OPERATING MANUAL

PROCESS INDICATOR
PIC-1101

Process Indicator PIC-1101

1 2 3 4

PIC-1101
96 X 96 X 65 mm

Technical Specification
1) Display : 4 digit, 7 segment LED display (0.56"inch)

2) Size : 96 X 96 X 65mm

3) Input : 0~10V DC, 4~20 mA DC , 0~20 mA DC,( selectable )

4) Output : 1Relay 1C/O


4-20mA Retransmission &
24V DC Transmitter Supply

5) Scalable range : -999 to 9999 (selectable)

6) Range & Decimal Point selectable. Reverse scaling possible.

7) Power Supply : 100-250V AC,50/60Hz

8) Protection Level : IP-65(Front side) AS per IS/IEC 60529:2001

Page - 1 www.multispanindia.com
USER CONFIGURATION

Process Value 1 2 3 4
Press SET key.

S E T
Press SET key

9 9 9 9 Press & key to set value


(Range : -999 to 9999)
Press SET key
P A S S
Press SET key

0 1 2 3 Press & key to set value


Press SET key

H Y S
Press SET key

0 0 1 0 Press & key to set value


(0 to 1000)
Press SET key
m o d e
Press SET key
L-a L H-AL or L-AL selectable
Press SET key

r t L w Retransmission Lowoutput
Press SET key
r t H I Retransmission Highoutput
Press SET key

I n p Input
Press SET key

0-10V DC 0 -1 0 4 -2 0 0 -2 0 Select by key


4-20mA DC 0-20mA DC
Decimal Point d p
Press SET key

0 0 0 0 Press & key to set Decimal point


Press SET key

Low Range L R N G (Range : -999 to 9999)


Press SET key

0 0 0 0 Press & key to set value


Press SET key

Page - 2 www.multispanindia.com
High Range H r n g (Range : -999 to 9999)
Press SET key

0 0 0 0 Press & key to set value


Press SET key

Filter time f L T R (range: 1 sec to 10 sec)


Press SET key

0 0 0 0 Press & key to set value


Press SET key

Off-set O F S T (range: -
+ 100 counts)
Press SET key

0 0 0 0 Press & key to set value


Press SET key

Correction Factor C R F C (range: -+ 999 counts)


Press SET key

0 0 0 0 Press & key to set value


Press SET key
Signal Low Level S L L (ampere range : 0-5mA)
only for 4-20mA
Press SET key
Press SET key
A 0. 0 Press & key to set value between 0.0 to 5.0
Press ENT key for
save & exit

Working

1). Do all connection as shown in connection diagram and turn on the instrument.
2). Display indicates process value according to 4-20mA i/p available and according
to decimal point set.
3). The Range Corresponding to 4-20mA is selectable from keypad.
4). When the input is 4mA then Display will show 0000 and when input is 20mA then display
will show 9999.
5). If you select lower alarm as a mode then initially relay will remain in on condition.
When process value equals (SET+HYST) then relay will turn OFF. Relay will again
turn ON at (SET POINT) and this on off action continues as process value varies.
6). If you select Higher alarm then initially relay will be in off condition. When
Process value touches (SET) value relay will turn on and relay will turn off at
(SET-HYST) and this cycle continues as process value varies.
7). If the input is not connected Display will show OPEN.
8). When The Input Exceeds the full scale Range (Approx above 20mA) Display will show
OVER.
9). In retransmission mode when parameter RTLW is 0000 then output will be 4mA & when
Parameter RTHIis 9999 then output will be 20mA

Page - 3 www.multispanindia.com
Connection Diagram

20 19 18 17 16 15 14 13 12 11
+ O/P
24V DC
- + O/P -
4 To 20mA DC
+ I/P
0-10V
- I/P +
0/4-20
(Trans.) (Retransmission) DC mA DC

Range: -999 To 9999 SELE.


Input: 0-10V DC,4-20mA DC,0-20mA DC
Made in India Output: 1R1C/O & 4 To 20mA DC Retrans.
100 ~ & 24V DC (Trans.)
250V AC
50/60 Hz
www.multispanindia.com
RELAY
NO C NC
L N
1 2 3 4 5 6 7 8 9 10