S6295 - SMOKE DETECTORS FOR FIRE ALARM


SYSTEMS

Smoke Detectors for Fire Alarm Systems


See General Information for Smoke Detectors for Fire Alarm Systems

MIRCOM TECHNOLOGIES LTD S6295


25 Interchange Way
Vaughan, ON L4K 5W3 CANADA

Investigated to ANSI/UL 268 (editions prior to the 7th ed.)


Velocity
Range Date Time of Firmware
Detector Compatibility (fpm) of Manufacture Version
Firmware
Model Application Type Restrictions Min Max Manufacture Version Update
MDH- D(ST) I None 1000 4000 - - -
SL2000I
MDH- D(ST) P None 1000 4000 - - -
SL2000P
MDH- D(ST) I None 500 4000 - - -
SM501I
MDH- D(ST) P None 500 4000 - - -
SM501P
MIR-338H, OAP P(IHD) D1 0 300 - - -
MIR-
338HL
MIT-338, OAP P D1 0 300 - - -
MIT-338L
MIX-1251 OAP I D4 0 1500 - - -
MIX- OAP I *4 0 1200 - - -
1251AP (c)
MIX- OAP I *1, *2 0 1200 - - -
1251B (c)
MIX- OAP I D4, *1, *2 0 1200 - - -
1251DOD
(c)
MIX-2251 OAP, D(I) P D2 0 4000 - - -
MIX- OAP, D(I) P *4 0 4000 - - -
2251AP (c)
MIX- OAP, D(I) P *1, *2 0 4000 - - -
2251BR (c)
MIX- OAP P *1, *2 0 4000 - - -
2251DOD
(c)
MIX- OAP, D(I) P *4 - - -
2251RAP
(C)
MIX-2251T OAP, D(I) P(IHD) D2 0 4000 - - -
MIX- OAP, D(I) P(IHD) *4 0 4000 - - -
2251TAP
MIX- OAP, D(I) P(IHD) D2 0 4000 - - -
2251TB
MIX- OAP P(IHD) D2 0 4000 - - -
2251TM
MIX- OAP, D(I) P(IHD) *4 0 4000 - - -
2251TMAP
MIX- OAP P(IHD) D2 0 4000 - - -
2251TMB
MIX-3000 OAP I D4 0 300 - - -
MIX-3100 OAP P D4 0 300 - - -
MIX-3200 OAP P(IHD) D4 0 300 - - -
MIX-4000 OAP I(IHD) *3 0 3000 - - -
(hc)
MIX-4100 OAP P *3 0 300 - - -
MIX-4200 OAP P *3 0 300 - - -
MIX- OAP P(IHD) D4 0 4000 - - -
COSAP
MIX- D(ST) P D2 300 4000 - - -
DH3000 (100) (2000)
(e)
MIX- D(ST) P D2 300 4000 - - -
DH3000R (100) (2000)
(e)
MIX- D(ST) P D2 1000 4000 - - -
DH3100 (100) (4000)
(d)
MIX- D(ST) P D2 1000 4000 - - -
DH3100R (100) (4000)
(d)
MIX-FTX- OAP, D(I) P D2 0 4000 - - -
P1, MIX-
2251B
MPD-65I OAP I D2 0 300 - - -
MPD-65P OAP P D2 0 300 - - -
NB-338-2, OAP P D2 0 300 - - -
NB-338-2L
NB-338- OAP P(IHD) D2 0 300 - - -
2H, NB-
338-2HL
NB-338-4- OAP P None 0 300 - - -
12, NB-
338-4-24
NB-338- OAP P(IHD) None 0 300 - - -
4H-12,
NB-338-
4H-24
SD-2WP OAP P D1 0 300 - - -
SD-2WP, OAP P D1 0 300 - - -
SD-4WP
SD-2WP- OAP P D1 0 300 - - -
LED
SD-2WT OAP P(IHD) D1 0 300 - - -
SD-2WT- OAP P(IHD) D1 0 300 - - -
LED
SD-4WT, OAP P(IHD) D1 0 300 - - -
SD-2WT

Pressure
Differential
Velocity Between
Range Sampling Date Time of Firmw
Detector Compatibility (fpm) Tube of Manufacture Versio
Firmware
Model Application Type Restrictions Min Max Min Max Manufacture Version Upda
MIX-DH200PL, D(ST) P D2 100 4000 0.03 1.4 - -
MIX0DH200RPL
MIX-DH200P D(ST) P D2 500 4000 0.01 1.2 - -
(b),
MIX0DH200RP
(b)

Control Unit
Compatibility
Base Model Related Detector Restrictions
772912, 782912 NB338-2, NB338-2H, MIT-338, MIT-338-H B1, B2
774912, 784912 NB338-2L, NB338-4-12, NB338-4-24, NB338--2H, NB-338-2HL, B2
NB338-4H-12, NB338-4H-24, MIT-338L, MIT-338HL
B200SR MIX-1251AP, MIX-2251AP, MIX-2251TAP, MIX-2251TMAP, MIX- #3
2251RAP (C)
B210LP MIX-1251AP, MIX-2251AP, MIX-2251TAP, MIX-2251TMAP, MIX- #3
2251RAP (C)
B224BI, B224RB MIX-1251AP, MIX-2251AP, MIX-2251TAP, MIX-2251TMAP, MIX- #3
2251RAP (C)
B501, B501B, B501BH, B501BH-2, B501BHT, B501BHT-2
MIX-1251AP, MIX-2251AP, MIX-2251TAP, MIX-2251TMAP, MIX- #3
2251RAP (C)
MIX-200IH (a) refer to manufacturer's list B2, B3
MIX-200IHT (a) refer to manufacturer's list B2, B3
MIX-B210LP, MIX-B501BH, MIX-B224BI, MIX-B224RB (RS)
MIX-1251, MIX-2251 B2
MIX-B501DOD MIX-1251DOD, MIX-2251DOD #1, #2
MIX2000, MIX- MIX-3000 B2
2001, MIX-2001R
MSB-65B MID-65I, MPD-65R B2
SDB-2W SD-268, SD-269 B2
SDB-4W SD-268, SD-269, SD168, SD-169 B1
B1 - Listing limited to specific system control unit. Information on compatible control unit indicated on installation drawing of control unit
and/or detector.

B2 - For connection to Listed control units with which compatibility was determined by test or a review of circuit parameters.
Interconnection and compatible models indicated on installation wiring diagram for detector (base) and/or control unit.

B3 - For connection to a Listed open area protection smoke or heat detector head with which compatibility was determined by test or a
review of circuit parameters. Refer to the manufacturer's installation instructions for a list of compatible models.

D1 - Listing limited to specific system control unit. Information on compatible control unit indicated on installation drawing of control unit
and/or detector.

D2 - For connection to Listed control units with which compatibility was determined by test or a review of circuit parameters.
Interconnection and compatible models indicated on installation wiring diagram for detector (base) and/or control unit.

D4 - For connection to any manufacturer's Listed compatible control unit.

#1 - For connection to Listed Control Unit, Model ZXa manufactured by Morely with which compatibility was determined by test or a review
of circuit parameters. Interconnection and compatible models are indicated on installation wiring diagram for Detectors and/or control
units.

#2 - For connection to Listed Control Unit, Shark Series 10 056 manufactured by Fike Protection with which compatibility was determined
by test or a review of circuit parameters. Interconnection and compatible models are indicated on installation wiring diagram for Detectors
and/or control units.

#3 - For connection to Listed Control Unit, Models FX-350 and FX-2000 manufactured by Mircom Technologies with which compatibility was
de6termined by test or a review of circuit parameters. Interconnection and compatible models are indicated on installation wiring diagram
for Detectors and/or control units.

#4 - For connection to Listed Control Unit, Models FA-300 and FA-1000/FX-2000 manufactured by Mircom Technologies with which
compatibility was determined by test or review of circuit parameters. Interconnection and compatible models are indicated on installation
wiring diagram for Detectors and/or Control Units.

*1 - For connection to Listed Control Unit, Model ZXa manufactured by Morely with which compatibility was determined by test or a review
of circuit parameters. Interconnection and compatible models are indicated on installation wiring diagram for Detectors and/or control
units.

*2 - For connection to Listed Control Unit, Shark Series 10 056 manufactured by Fike Protection with which compatibility was determined
by test or a review of circuit parameters. Interconnection and compatible models are indicated on installation wiring diagram for Detectors
and/or control units.
*3 - For connection to Listed control units, Models IAG ZXa UL and ZXe UL with which compatibility was determined by test or a review of
circuit parameters. Interconnection and compatible models are indicated on installation wiring diagram for Detector (Base) and/or control
units. The following model must have 2 or greater devices on each loop.

*4 - For connection to Listed Control Unit, Models FX-350 and FX-2000 manufactured by Mircom Technologies with which compatibility was
determined by test or review of circuit parameters. Interconnection and compatible models are indicated on installation wiring diagram for
Detectors and/or Control Units.

D(ST) - Duct Detector - Sampling Tubes

I - Ionization

P - Photoelectric

OAP - Open Area Protection

IHD - Includes Integral Heat Detector

D(I) - Duct Detector - Installation Inside Duct

Values in parenthesis under the air velocities indicate use of an air deflector.

Date of Manufacture identifies the manufacturing start date of all product models that will use the specific Time of Manufacture Firmware
Version. The date of manufacture is noncoded and in the format YEAR (in 4 digits), MONTH (in letters), DAY (in 2 digits).

Time of Manufacture Firmware Version identifies a numerical and/or alphabetic series designation that is product and date-code
specific and will only identify the Firmware Version at the time the product was manufactured. The numeric and/or alphabetic sequence is
defined by the manufacturer.

Firmware Version Update is a numerical and/or alphabetic sequential identification that is product and date-code specific and
sequentially identifies the Firmware Version Update from the previous version of firmware. The numerical and/or alphabetic sequence is
defined by the manufacturer.

(a) - Includes integral audible signal.

(b) - Suitable for use in ambient temperatures of 0-55 C (23-131 F).

(c) - Suitable for use in ambient temperatures of 0-49 C (32-120 F).

(d) - Suitable for use in ambient temperatures of 0-60 C (32-140 F).

(e) - Suitable for use in ambient temperatures of 0-66 C (32-150 F).

(hc) - Complementary listed under Heat-Automatic Fire Detectors (UQGS).

Trademark and/or Tradename:

Last Updated on 2018-10-11

The appearance of a company's name or product in this database does not in itself assure that products so identified have been
manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered
under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications
Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a
copyright notice in the following format: "© 2019 UL LLC"

You might also like