01/2008
Trip Curve LaVergne, TN, USA
IEC-SIT+SIT-A-10PU(1)
Standard Inverse Time (SIT and SIT-A)
3000TC
k T 1000
t d ( I ) = -------------------- × ---
3000TC0706-IEC-SIT-DE50869
⎛ ----⎞ – 1 β
I α
⎝ I s⎠
where:
td = Operate time (sec) 100
I = Current value
k = Coefficient values (see table)
Is = Current set point
α = Coefficient values (see table)
T = time setting (sec) at I/Is = 10 Operating Time in Seconds
10 12.5
β = Coefficient values (see table)
NOTES: 5
1. Sepam™ relays have two modes of setting: 2.5
The default method shown here, uses curves that are
referenced at ten times the current setting (Is)[10 Per 1 1.2
Unit]. 0.8
The alternate method is by TMS, which is similar to an
electromechanical time dial setting method. Curves 0.4
reflecting the TMS method are on a separate form.
2. The following minimum operate thresholds (I / Is) 0.2
apply: 0.1
SIT, VIT, LTI, EIT, UIT @ I / Is=1.2 0.1
RI, IAC-SIT, IAC-VIT, IAC-EIT @ I / Is=1.0
SIT-A, VIT-B, LTI-B, EIT-C, IEEE MI, IEEE VI, IEEE EI
@ I/ Is=1.1
3. When the monitored value is more than 20 times the
0.01
set point, the tripping time is limited to the value
corresponding to 20 times the set point.
1 10 100
4. if the monitored value exceeds the measurement
capacity of Sepam™ (40 IN for the phase current Current I / Is
channels, 20 INr for the residual current channels), the
tripping time is limited to the value corresponding to
the largest measurable value (40 IN or 20 INr).