Professional Documents
Culture Documents
TN271_transfer_plate_shear_14
111107
Bijan O Aalami2
Shear normal to the plane of a transfer plate (vertical shear) is generally high in magnitude and
requires special treatment. This Technical Note describes a procedure used for its design. The
procedure described is followed by a numerical example.
The shear design in transfer plates, in concept, is no different from the general philosophy of structural
engineering design. A designer ensures that: (i) there exists an uninterrupted load path from each load
on the structure to the foundation; and (ii) each load path has the strength to carry the forces it is
calculated for; and (iii) the structure is provided with adequate ductility to redistribute the forces and
develop the load paths envisaged by the designer. The following outlines the selection of load paths to
be used for design of vertical shear, and the determination of the required reinforcement along the path
length.
In flat slab construction common to commercial and residential buildings, the slab proper is generally
strong enough to resist the calculated vertical shear. Occasionally, slabs may have to be reinforced
against punching in the vicinity of supports. The significantly larger shear demand in transfer plates
oftentimes requires that a distinct grid work of physical or virtual beam spines be provided and
designed to direct the shear flow to the supports. Once a grid work of shear spines is envisaged, the
force in each of the spines is determined and the associated reinforcement calculated.
The spines can extend beyond the soffit of a slab, as is the case of physical beams, or they can be fully
concealed within the slab thickness (virtual beams). In both variations, the determination of shear force
to be carried by each spine and the design process are the same.
STRUCTURAL MODEL
Figure 1a shows the plan of a slab corner supported on a column. The arrows indicate the direction of
principal vertical shear. The intensity of vertical shear increases closer to the support. Figure 1b shows
a region in the slab, referred to as shear spine, reinforced to resist vertical shear. The shear spine
terminates at the shear flow boundary that encircles the support and must be adequate to sustain the
entire shear associated with the support it encircles.
Figure 1a shows the plan of a slab corner supported on a column. The arrows indicate the direction of
principal vertical shear. The intensity of vertical shear increases closer to the support.
1
Copyright 2007 ADAPT Corporation
2
Professor Emeritus, San Francisco State University; Principal, ADAPT Corporation
E-Mail support@adaptsoft.com
1733 Woodside Road, Suite 220, Redwood City, California, 94061, USA, Tel: (650) 306-2400 Fax (650) 306 2401
Technical Note
(a) Shear flow in slab next to column (b) Shear design components
At any design section shown in Fig, 1b, the demand actions on the section and the resistance provided
by the section are illustrated in Fig. 2
Vu = Demand shear;
Mu = Demand moment; and
Nu = Demand axial force.
2
Technical Note
T = Tensile force of longitudinal reinforcement;
Vc = shear force resistance provided by concrete;
Vs = shear resistance provided by shear reinforcement; and
P = force in post-tensioned tendons.
The focus of this Technical Note is the determination of the reinforcement associated with Vs. The
prerequisites for the validity of the procedure described herein are:
The section must have adequate reinforcement to resist the tensile force T;
The compression zone of the section must be adequate to resist the compression force C;
The concrete section and strength must be adequate to develop the internal compression
strut shown in Fig. 2. This is controlled by the maximum shear Vu that a section is permitted
to resist. Different building codes impose a limit on Vu, in order to avoid crushing of
concrete3.
Consider the transfer plate shown in Fig. 3. Its longer side is 25m. It has a thickness of 1.50m and
supports a multi-story tower above it.
The shear transfer in the plate is envisaged to be through the shear spines shown in Fig. 4. The spines
are considered continuous along the perimeter of the plate between the column supports. The non-
continuous spines from the columns toward the interior of the plate are extended far enough to where
the slab on its own can resist the vertical shear.
The provision of shear spines and the length of their extension are somewhat similar to the shearhead
used in common residential and commercial floor systems (Fig. 5). The shearheads terminate, where
the capacity of slab is adequate to resist the demand shear.
3
As an example ACI-318 (chapter 11) controls the crushing of concrete by limiting the value of Vs not to exceed
[(2/3)* √f’c]*bw*d , where bw is the width of the design section
3
Technical Note
The shear spines start at a distance “a” from the face of support (Fig. 6). The distance “a” depends on
whether the plate is conventionally reinforced or post-tensioned. ACI-318 (Chapter 11) suggests the
following:
Where “h” is the total depth of the section and “d” is distance of between the compression fiber and
the centroid of tension, but not less than 0.8h (ACI-318). The value of design shear in each instance is
determined at distance “a.” The shear reinforcement calculated at distance “a” is continued to the face
of support.
4
Technical Note
A central point in the selection of shear spines is that they must form a closed perimeter around each of
the supports, in order to capture the entire flow of vertical shear to the foundation. Figures 6 and 7
illustrate the boundary perimeter of the shear spines around a corner column. The values of design
shear for each of the boundary segments is shown in Fig. 7-b. The distribution of vertical shear for each
of the segments is illustrated in Fig. 8.
5
Technical Note
The cross-sectional geometry of each spine is not specified in building codes. Figure 9 provides a
guideline for its selection.
(a) Spine extends to slab boundary (b) Shear spine next to boundary
SHEAR REINFORCEMENT
The shear reinforcement generally consists of vertical bars (J-bars) placed at regular spacing
along each spine and across its width. The vertical bars are encased in a U stirrup and closed
at the top as shown in Fig. 10a for an example of 8 J-bars across the width of a shear spine.
Where congestion of reinforcement poses difficulty, headed bars as shown in Fig. 10b can be
used. The design process is the same for both options.
6
Technical Note
The mechanism for shear transfer through the vertical bars is illustrated in Fig. 11. The
following conservative assumptions will be made in arriving at the shear capacity:
The angle of cut in the figure is assumed 45 degrees. The parameters that impact the shear
transfer are:
For one square meter of plan, the shear capacity will be:
7
Technical Note
EXAMPLE
Determine the design shear capacity of 20mm diameter vertical bars placed at 250mm on
center along the shear spine and 200 mm on center normal to it for the following condition:
8
Technical Note
DESIGN EXAMPLE
Consider the transfer plate of the multi-story building shown in Fig. E-1. Views of transfer plate
are shown in Fig. E2.
9
Technical Note
The shear transfer for the plate was designed using virtual beam spines illustrated in Fig. E3.
10
Technical Note
11
Technical Note
Table 1 shows a selection of shear reinforcement for the different regions of the shear spines
for the above transfer plate. As indicated in the table, the design shear capacity of the bars
varies according to the depth of the plate.
12