Higher Power Consumption (for a given capacity)

 
The left graph shows the air purgers air purging capacity as an air volume flow. The red curve is 
the volume of the air in the condenser or receiver, and the green curve is the volume of the purged 
air at atmospheric pressure.

The air purger will suck or drag the air from the purging points with the refrigerant at a capacity of 
approx. 10 kW refrigerant flow at condensing pressure.