You are on page 1of 8

Technical Note

Minimum Steel for Reinforced Concrete Slabs


Subramanian Narayanan, Ph.D., F.ASCE 1

Abstract: Reinforced concrete slabs are often exposed to rain and radiation from the sun, in addition to normal loads, and hence have to be
Downloaded from ascelibrary.org by "Indian Institute of Technology, Roorkee" on 08/13/21. Copyright ASCE. For personal use only; all rights reserved.

provided with at least the minimum shrinkage and temperature reinforcement. Shrinkage and temperature reinforcement has traditionally
been specified as a certain percentage of the cross-sectional area (about 0.12%–0.18%), which is often empirical. Moreover, this was specified
when M20–M25 concrete and reinforcements of Grade Fe 415 were used, which have since been found to be inadequate by practicing
engineers. Some researchers have found that the reinforcement prescribed in codes has to be increased considerably to avoid cracks
due to shrinkage and temperature effects. Hence, a formula for minimum reinforcement has been developed for slabs, similar to that for
beams, which provides consistent safety against collapse due to cracking. It takes into account factors that may affect the behavior of these
slabs, such as concrete and steel strength and the ratio of depth to effective depth. DOI: 10.1061/(ASCE)SC.1943-5576.0000618. © 2021
American Society of Civil Engineers.
Author keywords: ACI 318; IS 456; Minimum steel; RC slabs; Shrinkage; Temperature.

Introduction steel of lower strengths, used during the times in which they were
prescribed. However, some studies suggest that the provisions in
RC slabs are used in floors and roofs as well as in the foundations these codes are not adequate to resist shrinkage and temperature
of buildings. In addition to the normally applied loads, these slabs stresses (Suprenant 2002; Frosch et al. 2003), because the shrink-
are exposed to rain or groundwater and the sun’s radiation. Hence, age strains are time dependent and increase with time and concrete
they have to be provided with at least minimum shrinkage and tem- strength. In addition, with the increased availability and use of
perature reinforcement. Shrinkage and temperature reinforcement high-strength concrete and high-strength steel reinforcements, it
requirements for the design of reinforced concrete structures have is necessary to modify these requirements. The objective of this
been included in several codes and standards. As they were devel- paper is to propose an equation for minimum steel for slabs, includ-
oped several years ago, these provisions are empirical and based on ing concrete and steel strengths as well as the ratio of depth of slab,
a certain percentage of the cross-sectional area (ranging from D, to effective depth of T-beam or slab, d, (D=d). The equation is
0.12% to 0.18%). These provisions have been in use for several proposed such that the capacity of the section is obtained, which is
years, without any change and mostly found to be satisfactory. about 1.3 times the cracking moment, for a certain percentage of
For example, the corresponding provision in the American Con- reinforcement provided.
crete Institute code, ACI 318-19 (ACI 2019), has not been modified
since 1928, almost 90 years.
Shrinkage cracks in slabs typically appear throughout the thick- Shrinkage Strains
ness of the concrete section (Babaei and Fouladgar 1997). Thus,
they not only allow the ingress of moisture and deleterious chem- While hardening, concrete loses moisture from its fine pores and
icals to reach the steel reinforcement but also may result in water shrinks. Shrinkage of concrete will result in tensile stresses, known
leakage from the upper floor to the lower floor. Such shrinkage as shrinkage stresses. The amount of shrinkage depends on the
cracks always pose problems with serviceability and durability. To water content, aggregate properties, and section geometry. There are
ensure satisfactory performance of RC structures, the shrinkage two main types of concrete shrinkage—autogenous shrinkage and
crack widths must be controlled to within acceptable limits. drying shrinkage [Eurocode 2 (CEN 2004); Bamforth et al. 2008].
Reinforcing steel, at close spacing, is often used to control such Autogenous shrinkage is caused by self-desiccation, whereas
cracks in structural slabs and walls. In general, providing a higher drying shrinkage is caused by loss of water due to evaporation.
percentage of crack-control steel will lead to the formation of more Autogenous shrinkage is fairly small compared with drying shrink-
cracks but with smaller crack widths. Crack-control steel will ex- age in concrete having a water (w)-cement (c) ratio (w=c) greater
perience much higher tensile stresses at the cracks than at other than 0.45, but it can represent 50% of the total shrinkage when w=c
locations (Ng and Kwan 2017). is 0.30 (Bamforth et al. 2008; Yang et al. 2001). Therefore, autog-
The minimum provisions for steel in the Indian, American, enous shrinkage may be greater for high-strength concrete, in
European, Australian, and New Zealand codes are reviewed. These which a low water-cement ratio is used.
minimum steel provisions are empirical and consider concrete and The total shrinkage strain, εcs , can be estimated per Clause 3.1.4
of Eurocode 2 as
1
Consulting Structural Engineer, 23 Napa Valley Rd., Gaithersburg, MD εcs ¼ εcd þ εca ð1Þ
20878. ORCID: https://orcid.org/0000-0003-0355-1206. Email: drnsmani@
gmail.com where εcd =drying shrinkage strain; and εca = autogenous shrink-
Note. This manuscript was submitted on December 2, 2020; approved age strain.
on June 1, 2021; published online on August 10, 2021. Discussion period The ultimate autogenous shrinkage strain at any time, t, days,
open until January 10, 2022; separate discussions must be submitted for εca ðtÞ, is given by Clause 3.1.4 of Eurocode 2 as
individual papers. This technical note is part of the Practice Periodical
on Structural Design and Construction, © ASCE, ISSN 1084-0680. εca ðtÞ ¼ β as ðtÞεca ð∞Þ ð2aÞ

© ASCE 06021005-1 Pract. Period. Struct. Des. Constr.

Pract. Period. Struct. Des. Constr., 2021, 26(4): 06021005


Table 1. Value for ks in Eq. (3)
s0 (mm) ks
100 1.0
200 0.85
300 0.75
≥500 0.70

where
Downloaded from ascelibrary.org by "Indian Institute of Technology, Roorkee" on 08/13/21. Copyright ASCE. For personal use only; all rights reserved.

εca ð∞Þ ¼ 2.5ðf c0 − 10Þ × 10−6 ð2bÞ

β as ðtÞ ¼ 1 − expð−0.2t0.5 Þ ð2cÞ

The drying shrinkage strain may be estimated based on


Eurocode 2 as
εcd ðtÞ ¼ ks εcd;0 β ds ðt; ts Þ ð3aÞ Fig. 1. Autogenous shrinkage strain in relation to cylinder strength of
concrete.
where β ds is given by
ðt − ts Þ
β ds ðt; ts Þ ¼ pffiffiffiffiffi ð3bÞ If a reinforced concrete slab is allowed to move freely, shrinkage
ðt − ts Þ þ 0.04 s30 and temperature changes will not cause much damage to the slab
as shrinkage strains may not induce significant stresses. However,
ACI 209.2R-08 suggests an average value for the ultimate
in reality, any slab will not move freely, as some restraint will
shrinkage strain, εshu , as
invariably be present. These restraints will restrict the free move-
εshu ¼ 780 × 10−6 mm=mm ð3cÞ ment and are responsible for the stresses developed in the slab
section. Clause 24.4.2 of ACI 318-19 states that when structural
where [for Eqs. (2a) and (2c)] fc0 = cylinder compressive strength of walls, columns, or supports provide significant restraint to shrink-
concrete; t = age of concrete at the instant considered (in days); ts = age and temperature movements, the restraint of volume changes
age of concrete at the beginning of drying shrinkage (or swelling), causes tension in slabs, as well as displacements, shear forces, and
i.e., at the end of curing period (because formwork may be assumed flexural moments in columns or walls. In these cases, it may be
to be removed after approximately one week, ts may be taken as necessary to increase the amount of slab reinforcement as speci-
7 days); ks = parameter depending on the notional size of the cross fied by ACI 318-19 in Clause 24.4.3.2, in both principal direc-
section, s0 (Table 1); s0 is the notional size (mm) of the cross sec- tions. However, ACI 318-19 does not give guidelines on how
tion ¼ 2Ac =u in which Ac is the cross-sectional area of the concrete much the increase should be. ACI 318-19 also states that the
member and u is the perimeter of that part of the cross section top and bottom reinforcement are both effective in controlling the
which is exposed to drying (the notional size of a wall drying from cracks.
both faces is equal to its thickness); and εcd;0 = nominal unre-
strained drying shrinkage derived from equations in Annex B.2 of
Eurocode 2. Minimum Reinforcement in Beams
The design values of autogenous shrinkage strain estimated by
using Eq. (2) are shown in Fig. 1. In this figure, M20–M90 indicate Before considering the minimum steel slabs, the minimum steel
the cylinder strength (Grade) of concrete in MPa. The autogenous provisions of beams are discussed because they are also flexural
shrinkage strain increases considerably as the strength of concrete members. In Clause 9.6.1 of ACI 318-19, the minimum flexural
increases from M20 to M90 and also with time. reinforcement for non-prestressed concrete beams is given as
pffiffiffiffiffi
0.25 fc0 1.4
As;min ¼ bw d ≥ b d ð5aÞ
Thermal Strains fy fy w

The restrained component of the thermal strain, εr , is given by the In addition, the value of fy to be used in Eq. (5a) is limited to a
following equation [Hong Kong Concrete Code (2013)]: maximum of 550 MPa in ACI 318-19.
Clause 26.5.1.1 of IS 456:2000 (BIS 2000) similarly stipulates
εr ¼ 0.8αðT 1 þ T 2 ÞR ð4Þ
0.85
As;min ≥ b d ð5bÞ
where R = restraint factor (taken as 0.2–0.4 for slabs); α = coef- fy w
ficient of thermal expansion of concrete (average value may be
taken as 10 × 10−6 =°C); T 1 = short-term difference between peak where bw = web width; and d = effective depth of a T-beam. For a
hydration temperature and mean ambient temperature; and T 2 = statically determinate T-beam with the flange in tension, bw is the
long-term variation in temperature from ambient to seasonal mini- lesser of the width of flange (bf ) and 2bw .
mum. T 1 can be estimated from tables and charts in CIRIA Guide The value of the cracking moment, M cr , of a flexural member
C766 (Concrete Society 2018). The value of T 1 is based upon the may be calculated as
thickness of the structural member, the cement content, and the type
of formwork. M cr ¼ fr Z ð6aÞ

© ASCE 06021005-2 Pract. Period. Struct. Des. Constr.

Pract. Period. Struct. Des. Constr., 2021, 26(4): 06021005


Table 2. Temperature and shrinkage reinforcement in slabs based on gross concrete area
Code specification
ACI 318-19 NZS 3101:2006 AASHTO
IS 456:2000 (Clauses 7.6.1.1 (Clauses 8.8.1 (1996) AASHTO (2017)
Description (Clause 26.5.2.1) and 24.4.3.3) and 2.4.4.4) (Section 8.20) (Section 5.10.6)
1.3
Slabs with mild steel bars 0.0015 Ag 0.0018 Ag 0.7 Ag =fy ≥ 0.0014 Ag ≥264.5 mm2 =m A f > 0.11ðAg =f y Þ
Slabs with high strength deformed 0.0012 Ag 0.0018 Ag 2ðb þ hÞ g y
bars or welded wire fabric
90,000
Spacing of reinforcement (s) mm ≤5d ≤ 300 ≤5D ≤ 450 Smaller of − 2.5cc ≤3D ≤ 450 ≤3D ≤ 450
fs
Downloaded from ascelibrary.org by "Indian Institute of Technology, Roorkee" on 08/13/21. Copyright ASCE. For personal use only; all rights reserved.

90,000
and
fs

Note: Ag = Gross-area of section; b = breadth of slab; cc = clear cover of reinforcement in mm; D = total depth of slab; d = effective depth of slab; f s = stress in
reinforcement in serviceability limit state in MPa; and f y = yield stress of reinforcement.

pffiffiffiffiffi the modulus of rupture based on ACI 318-19 as fr ¼


Using and temperature reinforcement, as given in Table 2 [IS
0.62 fc0 , M cr is written as 456:2000 (BIS 2007); ACI 318-19 (ACI 2019); AASHTO 1996;
! AASHTO 2017]. Although these empirical values specified in
pffiffiffiffiffi D2 pffiffiffiffiffi the codes have not been changed for a long time, they have been
0
Mcr ¼ 0.62 f c 1,000 × ¼ 103.33D2 f c0 ð6bÞ used satisfactorily for many years.
6
Optimal crack control is often achieved by using small bar diam-
Similarly, the nominal moment capacity of a flexural member eters at smaller spacing (Leonhardt 1988). Clause 7.7.6.2 of ACI
may be calculated per ACI 318-19 (without strength reduction 318-19 suggests that such reinforcements should have a maximum
factor, φ), as (McCormac and Brown 2015) spacing of five times the slab thickness or 450 mm, whichever is
smaller (Table 2). Per Clause 26.3.3(b) (2) of IS 456:2000 (BIS
M n ¼ f y Ast ðd − 0.5aÞ ð7aÞ 2007) and Amendment 3 of August 2007, the distance between
shrinkage and temperature reinforcement bars should not be more
where the depth of equivalent rectangular stress block than five times the effective depth of slab or 300 mm, whichever
fy Ast is smaller. According to the ACI 318-19 code, splices and end an-
a¼ ð7bÞ chorages of shrinkage and temperature reinforcements should be
0.85fc0 B designed for the full specified yield strength. In one way slabs,
where Ast = area of tension steel in the cross section; B = breadth of shrinkage, and temperature reinforcement are provided normal
the slab; d = effective depth of the slab; f y = yield stress of reinforc- to the flexural reinforcement [over the flexural reinforcement (bot-
ing steel; and fc0 = cylinder compressive strength of concrete. tom bars) in the positive moment region and below the flexural
The minimum steel reinforcement from Eq. (5a) will result in a reinforcement (top bars) in the negative moment region].
nominal moment capacity, Mn , which will be about twice the crack- Usually, slabs and other members are joined rigidly to other
ing moment, M cr , for rectangular beams and will safeguard the parts of the structure and cannot contract or expand freely. In such
beam against sudden failure due to cracking (Seguirant et al. situations, reinforcement beyond that suggested for minimum steel
2010). The earlier version of ACI 318-89 (ACI 1989) used only may need to be provided; otherwise, the slabs will crack due to the
the second expression of Eq. (5a), which is similar to the provision shrinkage stresses. However, analyzing the effects of shrinkage or
of IS 456:2000 [Eq. (5b)]. At the time these provisions were de- temperature change is complicated and neither the IS 456:2000
rived, Grade 27.5 MPa concrete and Grade 275 reinforcement steel nor the ACI 318-19 code provides guidelines for determining the
were considered normal and hence the expression on the right-hand effects due to shrinkage or temperature.
side of Eq. (5a) resulted in a minimum steel ratio of about 0.005. According to Clauses 7.6.1.1 and 8.6.1.1 of ACI 318-19, the min-
For Grade 415 steel and Grade 25 MPa concrete, Eq. (5b) results in imum flexural reinforcement to be provided in slabs is 0.0018 times
minimum steel of 0.20% of the cross-sectional area, which is about the gross concrete area of the section (Table 2). The Commentary to
two-thirds of that calculated using Eq. (5a). Based on the preceding Clause 8.6.1.1 of ACI 318-19 states that “However, whereas shrink-
discussions, the minimum steel requirements of concrete members age and temperature reinforcement is permitted to be distributed be-
should be a function of not only the strength of concrete but also the tween the two faces of the slab as deemed appropriate for specific
strength of reinforcements. conditions, minimum flexural reinforcement should be placed close
as practicable to the face of the concrete in tension due to applied
loads.” The Commentary also states that this minimum area of
Minimum Steel Requirements of Slabs steel is the same as that prescribed for shrinkage and temperature
reinforcement in Clause 24.4.3.2. This empirically specified area of
Slabs are often exposed to radiation from the sun and develop tem- steel for deformed bars and the welded-wire fabric has been used
perature stresses in addition to shrinkage stresses. Hence, nominal satisfactorily for many years.
reinforcements are often provided close to the surface that is being In IS 456:2000, the minimum steel requirement of slabs is pre-
affected to address temperature and shrinkage. Roof slabs are often scribed in Clause 26.5.2.1 as 0.15% of the gross cross-sectional
provided with a weathering course and tiles to reduce the temper- area for mild steel reinforcement and 0.12% for high-strength de-
ature stresses. Where shrinkage and temperature movements are formed bars. Per the Handbook on Indian Standard Code for Plain
permitted to occur freely, codes specify the amount of shrinkage and Reinforced Concrete, SP 24:1983 (BIS 1983), this minimum

© ASCE 06021005-3 Pract. Period. Struct. Des. Constr.

Pract. Period. Struct. Des. Constr., 2021, 26(4): 06021005


Table 3. Area of reinforcement for crack control and shrinkage as per AS 3600:2018
Depth of slab, D (mm)
Ast (mm2 =m width) 100 110 120 130 140 150 160 170 180 190 200 250
1.75D 175 193 210 228 245 263 280 298 315 333 350 438
3.5D 375 413 450 488 525 563 600 638 675 713 750 938
6.0D 600 660 720 780 840 900 960 1,020 1,080 1,140 1,200 1,500

reinforcement required for slabs is less than that required by beams, force); k = coefficient which allows for the effect of non-uniform
Downloaded from ascelibrary.org by "Indian Institute of Technology, Roorkee" on 08/13/21. Copyright ASCE. For personal use only; all rights reserved.

because the overload will be distributed laterally and sudden failure self-equilibrating stresses or tensile stresses due to restraint of in-
will be less likely, and hence is based on shrinkage and temperature trinsic deformations (generally k ¼ 0.8, however for rectangular
effects. sections k ¼ 0.8 when depth of the section D ≤ 300 mm, and k ¼
The provisions in NZS 3101:2006 (NZS 2006) include the yield 0.5 when D ≥ 800 mm; and k ¼ 1 when tensile stresses are due to
strength of steel and range between 0.17% and 0.14% of the gross restraint of extrinsic deformations); and σs = yield strength of the
cross-sectional area for steels of Grade 415–500 MPa. These mini- steel. For a slab of depth D ¼ 175 mm, with no axial force, and
mum steel provisions are compared in Table 2. assuming k ¼ 1.0, Act ¼ 0.5BD, with kc ¼ 0.4, and fct;eff ð28Þ ¼
The commentary to Clause 24.4.3.2 of ACI 318-19 states that 0.1fck [for concrete grade less than M60, a value of fct;eff ð28Þ ¼
“Previous editions of the code permitted a reduction in shrinkage 0.3ðf ck Þ2=3 is specified in Eurocode 2]. Substituting these values in
and temperature reinforcement for reinforcement with a yield Eq. (8a), the following equation is obtained:
strength greater than 420 MPa (i.e., Ast;min ¼ 0.0018 × 420=f y ≥
0.0014). However, as the mechanics of cracking suggested that As;min ¼ 0.02BDf ck =fy ð8bÞ
any increase in yield strength is not beneficial for the control of
cracking, this provision was removed in the 2019 edition. Also, the For fck ¼ 25 MPa and f y ¼ 415 MPa, the steel percentage is
0.20% provision for mild steel bar has been removed and 0.18% is 0.06% and for fck ¼ 45 MPa and f y ¼ 415 MPa, the steel percent-
uniformly recommended for all types of reinforcement.” age is 0.11%. These values are found to be much less than those
Interestingly Clause 9.5 of the Australian code, AS 3600:2018 specified in ACI 318-19 and IS 456:2000.
(AS 2018), and ACI 209R-92 (ACI 2008b) provide some guidance
on shrinkage and temperature effects and suggest reinforcement Brittle Failures in Some Precast Parking Structures
based on the depth of the slab and environmental exposure condi- When the ratio of the nominal moment to cracking moment
tions ranging from 1.75D to 6D mm2 =m, where D is the depth of (M n =M cr ) is less than 1.0, cracking could lead to an immediate
slab (Table 3). According to Gilbert (1992), the shrinkage and tem- collapse in statically determinate slabs or beam flanges. This fact
perature reinforcement required for a fully restrained slab could be was recently confirmed in the experimental study of the collapse
double that required by ACI 318-19. Cracks due to restrained dry- of precast, prestressed double-tee (DT) members in a 1,200-car
ing shrinkage can be serious, because unlike flexural cracks, they parking structure at Harrah’s Cherokee Resort in Cherokee, North
can extend the full depth of the member (Carino and Clifton 1995; Carolina, US, that occurred February 19, 2015, and April 15, 2016.
Babaei and Fouladgar 1997). The minimum steel requirements will The flange slabs of these DT members failed as soon as the first
not eliminate shrinkage cracking but will reduce the width of cracks. crack appeared, as shown in Fig. 2 (Lunn et al. 2015; Gamble et al.
Clause 3.5.2 of ACI 224R-01 (ACI 2008a) states that “The min- 2019). Because the flange reinforcement in that project was made
imum amount and spacing of reinforcement to be used in structural of carbon-fiber-reinforced polymer (CFRP) grids, there may be
floors, roof slabs, and walls for control of temperature and shrink- other issues connected with these failures. However, the basic prob-
age cracking is given in ACI 318-19 or ACI 350-06 (ACI 2006). lem was that M n was significantly smaller than M cr .
The minimum reinforcement percentage, which is between 0.18% To avoid such failures as shown in Fig. 2, the minimum
and 0.20%, does not normally control cracks to within generally reinforcement in slabs should consider the parameters that influ-
acceptable design limits. To control cracks to a more acceptable ence the behavior of slabs (e.g., the strength of concrete and steel),
level, the percentage requirement needs to exceed about 0.60%.” and not simply be specified as a percentage of the area of the slab,
Thus, this document says that the shrinkage and temperature as in the present codes. Hence, a new equation is proposed and is
reinforcement needs to be about three times more than the ACI compared with the provisions of other codes and that proposed by
318-19 minimum to obtain acceptable crack widths (see also Gamble (2017).
Suprenant 2002, 2016).

Recommendations by Other Researchers


Minimum Steel According to Eurocode 2
Per Clause 7.3.2 of Eurocode 2, the minimum reinforcement area Any reinforcement that is provided will not control the crack until
As;min may be calculated as cracks develop in concrete. The reinforcement will not prevent any
cracks, but can control both the crack spacing and crack widths
As;min ¼ kkc Act f ct;eff ðtÞ=σs ð8aÞ (Carino and Clifton 1995). Concrete cracks when the maximum
tensile stress in the slab equals the modulus of rupture. Cracking
where As;min = minimum reinforcement area; Act = area of the con- can be due to applied loads or restraint forces. When a crack devel-
crete within the tensile zone; fct;eff ðtÞ = mean value of the concrete ops in the concrete, there will not be any compatibility between the
tensile strength at time, t, when the first crack is expected to occur steel and concrete. At the crack, the steel reinforcement will carry
(t may be assumed to be 28 days); kc = coefficient which takes into the entire tensile stress and the stress in the concrete will be zero
account the stress distribution within the cross section (kc ¼ 1.0 for (Gilbert 1992). If the minimum amount of reinforcement is not
pure tension and kc ¼ 0.4 for bending without normal compressive provided, the slab will suddenly fail.

© ASCE 06021005-4 Pract. Period. Struct. Des. Constr.

Pract. Period. Struct. Des. Constr., 2021, 26(4): 06021005


Downloaded from ascelibrary.org by "Indian Institute of Technology, Roorkee" on 08/13/21. Copyright ASCE. For personal use only; all rights reserved.

Fig. 2. Failure in a parking garage in North Carolina of a flange slab of double-Tee member with a thickness of (a) 89 mm (3.5 in.); and (b) 120 mm
(4.75 in.). (Images courtesy of Jason Reigstad.)

Frosch et al. (2003) conducted a field evaluation of 20 bridges Table 4. Percentage minimum reinforcement for f y ¼ 415 MPa
in various locations in Indiana, US. They instrumented a typical Concrete strength, f ck 20 MPa 35 MPa
bridge structure to understand the behavior of transverse cracks
Direct tension 0.76 1.08
in a concrete bridge deck. They also conducted an experimental Bending 0.15 0.22
investigation on 10 reinforced concrete slab models. Based on these
investigations, they recommended that the total amount of reinforc-
ing steel to prevent uncontrolled crack growth is
pffiffiffiffiffi Leonhardt (1988) cautioned that when the first crack appears,
f c0 sudden failure of the slab may occur when the force transferred
As;min ¼ 0.50 A ð9Þ
fy g from the concrete to the reinforcement is greater than the strength
of the reinforcement. Cracking can be due to applied loads or
where Ag = gross area of section, mm2 ; As;min = minimum area of restraint forces. To prevent such failures, Leonhardt (1988) sug-
reinforcement in the cross section, mm2 ; f c0 = specified cylinder gested a minimum amount of reinforcement as given in Table 4.
compressive strength of concrete, MPa; and f y = specified yield He also provided a chart that can be used to find the steel stress
strength of reinforcement, MPa. at the first crack and the percentage of minimum reinforcement
This recommendation is based p onffiffiffiffiffi
the tensile strength of con- required to avoid reinforcement yielding when the first crack
crete in direct tension taken as 0.5 f c0 and full transfer of stress occurs.
from concrete to the reinforcement at the location of the crack. For
25 MPa concrete and grade Fe 415 reinforcement, this recommen-
dation results in 0.67% steel in the deck cross section. Recommended Equation for Minimum Steel
Realizing a minimum reinforcement requirement was needed for Slabs
and considering all the controlling factors such as concrete strength,
the yield stress of reinforcement, and the ratio of depth to effective As discussed previously, sufficient steel should be provided such
depth, the following equation was derived iteratively by Gamble that when the first crack occurs the reinforcement will not yield;
(2017): this amount of steel will also control the crack spacing and hence
the crack width. Steel stress at a first crack is given by (Leonhardt
rffiffiffiffiffi rffiffiffiffiffi 1988)
0.0018 × 420 f c0 D fc0
As;min ¼ × × 0.85Ag > 0.0014Ag
fy 30 d 30 σscr ¼ kkc fct ðtÞAct =As;min ð11aÞ
ð10aÞ
where As;min = minimum reinforcement area; Act = area of the con-
which can be simplified to crete within the tensile zone; f ct ðtÞ = concrete tensile strength at
  time, t, days, when the first crack is expected to occur (t may
0.1173 pffiffiffiffiffi0 D pffiffiffiffiffi
As;min ¼ fc Ag > 0.000256 f c0 Ag ð10bÞ be assumed to be 28 days); kc = coefficient which takes into ac-
fy d count the stress distribution within the cross section (kc ¼ 1.0 for
pure tension and kc ¼ 0.4 for bending without normal compressive
where Ag = gross cross-sectional area of the slab; As;min = minimum force); and k = coefficient to address non-uniform self-equilibrating
area of reinforcement in the cross section; f c0 = cylinder compres- stresses (k ¼ 0.8 per Eurocode 2).
sive strength of concrete; D = depth of the slab; and d = effective Eurocode 2 recommends the value for f ct;eff to be taken as the
depth. In Eq. (10a), 0.85 is a correction factor suggested by Gamble mean tensile strength of concrete, fctm . However, according to
(2017) to obtain M n =M cr values greater than 1.0. Comparing Eqs. (9) CIRIA Guide C766 (Concrete Society 2018), there may be reduc-
and (10), Eq. (9) suggests approximately 4.26 times more steel tions in tensile strength due to the combinations of scale effects,
than Eq. (10). tension stiffening, and early age and long-term sustained load

© ASCE 06021005-5 Pract. Period. Struct. Des. Constr.

Pract. Period. Struct. Des. Constr., 2021, 26(4): 06021005


Table 5. Comparison of percentage of minimum reinforcement for various concrete and steel strengths, assuming D=d ¼ 1.11
Eq. (10b) with fy (MPa) Eq. (11b) with f y (MPa)
f c0 (MPa) 415 500 550 415 500 550 ACI 318-19 IS 456:2000
25 0.16 0.13 0.13 0.19 0.16 0.15 0.18 0.12
30 0.17 0.14 0.13 0.21 0.17 0.15 0.18 0.12
35 0.18 0.15 0.14 0.22 0.18 0.17 0.18 0.12
40 0.20 0.16 0.15 0.24 0.20 0.20 0.18 0.12
45 0.21 0.17 0.16 0.25 0.21 0.21 0.18 0.12
Downloaded from ascelibrary.org by "Indian Institute of Technology, Roorkee" on 08/13/21. Copyright ASCE. For personal use only; all rights reserved.

pffiffiffiffiffi  
f c0 D
As;min ¼ 0.14 A ≥ 0.0015Ag ð11bÞ
fy d g

Assuming a value for D=d of 1.11, a comparison of minimum


percentage of reinforcement slabs based on Eqs. (10b) and (11b)
and ACI 318-19 and IS 456:2000 provisions is given in Table 5.
As steel strength increases, the required percentage of steel decreases.
The required percentage of steel is higher than that prescribed in
IS 456:2000 for most cases. The ACI 318-19 code governs when
the steel strength is 500 MPa or more and the concrete strength is
less than 35 MPa.
Fig. 3 (Table 6) compares minimum steel requirements according
to ACI 318-19, IS 456:2000, and Eqs. (10b) and (11b), as a M n =M cr
versus fc0 plot, for a slab with D ¼ 175 mm, d ¼ 137.5 mm, and
Grade 415 steel reinforcement. Table 7 compares Mn =M cr values
for the same slab with different fc0 values and Grade 500 steel.
Fig. 3. M n =M cr versus fc0 plot for a slab with D ¼ 175 mm, The Mn =M cr values for a slab with D ¼ 175 mm, d ¼
d ¼ 137.5 mm, and Grade 415 steel. 137.5 mm, and Grade 415 reinforcing bars decrease as the strength
of concrete increases both for ACI 318-19 and IS 456:2000 code
recommendations (Fig. 3; Tables 6 and 7). If the minimum
reinforcement ratio per ACI 318-19 is adopted, as the concrete
effects. Hence, it recommends that the value of f ct;eff be taken as strength increases, the cracking moment increases significantly
0.7f ct;eff . whereas the nominal moment increases only nominally (Gamble
The value of σscr can be assumed to be the yield stress of steel 2017). Both Eqs. (10b) and (11b) have Mn =M cr values greater than
reinforcement, to prevent yielding when the first crack appears. The 1.0 [about 1.11 for Eq. (10b) and about 1.32 for Eq. (11b)]. Fig. 3
valuepof modulus of rupture per Clause 19.2.3.1 of ACI 318-19 is shows that using the ACI 318-19 code expression, when fc0 ¼ 25
0.62 f c0 and kc ¼ 0.4 for bending. Substituting these values, tak- the value of M n =M cr ¼ 1.11; however, for stronger concretes this
ing fct as 0.7fct , introducing the D=d term, rearranging Eq. (9a), ratio is less than 1.0. IS 456:2000 and Eurocode 2 do not provide
and rounding off, the following equation is obtained: enough safety margin against cracking moment. From Table 7 it

Table 6. Comparison of Mn =M cr for a slab with different f c0 and with D ¼ 175 mm, d ¼ 137.5 mm, and Grade 415 steel
Eq. (10b) Eq. (11b) ACI 318-19
f c0 (MPa) M cr (kN · m) Ast (mm ) 2
M n (kN · m) M n =M cr Ast (mm ) 2
M n (kN · m) M n =M cr Ast (mm ) 2
M n (kN · m) Mn =M cr
25 15.82 315 17.56 1.11 376 20.81 1.31 315 17.57 1.11
30 17.33 345 17.33 1.11 412 22.91 1.32 315 17.64 1.02
35 18.72 372 18.72 1.11 445 24.80 1.32 315 17.69 0.95
40 20.01 398 20.02 1.12 475 26.54 1.32 315 17.72 0.89
45 21.23 432 21.23 1.12 504 28.18 1.33 315 17.75 0.84

Table 7. Comparison of Mn =M cr for a slab with different f c0 and with D ¼ 175 mm, d ¼ 137.5 mm, and Grade 500 steel
Eq. (10b) Eq. (11b) ACI 318-19
f c0 (MPa) M cr (kN · m) Ast (mm2 ) M n (kN · m) M n =M cr Ast (mm2 ) M n (kN · m) M n =M cr Ast (mm2 ) M n (kN · m) Mn =M cr
25 15.82 261 17.56 1.11 312 20.86 1.32 315 21.07 1.33
30 17.33 286 19.27 1.11 342 22.91 1.32 315 21.17 1.22
35 18.72 309 20.85 1.11 369 24.79 1.32 315 21.24 1.13
40 20.01 330 22.32 1.12 394 26.54 1.33 315 21.29 1.06
45 21.23 351 23.70 1.12 418 28.19 1.33 315 21.33 1.00

© ASCE 06021005-6 Pract. Period. Struct. Des. Constr.

Pract. Period. Struct. Des. Constr., 2021, 26(4): 06021005


can be seen that similar M n =M cr values of about 1.11–1.12 are Mn , values greater than 1.3 times the moment causing cracking,
obtained with Eq. (10b). Using Eq. (11b) we obtain values of Mcr , for all grades of steel reinforcement.
1.32–1.33 when Grade 500 steel is used. The Mn =Mcr values 6. It is advisable to validate the proposed equation either by
are improved to 1.33 from 1.0 for the ACI 318-19 code when Grade numerical modeling using finite element analysis or by con-
500 steel is used. ducting experimental research on slabs with different concrete
Clause 5.7.3.3.2 of AASHTO LRFD (AASHTO 2017) states and reinforcement strengths.
that the flexural capacity must be greater than the cracking moment
and 1.33 times the factored moment. Also, Clause 9.6.1.3 of ACI
318-19 states that “If As provided at every section is at least one- Data Availability Statement
third greater than As required by analysis, minimum flexural
reinforcement as per 9.6.1.1 and 9.6.1.2 need not be satisfied.” All the required data is available in the paper itself.
Downloaded from ascelibrary.org by "Indian Institute of Technology, Roorkee" on 08/13/21. Copyright ASCE. For personal use only; all rights reserved.

Example Acknowledgments
Determine the minimum reinforcement of a floor slab of 3.5 × 9 m. I wish to acknowledge with thanks the help of Dr. Adil Dar, Post-
Use M25 concrete and Grade Fe 415 steel. The designed depth of doctoral Research Fellow, Department of Civil & Environmental
slab is 175 mm and the main steel consists of 10-mm bars at a spac- Engineering, National University of Singapore, for making the
ing of 150 mm. Hence, the effective depth = 140 mm. drawings in this paper. I also thank Diane Harris for fixing issues
Using the ACI 318-19 Code, the minimum steel = 0.18 × regarding the language.
2
1,000=100
pffiffiffiffiffi × 175 ¼ 315 mm . The minimum steel per Eq. (11b) =
0.14ð 25=415Þð175=140Þð1,000 × 175Þ ≥ 0.0015ð1,000 × 175Þ¼
369 mm2 >263 mm2 . Using Eq. (11b) results in only 17% more steel Notation
in this case but provides safety against sudden failure when the first
crack appears. The following symbols are used in this paper:
Ac = cross-sectional area of concrete, mm2 ;
Act = area of concrete within tensile zone, mm2 ;
Summary and Conclusions
Ag = gross area of cross section, BD, mm2 ;
Reinforced concrete slabs should be provided with at least mini- As;min = minimum flexural reinforcement for non-prestressed
mum shrinkage and temperature reinforcement so that they will concrete beam or slab, mm2 ;
not suddenly collapse when the first crack appears in concrete. Ast = area of tension steel in cross section, mm2 ;
Several codes provide empirical provisions for these reinforcements. a = depth of equivalent rectangular stress block, mm;
They are dependent on a certain percentage of the area of the cross B = width of slab, mm;
section (ranging from 0.12% to 0.18%) and have not been changed bw = web width of T-beam, mm;
in the last several years. Shrinkage strain increases with time and D = depth of slab, mm;
concrete strength. The minimum steel provision for beams (which d = effective depth of T-beam or slab, mm;
are also flexural members) has recently been revised in ACI 318-19
f c0 = cylinder compressive strength of concrete, MPa;
and has an expression containing the strengths of both concrete and
fck = cube compressive strength of concrete, MPa;
steel. The current minimum steel provisions for slabs in different
codes have been reviewed. A new equation taking into account the f ct;eff ðtÞ = mean value of concrete tensile strength at time, t, MPa;
parameters that will influence the behavior of slabs has been derived f r = modulus of rupture of concrete, a measure of tensile
and compared with existing code provisions. Based on this the fol- strength, MPa;
lowing conclusions are drawn: f y = yield strength of steel reinforcement, MPa;
1. Most of the codes specify a percentage of the cross-sectional k = coefficient to consider reduction in restraint due to
area as the minimum steel. These percentages are not based on nonuniform and self-equilibrium effect;
any research but are empirical. kc = coefficient to consider stress distribution within cross
2. Reinforced concrete slabs provided with high-strength reinforce- section;
ment per the current minimum steel provisions, could collapse ks = parameter based on notional size of cross section s0 ;
at the cracking moment, as was seen in the parking structures M cr = cracking moment of section, kN · m;
located in North Carolina, US (Gamble et al. 2019). M n = nominal moment capacity of section, kN · m;
3. A new equation for the minimum steel of slabs has been derived, R = restraint factor (may be taken as 0.2–0.4 for slabs);
considering all the possible factors (such as concrete strength, s0 = notional size of cross section, mm ¼ 2Ac =u;
yield stress of reinforcement, and the ratio of depth to effective
T 1 = difference between peak temperature and mean ambient
depth) that may affect the behavior.
temperature, °C;
4. As the steel strength increases, the required percentage of steel
T 2 = long-term variation in temperature, °C;
decreases. The required percentage of steel is higher than that
prescribed in IS 456:2000 for most of the cases. ACI 318-19 ts = age of concrete at the beginning of drying shrinkage,
governs when the steel strength is 500 MPa or more and the days;
concrete strength is less than 35 MPa. u = perimeter of that part of cross section which is exposed
5. The provisions in ACI 318-19 and IS 456:2000 have been com- to drying, mm;
pared with the proposed equation as well as with that proposed α = coefficient of thermal expansion of concrete (average
by Gamble (2017). The proposed equation provides a consistent value 10 × 10−6 =°C);
safeguard against sudden collapse due to cracking. This is be- εca ðtÞ = autogenous shrinkage strain at time, t;
cause this proposed equation provides nominal moment capacity, εcd ðtÞ = drying shrinkage strain at time, t;

© ASCE 06021005-7 Pract. Period. Struct. Des. Constr.

Pract. Period. Struct. Des. Constr., 2021, 26(4): 06021005


εcd;0 = nominal unrestrained drying shrinkage; CEN (European Committee for Standardization). 2004. Eurocode 2:
εcs ðtÞ = total shrinkage strain at time, t; Design of concrete structures. Part 1-1: General rules and rules for
buildings. EN 1992-1-1:2004. Brussels, Belgium: CEN.
εr = restrained component of thermal strain at time, t; and Concrete Society. 2018. Early-age thermal crack control in concrete.
εshu = average value for ultimate shrinkage strain. Construction Industry Research and Information Association (CIRIA)
Guide C766. London: Concrete Society.
Frosch, R. J., D. T. Blackman, and R. D. Radabaugh. 2003. Investigation of
References bridge deck cracking in various bridge superstructure systems. Rep. No.
FHWA/IN/JTRP-2002/25, SPR 2404. West Lafayette, IN: Purdue Univ.
AASHTO. 1996. AAHTO Standard specifications for highway bridges. Gamble, W. L. 2017. “A minimum flexural reinforcement puzzle.” ACI
16th ed. Washington, DC: AASHTO. Concr. Int. 39 (1): 47–49.
AASHTO. 2017. AASHTO LRFD bridge design specifications. 8th ed. Gamble, W. L., G. H. Reigstad, and J. Reigstad. 2019. “Brittle failures in
Downloaded from ascelibrary.org by "Indian Institute of Technology, Roorkee" on 08/13/21. Copyright ASCE. For personal use only; all rights reserved.

Washington, DC: AASHTO. precast parking structures.” ACI Concr. Int. 41 (9): 32–39.
ACI (American Concrete Institute). 1989. Building code requirements for Gilbert, R. I. 1992. “Shrinkage cracking in fully restrained concrete
structural concrete (ACI 318-89) (revised 1992) and commentary (ACI members.” ACI Struct. J. 89 (2): 141–149.
318R-89) (revised 1992). ACI 318-89. Farmington Hills, MI: ACI. Hong Kong Concrete Code. 2013. Code of practice for structural use of
ACI (American Concrete Institute). 2006. Code requirements for environ- concrete. Hong Kong: Buildings Department.
mental engineering concrete structures. ACI 350-06. Farmington Hills, Leonhardt, F. 1988. “Special report: Cracks and crack control in concrete
structures.” PCI J. 22 (4): 124–145.
MI: ACI.
Lunn, D., G. Lucier, S. Rizkalla, N. Cleland, and H. Gleich. 2015. “New
ACI (American Concrete Institute). 2008a. Control of cracking in concrete
generation of precast concrete double tees reinforced with carbon fiber
structures. ACI 224R-01. Farmington Hills, MI: ACI.
reinforced polymer grids.” PCI J. 60 (4): 37–48. https://doi.org/10
ACI (American Concrete Institute). 2008b. Prediction of creep, shrinkage,
.15554/pcij.07012015.37.48.
and temperature effects in concrete. ACI 209R-92. Farmington Hills,
McCormac, J. C., and R. H. Brown. 2015. Design of reinforced concrete.
MI: ACI.
10th ed., 672. New York: Wiley.
AS (Standards Australia). 2018. Concrete structures. AS 3600. Sydney, Ng, P.-L., and A. K.-H. Kwan. 2017. “A rigorous analytical model for
Australia: AS. shrinkage cracking of reinforced concrete.” Mag. Concr. Res. 69 (3):
Babaei, K., and A. M. Fouladgar. 1997. “Solutions to concrete bridge deck 120–133. https://doi.org/10.1680/jmacr.16.00042.
cracking.” ACI Concr. Int. 19 (7): 34–37. NZS (New Zealand Standards). 2006. Part 1: The design of concrete
Bamforth, P., D. Chisholm, J. Gibbs, and T. Harrison. 2008. Properties structures, part 2: Commentary. NZS 3101:2006. Wellington,
of concrete for use in Eurocode 2. Concrete Center Publication No. New Zealand: NZS.
CCIP-029. Surrey, UK: Concrete Centre. Seguirant, S. J., R. Brice, and B. Khaleghi. 2010. “Making sense of mini-
BIS (Bureau of Indian Standards). 1983. Handbook on Indian standard mum flexural reinforcement requirements for reinforced concrete
code for plain and reinforced concrete. SP 24:1983. New Delhi, India: members.” PCI J. 55 (3): 64–85. https://doi.org/10.15554/pcij.06012010
BIS. .64.85.
BIS (Bureau of Indian Standards). 2000. Indian standard code of practice Suprenant, B. 2016. “Beware of structural designs that use reinforcing steel
for plain and reinforced cement concrete. IS 456:2000. New Delhi, for shrinkage and temperature crack control.” The Voice Newsletter,
India: BIS. June 1, 2016.
BIS (Bureau of Indian Standards). 2007. Amendment No.3, Aug. 2007 Suprenant, B. A. 2002. “Shrinkage and temperature reinforcement—Simple
to plain and reinforced concrete-code of practice. IS 456:2000. New topic; not-so-simple design issues.” Concr. Int. 24 (9): 72–76.
Delhi, India: BIS. Yang, Y., R. Sato, and K. Kawai. 2001. “Evaluation of autogenous shrink-
Carino, N. J., and J. R. Clifton. 1995. Prediction of cracking in rein- age and drying shrinkage based on bound water content of cementitious
forced concrete structures. Rep. No. NISTIR 5634. Gaithersburg, materials.” In Proc., JSCE from Transactions. Tokyo: Japan Society of
MD: Building and Fire Research Laboratory, NIST. Civil Engineers.

© ASCE 06021005-8 Pract. Period. Struct. Des. Constr.

Pract. Period. Struct. Des. Constr., 2021, 26(4): 06021005

You might also like