Professional Documents
Culture Documents
14
ENTEC ENTEC
ELECTRIC & ELECTRONIC CO., LTD
Copyright © 2017 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Release Note:
ENHANCED TECHNOLOGY i
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
TABLE OF CONTENTS
1. INTRODUCTION ........................................................................................................... 1
1.1. Description .......................................................................................................................... 1
1.2. Summary of Features........................................................................................................... 2
3. APPLICATION ............................................................................................................. 37
4. DIMENSIONS AND CONSTRUCTION .................................................................... 38
5. SIDE PANEL CONSTRUCTION ................................................................................ 39
5.1. Communication Port.......................................................................................................... 40
5.2. NTC Connector ................................................................................................................. 42
5.3. Current Input Connector .................................................................................................... 42
5.4. Voltage Input Connector .................................................................................................... 43
5.5. SCADA Connector (Option) ............................................................................................ 43
5.6. Monitor Connector ............................................................................................................ 44
5.7. Status Inputs Connector..................................................................................................... 44
5.8. Trip/Close Connector ........................................................................................................ 45
5.9. Outputs Connector............................................................................................................. 45
5.10. Power Input / Battery Input Connector ........................................................................... 46
5.11. Power Output Connector ................................................................................................. 46
5.12. DC Inputs Connector (Option) ........................................................................................ 46
5.13. External I/O Unit ETIO10 (Option) ................................................................................ 47
ENHANCED TECHNOLOGY ii
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY iv
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY v
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY vi
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
1. INTRODUCTION
1.1. Description
ETR300-R with microprocessor-based digital control technology is designed to provide protective
coordination and fault clearance of distribution systems for continuous best quality of electric
service.
Remote monitoring and control can be provided by RTU(Remote Terminal Unit - Option) which
fundamentally installed.
ETR300-R provides protection, control, and monitoring functions with both local and remote. It
also displays the present trip/alarm conditions, and measured system parameters.
Recording of past trip, alarm or control events, maximum demand levels, and energy metering is
also performed.
Users can operate Close and Trip, and also control ETR300-R with key buttons on the user
interface panel; Protection Enabled, Ground Enabled, SEF Enabled, Reclose Enabled, Control
Locked, Remote enabled, GROUP settings, Loop control Enabled, Loop control auto restore, Hot
line tag and so on.
Users can manage the Recloser interface software using a portable PC for modification of settings,
acquisition of event data, and management of operation history.
To provide fully protective coordination for the continuous best quality of electric distribution,
ETR300-R contains many T-C characteristic curves developed by IEEE C37.112, IEC255-3,
McGraw Edison, and KEPCO and so on. Users can select any time of current curve simply by
programming and modifying.
ENHANCED TECHNOLOGY 1
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 2
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
MONITORING (COMMON)
Phase Difference
Synchro’ Check
Open Phase
Live Line Block
Fault Locator (applies to Recloser mode only)
Load Current Alarm
Power Factor (Lead and Lag)
Live Line
Operation Count
Conact Wear per Phase
Battery Automatic Load Test & Battery Management
Power Quality
- Interrupt
- Sag
- Swell
- Harmonics
- Current Unbalance
- Voltage Unbalance
- Under Voltage
- Over Voltage
- Under Frequency
Transdurer(TD) Monitor
Recloser Trip/Close Coil
Breaker Failure with Current Supervision
System Power
Recloser Gas Over/Under Pressure
ENHANCED TECHNOLOGY 3
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
EVENT RECORDER
S/W Operation Recorder - last 30,000 events
Fault Event Recorder - last 10,000 events
Fault Waveform(60 cycles× 64 samples) - last 32 events
System Event Recorder - last 30,000 events
Setting Change Event Recorder - last 30,000 events
Load&Energy Recorder
- Average Load & Energy – last 27,500 events (Max 1,145 days)
- Peak Load & Energy in every hour – last 27,500 events
- Peak Load & Energy in every day – last 27,500 events
Diagnostic Event Recorder - last 30,000 events
PQM Detection Event Recorder - last 10,000 events
Load Current Alarm Event Recorder - last 10,000 events
MAINTENANCE
Restart, Diagnostic and Operation counters
Fault Trip and Fault counters
PQM counters
Communication counters
User counters
Interrupt Time
Contact Wear per Phase
METERING
Each Phase Current and Angle : Ia, Ib, Ic, Ig, Isef
Each Phase Pick Current : Ia, Ib, Ic, Ig, Iq
Each Phase and Line to Line Voltage and Angle : Va, Vb, Vc, Vr, Vs, Vt, Vab, Vbc, Vca, Vrs,
Vst, Vtr
Current and Voltage Symmetrical Component : I1, I2, 3I0, V1, V2, 3V0
Source and Load side Frequency, Frequency Change Rate, Slip Frequency and Slip Angle
Single Phase and Three Phase Power : Active Power(kW), Rective Power(kVar), Apparent
Power(kVA), Power Factor(%)
ENHANCED TECHNOLOGY 4
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
COMMUNICATIONS
Side panel RS232-1 and RS232-2 Serial Port : DNP 3.0, Modbus, IEC60870-5-101 and Multi-
Bit Protocol, ETR300-R Interface Software
Side panel RS485 Port : DNP 3.0, Modbus, IEC60870-5-101 and Multi-Bit Protocol
Side panel Eth1 and Eth2 Ethernet Port or Fiber Optic(Option) Port : DNP 3.0, Modbus,
IEC61850, IEC60870-5-104 and Multi-Bit Protocol Protocol, ETR300-R Interface Software
Side panel PORT SPI-1,2 (Option) : I/O expendable communication(RJ-45, RS-422
communication method used)
Front Panel USB-B Type Port: ETR300-R Interface Software
USER INTERFACE
Fault Indicators
Manual Battery Load Test: Battery Voltage and Charge Voltage
Dual Functional Keypads
20×8 Character LCD Display
59 LED indicators - Fault indications, Sequence status, Battery status, etc
Setting Range Help Messages
Access Security(3 Passwords with Different Authorites)
ENHANCED TECHNOLOGY 5
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
OTHERS
Loop Control (applies to Recloser mode only)
Programmable Logic Control(PLC)
Time Synchronism Device (IRIG) – Option
Wifi – Option
GPS - Option
AUXILIARY INPUTS
12 Opto-isolated Programmable Inputs – Option
8 Opto-isolated Programmable External Inputs - Option
AUXILIARY OUTPUTS
8 Dry Contact Programmable Outputs – Option
8 Dry Contact Programmable External Outputs - Option
ENHANCED TECHNOLOGY 6
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
2. TECHNICAL SPECIFICATIONS
2.1. Inputs and Outputs
SYSTEMS
3phase-3wire or 3phase-4wire, 38㎸ maximum, 800 Amp maximum
FREQUENCY
50 / 60㎐ system and ABC/ACB phase rotation
ENHANCED TECHNOLOGY 7
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 8
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Environmental
Cold : IEC 60068-2-1 :2007
Test Ad : 16 hours at -40℃
Dry Heat : IEC 60068-2-2 :2007
Test Ad : 16 hours at +85℃
Damp heat Cyclic : IEC 60068-2-30 : 2005
Severity Level : 25℃ to 55℃, 2cycles,
Relative Humidity : 95%
Vibration : IEC 60255-21-1 : 1988
Shock and bump : IEC 60255-21-2 : 1988
ENHANCED TECHNOLOGY 9
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Safety
Dielectric Strength : IEC 60255-27 : 2013
2000 Vac on Control inputs, control outputs, and analog inputs, communication for
1minute
Impulse : IEC 60255-27 : 2013, 0.5 J, 5 kV, 1.2/50 ㎲
Insulation resistance : IEC 60255-27 : 2013, 100 ㏁ at 500 V d.c
ENHANCED TECHNOLOGY 10
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
VOLTAGE METERING
Rated voltage : AC effective value voltage 4 V
Phase A, B, C : ±0.5% of reading ( 20 ~ 200% of rated voltage), ±0.5˚
V1, V2, 3V0 : ±0.6 % of reading ( 20 ~ 200% of rated voltage), ±1˚
CURRENT METERING
Rated current(a,b,c,n) : AC 0.6 Arms
Ia, Ib, Ic, In : ±0.5mA or 0.5 % of reading(0.01~1.5 A), ±0.5˚
I1, I2, 3I0 : ±1.0 mA or 3 % of reading(0.01~1.5A ), ±1˚
Rated current(se) : AC 1.5mArms
Ise : ±0.05 mA or 0.5 % of reading(0.5~300.0 mA), ±1˚
POWER METERING
Apparent Power : ±1.2 %( Rated Voltage >80 %, Rated Current >0.03)
Active Power : ±0.7 % PF=1, ±1% PF>0.87(Rated Voltage >80%, Rated Current >0.03)
Reactive Power : ±0.7 % PF=0, ±1% PF<0.5(Rated Voltage >80%, Rated Current >0.03)
FREQUENCY METERING
Source/Load Voltage Frequency : ±0.01 Hz
Z0 Impedance
Z0 Impedance, Y0 Admitance : ±0.7 % (Rated Voltage >80%, Rated Current >0.03)
The above measurement accuracy is applied only for ETR300-R controller. The measurement
accuracy of voltage and current including recloser is about ±1 %.
ENHANCED TECHNOLOGY 11
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 12
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 13
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Inrush Restraint
Phase/Ground/SEF/Neq Seq’ Function….………..DISABLE/ ENABLE
Fault Pickup Level at Inrush Restraint Duration
Phase/Ground/Neg Seq’ Pickup Level ……….10 to 20,000A in steps of 1A
SEF Pickup Level…………………….……….0.1 to 2,000.0A in steps of 0.1A
Dropout Level…………………………………5%
Restore Minimum Time
Phase/Ground//SEF/ NEQ Function…………..DISABLE/ ENABLE
Restore Minimum Time……………………….0.01 to 600.00s in steps of 0.01s
Inrush Restraint Reset
Phase/Ground/Neg Seq’ Rest Current…….…..10 ~ 1600A in steps of 1A
SEF Rest Current…….………………………..0.1 ~ 160.0A in steps of 0.1A
Reset Time…………………………………….0.01 to 600.00s in steps of 0.01s
Phase/Ground/Neg Seq’ Curves
Curve Type…………………………………….Total 62 Curves
- ANSI/IEEE : Normally, Very, Extremely
- IEC : Normally, Very, Extremely, Long Time Inverse, Short Time Inverse
- EB : Normally, Very, Long Time Very Inverse, Extremely Inverse
- Definite Time : DEF-1s, DEF-10s
- Korean(Kepco) Curve : N1, N2, N3, N4
- User programmable curves : USER-1, USER-2, USER-3, USER-4
- McGraw-Edison : Non-Standard Curves 32
- Fuse Non-standard Curve : 3 (RI, HR, FR)
Time Dial……………………………………..0.01 to 15.00 in steps of 0.01
Time Adder……………………………………0.00 to 600.00s in steps of 0.01s
Minimum Response Time…………………….0.00 to 10.00s in steps of 0.01s
Reset Type…………………………………….INSTANTANEOUS/LINEAR
Outage Time .............................................................. 0.01 to 600.00s in steps of 0.01s
Outage Current .......................................................... OFF, 1 to 630A in steps of 1A
Make Use ‘I’……………………………………….NO/YES
Pickup Level Accuracy.............................................. 5%
Timing Accuracy ....................................................... 5% of setting time or ± 20㎳
ENHANCED TECHNOLOGY 14
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 15
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Voltage Protection
Under Voltage 1,2
Function………………………………………..DISABLE/TRIP/ALARM/TRIP&ALARM
Pickup Level …………………………………...0.10 to 1.40xVT in steps of 0.01xVT
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Minimum Normal Voltage……………………..0.10 to 1.40xVT in steps of 0.01xVT
Active Voltage Type…………………………… Any One(1P)/Any Two(2P)/All Three(3P)
Under Voltage Auto Restoration
Function……………………………………….. DISABLE/ENABLE
Pickup Level …………………………………...0.10 to 1.40xVT in steps of 0.01xVT
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Reset Time……………………………………..1 to 100 min. in steps of 1 min.
Retoration Source Side………………………...VS/VL/VS&VL
Active Voltage Type…………………………… Any One(1P)/Any Two(2P)/All Three(3P)
ENHANCED TECHNOLOGY 16
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Frequency Protection
Under Frequency 1,2
Function……………………………………….. DISABLE/ENABLE
Pickup Level …………………………………... 45.00 to 65.00 in steps of 0.01㎐
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Reset Time………………………….…………. 0.00 to 600.00s in steps of 0.01s
Minimum Normal Voltage……………………...0.00 to 1.40xVT in steps of 0.01xVT
Minimun Normal Current………………………OFF, 1 to 630A in steps of 1A
Over Frequency 1,2
Function……………………………………….. DISABLE/ENABLE
Pickup Level …………………………………... 40.00 to 65.00 in steps of 0.01㎐
ENHANCED TECHNOLOGY 17
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 18
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Power Protection
Function..................................................................... DISABLE/TRIP/ALARM/TRIP&ALARM
Fuction Bloke Time After Close ............................... 0.02 to 300.00sec in steps of 0.01 sec
Forward Power 1,2
Pickup Level ………………………………….OFF, 0.00 to 300.00MW in steps of 0.01MW
Time Delay……………………………………0.00 to 600.00sec in steps of 0.01sec
Polarizing Power………………………………3-Phase Active Power
Directional Power 1,2
Active Minimum Powr Level..………………. OFF, -300.00 to 300.00 in steps of 0.01MW
Angle………………………………………….0.00 to 359.99° in steps 0.01°
Time Delay……………………………………0.00 to 600.00sec in steps of 0.01sec
Polarizing Power………………………………3-Phase Active Power and Reactive Power
Level Accuracy.......................................................... 5%
Timing Accuracy ....................................................... Max. 50㎳ at 0㎳ trip time delay
5% of trip time or ± 20㎳
ENHANCED TECHNOLOGY 19
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Z0 Admittance Protection
Function..................................................................... DISABLE/ENABLE
Protection Type.......................................................... G&B/G/B
Detecting Direction .................................................... NONE/FORWARD/REVERSE
Minimun S.E.F Current ............................................. 0.1 to 160.0 A in steps of 0.1A
Minimum 3V0 Voltage .............................................. 0.10 to 1.40xVT in steps of 0.01xVT
Time Delay ................................................................ 0.00 to 600.00s in steps of 0.01s
Reset Time ................................................................. 0.00 to 600.00s in steps of 0.01s
Right Conductance (G) ............................................. 0.02 to 500.00 mS in steps of 0.01 mS
Left Conductance (G) ............................................... 0.02 to 500.00 mS in steps of 0.01 mS
Up Susceptance (B) .................................................. 0.02 to 500.00 mS in steps of 0.01 mS
Down Susceptance (B) ............................................. 0.02 to 500.00 mS in steps of 0.01 mS
Level Accuracy .......................................................... ± 5%
Timing Accuracy ....................................................... Max. 50㎳ at 0㎳ trip time delay
5% of trip time or ± 20㎳
ENHANCED TECHNOLOGY 20
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Lockout Priority
Lockout Priority ........................................................ PHASE/ GROUND
ENHANCED TECHNOLOGY 21
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Auto Section
Type Select ................................................................ OFF/AUTO SETCTION/TIE POINT
Auto Sectionalizer Control
Auto Sectionalizer Operate Count ...…………..1 to 5 Count in steps of 1 Count
Auto Sectionalizer Operate Time Delay…….....0.00 to 600.00sec in steps of 0.01 sec
Auto Sectionalizer Reset Time Delay……….....0.00 to 600.00sec in steps of 0.01 sec
Time Delay……………………………………..0.00 to 600.00s in steps of 0.01s
Tie Point Switch Control
Tie Point Switch Operate Count ......…………..1 to 5 Count in steps of 1 Count
Tie Point Switch Close Time Delay…..…….....0.00 to 600.00sec in steps of 0.01 sec
Tie Point Switch Open Time Delay.…..…….....0.00 to 600.00sec in steps of 0.01 sec
Tie Point Switch Reset Time Delay…...…….....0.00 to 600.00sec in steps of 0.01 sec
Dead Line Time Delay at Source Side…...….....0.00 to 600.00sec in steps of 0.01 sec
Dead Line Time Delay at Load Side..…...….....0.00 to 600.00sec in steps of 0.01 sec
Timing Accuracy ....................................................... Max. 50㎳ at 0㎳ open/close time delay
5% of setting time or ± 20㎳
ENHANCED TECHNOLOGY 22
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
2.6. Monitoring
Phase Difference
Function..................................................................... DISABLE/ENABLE
Dead Voltage Maximum Level.................................. 0.10 to 1.40xVT in steps of 0.01xVT
Live Voltage Minimum Level ................................... 0.10 to 1.40xVT in steps of 0.01xVT
Maximum Voltage Difference ................................... 0.10 to 1.40xVT in steps of 0.01xVT
Maximum Angle Difference...................................... 1° to 100° in steps of 1°
Maximum Frequency Difference .............................. 0.01 to 5.00Hz in steps of 0.01Hz
Difference Check Phase ............................................ ALL/A/B/C
Time Delay ................................................................ 0.00 to 600.00sec in steps 0.01sec
Voltage Level Accuracy ............................................ 5%
Angle Level Accuracy ............................................... ± 2°
Frequency Level Accuracy ........................................ at VT ± 0.02㎐, at CVD ± 0.05㎐
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
Syncro’ Check
Function..................................................................... DISABLE/ENABLE
Dead Voltage Maximum Level.................................. 0.10 to 1.40xVT in steps of 0.01xVT
Live Voltage Minimum Level ................................... 0.10 to 1.40xVT in steps of 0.01xVT
Maximum Voltage Difference ................................... 0.10 to 1.40xVT in steps of 0.01xVT
Maximum Angle Difference...................................... OFF, 20.0° to 80.0° in steps of 0.1°
Maximum Frequency Difference(Slip Freq.) ............ 0.5 to 5.00Hz in steps of 0.01Hz
Syncro’ Check Phase ................................................. A/B/C/AB/BC/CA
Compensation Angle ................................................. 0° to 330° in steps of 30°
Load Side Voltage Compensation Factor .................. 0.50 to 2.00 in steps of 0.01
Recloser Closing Time .............................................. 0.00 to 600.0msec in steps 0.1msec
Closing Wait Time ..................................................... 1 to 600sec in steps 1sec
Voltage Level Accuracy ............................................ 5%
Angle Level Accuracy ............................................... ± 2°
Frequency Level Accuracy ........................................ at VT ± 0.02㎐, at CVD ± 0.05㎐
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
ENHANCED TECHNOLOGY 23
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Open Phase
Function..................................................................... DISABLE/ENABLE
On Level .................................................................... 0.10 to 1.40xVT in steps of 0.01xVT
Off Level ................................................................... 0.10 to 1.40xVT in steps of 0.01xVT
Time Delay ................................................................ 0.00 to 600.00s in steps of 0.01s
Level Accuracy .......................................................... 5%
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
Fault Locator
Function..................................................................... DISABLE/ENABLE
Total Length of Feeder .............................................. 0.1 to 99.9 of 0.1km
Real impedance of the feeder positive seq. ............... 0.01 to 99.99 of 0.01ohms
Imaginary impedance of the feeder positive seq. ...... 0.01 to 99.99 of 0.01ohms
Real impedance of the feeder zero seq. ..................... 0.01 to 99.99 of 0.01ohms
Imaginary impedance of the feeder zero seq ............. 0.01 to 99.99 of 0.01ohms
ENHANCED TECHNOLOGY 24
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Live Line
Pickup Level.............................................................. 0.10 to 1.40xVT in steps of 0.01xVT
Time Delay ................................................................ 0.00 to 600.00sec in steps of 0.1sec
Dropout Level ........................................................... 95 to 98% of Pickup
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
Operation Counter
Function..................................................................... DISABLE/ENABLE
Alarm Count .............................................................. 1 to 20000 in steps of 1
Reset Count ............................................................... 0 to 10000 in steps of 1
ENHANCED TECHNOLOGY 25
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Battery Management
Function..................................................................... DISABLE/ENABLE
Charge Time .............................................................. 60 to 6,000 min. in steps of 1 min.
Discharge Time.......................................................... 60 to 6,000 min. in steps of 1 min.
Alarm Pickup Level................................................... 0.00 to 100.00% in steps of 0.01%
Reset Battery Capacity .............................................. 0.00 to 100.00% in steps of 0.01%
ENHANCED TECHNOLOGY 26
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Over Voltage
Pickup Level ………………………………….0.10 to 1.40xVT in steps of 0.01xVT
Time Delay……………………………………0.00 to 600.00sec in steps of 0.01sec
Under Frequency
Pickup Level …………………………………..OFF, 45.00 to 65.00Hz in steps of 0.01Hz
Time Delay……………………………………0.00 to 600.00sec in steps of 0.1sec
Over Frequency
Pickup Level …………………………………..OFF, 45.00 to 65.00Hz in steps of 0.01Hz
Time Delay……………………………………0.00 to 600.00sec in steps of 0.01sec
Current Unbalance/THD Detect Limit Current ......... 0 to 630A in steps of 1A
Level Accuracy.......................................................... at VT ± 0.02㎐, at CVD ± 0.05㎐
or ± 5%
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
TD Monitor
TD1 Rate ................................................................... 1 to 200 in steps of 1
TD1 Ratio .................................................................. 1 to 3000 in steps of 1
TD1 Offset................................................................. -10000 to +10000 in steps of 1
TD1-1 Type ............................................................... UNDER/OVER
TD1-1 PU ................................................................. OFF, 0.1 to 6000.0 in step of 0.1
TD1-1 Delay ............................................................. 0.00 to 600.00 in step of 0.01sec
TD1-2 Type ............................................................... UNDER/OVER
TD1-2 PU ................................................................. OFF, 0.1 to 6000.0 in step of 0.1
TD1-2 Delay ............................................................. 0.00 to 600.00 in step of 0.01sec
Level Accuracy.......................................................... ± 5%
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
Dropout Level ........................................................... 90% of Pickup when Over Type
110% of Pickup when Under Type
※. NOTE : There is 4 more channels(TD2 ~ TD4, ETD1 ~ ETD4) the same as above.
ENHANCED TECHNOLOGY 27
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
System Power
Function..................................................................... OFF/ON
+12V Pickup .............................................................. OFF, 0.1 to 10.0 V in steps of 0.1V
Time Delay ................................................................ 0.01 to 10.00 sec in steps of 0.01 sec
-12V Pickup............................................................... OFF, 0.1 to 10.0 V in steps of 0.1V
Time Delay ................................................................ 0.01 to 10.00 sec in steps of 0.01 sec
Ref. V Pickup ............................................................ OFF, 0.1 to 10.0 V in steps of 0.1V
Time Delay ................................................................ 0.01 to 10.00 sec in steps of 0.01 sec
Level Accuracy .......................................................... ± 5%
Timing Accuracy ....................................................... ± 5% of setting time or ± 20msec
ENHANCED TECHNOLOGY 28
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 29
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
2.8. Recorder
OPERATION EVENT RECORDER
Trigger Source
Recloser Closed(Manual/Remote/Auto/External/Panel Control CLOSE)
Recloser Opened(Manual/Remote/Auto/External/Panel Control OPEN)
Storage Capacity : Total 30,000 Events
ENHANCED TECHNOLOGY 30
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 31
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 32
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 33
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
COUNTER
System Restart Counter : 0 to 1,000,000 or 0 to 65,534
Diagnostic Counter : 0 to 1,000,000 or 0 to 65,534
Operation Counter : 0 to 1,000,000 or 0 to 65,534
Fault Counters : 0 to 1,000,000 or 0 to 65,534
PQM Counters : 0 to 1,000,000 or 0 to 65,534
Communication Counter : 0 to 1,000,000 or 0 to 65,534
User Counter : 0 to 1,000,000 or 0 to 65,534
NOTE: Depending on the “16bit Count Use” setting in the menu “GLOBAL SETTING /
GENERAL / DEVICE / OTHERS”, the roll-over limit of each counter is applied
differently.
When the setting is OFF, each counter is rolled over to 0 if the counter value
exceeds 1,000,000
When the setting is ON, each counter is rolled over to 0 if the counter value
exceeds 65,534
INTERRUPT TIME
Total, Phase A, B and C Interrupt Time : 0 to 1,000,000 sec or 0 to 65,534 sec
Momentary Interrupt Time : 0 to 1,000,000 sec or 0 to 65,534 sec
Temporary Interrupt Time : 0 to 1,000,000 sec or 0 to 65,534 sec
Sustained Interrupt Time : 0 to 1,000,000 sec or 0 to 65,534 sec
NOTE: Depending on the “16bit Count Use” setting in the menu “GLOBAL SETTING /
GENERAL / DEVICE / OTHERS”, the roll-over limit of each interrupt time is
applied differently.
When the setting is OFF, each interrupt time is rolled over to 0 sec if the
interrupt time exceeds 1,000,000 secs
When the setting is ON, each interrupt time is rolled over to 0 sec if the
interrupt time exceeds 65,534
ENHANCED TECHNOLOGY 34
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
PEAK CURRENT
Phase A, B, C, G Peak Current and Negative Sequence Peak Current
Trigger Source
Load Current Alarm Detect
ENERGY
Positive Active Power Energy – A, B, C, 3ф : 0 to 60,000 kWh or 0 to 999,999,999 kWh
Positive Rective Power Energy – A, B, C, 3ф : 0 to 60,000 kVarh or 0 to 999,999,999 kvarh
Negative Active Power Energy – A, B, C, 3ф : 0 to 60,000 kWh or 0 to 999,999,999 kWh
Negative Rective Power Energy – A, B, C, 3ф : 0 to 60,000 kVarh or 0 to 999,999,999 kvarh
NOTE: Depending on the “16bit Ener’ Use” setting in the menu “GLOBAL SETTING /
GENERAL / DEVICE / OTHERS”, the roll-over limit of each energy value is
applied differently.
When the setting is OFF, each energy value is rolled over to 0 if the energy
value exceeds 999,999,999
When the setting is ON, each energy value is rolled over to 0 if the energy value
exceeds 60,000
DEMAND
Demand Current – A, B, C, G, Negative Sequence
Demand Positive Active Power – A, B, C, 3ф
Demand Positive Reactive Power – A, B, C, 3ф
Demand Negative Active Power – A, B, C, 3ф
Demand Negative Reactive Power – A, B, C, 3ф
ENHANCED TECHNOLOGY 35
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
2.9. Communications
Table 2-2. Communications
RS232,1200-115200bps, None, Odd or Even Parity, 7 or 8 Data
bits, 1 or 2 Stop bit
Side panel RS232-1
DNP 3.0, Modbus, IEC60870-5-101 and Multi-Bit Protocol,
Interface Software
RS232,1200-115200bps, None, Odd or Even Parity, 7 or 8 Data
bits, 1 or 2 Stop bit
Side panel RS232-2
DNP 3.0, Modbus, IEC60870-5-101 and Multi-Bit Protocol,
Interface Software
RS485,1200-115200bps, None, Odd or Even Parity, 7 or 8 Data
Side panel RS485 bits, 1 or 2 Stop bit
DNP 3.0, Modbus, IEC60870-5-101 and Multi-Bit Protocol
RJ-45 or Fiber Optic(Option),10BASE-T/100BASE-T
Side panel EN1, EN2 DNP 3.0, Modbus, IEC61850, IEC60870-5-104 and Multi-Bit
Protocol, Interface Software
Side panel SPI-1, SPI-2 RJ-45, RS-422 communication method used
(* Option) I/O expendable communication port
Side panel Wifi SMA-Female Type
(* Option) Interface Software
USB- B Type
Front Panel USB
ETR300-R interface software
ENHANCED TECHNOLOGY 36
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
3. APPLICATION
ETR300-R has two control types(Recloser type(default) and Sectionalizer type). Control Type
setting is available in the menu “MAIN MENU / GLOBAL SETTING / GENERAL / DEVICE /
CONTROL TYPE”. The control type must be selected according to the installed body. The
Recloser function(fault trip) is active on Recloser type, and when the recloser body, Recloser type
must be selected. But, The Sectionalizer(fault indication) function is active on Sectionalizer type,
and when the swich body or sectionalizer body, Sectionalizer type must be selected. If the selected
control type and the body type do not match, erroneous operation or non-operating occurs.
Depending on the control type, different setting menus are applied. Applied setting menus are
shown below according to the control type.
Recloser Function
SECTIONALIZER
(SECMODE = 1)
Sectionalizer Function
*. NOTE ) The remaining functions are applied in common regardless of the Control Type.
ENHANCED TECHNOLOGY 37
RECLOSER CONTROL ETR300-R
ENT
ESC
5
3
1
6
4
2
FUN
C
B
A
SEF
27 UV
59 OV
50 IOC
51 TOC
50 IOCL
VC / VT
VB / VS
VA / VR
81 UF/OF/RF
25 SYNCHRONISM
ETR300-R
ENHANCED TECHNOLOGY
M10 9 2 1 3 2 1
RS232 1L/ACT
DBG 1SPEED
RX 2L/ACT
TX 2SPEED
FG N P
SEF IN IC IB IA VN VT VS VR VN VC VB VA 108 107 106 105 104 103 102 OUT101 112 111 110 109 108 IN107 106 105 104 103 102 IN101
CT PT OUTPUT INPUT
MONITORS INPUT TRIP/CLOSE OUTPUT POWER OUT POWER IN
IN201 202 203 204 205 206 207 208 OUT205 OUT206 OUT207
4. DIMENSIONS AND CONSTRUCTION
PW
COM
DC +
DC -
TRIP
38
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
M10 9 2 1 3 2 1
RS232 1L/ACT
DBG 1SPEED
RX 2L/ACT
TX 2SPEED
- + FG N P
NTC WIFI IRIG-B RS485 RS232-2 RS232-1 Eth2 Eth1
SEF IN IC IB IA VN VT VS VR VN VC VB VA 108 107 106 105 104 103 102 OUT101 112 111 110 109 108 IN107 106 105 104 103 102 IN101
CT PT OUTPUT INPUT
MONITOR INPUT TRIP/CLOSE OUTPUT POWER OUT POWER IN
CLOSE
DC +
DC -
COM
950
950 950
Cable standard for connector refers to “Table 5-1. Cable Standard for Connector”.
ENHANCED TECHNOLOGY 39
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
5 GND Ground
Figure 5-2.RS232
6 DSR Data Set Ready(IN)
9 N/C No Connection
2) RS485 PORT
RS485 has 3pins as in ‘Table 5-3. RS485 Pin Description’.
1 RS485+
2 RS485-
3 SG (Cable Shield) FG N P
Figure 5-3.RS485
ENHANCED TECHNOLOGY 40
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
3) ETHERNET PORT
Ethernet1 and 2 are RJ-45 that has 8pins as in ‘Table 5-4.Ehternet(TP) Pin Description’.
Ethernet port can be selected between TP and FX type. If FX type is used, LC type optical
communication will be supported.
1SPEED
2SPEED
2 Green Transmit-
Eth2 Eth1
3 White/Orange Receive+
[ Ethernet TP ]
4 Blue Unused
1L/ACT
2L/ACT
6 Orange Receive- 2SPEED
[ Ethernet FX ]
8 Brown Unused
Figure 5-4.Ethernet Port
4) SPI PORT(Option)
SPI-1 and SPI-2 are RJ-45 and are used for
communication with External I/O Unit ETIO10.
For detailed information on External Unit, refer to
“5.13. External I/O Unit ETIO10 (Option)”. SPI-2 SPI-1
Figure 5-5.SPI-1(Option)
5) IRIG-B Connector - Option
It is a IRIG-B connector for time synchronization function using Time Synchronization module.
2 1
Table 5-5. IRIG-B Pin Description
Connector Pin Description
IRIG-B 1 POSITIVE
Connector 2 NEGATIVE - +
Figure 5-6. IRIG-B
ENHANCED TECHNOLOGY 41
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
M10 9
Table 5-7. NTC Pin Description
Connector Pin Description
NTC 01 NTC Thermistor
Connector 02 (10 ㏀ B25/85K 3435) NTC
SEF IN IC IB IA
ENHANCED TECHNOLOGY 42
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
8 7 6 5 4 3 2 E01
VN VT VS VR VN VC VB VA
108 107 106 105 104 103 102 OUT101 112 111 110 109 108 IN107 106 105 104 103 102 IN101
OUTPUT INPUT
Digital output (DO) part is composed of a total of 8 relay outputs. Connector to output commands
from the control part.
Digital input (DI) part receives 12 status signals in total by using electrically insulated contacts.
Connector to as part of the receiving of status inputs from the control element.
ENHANCED TECHNOLOGY 43
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
1 Open ST’
2 Close ST’
3 Manual Unlock ST’
K01 2 3 4 5 6 7 8 9 10
Status 4 Spare
Input 5 Door ST’ Figure 5-13. Status Input Terminal
Connector 6 Close/open power good
7 Spare
8 Spare
9,10 Common
ENHANCED TECHNOLOGY 44
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
CLOSE
DC +
DC -
COM
TRIP
Table 5-12. TRIP / CLOSE Pin Description
Connector Pin Description
1 CLOSE(-)
2 TRIP(-)
TRIP/CLOSE
3 COM COSE/TRIP(+) J01 2 3 4 5
Connector
4 DC Power Input(+) Figure 5-14. TRIP/ CLOSE Terminal
5 DC Powre Input(-)
ENHANCED TECHNOLOGY 45
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Table 5-14. Power/Battery Input Pin Description BAT+ BAT- AC24+ AC24-
ENHANCED TECHNOLOGY 46
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
1) COM Port
RJ-45
ETR300-R Communication between
side panel Port A and RS422
2) DC Power Input
DC Power Voltage : 12, 24, 110Vdc
Figure 5-19. External I/O Unit ETO10
DC Power Continuous : 4W
3) Inputs Channels
Input 8 Channels
Nominal Voltages and Operating Range
250Vdc(-15%,+20%)
125Vdc(-15%,+20%)
48Vdc(-15%,+20%)
24Vdc(-15%,+20%)
12Vdc(-10%,+30%)
Operating current : < 5mA at Nominal Voltages
ENHANCED TECHNOLOGY 47
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
4) Output Channels
Output 8 Channels
300Vac / 350Vdc Varistor for differential surge protection
Operate / Release time : < 5ms at +20℃(+68℉)
Maximum operating power
I/O UNIT
PORT1 DO DI IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 TD1 TD2 TD3 TD4
POW
RUN
TX
RX
8 4 12 8 4
TEST
950
ENHANCED TECHNOLOGY 48
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ETR300-R
1 2
3 4
5 6
51 TOC
50 IOC
50 IOCL
B
ESC FUN
C
ENT SEF
27 UV
59 OV
81 UF/OF/RF
VA / VR
VB / VS
VC / VT
ENHANCED TECHNOLOGY 49
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
6.1. Construction
Panel consists of eight sections as below;
Operation Section
Local Control Section
Menu Control Section
Other Control Section
Fault Indication Section
Voltage Elements Section
Reclosing Sequence Status Section
System Diagnostic Section
Battery Status Section
User Selected LED Section
Other Status Section
CLOSE
Pressing CLOSE push-button sends a close signal to the Recloser.
ETR300-R has a feature of Manual Close Time Delay. The Close Time Delay allows a delay of
0.00 to 600.00 seconds after pressing the close push-button before closing the recloser. During the
manual close delay time, if the CLOSE push-button is pressed, it closes immediately without
waiting for the close delay time to be completed.
POSITION LED
Indicates the position of the Recloser. Position indicator is based on the Recloser 52a contacts.
ENHANCED TECHNOLOGY 50
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Protection Enabled
When the LED is illuminated, all protection elements(in case of Reclose mode) and fault indication
elements(in case of Sectionalizer mode) are enabled. The protection can be disabled by pressing the
“PROTECTION ENABLED” push button on the front panel.
NOTE : If “PROTECTION ENABLED” is ON, all protection elements and fault indcation
are operating, however, Ground fault and Sensitive Earth Fault Elements are
individually set for enable or disable on front panel by LED ON/OFF button.
ENHANCED TECHNOLOGY 51
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Ground Enabled
GROUND ENABLED LED is ON and OFF by pressing the “GROUND ENABLED” push-button.
When the “PROTECTION ENABLED” and “GROUND ENABLED” LEDs are both ON, ground
overcurrent protection element(in case of Reclose mode) and ground fault indication element(in
case of Sectionalizer mode) operate. However, even if the “GROUND ENABLED” is ON and the
“PROTECTION ENABLED” LED is OFF, ground fault elements do not operate. If the
“GROUND ENABLED” is OFF, and the “PROTECTION ENABLED” is ON, ground fault
elements do not operate.
When “GROUND ENABLED” is OFF, “SEF ENABLED” becomes OFF at the same time. Also,
when “SEF ENABLED” is ON, “GROUND ENABLED” becomes ON.
SEF Enabled
SEF Enabled LED is ON and OFF by pressing “SEF ENABLED” push-button. When the
“PROTECTION ENABLED” and “SEF ENABLED” LEDs are both ON. Sensitive earth fault
elements operate. However, even if the “SEF ENABLED” is ON and the “PROTECTION
ENABLED” LED is OFF, sensitive earth fault elements do not operate. If the “SEF ENABLED” is
OFF, and the “PROTECTION ENABLED” is ON, sensitive earth fault elements do not operate.
When “SEF ENABLED” is ON, “GROUND ENABLED” becomes ON. Also, when “GROUND
ENABLED” is OFF, “SEF ENABLED” becomes OFF at the same time.
Reclose Enabled
When the “RECLOSE ENABLED” LED is ON, the auto reclosing(79) element(in case of Reclose
mode) is enabled. The auto reclosing can be disabled by pressing the “RECLOSE ENABLED”
push-button at the front panel.
Control Locked
When the “CONTROL LOCKED” LED is on, all the functions in the operation section and Local
control section are locked. These can be unlocked by pressing the “CONTROL LOCKED” push-
button at the front panel.
NOTE : Even though Control Locked function is locked, Lamp Test and menu control section
can be normally operated.
ENHANCED TECHNOLOGY 52
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Remote Enabled
When the “REMOTE ENABLED” LED is ON, all remote control functions (e.g. SCADA system)
are enabled. This can be disabled by pressing the “REMOTE ENABLED” push-button at the front
panel. SCADA control refers to supported communications protocol such as DNP3.0, MODBUS,
IEC60870-5-101, IEC60870-5-104 and IEC61850, etc.
NOTE : When the “REMOTE ENABLED" LED is ON, depending on user’s request and
option, Push-Button controls on the front panel can be blocked except for LAMP
TEST and MENU Control Section.
Group Select
This button is used to change the setting group applied to ETR300-R.
The procedure of changing the active setting group using the "GROUP SELECT" push-button on
the front panel is as follows.
Use the "GROUP SELECT" push-button
1 2
to select the setting group you want to GROUP SELECT MODE
3 4
At this time, if you press the [ENT] button, the selected setting group will be applied. The
flashing "SET GROUP" LED will light up. ENT
If [ESC] button is pressed or if [ENT] button is not pressed for a long time, the setting group
before the "GROUP SELECT" push-button control will be returned.
NOTE : If ‘LOOP CONTROL’ function is activated, selected group is not changed to press
the [GROUP SELECT] button.
ENHANCED TECHNOLOGY 53
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Battery Test
When “BATT’ TEST” push-button is pressed, battery load test is run.
On Test, Battery is disconnected from the
1 2
[BATTERY TEST MODE]
charge circuit and connected the battery with 3 4
load resistor and check the battery. Load resistor BATTERY(V) : 24.00 5 6
CHARGER(V) : 26.00
shall be connected with AC supply. BAT STATUS : OK
CHG STATUS : OK
ENT
ENHANCED TECHNOLOGY 54
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Trip Test
By pressing this button, fault simulation is activated like 1500A of fault current flows on phase A,
B, C. Protection function is operated according on the setting.
ENHANCED TECHNOLOGY 55
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
LCD DISPLAY
8x20 Characters display
CONTROL KEYS
[▲] [▼] [◀] [▶]
Arrow keys are used for the moving between the menu window and the changing of the setting
value
[▲] (METER) : Up arrow key is used to move to the meter menu, operable in menu starting mode
[▼] (AWAKE) : Down arrow key is used for panel awake from sleep mode
[◀] (EVENT) : Left arrow key is used to move to the event menu, operable in menu starting mode
[▶] (SET) : Right arrow key is used to move to the setting menu, operable in menu starting mode
[FUN] : To move to main menu when present mode is in starting mode
[ESC] : To cancel for data input mode or return the display to the previous level
[ENT] : To select sub menu or data input
NOTE
If control panel is awaken from sleep mode using [AWAKE] key, it must be set to “KEY”
or “BOTH” in setting menu “MAIN MENU / GLOBAL SETTING / GENERAL / DEVICE
/ PANEL SLEEP / Awake Method”.
1 2
3 4
5 6
ESC FUN
ENT
ENHANCED TECHNOLOGY 56
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
[FUN] Key
Press [FUN] key to enter Main menu for displaying information or changing settings. [FUN] key is
also used to display a help message in setting change mode and to cancel the help message display.
[ESC] Key
The ESC key can be used to cancel data input mode and return to the previous menu.
[ENT] Key
ENT key is used to select a menu by using Up and Down arrow key. Enter key is also used to
accept a new setting by using Up or down arrow key.
ENHANCED TECHNOLOGY 57
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
TRIP TYPE
51 TOC : Shows Time Overcurrent Trip.
50 IOC : Shows Instantaneous Overcurrent trip
50 IOCL : Shows Instantaneous Overcurrent Lockout
trip
FAULT INDICATION
A, B, C : Indicates a phase fault has occurred on one
of the phase lines
G (GROUND) : Indicates an ground fault has
occurred
Figure 6-7. Fault Indication Section
SEF : Indicates a sensitive earth fault has occurred on
the neutral line
NOTE : Fault Indication LEDs will remain on after lighting, and will be turned off by "FI
RESET" command.
59 OV
NOTE : 27UV, 59OV and 81UF/OF/RF LEDs will remain on after lighting, and will be
turned off by Recloser closing.
ENHANCED TECHNOLOGY 58
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
AC SUPPLY : Satus of supplying the external AC Figure 6-11. Battery Status Section
power.
CHARGER : If Charger LED is On, charger is normal status.
BATTERY : If Battery LED is On, battery is normal status.
NOTE : Battery voltage and charge circuit voltage are always monitored periodically.
ENHANCED TECHNOLOGY 59
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ULED3 32 POWER The LED is ON when the power fault trip is occurred.
ULED4 49 DEMAND The LED is ON when the demand fault trip is occurred.
ENHANCED TECHNOLOGY 60
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
GROUP #
It displays the currently applied Set Group to ETR300-R.
1 2
Please refer to the explanation of “GROUP SELECT”
button in “6.1.2. Local Control Section” for procedure of 3 4
changing the set group locally.
5 6
REVER POWER
When reverse current flows, REVERSE POWER LED
becomes On. Reverse power is determined by 3-phase
power factor.
Figure 6-14. Other Status Section
CLPU ON
In the Cold Load and Inrush Restraint Duration, CLPU
ON LED becomes On.
ENHANCED TECHNOLOGY 61
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENT
RECLOSER CONTROL [MAIN MENU] >1.GLOBAL SETTING
ETR300-R
CURRENT(A) / VOLT(KV)
>4.MAINTENANCE
IA: 00000 IB: 00000
IC: 00000 IN: 00000
SEF: 00.00
VA: 00.00 VR: 00.00 >5.TIME
VB: 00.00 VS: 00.00
VC: 00.00 VT: 00.00
>6.STATUS
>7.METERING
VS STATUS [ - ]
VL STATUS [ - ]
VS LOOP OPERATE[ - ]
VL LOOP OPERATE[ - ]
AUTO RESTORE [ - ]
S-CNG[OFF] S-GR[GR1]
ENHANCED TECHNOLOGY 62
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
[MAIN MENU]
>1.LIVE LINE
>1.GLOBAL SETTING >1.GENERAL >1.SYSTEM >1.POWER LINE 2.OPERATION COUNT
2.CURRENT SENSING 3.CONTACT WEAR
3.VOLTAGE SENSING 4.BATT LOAD TEST
>2.EVENT RECORDER
5.BATT MANAGEMENT
6.POWER QUALITY
>3.MONITORING 7.TD MONITOR
8.SYSTEM POWER
>4.LOOP CONTROL
>1.PASSCODE 1 >1.LOGIC TIMER
>5.PASSCODE 2.PASSCODE 2 2.PULSE TIMER
3.PASSCODE 3 3.PULSE COUNT
4.INPUT PORTS
>6.PLC
5.OUTPUT PORTS
>1.CONTROL TYPE 6.LATCH LOGIC
>7.DEVICE 2.OPERATION TIME
3.H/W OPTION
4.GAS SENSOR
>*.SAVE SETTINGS
5.MANUAL CLOSE
6.LCD DISPLAY
7.PANEL SLEEP
8.TIME ZONE
9.OTHERS
10.FACTORY DEBUG >1.DNP3 SLAVE 1
2.DNP3 SLAVE 2
>2.COMMUNICATION >1.PROTOCOLS >1.DNP3 3.COMMON
>1.IEC60870-5-101
>2.IEC60870-5 2.IEC60870-5-104
3.COMMON
>3.MODBUS
4.IEC61850
5.SNTP
6.SNMP
7.ETIMS
>1.MULTI-BIT A
>8.MULTI-BIT 2.MULTI-BIT B
>2.PORTS >1.RS232-1
2.RS232-2
3.RS485
4.ETHERNET1 >1.CALLING STRING
5.ETHERNET2 2.CALLING NUMBER
3.INITIAL STRING
>3.DIALUP MODEM >1.RS232-1 MODEM 4.CONNECTION
>6.EVENT&ETC
>2.GROUP 2
ⓐ
>*.SAVE SETTINGS
>3.GROUP 3
>2.GROUP SETTING
>1.OPERATION >4.GROUP 4
2.FAULT
3.FAULT CYCLE >5.GROUP 5
>1.OPERATION
>3.EVENT 4.SYSTEM
2.FAULT
5.SET CHANGE
3.FAULT CYCLE >6.GROUP 6
6.LOAD&ENERGY/MIN
4.SYSTEM
7.LOAD&ENERGY/HOUR
5.SET CHANGE
8.LOAD&ENERGY/DAY
6.LOAD & ENERGY
9.DIGNOSTIC
7.DIGNOSTIC
10.PQM
8.PQM
11.LOAD CURR' ALARM
9.PQM CYCLE
10.LOAD CURR' ALARM
>12.CLEAR SAVED DATA
11.ABOVE ALL
*. NOTE ) Menu Structure Tree may be different according to the version and option of ETR300-R.
ENHANCED TECHNOLOGY 63
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
>1.PHASE/NEG SEQ'
>3.INTERVALS
2.GROUND
3.SEF
>1.(+)PHASE FAST 4.OTHERS
>2.TIME OC-PHA 2.(+)PAHSE DELAY
3.(-)PHASE FAST
4.(-)PAHSE DELAY >1.(+)GROUND FAST
>3.TIME OC-GND 2.(+)GROUND DELAY
3.(-)GROUND FAST
>1.(+)NEG SEQ FAST
4.(-)GROUND DELAY
2.(+)NEG SEQ DELAY
>4.TIME OC-NEQ
3.(-)NEG SEQ FAST
4.(-)NEG SEQ DELAY
>5.INST OC-PHA >1.(+)INST OC-PHA
2.(-)INST OC-PHA
>1.(+)INST OC-GND
>6.INST OC-GND
2.(-)INST OC-GND
>1.(+)INST OC-SEF
>7.INST OC-SEF 2.(-)INST OC-SEF
>1.(+)INST OC-NEQ
>8.INST OC-NEQ 2.(-)INST OC-NEQ
>1.(+)INST OCL-PHA
>9.INST OCL-PHA
2.(-)INST OCL-PHA
>1.(+)INST OCL-GND
>10.INST OCL-GND
2.(-)INST OCL-GND
>1.(+)INST OCL-NEQ
>11.INST OCL-NEQ 2.(-)INST OCL-NEQ
>18.POWER >1.FUNCTION
2.FORWARD POWER
>19.DEMAND 3.DIRECTION POWER
>1.PHASE
2.GROUND
>20.Z0 ADMITTANCE 3.NEG SEQ'
4.ACTIVE POWER
5.REACTIVE POWER
>21.HOTLINE TAG
>1.USER CURVE 1
2.USER CURVE 2
>22.USER CURVE 3.USER CURVE 3
4.USER CURVE 4
>23.OTHERS >1.PICKUP CURRENT
>1.PHASE DIFFERENCE
2.INRUSH DURATION T
>2.SECTIONALIZER 2.SYNCHRO' CHEC
4.AUTO SECTION
3.OPEN PHASE
4.LIVE LINE BLOCK
>3.MONITORING
5.FAULT LOCATOR
6.LOAD CURR' ALARM
>*.SAVE SETTINGS 7.POWER FACTOR
*. NOTE ) Menu Structure Tree may be different according to the version and option of ETR300-R.
ENHANCED TECHNOLOGY 64
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
EVENT RECORDER
Set items related to the format of event beind recoded and whether event is recorded.
MONITORING
Set items related to monitoring for power system and ETR300-R.
Consists of LIVE LINE, OPERATION COUNT, CONTACT WEAR, BATTERY LOAD TEST,
BATTERY MANAGEMENT, POWER QUALITY, TD MONITOR and SYSTEM POWER.
LOOP CONTROL
Set items related to loop control elements. This menu is only applied when “RECLOSER” type is
set in “MAIN MENU / GLOBAL SETTING / GENERAL / DEVICE / CONTROL TYPE” menu.
PASSCODE
Set items related to passcode security.
Consists of PASSCODE1, PASSCODE2 and PASSCODE 3.
PASSCODE 1 is applied when changing General Global settings and Group Settings, and
PASSCODE 2 is applied when communication setting is changed. PASSCODE 3 is applied when
clearing or resetting registered data such as event logs, counter logs, energy data, etc.
PLC
Set items related to PLC (Programmable Logic Control) elements.
Consists of LOGIC TIMER, PULSE TIMER, PULSE COUNT, INPUT PORTS, OUTPUT PORTS
and LATCH LOGIC.
DEVICE
Set items related to Controller ETR300-R.
Consists of CONTROL TYPE, OPERATION TIME, H/W OPTION, GAS SENSOR, MANUAL
CLOSE, LCD DISPLAY, PANEL SLEEP, TIME ZONE and OTHERS.
ENHANCED TECHNOLOGY 65
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
COMMUNICATION
Set items related to communication elements.
Consists of PROTOCOLS, PORTS, DIALUP MODEM, FTP-SSL, WIFI and EVENT&ETC.
SAVE SETTING
Save all changed values in the menu.
[GROUP SETTING] 1 2
>1.GROUP 1 3 4
2.GROUP 2 5 6
3.GROUP 3
4.GROUP 4
5.GROUT 5
6.GROUT 6
ESC FUN
The [GROUP SELECT] button is used to select a set group applied to present ETR300-R. Please
refer to the explanation of “GROUP SELECT” button in “6.1.2. Local Control Section” for
ENT
procedure of changing the set group locally.
NOTE : If ‘LOOP CONTROL’ function is activated, selected group is not changed to press
the [GROUP SELEC] button.
All set groups have the same submenus. Each set group is classified into RECLOSER,
SECTIONALIZER and MONITORING sub menus.
When set to "RECLOSER" type in “MAIN MENU / GLOBAL SETTING / GENERAL / DEVICE
/ CONTROL TYPE”, only "RECLOSER" and "MONITORING" menus are operated
("SECTIONALIZER" menu is not operated).
When set to "SECTIONALIZER" type, only "SECTIONALIZER" and "MONITORING" menus
are operated ("RECLOSER" menu is not operated).
ENHANCED TECHNOLOGY 66
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
6.2.4. Event
ERT300-R event information is shown in this menu.
Consists of OPERATION, FAULT, FAULT CYCLE, SYSTEM, SET CHANGE,
LOAD&ENERGY/MIN, LOAD&ENERGY/HOUR, LOAD&ENERGY/DAY, DIAGNOSTIC,
PQM, LOAD CURRENT ALARM and CLEAR SAVED DATA.
6.2.5. Maintenance
Shows about Event Maintenance items.
COUNT : Shows counters related with system restart and diagnostic.
INTERRUPT TIME : Cumulated time of Interruption occurred is displayed.
CONTACT WEAR : Shows damaged status of Interrupter.
DATA RESET : Maintenance related data is Reset.
CONTROLLER INFO : Present ETR300-R information is displayed.
IP INFORMATION : Shows H/W address and IP for ETH1&2
MECHANISM SCALE : Correction scale factor for main body sensor is displayd.
For more detail information, please refer to “10. MAINTENANCE” .
6.2.6. Time
Present time can be set and checked.
If “GLOBAL SETTING / GENERAL / DEVICE / TIME ZONE / Time Syn’ Type” is “GMT”
and “GLOBAL SETTING / GENERAL / DEVICE / H/W OPTION / IRIG Use” is “ON”, do not
set current time manually.
6.2.7. Status
Present status of recloser, fault, dignostic and Input/Output are displayed.
6.2.8. Metering
Shows metering values. For more details, refer to (see “13. METERING”)
ENHANCED TECHNOLOGY 67
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
NOTE :
If “ALARM” and “ERROR” in the self check, ETR300-R is in abnormal
ENHANCED TECHNOLOGY 68
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
GPS/IRIG MODULE
Initial Screen 4
This screen displays IRIG/GPS related with time synchronization.
STATUS[ NOT INSTALL]
G01/01/2017 00:00:00
L01/01/2017 00:00:00
<-: -D -M -S> STATUS: This screen displays time synchronization information.
<-: -D -M -S>
LINK SUCCESS: Time synchronization device is well installed.
GPS/IRIG MODULE LINK FAIL: The connection of time synchronization is not normal.
STATUS[ NOT INSTALL] NOT INSTALL: Time synchronization device is not installed.
G01/01/2017 00:00:00
L01/01/2017 00:00:00
< ⓐ > G: This screen displays UTC (Universal Time Coordinated) time.
< ⓑ >
L: This screen displays Local Time.
ENHANCED TECHNOLOGY 69
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
CYCLE RESET: When fault is clear during 79 Cycle, it is under auto reset
status.
RUNNING: After clearing fault current, reset timer is running to make
auto reset.
AT RESET CL: After fault caused by Volage and frequency auto restation
function, AT RESET CL indicates status for auto closing.
RUNNING: After fault, when line returns to normal status, restartion timer
is running to make auto closing.
ENHANCED TECHNOLOGY 70
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
S-CNG : When loop control is operating, it can display the possibility of auto
set group change. It is only available when MID and TIE status.
ENHANCED TECHNOLOGY 71
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 72
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
MAIN MENU
[10~1600:1A]
Primary and secondary current is related CT ratio.
(Primary current) = (Secondary current) × (CT ratio)
As above example screen, to move to Phase, use [▲] [▼] key and press [ENT] key to move into
value column.
Use [▲] [▼] keys and [◀] [▶] keys to change a new value.
Press [ENT] key, then you see the changed Phase value.
NOTE : You must save all changed values at ”Setting Save” menu.
ENHANCED TECHNOLOGY 73
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
* NOTHING CHANGED *
screen ④ is displayed.
SETTING CHANGED
PRESS <ENT> NOTE :
TO SAVE (UP/DOWN)
Changed set value is applied if the changed set value is saved.
If changed set value saving is cancelled, previous value is
remained.
ENHANCED TECHNOLOGY 74
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
7. GLOBAL SETTING
Place the cursor in “GLOBAL SETTING”, press [ENT] button, it is moved to GLOBAL
SETTING. This menu consists of “GENERAL” menu and “COMMUNICATION” menu.
[GLOBAL SETTING]
>1.GENERAL
2.COMMUNICATION
[GENERAL]
>1.SYSTEM
2.EVENT RECODER
3.MONITERING
4.LOOP CONTROL
5.PASSCODE
6.PLC
7.DEVICE
*.SAVE SETTING
NOTE : Changed set value must be saved to be applied. When escaping from “*.SAVE
SETTING” menu or moving to high menu, changed set value is saved by ‘Changed set value
saved message’.
ENHANCED TECHNOLOGY 75
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
7.1.1. System
Place the cursor on “SYSTEM” in GENERAL menu, press [ENT] button, it is moved to this menu.
In this menu, elements related with SYSTEM, are set and it has sub-menu as below.
[SYSTEM]
>1.POWER LINE
2.CURRENT SENSING
3.VOLTAGE SENSING
CAUTION : This setting change may influence metering and whole system, precaution is
requested.
[POWER LINE]
Range ABC, ACB
System Frequency:60
>Phase Rotation: ABC
Default ABC Step ~
Phase Combina’: abc
[ABC/ACB]
Select the phase rotation of the power system.
ENHANCED TECHNOLOGY 76
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
[POWER LINE]
Range abc, cab, bca, acb, bac, cba
System Frequency:60
Phase Rotation: ABC
Default abc Step ~
>Phase Combina’: abc
Put real phase of power system to a bushing or a terminal of a control
[Combination of ABC]
device. As example, if setting value is cab, it means that bushing A is
connected with phase C, bushing B is connected with phase A and
bushing C is connected with phase B.
NOTE: In order to get the details relevant to the connection for ETR300-R-600, refer the
following figure and table.
ENHANCED TECHNOLOGY 77
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Table 7 2. Phase selection according to the reference voltage and phase rotation
Line feeding Recommend Setting Phase Mapping Result
Bushing Terminal Phase Source Side LCD/INDEX Display : Bushing/Controller
Combination Source V(Load V) / Current Terminal
Case 1 : abc abc 1V Va(Vr)/Ia A(R)/IA
ABC Vb(Vs)/Ib B(S)/IB
Vc(Vt)/Ic C(T)/IC
Case 2 : cab cab Va(Vr)/Ia B(S)/IB
ABC Vb(Vs)/Ib C(T)/IC
Vc(Vt)/Ic A(R)/IA
Case 3 : bca bca Va(Vr)/Ia C(T)/IC
ABC Vb(Vs)/Ib A(R)/IA
Vc(Vt)/Ic B(S)/IB
Case 4 : acb acb Va(Vr)/Ia A(R)/IA
ABC Vb(Vs)/Ib C(T)/IC
Vc(Vt)/Ic B(S)/IB
Case 5 : bac bac Va(Vr)/Ia B(S)/IB
ABC Vb(Vs)/Ib A(R)/IA
Vc(Vt)/Ic C(T)/IC
Case 6 : cba cba Va(Vr)/Ia C(T)/IC
ABC Vb(Vs)/Ib B(S)/IB
Vc(Vt)/Ic A(R)/IA
Case 7 : abc abc 2V Va(Vr)/Ia R(A)/IA
RST Vb(Vs)/Ib S(B)/IB
Vc(Vt)/Ic T(C)/IC
Case 8 : cab cab Va(Vr)/Ia S(B)/IB
RST Vb(Vs)/Ib T(C)/IC
Vc(Vt)/Ic R(A)/IA
Case 9 : bca bca Va(Vr)/Ia T(C)/IC
RST Vb(Vs)/Ib R(A)/IA
Vc(Vt)/Ic S(B)/IB
Case 10 : acb acb Va(Vr)/Ia R(A)/IA
RST Vb(Vs)/Ib T(C)/IC
Vc(Vt)/Ic S(B)/IB
Case 11 : bac bac Va(Vr)/Ia S(B)/IB
RST Vb(Vs)/Ib R(A)/IA
Vc(Vt)/Ic T(C)/IC
Case 12 : cba cba Va(Vr)/Ia T(C)/IC
RST Vb(Vs)/Ib S(B)/IB
Vc(Vt)/Ic R(A)/IA
ENHANCED TECHNOLOGY 78
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
*. NOTE ) Setting value for ‘Source Side’ is available from “GLOBAL SETTING / GENERAL /
SYSTEM / VOLTAGE SENSING” in the menu..
ENHANCED TECHNOLOGY 79
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 80
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 81
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 82
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 83
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 84
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 85
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
7.1.2. Monitoring
Place the cursor on “MONITERING” in GENERAL menu, press [ENT] button to move into this
menu.
[MONITERING]
>1.LIVE LINE
2.OPERATION COUNT
3.CONTACT WEAR
4.BATT LOAD TEST
5.BATT MANAGEMENT
6.POWER QUALITY
7.TD MONITOR
8.SYSTEM POWER
Set the live line level and this is set in multiple of previous rating.
[0.10~1.40:0.01xVT]
ENHANCED TECHNOLOGY 86
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
Alarm Count
Set_Val
_
AND DIGOPRC
Operation Count +
Set a number to alarm when Recloser operation number meets this set.
[1~20000:1]
ENHANCED TECHNOLOGY 87
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
NOTE :
1. When entering “MENU/ MAINENANCE/ DATA RESET”
menu to reset operation count, password 3 authentication is
required
2. The current operation count can be checked in the “MENU/
MAINENANCE/ COUNT/ ETR300-R” menu.
ENHANCED TECHNOLOGY 88
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 89
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
NOTE :
1. Password 3 authentication is required when entering “MENU/ MAINENANCE/ DATA
RESET” menu to reset “Phase A Contact Wear”, “Phase B Contact Wear” and “Phase C
Contact Wear”.
2. Current contact wear of each phase can be checked in “MENU/ MAINENANCE/
CONTACT WEAR” menu.
ENHANCED TECHNOLOGY 90
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
ENHANCED TECHNOLOGY 91
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
NOTE :
1. Password 3 authentication is required when entering
“MENU / MAINENANCE / DATA RESET” menu to reset
the battery capacity.
2. Current battery capacity can be checked in “MENU /
METERING / CONTROLLERL REF” menu.
ENHANCED TECHNOLOGY 92
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
[PQM]
>1.PQM FUNCTION
2.INTERRUPT
3.SAG
4.SWELL
5.HARMONICS
6.CURR UNBALANCE
7.VOLT UNBALANCE
8.UNDER VOLTAGE
9.OVER VOLTAGE
10.UNDER FREQUENCY
11.ITHD/UBI I LIMIT
The ETR300-R provides voltage and current measurement signals at a rate of 64 samples / cycle pe
r cycle, providing instantaneous voltage drop (Sag), instantaneous voltage swell, interrupt, undervo
ltage, overvoltage, And power quality monitoring functions such as voltage / current imbalance.
The power quality for power grid is classified into several categories according to the voltage
magnitude and duration according to the international standard IEEE 1159 "Recommended Practice
on Monitoring Electric Power Quality". The power quality categories are listed in “Figure 7-3.
Power Quality Category according to IEEE 1159 (Interrupt, Sag, Swell)” and “Table 7-3. Power
Quality Category according to IEEE 1159 (Interrupt, Sag, Swell)”.
When the power quality monitoring element occurs, record the PQM event, PQM waveform and
PQM counter. In addition, when the related communication point is used, the occurrence event can
be transmitted to the master station through the remote communication.
ENHANCED TECHNOLOGY 93
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
0.9 pu
0.1 pu
Interruption
30cycle 3sec
0.5cycle 1min
Figure 7-3. Power Quality categories according to IEEE 1159 (Interrupt, Sag, Swell)
Table 7-1. Power Quality categories according to IEEE 1159 (Interrupt, Sag, Swell)
Category Time Voltage Value
Short-term fluctuation
Long-term fluctuation
ENHANCED TECHNOLOGY 94
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
1) PQM Function
Place the cursor on “PQM FUNCTION” in PQM menu, press [ENT] button to move into this
menu.
GLOBAL SETTING / GENERAL / MONITORING / PQM / PQM FUNCTION / Function
[PQM FUNCTION] Range DISABLE, ENABLE
>Function: DISABLE
Default DISABLE Step ~
2) Interrupt
Place the cursor on “INTERRUPT” in PQM menu, press [ENT] button to move into this menu.
GLOBAL SETTING / GENERAL / MONITORING / PQM / INTERRUPT / Level
[INTERRUPT] Range 0(OFF), 0.10~ 0.49 xVT
>Level: OFF
>Time: 2.0 Default OFF Step 0.01 xVT
3) Sag
Place the cursor on “ SAG” in PQM menu, press [ENT] button to move into this menu.
GLOBAL SETTING / GENERAL / MONITORING / PQM / SAG / Level
[SAG] Range 0(OFF), 0.50~ 0.99 xVT
>Level: OFF
>Time: 2.0 Default OFF Step 0.01 xVT
ENHANCED TECHNOLOGY 95
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
4) Swell
Place the cursor on “SWELL” in PQM menu, press [ENT] button to move into this menu.
GLOBAL SETTING / GENERAL / MONITORING / PQM / SWELL / Level
[SWELL] Range 0(OFF), 1.01~ 1.50 xVT
>Level: OFF
>Time: 2.0 Default 0 Step 0.01 xVT
5) Harmonics
Place the cursor on “HARMONIC” in PQM menu, press [ENT] button to move into this menu.
GLOBAL SETTING / GENERAL / MONITORING / PQM / HARMONICS / VTHD Pickup
[HARMONICS] Range 0(OFF), 0.5 ~ 100.0 %
>VTHD Pickup: OFF
>VTHD Delay: 1.00 Default OFF Step 0.1%
>ITHD Pickup: OFF
>ITHD Delay: 1.00
ENHANCED TECHNOLOGY 96
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
6) Current Unbalance
Place the cursor on “CURR UNBALANCE” in PQM menu, press [ENT] button to move into this
menu.
GLOBAL SETTING / GENERAL / MONITORING / PQM / CURR UNBALANCE / Pickup
[CURR UNBALANCE] Range 0(OFF), 0.5 ~ 100.0 %
>Pickup: 30.0
>Time Delay: 4.00 Default 30.0 Step 0.1 %
Set a detect level of Current Unbalance for Power Quality.
Unbalance current is calculated by following formula.
[0(OFF),0.5~100.0%]
I2
UI rate 100
I1
ENHANCED TECHNOLOGY 97
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
7) Voltage Unbalance
Place the cursor on “VOLTAGE UNBALANCE” in PQM menu, press [ENT] button to move into
this menu.
GLOBAL SETTING / GENERAL / MONITORING / PQM / VOLT UNBALANCE / Pickup
[VOLT UNBALANCE] Range 0(OFF), 0.5 ~ 100.0 %
>Pickup: 30.0
>Time Delay: 4.00 Default 30 Step 0.1 %
Set a detect level of Voltage Unbalance for Power Quality.
Unbalance voltage is calculated by following formula.
[0(OFF),0.5~100.0%]
V2
UVrate 100
V1
ENHANCED TECHNOLOGY 98
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
8) Under Voltage
Place the cursor on “UNDER VOLTAGE” in PQM menu, press [ENT] button to move into this
menu.
GLOBAL SETTING / GENERAL / MONITORING / PQM / UNDER VOLTAGE / Pickup
[UNDER VOLTAGE] Range 0(OFF), 0.10~ 1.40 xVT
>Pickup: 0.80
>Time Delay: 4.00 Default 0.80 Step 0.01 xVT
Set pickup voltage level to detect for under voltage element of power
0(OFF),0.10~1.40xVT quality.
9) Over Voltage
Place the cursor on “OVER VOLTAGE” in PQM menu, press [ENT] button to move into this
menu.
GLOBAL SETTING / GENERAL / MONITORING / PQM / OVER VOLTAGE / Pickup
[OVER VOLTAGE] Range 0(OFF), 0.10~ 1.40 xVT
>Pickup: 1.20
>Time Delay: 4.00 Default 1.20 Step 0.01 xVT
Set pickup voltage level to detect for over voltage element of power
0(OFF),0.10~1.40xVT quality.
ENHANCED TECHNOLOGY 99
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
7.1.2.7. TD Monitor
Place the cursor on “TD MONITOR” in MONITORING menu, press [ENT] button to move into
this menu. It is to set Transducer to monitor DC Analog input.
NOTE :
This menu is applicable only when a transducer (TD) input port and an external tranducer
input port are installed.
In the case of OFF on ‘EXT. I/O Use’ and ‘TD Input use” of “MAIN MENU/ GLOBAL
SETTING/ GENERAL/ DEVICE/ H/W OPTION”, TD Monitor function of this menu does
not work.
*. NOTE ) The setting items and application for TD2 ~ 4, ETD1 ~ 4 chanels are the same as above
TD1.
The purpose of using LOOP CONTROL is to isolate a fault area and protect the normal operation
area by coordinating with C/B or Recloser when a fault occurs.
Loop control is able to provide automation system with using Sectionalizing Recloser, MID point
Recloser, TIE point Recloser.
Loop control is performed by voltage sensing of DV(Dead Line Voltage), LV(Live Line Voltage).
Sectionalizing Recloser(SEC)
When a fault is occurred from the source side of Sectionalizing Recloser and backup C/B operates,
the line becomes DV and if it continues, it is figured as a permanent fault. Hence, Sectionalizing
Recloser is opened. After Sectionalizing Recloser is opened and TIEpoint Recloser is closed, the
current flows in opposite way. Therefore, the load side of Sectionalizing Recloser can keep the live
line. When Load side of Sectionalizing Recloser has a fault, OCR Function is operated and the load
side is disconnected.
MIDpoint Recloser(MID)
When a fault is occurred in the source side of MIDpoint Recloser and backup C/B or Sectionalizing
Recloser operates, the line becomes DV status and if it continues, it is figured as a permanent fault,
then automatically the setting is changed to Alternate setting. After changed to Alternate setting,
when TIEpoint Recloser is closed, the current flows in opposite way. During TIEpoint Recloser
closed, when a fault occurs, MIDpoint Recloser trips once and lockouts. After recovering the fault,
connect C/B and when the line becomes LV, the setting is automatically changed to Primary setting
and MIDpoint Recloser is closed.
When Load side of MIDpoint Recloser gets a fault, OCR Function is operated and disconnects the
load side.
S-CNG : When loop control is operating, it can display the possibility of auto
set group change. It is only available when MID and TIE status.
7.1.3.1. Setting
Place the cursor on “LOOP CONTROL” in GENERAL menu, press [ENT] button to move into this
menu.
NOTE :
When the Loop Control function is activated, the “GROUP SELECT” command via the field
and remote control is not applied since the set group is applied by the ‘Primary’ and ‘Altrnate’
settings.
Dead Line TD Timer is a cumulate timer that counts the dead line time
when doing reclosing of the upper C / B or recloser. This timer does not
reset the accumulated count even if it becomes live line and it is reset
only by 'DL Reset TD' setting. The set time should be set to be equal to
or greater than the largest time of the sum of the reclosing times of the
upper C/B or recloser.
LOOP CONTROL
ENABLED Key
LOOP CONTROL
ENABLED LED
DL Reset TD
Live Line TD
Live Line Lv
LOOP CONTROL
AUTO RESTORE Key
LOOP CONTROL
AUTO RESTORE LED
MANUAL OPEN
LOOP CONTROL
ENABLED Key
LOOP CONTROL
ENABLED LED
DL Reset TD
Live Line TD
Live Line Lv
RBT After LC
LOOP CONTROL
ENABLED Key
LOOP CONTROL
ENABLED LED
DL Reset TD
Live Line TD
Live Line Lv
Dead Line Lv
Live Line Lv
RBT After LC
Cng Alt-Mid - X ON X ON X -
Cng Alt-Tie - X X ON X X -
LC After OP - - X ENABLE X - -
OT Both DL - X X 10.00 X X -
LOOP CONTROL
- ON ON ON ON ON -
ENABLED
LOOP CONTROL
- ON ON OFF ON ON -
AUTO RESTORE
Step1 : When Permanent Fault occurs at F1, CB1 operates reclosing sequence and then Trip
Lockouts. During CB1 operation, accumulates Dead line time and the accumulated time
becomes “Dead Line TD”. When a line is Dead Line, “Live Line TD” operates.
“Dead Line TD” is set by summing all reclosing time of back line equipment.
SEC, MID, TIE has the same setting time.
Step2 : “Live Line TD” is set, and if the line is not becoming Live line within a set time,
SEC(RC1), MID(RC2), TIE(RC3) operate.
To operate “Live Line TD” from SEC→MID→TIE in turn, MID shall have longer time
set than SEC, TIE shall have longer time set than MID. When “Live Line TD” is enable,
SEC(RC1) is opened automatically, MID(RC2) changes to alternate set group setting.
Step3 : When “Live Line TD” is finished, TIE(RC3) changes to alternate group setting
automatically, and then automatically close. F1 is isolated by Loop control operation, the
rest of region shall be alive by backward distributing line.
Step4 : After removing a Fault, close CB1, then, SEC(RC1) automatically close after Auto-
Restoration Time.
Step5 : Manually open TIE(RC3), change MID(RC2), TIE(RC3) setting to primary group setting.
Enable Loop control of TIE(RC3) to recover the line as previous normal line.
Step1 : When Permanent Fault occurs at F2, SEC(RC1) operate reclosing sequence and tirp
lockout. During SEC(RC1) operation, accumulate Dead line time, and the accumulated
Dead line time becomes “Dead Line TD”. When the line is Dead Line, “Live Line TD”
operates.
“Dead Line TD” is set by summing all reclosing time of back line equipment.
MID, TIE point recloser has the same setting time.
Step2 : “Live Line TD” is set, and if the line is not becoming Live line within a set time,
MID(RC2), TIE(RC3) operate. To operate “Live Line TD” from MID→TIE in turn, TIE
shall have longer time set than MID.
When “Live Line TD” is enable, MID(RC2) changes to alternate group setting automatically.
Step3 : When “Live Line TD” is finished, TIE(RC3) automatically close after changing to
alternate group setting.
Step4 : When closing TIE(RC3), MID(RC2) trip once and lockout because of F2 fault.
F2 is isolated by Loop control operation, the rest of region shall be alive by backward
distributing line.
Step5 : After removing a Fault, close SEC(RC1), then, MID(RC3) automatically changes to
alternate group setting after Auto Restoration Time.
Step6 : Manually open TIE(RC3) and change to primary group setting.
Enable Loop control of TIE(RC3) to recover the line as previous normal line.
Step1 : When Permanent Fault occurs at F3, MID(RC2) operate reclosing sequence and tirp
lockout. During MID(RC2) operation, accumulate Dead line time, and the accumulated
Dead line time becomes “Dead Line TD”. When the line is Dead Line, “Live Line TD”
operates.
“Dead Line TD” is set by summing all reclosing time of back line equipment.
Step2 : “Live Line TD” is set, and if the line is not becoming Live line within a set time,
TIE(RC3) operate. When “Live Line TD” is enable, TIE(RC3) changes to alternate group
setting automatically.
Step3 : When closing TIE(RC3), TIE(RC3) trip once and lockout because of F3 fault.
F3 is isolated by Loop control operation, the rest of region shall be alive by backward
distributing line.
Step4 : After removing the fault, close MID(RC3)
Step5 : Manually open TIE(RC3) and change to primary group setting.
Enable Loop control of TIE(RC3), and recover the previous the line as the previous
normal line.
Cng Alt-Mid - X X X -
Cng Alt-Tie - X ON X -
LC After OP - - ENABLE - -
OT Both DL - X 10.00 X -
LOOP CONTROL
- ON ON ON -
ENABLED
LOOP CONTROL
- ON OFF ON -
AUTO RESTORE
Step1 : When Permanent Fault occurs at F1, CB1 operates reclosing sequence and then Trip
Lockouts. During CB1 operation, accumulates Dead line time and the accumulated time
becomes “Dead Line TD”. When a line is Dead Line, “Live Line TD” operates.
“Dead Line TD” is set by summing all reclosing time of back line equipment.
SEC, TIE has the same setting time.
Step2 : “Live Line TD” is set, and if the line is not becoming Live line within a set time,
SEC(RC1), TIE(RC2) operate. To operate “Live Line TD” from SEC→TIE in turn, TIE
shall have longer time set than SEC.
When “Live Line TD” is finished, SEC(RC1) is opened automatically, TIE(RC2)
automatically changes to alternate group setting and close.
F1 is isolated by Loop control operation, the rest of region shall be alive by backward
distributing line.
Step3 : After removing the fault, close CB1, SEC(RC1) is automatically closed after Auto
Restoration Time.
Step4 : Manually open TIE(RC2) and change to primary group setting.
Enable Loop control of TIE(RC2) and recover the line as the previous normal line.
Step1 : When Permanent Fault occurs at F2, SEC(RC1) operates reclosing sequence and then Trip
Lockouts. During SEC(RC1) operation, accumulates Dead line time and the accumulated
time becomes “Dead Line TD”. When a line is Dead Line, “Live Line TD” operates.
Step2 : “Live Line TD” is set, and if the line is not becoming Live line within a set time,
TIE(RC2) automatically changes to alternate group setting and close.
When closing TIE(RC2), TIE(RC2) trip once and lockouts because of F2.
Step3 : After removing the fault, close SEC(RC1).
Step4 : Manually open TIE(RC2) and change to primary group setting.
Enable Loop control of TIE(RC2) and recover the line as the previous normal line.
7.1.4. Passcode
Place the cursor on “PASSCODE” in GENERAL menu, press [ENT] button to move into this
menu.
When entering to “PASSCODE” menu, Passcord 3 certification is necessary.
ETR300-R has 3 (three) Passcods, Passcords can be changed in this menu.
Passcode 1 is applied when changing General Global settings and Group Settings, and Passcode 2
is applied when communication setting is changed. Passcode 3 is applied when clearing or resetting
registered data such as event logs, counter logs, energy data, etc.
The setting range and the procedure for changing the three passcods are the same.
Put Passcode 1.
[0000~9999:1]
7.1.5. PLC
Place the cursor on “PLC” in GENERAL menu, press [ENT] button to move into this menu.
[PLC]
>1.LOGIC TIMER
2.PULS TIMER
3.PULS COUNT
4.INPUT PORTS
5.OUTPUT PORTS
6.LATCH LOGIG
TM□
X
A B
Y
0s/0s
Figure 7-13. Logic Timer Symbol
PTM□
A B
Y
0s
Figure 7-14. Pulse Timer Symbol
CPC□
L
A TX Q C
B R
0
Figure 7-15. Pulse Counter Symbol
1) INPUT DEBOUNCE
Place the cursor on “INPUT DEBOUNCE” in INPUT PORTS menu, press [ENT] button to move into
this menu.
IN□
X
A B
X
0s
Figure 7-16. Input Debounce Timer Symbol
*. NOTE ) ① IN102 ~ IN112 and IN201 ~ IN216 are the same as IN101 above.
② IN101 ~ IN112 are the SCADA input ports of the side panel, so the IN101 ~ IN112
settings do not apply unless the Scada I / O board is installed (‘SCADA I / O Use’
setting in “GLOBAL SETTING/ GENERAL/ DEVICE/ H/W OPTION” menu is
ON)
③ IN301 ~ IN308 are the same as IN101 above. If the ETIO10 unit is not installed, the
IN301 ~ IN308 settings will not be applied, since the IN301 ~ IN308 are external
input ports of the ETIO10 unit (‘EXT. I/O Use’ setting in the “GLOBAL SETTING/
GENERAL/ DEVICE/ H/W OPTION” menu is ON, it is applied)
OUT□
A
Y C
B R
0s
Figure 7-17. Output Pulse Timer Symbol
*. NOTE ) ① OUT102 ~ OUT108 and OUT201 ~ OUT216 are the same as OUT101 above.
② OUT101 ~ OUT108 is the scada output port of the side panel. Therefore, OUT101 ~
OUT108 settings are not applied unless the Scada I / O board is installed (‘SCADA
I/O Use’ setting in “GLOBAL SETTING/ GENERAL/ DEVICE/ H/W OPTION”
menu is ON)
③ OUT301 ~ OUT308 are the same as OUT101 above. OUT301 ~ OUT308 is the
external output port of the ETIO10 unit. If the ETIO10 unit is not installed, the
above OUT301 ~ OUT308 settings will not be applied (‘EXT. I/O Use’ setting in the
“GLOBAL SETTING/ GENERAL/ DEVICE/ H/W OPTION” menu is ON, it is
applied)
LT□
A S
Q C
B R
OS□
A B
- Buffer output.
If user wants pulse signal output at OUT101 port during Phase Time OverCurrent(Fast/Delay) fault
occurrence, set the PLC logic as the formula below.
When any one of following : Phase Time Over Current(Fast/Delay) fault occurs, Logic Timer
01(TM01) is outputted. The Pickup Time and Dropout Time of Logic Timer 01 is set in
“GLOBAL SETTING/ GENERAL/ PLC/ LOGIC TIMER” menu.
※. NOTE ) Time Over Current Element related Logic Bit designation
① 151P1T : (+) Time Over Current1(Fast) Time-out – Phase
② 151P2T : (+) Time Over Current1(Delay) Time-out - Phase
③ 251P1T : (-) Time Over Current1(Fast) Time-out – Phase
④ 251P2T : (-) Time Over Current1(Delay) Time-out - Phase
2) IOUT101 = TM01
Map the output of Logic Timer 01 into the input of Output101 Pulse Timer. When the Pulse
Timer input signal is 1, pulse signal is outputted. Output pulse time is set in “GLOBAL
SETTING/ GENERAL/ PLC/ OUTPUT PULSE TIME” menu.
3) BOUT101 = 0
The logic diagram for the logical expression example above is as “Figure 7-20. OUT101 Output
Signal Logic Diagram”.
Logic Timer
151P1T Output Pulse Timer
151P2T X TM01
251P1T OUT101
Y
251P2T R Y
0s/0s
0.1s
0
Logic Timer
151P1T
151P2T X TM01
251P1T
Y
251P2T
0s/0s
0
: : : :
: : : :
NOTE : 1. When editing PLC logic, there must not be any blank space.
2. When editing PLC logic, you can see the list of logic that can be input to the
equation by pressing the ‘F1’ key.
7.1.6. Device
Place the cursor on “DEVICE” in GENERAL menu, press [ENT] button to move into this menu.
[DEVICE]
>1.CONTROL TYPE
2.OPERATION TIME
3.H/W OPTION
4.GAS SENSOR
5.MANUAL CLOSE
6.LCD DISPLAY
7.PANEL SLEEP
8.TIME ZONE
9.OTHERS
10.FACTORY DEBUG
[0.05~100.00:0.01 s] Set fail time for decision Circuit Breaker’s opening operation fail.
[0.000~1.000:0.001s] Set fail time for decision Circuit Breaker’s closing operation fail.
[OFF/ON]]
When set to OFF, the following applies;
Input / output control of IN301 ~ IN308 and OUT301 ~ OUT308
ports is disabled and port status is always “OFF”
External TD is measured always as 0.
Monitor function doesn’t work about External TD input port.
[OFF/ON]]
When set to OFF, the following applies;
TD is measured always as 0.
Monitor function doesn’t work about TD input port.
Set whether the gas sensor of the main body is installed or not.
[NONE/INSTALL] Set to INSTALL when the main body is a gas type, and set to NONE
if it is a polymer type.
Set whether to display the fault pop-up screen when a fault occurs.
[OFF/ON] The fault pop-up screen is shown in “"Table 7-8. Fault Pop-up Screen”.
Set a time for sleep mode delay. Within this set time, if there is no key
[0(OFF),1~100:1m]
operation on interface panel, ETR300-R goes into sleep mode.
[KEY/DOOR/BOTH]
DOOR : Using door pin attached on the control door, when the
door is open, the control panel is awaken from sleep mode.
KEY : When “AWAKE” key button on the front panel is pushed, the
control panel is awaken from sleep mode.
BOTH : DOOR and KEY are all used.
Display the receive UTC time and the local time off-set direction.
[+/-]
Local time is faster than UTC time, select “+”, otherwise, select “-“.
Set the difference of “Hour” between UTC time and Local time.
[0~23:1hr]
[0~59:1min] Set the difference of “Minute” between UTC and Local time.
NOTE : Korea Local time is 9 hour faster than UTC time, set it as follows (+9:00);
Sing : +, Hour : 9, Min : 0
The default value of above settings can vary according to the option type.
NOTE :
If the setting values associated with GMT are set up incorrectly, the problems can be
happened as follows.
- If the "Time Sync Type" is set to be GMT, the time of the internal clock in ETR300-R
can be changed incorrectly at time synchronization.
- If the time type of the DNP communication event is set to be GMT, the time of event
transmitted is not correct.
NOTE :
In fact, even though time synchronization module is installed, if “IRIG Use” setting is set
with "NO" in “GLOBAL SETTING / GENERAL / DEVICE / H/W OPTION” menu, the
time synchronization module is not able to be used.
7.1.6.9. Others
Place the cursor on “OTHERS” in DEVICE menu, press [ENT] button to move in this menu.
[OFF/ON]
OFF : Use 32bit format Count Data. Each count data is rolled over
to 0 if the counter value exceeds 1,000,000.
ON : Use 16bit format Count Data. Each count data is rolled over
to 0 if the counter value exceeds 65,534.
[OFF/ON]
OFF : Use 32bit format Energy Data. Each energy data is rolled
over to 0 if the counter value exceeds 999,999,999.
ON : Use 16bit format Energy Data. Each energy data is rolled
over to 0 if the counter value exceeds 60,000.
7.2. Communication
Place the cursor on “COMMUNIATION” in GLOBAL SETTING menu, press [ENT] button to
move into this menu. Communication and its related elements are sent in this menu and it has sub-
menu as below.
[COMMUNICATION]
>1.PROTOCOLS
2.PORTS
3.DIALUP MODEM
4.FTP-SSL
5.WIFI
6.EVENT&ETC
*.SAVE SETTINGS
NOTE : Changed set value must be saved to be applied. When escaping from “*.SAVE
SETTING” menu or moving to high menu, changed set value is saved by ‘Changed set value
saved message’.
[PROTOCOLS]
>1.DNP3
2.IEC60870-5
3.MODBUS
4.IEC61850
5.SNTP
6.SNMP
7.ETIMS
8.MULTI-BIT
Setting items of “DNP3 SLAVE 1” and “DNP3 SLAVE 2” menu are same as following;
[NOTRIG/PERIOD]
NOTRG: If there is no event occurrence during setting unsolicited
time after the last event occurs, the event data is transmitted.
PERIOD: Unsolicited message is sent to a master with whole event
data occurring after setting unsolicited time starting and elapsing
when the first event occurs.
[DNP3 SLAVE1]
Range 0 ~ 255
>Master IP Oct1: 0
Master IP Oct2: 0
Default 0* Step 1
Master IP Oct3: 0
Master IP Oct4: 0
Select the IP Address for DNP3 Communication.
IP Address : 192.xxx.xxx.xxx
[0~255:1] ① ② ③ ④
Set whether DNP Secure Authenitication is used i.e, SAv2, SAv5 or not
[DISABLE/SAv2/SAv5]
[1~255:1s]
transfer the Data. If there isn’t the Confirm during this setting time
and Data retries is available, ETR300-R transfers the Data again.
[IEC60870-5-101]
Range 0(OFF), 0~255
>COT Size : 1
>IOA Size : 2
Default 5 Step 1 sec
One Ch Response: NO
Frame Repet’ TO: 30
>Select Timeout: 5
[0(OFF),0~255:1]
Enter the period after a previously received select will timeout.
2) IEC60870-5-104
Move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PROTOCOL/ IEC60870-
5/ IEC60870-5-104” to select setting for IEC60870-5-104.
[IEC870-5-104]
Range DISABLE, ENABLE
>Function: DISABLE
>Port Select: ETH1
Default DISABLE Step ~
ASDU Address: 0
Cyclic Period: 60
Timeout(t0): 120
Set whether IEC60870-5-104 protocol is used for communcation.
[DISABLE/ENABLE]
[IEC60870-5-104]
Range CP56, CP24
>MME Time-Tag: CP56
>Flt Time-Tag: CP56
Default CP56 Step ~
k(Max Tx): 12
w(Max Rx): 8
Select whether a time tag format for integrated totals.
CP56 : The time tag format is CP56Time2a.
[CP56/CP24]
CP24 : The time tag format is CP24Time2a.
[COMMON]
Range 0 ~ 65535
>CSEMB Start: 27000
>PMENA Start: 10000
Default 27000 Step 1
>PMENB Start: 12000
>PMENC Start: 14000
Set the start address of Set-point Command, Scaled Value for
[0~65535:1]
IEC60870-5-101/104 protocol.
[COMMON]
Range 0 ~ 65535
>CSEMB Start: 27000
>PMENA Start: 10000
Default 10000 Step 1
>PMENB Start: 12000
>PMENC Start: 14000
Set the start address of Set-point Parameter of Measured Values,
[0~65535:1] Normalized Value for IEC60870-5-101/104 protocol.
[COMMON]
Range 0 ~ 65535
>CSEMB Start: 27000
>PMENA Start: 10000
Default 12000 Step 1
>PMENB Start: 12000
>PMENC Start: 14000
Set the start address of Set-point Parameter of Measured Values, Scaled
[0~65535:1]
Value for IEC60870-5-101/104 protocol.
[COMMON]
Range 0 ~ 65535
>CSEMB Start: 27000
>PMENA Start: 10000
Default 14000 Step 1
>PMENB Start: 12000
>PMENC Start: 14000
Set the start address of Parameter of Measured Values, Short Floating
[0~65535:1]
Point Number for IEC60870-5-101/104 protocol.
[COMMON]
Range MODE B , MODE D
PMENA Start: 10000
PMENB Start: 12000
Default MODE B Step -
PMENC Start: 14000
>MIT Mode : MODE B
Set the start address of Parameter of Measured Values, Short Floating
[MODE B/MODE D] Point Number for IEC60870-5-101/104 protocol.
1) Communication Connection
The ETR300-R can accept Multi-Bit Protocol Communication with the maximum two ETR300-R
through two Multi-Bit Protocol(Multi-Bit A and Multi-Bit B).
Each Multi-Bit Protocol is exchanging in real time Receiving Date 8 bit and Transmitting Date 8
bit with connected ETR300-R. Each Multi-Bit Protocol can select transmitted ID(Tx ID) and the
received ID(Rx ID). Tx ID must be same to the peer Rx ID, Rx ID must be same to the peer Tx ID.
It will be detected correct communication connection through Tx ID and Rx ID.
For example, in Figure 7-22, ETR300-R #2 can communicate with ETR300-R #1 using Multi-Bit A
protocol, and can communicate with ETR300-R #3 using Multi-Bit B protocol. (ETR300-R #1 can
communicate using Multi-Bit A protocol, ETR300-R #3 uses Mult-Bit B protocol)
It means that, Mult-Bit A protocol’s Rx ID on ETR300-R #1 and Mult-Bit A protocol’s Tx ID on
ETR300-R #2 must be same, Tx ID and Rx ID have to be equal. Rx ID and Tx ID of Multi-Bit B
protocol on ETR300-R #2 have to be same to the peer things.
The Multi-Bit Protocol checks whether there is communication error by checking error such as
CRC error, ID error and reception error on received data. If a communication error is detected, the
received data is ignored. If the received data is recovered to normal, data transmission / reception
proceeds normally. When occurring CRC error, ID error and reception error, ETR300-R records the
event and supports the corresponding BI point, so that the master station can monitor the
information by remote communication.
Multi-Bit A Protocol
Reception bit name : RMBA01 ~ RMBA08
Transmission bit name : TMBA01 ~ TMBA08
Multi-Bit B Protocol
Reception bit name : RMBB01 ~ RMBB08
Transmission bit name : TMBB01 ~ TMBB08
EOPEXT = RMBA01
TMBA01 = CLST
: : : :
Tx: Tx:
R1(Main, N/C) R2(Stand by, N/O)
Rx: Rx:
SRC#1 SRC#2
Load
CB Status(Closed) 02 02 CB Status(Closed)
N/C 05 05 N/C
N/C
Opening by Dead Line AND RMBA02 is "0" 06 06 N/C
N/C 05 05 N/C
LSET03 27BLT*CLST*RMBA02
LRST03 !RMBA02+!RMBA01+!RMBA03+!RMBA08
EOPEXT 27BDT*27BD2T*CLST*RMBA04
ECLEXT 27BLT*OPST
- DIGERR : System Diagnostic Error Status - 27BD2T : Live Line Status in Dead Side
- CLST : Recloser CLOSE Status - 27BDT : Dead Line Status in Source Side
- OPST : Recloser OPEN Staus - 27BD2T : Dead Line Status in Dead Side
[PORT SETUP]
>1.RS232-1
2.RS232-2
3.RS485
4.ETHERNET1
5.ETHERNET2
[2W/4W/DIAL/NONE]
2W : 2 wire private line is used and continuously Carrier is
monitored to control data flow by DCD(Data Carrier Detect).
4W : 4 wire private line is used and RTS(Request To Send) and
CTS(clear to Send) signal are used to control data flow.
DIAL : Dial-Up1 modem is used.
NONE : Not used.
[DISABLE/ENABLE]
ENABLE : Data is transferred after confirming CTS signal is
Asserted.
DISABLE : Data is transferred regardless of CTS signal.
[DISABLE/ENABLE]
ENABLE : Data is transferred after confirming DCD signal is
Deasserted.
DISABLE : Data is transferred regardless of DCD signal
[10~30000:10ms]
before sending RTS signal in 2 wire communication type. After a set
time, if DCD signal is ON, ETR300-R does not transfer the data and
treat it as DCD Fail. It is available if ‘DCD Usage’ setting is ON.
IP Addr´1,2,3,4 is ①,②,③,④
CONNECT 9600
The modem has a "quiet mode" that disables these messages.
The AT command is ATQ1. There will be no OK printed in response to this command.
Dialing
The user should insert an order for Reset.
Wait 0.5 second
Make a phone call by using Dialing String and Dialing Number.
Checks DCD is Asserted
※. Dial connection waiting time is depending on “ Data Link Timeout” set by the user.
Hang up
DTR Line is deasserted
Wait 2 second
DTR Line is asserted
Wait 2 second
※. ETR300-R will hang up the modem after a delay of 30 seconds with no valid packet received or
transmitted.
[DIALUP MODEM]
>1.RS232-1 MODEM
2.RS232-2 MODEM
Modem settings can be made individually for the RS232-1 and RS232-2 ports. Move the cursor to
the port you want to set and press [ENT] to enter. (These ports have same settings.)
[RS232-1 Modem]
>1.CALLING STRING
2.CALLING NUMBER
3.INITIAL STRING
4.CONNECTION
1) Calling String
In order to set “Calling String”, move to “MAIN MENU/ GLOBAL SETTING/
COMMUNICATION/ DIAL MODEM/ CALLING STRING”
[! ~ z]
ATD : Default Dial Type(Already set in modem(Default Dial type)
ATDT : Tone Dial
ATDP : Pulse Dial
2) Calling Number
Move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ DIAL MODEM/
CALLING NUMBER”
3) Initial String
Move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ DIAL MODEM / INITIAL
STRING”
4) Connection
Move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ DIAL MODEM/
CONNECTION”
7.2.4. FTP-SSL
Move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ FTP-SSL to file transfer in
order to configure protocol SSL.
NOTE :
The Fault Current occurrence time of each Sequence is when it
becomes no voltage after experience the Fault Current.
[32/64/128/256]
ALL : all status is buffed for same point.
LAST : Only last event is buffed for same point.
[ALL/LAST]
ALL : all analog is buffed for same point.
LAST : Only last event is buffed for same point.
[ALL/LAST]
ALL : all analog is buffed for same point.
LAST : Only last event is buffed for same point.
[ALL/LAST]
ALL : all counter is buffed for same point.
LAST : Only last event is buffed for same point.
NOTE :
This setting is set to be GMT and the setting values associated
with UTC(in “TIME ZONE” menu) are set up incorrectly, the
time internal clock in ETR300-R can be changed incorrectly at
time synchronization.
NOTE :
This setting is set to be UTC and the setting values associated
with GMT(in “TIME ZONE” menu) are set up incorrectly, the
time of event transmitted is not correct.
8. GROUP SETTING
Place the cursor on “GROUP SETTING” in MAIN menu, press [ENT] button to move into this
menu.
[GROUP SETTING]
>1.GROUP 1
2.GROUP 2
3.GROUP 3
4.GROUP 4
5.GROUP 5
6.GROUP 6
The GROUP SETTING menu has six identical subgroup settings. The setting group which is
turned on "SET GROUP" LED is applied to the ETR300-R. The [GROUP SELECT] button is used
to select a set group applied to present ETR300-R. Please refer to the explanation of “GROUP
SELECT” button in “6.1.2. Local Control Section” for procedure of changing the set group
locally.
NOTE : If ‘LOOP CONTROL’ function is activated, selected group is not changed to press
the [GROUP SELEC] button.
[GROUP 1]
>1.RECLOSER
2.SECTIONALIZER
3.MONITORING
*.SAVE SETTING
NOTE : Changed set value must be saved to be applied. When escaping from “*.SAVE
SETTING” menu or moving to high menu, changed set value is saved by ‘Changed set value
saved message’.
All set groups have the same submenus. Each set group is classified into RECLOSER,
SECTIONALIZER and MONITORING sub menus.
When set to "RECLOSER" type in “MAIN MENU / GLOBAL SETTING / GENERAL / DEVICE
/ CONTROL TYPE”, only "RECLOSER" and "MONITORING" menus are operated
("SECTIONALIZER" menu is not operated).
When set to "SECTIONALIZER" type, only "SECTIONALIZER" and "MONITORING" menus
are operated ("RECLOSER" menu is not operated).
8.1. Recloser
Place the cursor on “RECLOSER” in GROUP# menu, press [ENT] button to move into this menu.
This menu sets the protection elements that operate when the recloser control type is set.
[RECLOSER]
>1.AUTO RECLOSING
>2.TIME OC-PHA
3.TIME OC-GND
4.TIME OC-NEQ
5.INST OC-PHA
6.INST OC-GND
7.INST OC-SEF
8.INST OC-NEQ
9.INST OCL-PHA
10.INST OCL-GND
11.INST OCL-NEQ
12.INRUSH RES’/CLPU
13.HARMONIC BLOCK
14.DIRECTION
15.BROKEN CONDUCT
16.VOLTAGE
17.FREQUENCY
18.POWER
19.DEMAND
20.Z0 ADMITANCE
21.HOTLINE TAG
22.USER CURVE
23.OTHERS
Phase fast/delay time overcurrent 51P-1,2 GROUP SETTING / ... / RECLOSER / TIME OC-PHA
Ground fast/delay time overcurrent 51G-1,2 GROUP SETTING / ... / RECLOSER / TIME OC-GND
Negative squence fast/delay time overcurrent 51Q(46)-1,2 GROUP SETTING / ... / RECLOSER / TIME OC-NEQ
Phase instantaneous overcurrent 50P-1 GROUP SETTING / ... / RECLOSER / INST OC-PHA
Ground instantaneous overcurrent 50G-1 GROUP SETTING / ... / RECLOSER / INST OC-GND
Sensitive Earth Fault protection 50SG GROUP SETTING / ... / RECLOSER / INST OC-SEF
Negative sequence instantaneous overcurrent 50Q(46)-1 GROUP SETTING / ... / RECLOSER / INST OC -NEQ
Phase instantaneous lockout overcurrent 50P-2 GROUP SETTING / ... / RECLOSER / INSTL OC-PHA
Ground instantaneous lockout overcurrent 50G-2 GROUP SETTING / ... / RECLOSER / INSTL OC-GND
Negative sequence instantaneous lockout overcurrent 50Q(46)-2 GROUP SETTING / ... / RECLOSER / INSTL OC -NEQ
Ground directional time control 67G GROUP SETTING / ... / RECLOSER / DIRECTION / GROUND
Sensitive Earth Fault directional time control 67SG GROUP SETTING / ... / RECLOSER / DIRECTION / SEF
Negative sequence directional time control 67Q GROUP SETTING / ... / RECLOSER / DIRECTION / NEG SEQ
Under voltage 1/2 27-1,2 GROUP SETTING / ... / RECLOSER / VOLTAGE / UNDER VOLT1,2
GROUP SETTING / ... / RECLOSER / VOLTAGE / UV
Under voltage restoration 27R
RESTROATION
Over voltage 1/2 59-1,2 GROUP SETTING / ... / RECLOSER / VOLTAGE / OVER VOL1,2
GROUP SETTING / ... / RECLOSER / VOLTAGE / NEUTRAL
Neutral over voltage 1/2 64N-1,2
OVERVOLT1,2
GROUP SETTING / ... / RECLOSER / VOLTAGE / OV
Over voltage restoration 59R
RESTROATION
GROUP SETTING / ... / RECLOSER / VOLTAGE / NEQ OVER
Negative sequence over voltage 1/2 47-1,2
VOLT1,2
GROUP SETTING / ... / RECLOSER / FREQUENCY/ UNDER
Under frequency 1/2 81U-1,2
FREQUENCY 1, 2
GROUP SETTING / ... / RECLOSER / FREQUENCY/ OVER
Over frequency1/2 81O-1,2
FREQUENCY 1,2
GROUP SETTING / ... / RECLOSER / FREQUENCY/
Frequency decay 81D
FREQUENCY DECAY
GROUP SETTING / ... / RECLOSER / FREQUENCY/
Frequency restoration 81R
FREQUENCY RESTROATION
Forward power 32FP GROUP SETTING / ... / RECLOSER / POWER / FORWARD POWER
Direction power 32P GROUP SETTING / ... / RECLOSER / POWER / DIRECTION POWER
Phase demand current 49P GROUP SETTING / ... / RECLOSER / DEMAND / PHASE
Ground demand current 49G GROUP SETTING / ... / RECLOSER / DEMAND / GROUND
Negative sequence demand current 49Q GROUP SETTING / ... / RECLOSER / DEMAND / NEG SEQ’
Active demand power 49W GROUP SETTING / ... / RECLOSER / DEMAND / ACTIVE POWER
Reactive demand power 49V GROUP SETTING / ... / RECLOSER / DEMAND / REACTIVE POWER
51Q 50Q
OPTION 46BC 49Q
1,2 1,2
Isef
50SG
ZCT
3I0
21YN
In 51G 50G
49G
1,2 1,2
67SG
In
47 64N
1,2 1,2
CLPU
52 27R 59R 81R 79
1,2
3VD
All overcurrent protection function consist of dual-elements ((+) and (-)) of individual operations.
It can be operated in several ways depending on the configuration of the line system and the user's
request. Several application example of dual overcurrent protection elements are as follows;
By using directional elements and dual overccurent protection elements ((+) and (-)), it is possible
to protect simultaneously both sides of the source line on ring line system operation. After setting
the directional type as forward, when using the dual-elements (function is set to ENABLE), The (+)
element does fault protection about the forward direction and the (-) element does the fault
protection about the reverse direction.
The (+) element operates as the setting type of the directional element, and the (-) element operates
as the opposite direction to the setting type of the directional element. If the type of the directional
element is set as NONE, the (+) and (-) elements operate simultaneously regardless of the direction
of the fault.
Forward powerflow
S1 S2
ETR300-R
Reverse powerflow
When working in a radial line system, the directional element does not work and only one of the
(+) or (-) elements is used. ((+) element is recommended)
Powerflow
ETR300-R Load
Source Side
In the case of time overcurrent function, each element can be used for trip or alarm purposes. Thus,
one of the dual overcurrent protection elements can be operated as the trip element and another one
is operated as the alarm element.
When it is a temporay fault due to contact of external object, lightning, or loss of insulation, the
system will automatically reclose after high speed interruption, resulting in minimization of failure
range and power outage period.
Auto Reclosing function is applied when fault current is larger than the fault pickup current, the
system will repeat trip and reclosing according to the sequence. Then, it will be LOCKOUT or
return to the normal sequence status after AUTO Reset TIME.
1) LOCKOUT
In the situations stated below, the Lockout occurs. In the Lockout state, the system doesn’t reclose
automatically, so the user should close Recloser(or CB) manually at the site or remotely.
• In case when the failure occurs continuously and the recloser(or CB) has repeated trip for the
number of times set previously. (Permanent failure)
• When the user opens the recloser(or CB) manually
• In case of trip due to Instantaneous lockout overcurrent element
• In case of trip when fault current is larger than pickup current of Inrush Restraint function
during Inrush Restraint
• In case of trip due to the current larger than CLPU pickup current for the period of CLPU
operation
• In case of trip due to protection elements (Voltage(27,59), Frequency(81) and Demand, etc.)
excluding OverCurrent Trip.
• In case of trip due to the Hot Line Tag function
• In case of Overcurrent Trip while Auto Reclosing function is disabled (‘RECLOSE ENABLE’
Lamp OFF)
This “Figure 8-5. Lockout Sequence Operation” shows the typical protection sequence of lockout
after 4 times of OCR trips when the total operation time is set as 4.
AMP
*LOCKOUT*
PICKUP
CURRENT
NORMAL
CURRENT
TIME
Reset Cycle Lockout
(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC (6) 3rd Reclose Interval Time
(7) 4th Trip - 4th TCC
After Recloser(or CB) is closed manually at site or remote controller from the status of Lockout,
and it passes Lockout Reset Time. Lockout status will convert into reset, then normal reclosing
fucntiond will be activated.
2) RESET
RESET means the system has returned to normal state. The reset occurs in the following
situations.
Lockout Reset : In case when Recloser(or CB) is closed manually at the site or remotely and
the Lockout Reset Time has passed.
Cycle Reset : While it is in sequence, the over current is removed before lockout as well as
the Auto Reset Time has passed.
The “Figure 8-6. Reset Sequence Operation” shows the sequence where the system return to
normal status because the overcurrent is removed after 2 times of reclosing operations when the
total operation time is set as 4.
AMP
PICKUP
CURRENT
NORMAL
CURRENT
TIME
Reset Cycle Reset
(1) 1st Trip - 1st TCC (2) 1st Reclose Interval Time
(3) 2nd Trip - 2nd TCC (4) 2nd Reclose Interval Time
(5) 3rd Trip - 3rd TCC (6) 3rd Reclose Interval Time
If fault occurs during the Auto Reset Time, only remaining reclosing operations will be performed
and then, the system will lockout.
3) CYCLE
It indicates the current sequence status. It occurs when OCR fault trips only except Instantaneous
lockout overcurrent elements, and maintain as cycle until operation time reach to the setting.
During Cycle, Later certain period after fault trip, it automatically operates reclosing function.
(But, Cycle occurs only when Auto Reclosing is enabled(‘RECLOSE ENABLE’ LED ON)
[AUTO RECLOSING]
>1.FUNCTION
2.OPERATIONS
3.INTERVALS
Each of the setting items under AUTO RECLOSING menu are described below.
Function Setup
GROUP # / RECLOSER / AUTO RECLOSING / Reclose Fun
[FUNCTION] Range ENABLE, DISABLE
>Reclose Fun: ENABLE
Default ENABLE Step -
Operations Setup
Set the operation of phase fault, ground fault, SEF fault and negative sequence fault. The operation
settings are applied individually according to the fault type. OPERATION menu is classified as
below;
[OPERATIONS]
>1.PHASE
2.GROUND
3.SEF
4.NEG SEQ’
Auto reclosing function of ETR300-R supports maximum of 5 reclosing shots. It is possible to set
the curve (FAST or DELAY) to be applied for each shot. This feature allows to implement the
‘Save Fuse’ scheme by using the combination of 2 Fast and 2 Delay curves (total 4 shots trip
lockout i.e. first and second shot should be fast trip time curves and third and fourth shots should
be delayed trip time curves).
Each of the setting items under the OPERATIONS menu are described below.
The ground operation settings process is the same as the phase operation.
The negative sequence operation settings process is the same as the phase operation.
Intervals Setup
Set the reclosing time of phase fault, ground fault, SEF fault and negative sequence fault. The
reclosing time is applied individually according to the fault type. INTERVALS menu is classified
as below;
[INTERVALS]
>1.PHASE/NEG SEQ’
2.GROUND
3.SEF
4.OTHER
Each of the setting items under the INTERVALs menu are described below.
Set the reclosing interval time of phase fault and negative sequence fault at the same time.
However the interval time is applied according to phase fault and negative sequence fault,
respectively.
Multiple time curves and time dials are available for the phase time overcurrent element to
respectively coordinate with other protection elements in the ETR300-R and other external devices
on the distribution system. US, ANSI/IEEE, IEC, ESB, USER and non-standard time current
curves are included in the ETR300-R.
A User Programmable curve option is also available for user to allow creating custom’s time
current curves for more enhanced coordination than the standard curve types.
The Reset type can be either instantaneous or linear. The phase time delay reset mode applies to the
US, ANSI/IEEE, IEC, ESB, USER curves. The instantaneous mode is used to coordinate with other
instantaneous reset devices such as a recloser or other protective equipment on the distribution
system. In the instantaneous mode, the time overcurrent element will reset instantaneously when
the measured current level drops below the pickup setting for one cycle. Linear reset mode, the
recloser is used for the cooperation with the protection device necessary for delay time as
mechanical relay reset.
Phase time overcurrent does not work during inrush restraint in order to prevent malfunction of
inrush current generated when relcloser or nearby power distribution device is closed.
[Time OC-PHA]
>1.(+)PHASE FAST
2.(+)PHASE DELAY
3.(-)PHASE FAST
4.(-)PHASE DELAY
(+) PHASE FAST setting menu is available for setting (+) PHASE FAST Curve.
Curve A(101) B(117) C(133) D(116) E(132) IEC-EI K(162) L(107) M(118) N(104)
Setting 11 12 13 14 15 16 17 18 19 20
Curve IEC-NI P(115) R(105) T(161) V(137) IEC-VI W(138) Y(120) Z(134) 1(102)
Setting 21 22 23 24 25 26 27 28 29 30
Curve 2(135) 3(140) 4(106) 5(114) 6(136) 7(152) 8(113) 8*(111) 9(131) 11(141)
Setting 31 32 33 34 35 36 37 38 39 40
Setting 41 42 43 44 45 46 47 48 49 50
Curve US-VI US-EI ES-NI ES-VI USER-1 USER-2 USER-3 USER-4 DEF-1S DEF-10S
Setting 51 52 53 54 55 56 57 58 59 60
Curve IEEE-NI IEEE-VI IEEE-EI US-STI US-STVI IEC-LTI IEC-STI ES-LTVI ES-EI RI
Setting 61 62
Curve HR FR
GROUP # / RECLOSER / TIME OC-PHA / PHASE FAST / Low Set Definite Time
[(+)PHASE FAST] Range 0(OFF), 0.01 ~ 600.00 sec
Curve: [US-VI]
Time Add.: 0.00 Default 0(OFF), Step 0.01 sec
M.R.T: 0.00
Reset Method: INST Low set definite time is used to restrict a trip time to be a definite time
>Low Set DT: OFF
adjacent to a pickup current by T-C curve. When the trip time is greater
[0(OFF),0.01~600.00]
than the low set definite time, low set definite time is applied for
operation.
‘(+) PHASE DELAY’ settings settings are very similar ‘(+) PHASE FAST’ time overcurrent
setting.
‘(-) PHASE FAST’ settings are very similar to ‘(+) PHASE FAST’ time overcurrent setting.
‘(-) PHASE DELAY’ settings are very similar to ‘(+) PHASE FAST’ time overcurrent setting.
Ground time overcurrent does not work during inrush restraint in order to prevent malfunction of
inrush current generated when relcloser or distribution device is closed.
[Time OC-GND]
>1.(+)GROUND FAST
2.(+)GROUND DELAY
3.(-)GROUND FAST
4.(-)GROUND DELAY
(+) GROUND FAST setting menu is available for setting (+) GROUND FAST Curve.
‘(+) GROUND DELAY’ settings settings are very similar ‘(+) GROUND FAST’ time overcurrent
setting.
‘(-) GROUND FAST’ settings are very similar to ‘(+) GROUND FAST’ time overcurrent setting.
‘(-) GROUND DELAY’ settings are very similar to ‘(+) GROUND FAST’ time overcurrent setting.
Negative sequence time overcurrent does not work during inrush restraint in order to prevent
malfunction of inrush current generated when relcloser or nearby distribution device is closed.
[Time OC-NEQ]
>1.(+)NEG SEQ’ FAST
2.(+)NEG SEQ’ DELAY
3.(-)NEG SEQ’ FAST
4.(-)NEG SEQ’ DELAY
(+) NEG SEQ’ FAST setting menu is available for setting (+)NEG SEQ’ FAST Curve.
‘(+) NEG SEQ’ DELAY’ settings settings are very similar ‘(+) NEG SEQ’ FAST’ time overcurrent
setting.
‘(-) NEG SEQ’ FAST’ settings are very similar to ‘(+) NEG SEQ’ FAST’ time overcurrent setting.
‘(-) NEG SEQ’ DELAY’ settings are very similar to ‘(+) NEG SEQ’ FAST’ time overcurrent
setting.
[INST OC - PHA]
>1.(+)INST OC-PHA
2.(-)INST OC-PHA
[1~5:1shot]
If Active Shot = 1, then (+)INST OC -PHASE element is enabled for
the first trip operation and next trip operations.
(-) INST OC-PHA settings are very similar with (+) INST OC-PHA settings.
[INST OC - GND]
>1.(+)INST OC-GND
2.(-)INST OC-GND
[1~5:1shot]
If Active Shot = 1, then ground instantaneous overccurent element is
enabled for the first trip operation and every following trip operation.
(-) INST OC-GND settings are very similar to the (+) INST OC-GND settings.
For user systems, a directional SEF is available. The directional control is polarized by a zero
sequence voltage(V0). The CVD or PTs should be connected Wye-grounded.
A sensitive earth fault element does not work during the inrush restraint to prevent malfunction of
the inrush current that occurs when the relcloser or nearby distribution device is closed.
[INST OC - SEF]
>1.(+)INST OC-SEF
2.(-)INST OC-SEF
Set Time Delay for sensitive earth fault trip. If it is set for 0, trips
[0.00~600.00:0.01s] immediately sensitive earth fault current without delay.
(-) INST OC- SEF settings are very similar to the (+)INST OC- SEF settings.
[INST OC - NEQ]
>1.(+)INST OC-NEQ
2.(-)INST OC-NEQ
[1~5:1shot]
If Active Shot = 1, then negative sequence instantaneous overccurent
element is enabled for the first trip operation and every following trip
operation.
(-) INST OC- NEQ settings are very similar to the (+) INST OC- NEQ settings.
When this element is enabled, this element is operated prior to any other phase overcurrent
elements. If a fault current is higher than the pickup setting value, Lockout is operated.
This element can be set by a number of its active trip that is applied to the full operation to lockout,
time delay and fault current.
This function is very useful to prevent widespread line faults due to reclosing operations in case of
permanent fault.
The operating time of this element should be set for equal to or faster than and phase instantaneous
overccurent element. This element is enabled in the group setting and PROTECTION ENABLED
in user interface panel.
This element element is not affected by the inrush restrain and cold load pickup scheme
[INST OCL-PHA]
>1.(+)INST OCL-PHA
2.(-)INST OCL-PHA
[1~5:1shot]
If Active Shot = 1, then (+)INST OCL-PHASE element is enabled for
the first trip operation and next trip operations.
(-) INST OCL-PHA settings are very similar with (+) INST OCL-PHA settings.
Following settings are used to program the ‘INST OCL –GND’ element.
[1~5:1shot]
If Active Shot = 1, then ground instantaneous lockout overccurent
element is enabled for the first trip operation and every following trip
operation.
(-) INST OCL-GND settings are very similar to the (+) INST OCL-GND settings.
When this element is enabled, this element is operated prior to any other negative sequence
overcurrent elements. If a fault current is higher than the pickup setting value, Lockout is operated.
This element can be set by a number of its active trip that is applied to the full operation to lockout,
time delay and fault current.
This function is very useful to prevent widespread line faults due to reclosing operations in case of
permanent fault.
The operating time of this element should be set for equal to or faster than and negative sequence
instantaneous overccurent element. This element is enabled in the group setting and
PROTECTION ENABLED in user interface panel.
This element element is not affected by the inrush restrain and cold load pickup scheme
Following settings are used to program the ‘INST OCL – NEQ’ element.
GROUP # / RECLOSER / INST OCL– NEQ / (+)INST OCL– NEQ / Time Delay
[(+)INST OCL-NEQ] Range 0.00~600.00 sec
Function: DISABLE
Pickup: 8000 Default 0.00 Step 0.01 sec
>Time Delay: 0.00
Active Shot: 1 Set Time Delay for negative sequence instantaneous lockout
overccurent element. If it is set for 0, trips immediately on negative
[0.00~600.00:0.01s]
sequence fault current without delay.
GROUP # / RECLOSER / INST OCL– NEQ / (+)INST OCL– NEQ / Active Shot
[(+)INST OCL-NEQ] Range 1~5 shot
Function: DISABLE
Pickup: 8000 Default 1 Step 1shot
Time Delay: 0.00
>Active Shot: 1 Sets the time when this element is activated.
[1~5:1shot]
If Active Shot = 1, then negative sequence instantaneous lockout
overccurent element is enabled for the first trip operation and every
following trip operation.
(-) INST OCL- NEQ settings are very similar to the (+) INST OCL- NEQ settings.
Current
Trip
Inrush Current 1
Inrush Duration
Fault Pickup Current
Inrush Current 51
Restraint Region Operation Region
Trip
Inrush Current 2
51 Pickup Current
Inrush Reset Current Inrush Current 3
Reset Time
Normal Current
Region
Time
Inrush
Current 2 Inrush Restraint Duration Normal Condition
Oneshot Trip and Lockout Reclosing Avaliable
Inrush
Current 3 Inrush Restraint Duration Normal Condition
Oneshot Trip and Lockout Reclosing Avaliable
After it’s done black out more than outage time, it restores load current supply, inrush current
restraint algorithm is applied. When the restoration of load supply is occured, in the case of that
generated inrush current is greater than inrush duration fault pickup current as inrush current 1 of
“Figure 8-7. Inrush Restratint Operation Characteristics”, it’s considered as fault current,
recloser does trip operation during inrush duration. (But, when the delay curve of time overcurrent
element is ENABLE, recloser does operation). When inrush current is less than inrush duration
fault pickup current as inrush current 2 of “Figure 8-7. Inrush Restratint Operation
Characteristics” After fault protection operation is suppressed during R.M.T Time(Restore
Minimu Time), recloser does trip operation after inrush duration.
However, inrush duration is removed if inrush current is less than reset current before R.M.T Time
(Restore Minimum Time) as inrush current 3 of “Figure 8-7. Inrush Restratint Operation
Characteristics”.
When faul current is flowed more than inrush duration fault pick up current during inrush duration,
reloser does 1st trip operation and goes to lockout status on RECLOSE ENABLED.
NOTE:
According to setting of “Make use ‘I’”, in order to activate inrush current restraint sectopm the
condition to decide the restoration of load supply will be changed. If “YES” is set, the
decision is made when the load current becomes over 2A. If “NO” is set, the decision is made
when a recloser is closed (51A) by local or remote control.
[INRUSH RESTRAINT]
>1.FUNCTION
2.PICKUP CURRENT
3.RESTORE MIN. TIME
4.INRUSH RES’ RESET
5.PHASE CURVE
6.GROUND CURVE
7.NEG SEQ’ CURVE
8.OTHERS
1) Fuction Setup
NOTE:
The above setting applies the pickup current to operate the time overcurrent element, and the
multiple of current pickup current which is applied to the T-C curve during the time
overcurrent operation applies the pickup current setting value of the delay curve.
If the function of the delay curve is disabled, the time overcurrent element does not operate
(does not trip) even if a fault current occurs during the inrush current restraint duration.
NOTE:
Depending on the above settings, the inrush current restraint duration release condition will be
different. If it sets to EANBLE, the restore minimum time is applied and regardless of current
size, the inrush current restraint duration is released after a restore minimum time.
On the other hand, if it sets to DISABLE, the restore minimum time is not applied and the
current size should fall below the reset current, and the inrush current restraint duration is
released.
GROUP#/ RECLOSER/ INRUSH RES’/CLPU/ INRUSH RESTRAINT/ INRUSH RES’RESET / Reset Time
[INRUSH RES’ RESET] Range 0.01 ~ 600.00 sec
P-Reset I: 500
G-Reset I: 250 Default 0.60 Step 0.01 sec
S-Reset I: 10.0
Q-Reset I: 500
>Reset Time: 0.60
Sets the time to reset inrush current restraint duration.
[0.01~600.00:0.01 s]
Set the T-C curve to be applied during the Inrush current restraint duration.
*. NOTE) Ground Curve and NEG SEQ’ CURVE are same as PHASE CURVE above.
*. NOTE) Ground Curve and NEG SEQ’ CURVE are same as PHASE CURVE above.
GROUP#/ RECLOSER / INRUSH RES’/CLPU / INRUSH RESTRAINT / PHASE CURVE / Reset Method
[PHASE CURVE] Range INST, LINEAR
Curve: [US-VI]
Time Dial: 1.00 Default INST Step ~
Time Add.: 0.00
M.R.T: 0.00 In case that current level is decreased under Pickup level, Phase cold
>Reset Method: INST
load pickup element is reset.
[INST/LINEAR]
INST : After 1 cycle, Reset.
LINEAR : When the fault value is reached at selected curve’s
Rt(Reset characteristic constant) value, Reset.
*. NOTE) Ground Curve and NEG SEQ’ CURVE are same as PHASE CURVE above.
6) Other Setup
GROUP #/ RECLOSER / INRUSH RES’/CLPU / INRUSH RESTRAINT / OTHERS / Make Use ‘I’
[OTHERS] Range NO, YES
>Outage Time: 5.00
>Make Use ‘I’: NO Default NO Step ~
Set whetherer or not to use current as decision condition for operating
function.
[NO/YES]
When it sets to NO, the inrush current restraint interval becomes
active when relcoser is changed from open to close status.
When it set to YES, when the current increases above 2A, the
inrush current restraint interval is active.
In the state of cold load, this type is used to restrain the operation of protection functions to over
current occurring by change of load (the close of a switch on long-distance line, incoming heavy
load etc.). This function to restrain protection functions rises or drops the pickup level of time
overcurrent element during certain time (Pickup Multi) defined by a user.
As example, when ‘Pickup Multi’ and ‘Interval Time’ are set to be 3.0 and 60min respectively,
over 30 min after power loss, the applied cold load multiple is 2. If the minimum working currentis
set to be 200A, the current of Over Current Pickup becomes 400A, twice as much as the minimum
working current. In addition, after 60 min, the cold load multiple is fixed to be 3.
When ‘Pickup Multi’ and ‘Interval Time’ are set to be 3.0 and 60 min respectively, the graph of the
cold load multiple in “Figure 8-8. Cold Load Multipilier” is shown as follows.
NOTE:
The risen level of overcurrent pickup by multiple of cold load is the pickup level to operate
overcurrent protection element. The standard current level of T-C curve is a minimum
working current.
T(60min) T(60min)
0.5×T 0.5×T
(30min) (30min)
×3
×2
×1
Time(min)
GROUP #/ RECLOSER / INRUSH RES’/CLPU / COLD LOAD PICKUP / Make Use ‘I’
[COLD LOAD PICKUP] Range YES, NO
>Function: ENABLE
>Make Use ‘I’: NO Default NO Step ~
Pickup Multi: 2.0
Interval Time: 10 Set whether or not to be used as a decision condition for operating the
cold load pickup function.
[NO/YES]
If it sets to NO, power loss and power restoration are considered
as open or close state of relcoser.
If it sets to YES, determine power loss and power restoration as
current (less than or equal to 2A)
If measured second harmonic current content exceeds the adjustable pickup threshold setting value,
the second harmonic block function can restraint to operate overcurrent elements until the inrush
current has subsided.
2HB
Function 2HBAT
Pickup 2HBBT
Time Delay 2HBCT
Reset Time 2HBT
Minimum Current
Ia
Ib
Ic
E2HBE
Function
E2HBE &
Min Curr.
Ia +
IaRms.H2 +
-
/IaRms - & 2HBAT
2nd
Ib +
- Harmonic IaRms.H2
Calculation +
/IaRms - & Time Delay Reset Time 2HBBT
Ic +
-
IaRms.H2
+ 2HBCT
/IaRms - &
OR 2HBT
Pickup
The fifth harmonic block function process is same as the second harmonic block function above.
This setting is to restrain the inrush current caused by the second harmonic element.
GROUP #/ RECLOSER/ HARMONIC BLOCK / 2ND BLOCKING / Function
[2ND BLOCKING] Range DISABLE, ENABLE
>Function: DISABLE
Pickup: OFF Default DISABLE Step ~
Time Delay: 1.00
Reset Time: 1.00
Min.I: 60
Set the second harmonic function as enabled or disabled.
[DISABLE/ENABLE]
*. NOTE ) 5TH BLOCKING setting process is same as 2ND BLOCKING settings above.
If directional controls are selected, it will determine whether current flow in each phase is in
forward or reverse direction, as determined by the connection of the phase CTs, selected Maximum
Torque Angle (MTA), voltage and current phasors. To increase security of all directional controls,
add one power frequency cycle of intentional delay to prevent incorrect operation.
The directional controls settings can be different in each GROUP settings.
Each of the directional control elements has four setting items as follow:
[DIRECTION]
>1.PHASE
2.GROUND
3.SEF
4.NEG SEQ
If Polarized voltage becomes lower than the Minimum polarized Voltage, phase direction control is
lost and phase over current is not detected. On the other hand, if phase direction control is set for
‘NONE’, regardless of phase direction, phase over current is detected.
Phase direction control type can be set in order to detect phase over current. Depending on control
type, over current can be detected in Forward direction or reverse direction or regardless of
direction.
Following “Figure 8-12. Phasor Diagram for I1 Directional Polarization” shows normal current
(I1) direction polarity phasor diagram in complex plane.
Polarizing Referance V1
Voltage:
Ze
ro
I1 M.T.A= 60° Lag
To
in e
rq
eL
ue
rq u
To
L in
um
e
x im
Ma
FO
RW
OR
RE
VE
D
RS
E
Polarized voltage drops Min. polarized voltage, ground direction control is cancelled and ground
over current is not detected. On the other hand, if ground direction control is set for ‘NONE’,
ground over current is detected regardless of direction.
Ground direction control type is set to detect ground over current. Depending on control type, over
current is detected or is not detected.
Following figure shows phasor graph of zero phase current direction polarity in complex plane.
Polarizing Referance
-V0
Voltage:
Typical Fault
Angle
M.T.A= 60° Lag
Ze
I0
ro
To
rq
ue
Li
ne
ne
Li
u e
rq
To
m um
xi
Ma
FO
RW
OR
D
RE
VE
RS
E
V0
If polarizing voltage drops minimum polarizing voltage, negative sequence direction control is
cancelled and over current is not detected. On the other hand, if negative sequence direction control
type is set for ‘NONE’, over current is detected regardless of direction.
Set negative sequence direction control type to detect negative sequence overcurrent. Depending on
control type, overcurrent is detected in forward or reverse or both direction.
Following figure shows phasor graph of negative sequence current(I2) direction polarity.
Polarizing Referance
-V2
Voltage:
Ze
I2
or
To
rqu
e
Li
ne
e
e L in
rq u
To
um
im
M ax
FO
R
W
O
R
D
R
EV
ER
SE
V2
[NEG SEQ’]
Range 0(OFF), 0.10 ~ 0.80 xVT
Type: NONE
M.T.A: 60
Default 0.30 Step 0.01 xVT
>M.P.V(-V2): 0.30
Block OC: YES
Set Minimum Polarizing Voltage to check Negative Sequence. Voltage
shall be higher than this set value to check the direction. Otherwise,
0(OFF),0.10~0.80xVT
direction check will be blocked. In case of setting 0(OFF), direction
checking is disabled.
46BC
Function 46BC
Pickup 46BCT
Time Delay
Minimum Curr.
I₁
I₂
E150P1E
.
The figure below shows the function logic diagram of Broken Conductor.
Function
E46BCE &
Min Curr.
Ia +
-
Positive
/Negative
Ib +
Sequence
+ & 46BC
- -
Current
Calculation Time Delay
Ic + 46BCT
- 0
Pickup
[VOLTAGE]
>1.UNDER VOLT1
2.UNDER VOLT2
3.UV RESTORATION
4.OVER VOLT1
5.OVER VOLT2
6.NEUTRAL OVERVOLT1
7.NEUTRAL OVERVOLT2
8.OV RESTORATION
9.NEQ OVER VOLT1
10.NEQ OVER VOLT2
[UNDER VOLT1]
Range 1P, 2P, 3P
Function: OFF
Pickup: 0.80
Default 1P Step ~
Time Delay: 5.00
Min. V: 0.10
Set a number of phase to be detected for Undervoltage.
>Voltage Type: 1P
1P : More than 1 phase is detected with more than pickup voltage.
[1P/2P/3P]
2P : More than 2 phases are detected with more than pickup voltage.
3P : More than 3 phases are detected with more than pickup voltage.
3) UV RESTORATION Setup
The neutral overvoltage 1 settings process a very similar method to the overvoltage 1. However,
there is no setting menu for voltage type.
The neutral overvoltage 2 settings process a very similar method to the overvoltage 1. However,
there is no setting menu for voltage type.
The negative sequence overvoltage 1 settings process a very similar method to the overvoltage 1.
However, there is no setting menu for voltage type.
The negative sequence overvoltage 1 settings process a very similar method to the overvoltage 1.
However, there is no setting menu for voltage type.
7) OV RESTORATION Setup
[OV RESTORATION]
Range 1~100 min
Function: OFF
Pickup: 1.05
Default 5 Step 1min
Time Delay: 30.00
>Reset Time: 5
Set the operation reset time of overvoltage restoration function.
Source Side: VS
Voltage Type: 3P
The overvoltage restoration function does not work if the voltage does
[1~100:1m]
not return to normal status during the setting time after tripping by
overvoltage function.
[VS/VL/VS&VL]
VS : Recloser’s Source Side(A,B,C phase) Voltage
VL : Recloser’s Load Side(R,S,T phase) Voltage
VS&VL : Overvoltage element operates one of either Source side or
load side voltage becomes lower voltage level compared with pickup
setting in OV RESTORATION.
[FREQUENCY]
>1.UNDER FREQUENCY1
2.UNDER FREQUENCY2
3.OVER FREQUENCY1
4.OVER FREQUENCY2
5.FREQUENCY DELAY
6.AUTO RESTORATION
The underfrequency minimum voltage and underfrequency minimum current are used to prevent
incorrect operation when the recloser is closed by a local/remote control..
The underfrequency elements are enabled in the group settings and PROTECTION ENABLED in
user interface panel.
Overfrequency minimum voltage and minimum current is used to prevent mal-operation when
recloser is closed locally or remotely.
The overfrequency elements are enabled in the group settings and PROTECTION ENABLED in
user interface panel.
[POWER]
>1.FUNCTION
2.FORWARD POWER
3.DIRECTIONAL POWER
*. Note )
NON-OPERATION OPERATION
-P P+
0
Directional
Power
Operation
Area
Minimum
Operation
Power Torque
Angle P
Restraint
Area
[DEMAND]
>1.PHASE
2.GROUND
3.NEG SEQ’
4.ACTIVE POWER
5.REACTIVE POWER
Directional Type
Forward Reverse None (Bidirectional)
B0
B0 B0
GRight G0
G
B0 B0 B0
Operational Type
BUp BUp
B
G0 G0 G0
BDown BDown
B0 B0 B0
BUp BUp
G&B
BDown BDown
[G&B/G/B]
G&B: Determines the operating zone by Conductance (real part of
admittance) and Susceptance (imaginary part of admittance)
G: Determines the operating zone by Conductance (real part of
admittance).
B: Determines the operating zone by Susceptance (imaginary part of
admittance).
[NONE/FOR/REV]
NONE
− When G&B and G type, it operates if the Conductance is out of the
Right Conductance and Left Conductance setting.
− When G&B and B type, it operates if the Susceptance is out of the
Up Susceptance and Down Susceptance settings.
FORWARD
− When G&B and G type, it operates if the Conductance is out of the
Right Conductance settings.
− When G&B and B type, it operates if the Susceptance is out of the
Up Susceptance settings.
REVERSE
− When G&B and G type, it operates if the Conductance is out of the
Left Conductance settings.
When G&B and B type, it operates if the Susceptance is out of the
Down Susceptance settings.
[HOTLINE TAG]
>1.PHASE
2.GROUND
3.SEF
4.NEG SEQ’
8.1.22.1. PHASE
In this menu, T-C curve of phase time overcurrent elememts applied in Hotline Tag function is set.
8.1.22.2. GROUND
This menu sets the T-C curve of the ground time overcurrent elememts applied in the Hotline Tag
function. The setting items are the same as the PHASE menu.
8.1.22.3. SEF
This menu sets the time delay for sensitive earth fault in Hotline Tag function.
Set the time delay of sensitive earth fault in Hotline Tag function.
[0.00~600.00:0.01 s]
US
Trip Time(Sec) = TD × (α / (Mβ-1) + γ) + TA
ANSI/IEEE
Trip Time(Sec) = TD × (α / (Mβ-1) + γ) + TA
IEC
Trip Time(Sec) = TD × (α / (Mβ-1)) + TA
ES
Trip Time(Sec) = TD × (α / (Mβ-1) + γ) + TA
USER-DEFINED
Trip Time(Sec) = TD × (α / (Mβ-1) + γ) + TA
RESET TIME
Reset Time(Sec) = TD × (Rt / (1-M2))
NOTE :
“Recloser clearing time curves” are used when rated voltage of recloser is 15㎸ or 27㎸,
otherwise which added 30㎳(±4㎳) are used when it is 38㎸.
[USER CURVE]
>1.USER CURVE1
2.USER CURVE2
3.USER CURVE3
4.USER CURVE4
“RI” curve is a special curve to be used in conjunction with mechanical relay. When “RI” curve is
applied, time overcurrent element is operated by following formula.
1
Trip Time I Is
0.339 0.236
“HR” curve is a special curve to be used in conjunction with the fuse. When “HR” curve is
applied, time overcurrent element is operated by following formula.
I
log 2 ( 3.832) 3.66 1
Trip Time 10 Is
0.1
“FR” curve is a special curve to be used in conjunction with the fuse. When “FR” is applied,
inverse protection element is operated by following formula.
I
log ( 7.16) 3.0 1 I
Trip Time 10 Is
, when 1.2 2.0 ··formula (1)
0.1 IS
I
log ( 5.4 ) 2.47 1 I
Trip Time 10 Is
, when 2.0 2.66 ·formula (2)
0.1 IS
I
log ( 4.24) 1.98 1 I
Trip Time 10 Is
, when 2.66 ··formula (3)
0.1 IS
8.1.23.5. Curves
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : US NORMALLY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
15.00
13.00
2 11.00 2
9.00
Time(Second)
Time(Second)
7.00
1 1
0.9 5.00 0.9
0.8 0.8
0.7 4.00 0.7
0.6 0.6
3.00
0.5 0.5
0.4 0.4
2.00
0.3 0.3
0.2 0.2
1.00
0.1 0.1
0.09 0.5 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : US VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
15.00
13.00
11.00
1 1
0.9 9.00 0.9
0.8 0.8
0.7 7.00 0.7
0.6 0.6
0.5 5.00 0.5
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : US EXTREMELY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 15.00 0.6
0.5 13.00 0.5
11.00
0.4 0.4
9.00
0.3 0.3
7.00
4.00
3.00
0.1 0.1
0.09 0.09
0.08 2.00 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.03 0.03
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : US SHORT TIME INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
15.00
1 13.00 1
0.9 0.9
0.8 11.00 0.8
0.7 0.7
9.00
0.6 0.6
0.5 7.00 0.5
0.4 0.4
5.00
0.3 4.00 0.3
3.00
0.2 0.2
2.00
0.1 0.1
0.09 0.09
0.08 0.08
0.07 1.00 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.5
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : US SHORT TIME VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 15.00 0.7
13.00
0.6 0.6
11.00
0.5 0.5
9.00
0.4 0.4
7.00
0.3 0.3
5.00
0.2 4.00 0.2
3.00
0.04 0.04
0.03 0.03
0.5
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC NORMALLY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
VARIATIONS ± 5% OR 0.01 SECONDS
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 1 2
0.8
Time(Second)
Time(Second)
0.7
0.6
1 0.5 1
0.9 0.9
0.8 0.4 0.8
0.7 0.7
0.6 0.3 0.6
0.5 0.5
0.3 0.3
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEC VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
VARIATIONS ± 5% OR 0.01 SECONDS
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
1
0.4 0.4
0.8
0.3 0.7 0.3
0.6
0.5
0.2 0.2
0.4
0.3
0.1 0.1
0.09 0.2 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.1
0.04 0.04
0.03 0.03
0.05
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
1,000 1,000
900 900
800 800
700 700
600 RECLOSER CLEARING TIME CURVE 600
500 : IEC EXTREMELY INVERSE 500
400 CURVES ARE AVERAGE CLEARING TIME 400
VARIATIONS ± 5% OR 0.01 SECONDS
300 300
200 200
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
Time(Second)
Time(Second)
5 5
4 4
3 3
2 2
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 1 0.09
0.08 0.08
0.07 0.8 0.07
0.06 0.7 0.06
0.05 0.6 0.05
0.04 0.5 0.04
0.4
0.03 0.03
0.3
0.02 0.02
0.2
0.1
0.05
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
1,000 1,000
900 900
800 800
700 700
600 RECLOSER CLEARING TIME CURVE 600
500 : IEC LONG TIME VERY INVERSE 500
400 CURVES ARE AVERAGE CLEARING TIME 400
VARIATIONS ± 5% OR 0.01 SECONDS
300 300
200 200
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
Time(Second)
Time(Second)
1
4 4
0.8
3 0.7 3
0.6
0.5
2 2
0.4
0.3
1 1
0.9 0.2 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.1
0.4 0.4
0.3 0.3
0.05
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
1,000 1,000
900 900
800 800
700 700
600 RECLOSER CLEARING TIME CURVE 600
500 : IEC SHORT TIME INVERSE 500
400 CURVES ARE AVERAGE CLEARING TIME 400
VARIATIONS ± 5% OR 0.01 SECONDS
300 300
200 200
100 100
90 90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
Time(Second)
Time(Second)
4 4
3 3
2 2
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
1
0.3 0.3
0.8
0.7
0.2 0.6 0.2
0.5
0.4
0.02 0.02
0.05
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ES NORMALLY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 15.00 3
13.00
2 11.00 2
9.00
Time(Second)
Time(Second)
7.00
1 5.00 1
0.9 0.9
0.8 0.8
4.00
0.7 0.7
0.6 3.00 0.6
0.5 0.5
0.4 0.4
2.00
0.3 0.3
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ES VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
15.00
Time(Second)
Time(Second)
13.00
11.00
1 9.00 1
0.9 0.9
0.8 7.00 0.8
0.7 0.7
0.6 0.6
5.00
0.5 0.5
4.00
0.4 0.4
3.00
0.3 0.3
2.00
0.2 0.2
1.00
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.5
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ES EXTREMELY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
15.00
0.2 13.00 0.2
11.00
9.00
0.02 0.02
1.00
0.5
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ES LONG TIME VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 15.00 7
6 13.00 6
5 11.00 5
4 9.00 4
3 7.00 3
5.00
2 2
4.00
Time(Second)
Time(Second)
3.00
1 1
0.9 2.00 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
1.00
0.4 0.4
0.3 0.3
0.5
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEEE NORMALLY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
15.00
13.00
10 10
9 11.00 9
8 8
7 9.00 7
6 7.00 6
5 5
4 5.00 4
4.00
3 3
3.00
2 2
2.00
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 1.00 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : IEEE VERY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 15.00 8
7 13.00 7
6 6
11.00
5 5
9.00
4 4
7.00
3 3
5.00
2 4.00 2
Time(Second)
Time(Second)
3.00
1 2.00 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 1.00 0.5
0.4 0.4
0.3 0.3
0.5
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : US EXTREMELY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
15.00
2 2
13.00
11.00
Time(Second)
Time(Second)
9.00
1 7.00 1
0.9 0.9
0.8 0.8
0.7 5.00 0.7
0.6 4.00 0.6
0.5 0.5
3.00
0.4 0.4
0.2 0.2
1.00
0.1 0.1
0.09 0.09
0.08 0.5 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : DEFINITE TIME 1 sec, 10 sec 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 DEF-10S 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 DEF-1S 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : ANSI MODERATELY INVERSE 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
N2
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
N4
N3
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
N1
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : A, B, C, D, E 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
C
0.1 0.1
0.09 0.09
0.08 0.08
0.07 B 0.07
0.06 D 0.06
0.05 E 0.05
0.04
A 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : KP, L, M, N 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
N K
0.1 0.1
0.09 L 0.09
0.08 M 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : P, R, T, V 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7
0.6
V 0.7
0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
T
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05
P R 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : P, R, T, V 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7
0.6
V 0.7
0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
T
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05
P R 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : 1, 2, 3, 4, 5 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1
0.9 3 1
0.9
0.8 0.8
0.7 0.7
0.6 2 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08
0.07
5 0.08
0.07
0.06
1 4 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : 6, 7, 8, 8*, 9 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30
7 30
20 20
10 10
9 9
8 8
7 7
6 6
5 9 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
8
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 8* 0.06
0.05 0.05
0.04
6 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
26) Non Standard Curves (11, 13, 14, 15, 16, 17, 18)
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : 11, 13, 14, 15, 16, 17, 18 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
11
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 18 0.5
14
0.4 0.4
0.3 0.3
0.2 0.2
13
0.09 16 0.09
0.08
0.07
15 0.08
0.07
0.06 0.06
0.05 0.05
0.04 17 0.04
0.03 0.03
0.02 0.02
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
Figure 8-45. Non Standard Curves (11, 13, 14, 15, 16, 17, 18)
100
200
300
400
500
600
700
800
900
10k
1k
2k
3k
4k
5k
6k
7k
8k
9k
100 100
90 90
80 80
70 RECLOSER CLEARING TIME CURVE 70
60 : FUSE (RI, HR, FR) 60
50 CURVES ARE AVERAGE CLEARING TIME 50
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 RI 3
2 2
Time(Second)
Time(Second)
1 1
0.9 0.9
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
0.3 0.3
0.2 0.2
0.1 0.1
0.09 0.09
0.08 0.08
0.07 0.07
0.06 0.06
0.05 0.05
0.04 0.04
0.03 0.03
0.02 0.02
FR HR
0.01 0.01
1k
2k
3k
4k
5k
6k
7k
8k
9k
10k
100
200
300
400
500
600
700
800
900
8.1.24. Others
8.1.24.1. Sequence Coordination
When several Reclosers are connected in series to protect distribution systems, ETR300-R contains
Sequence Coordination feature which can prevent the simultaneous trip operations in both of Back-
up and Down-line Reclosers due to phase/ground fault. Sequence Coordination feature is activated
only if one out of several Down-line Reclosers connected to one Back-up Recloser detects a fault
current.
The same characteristics of fast and delay operations in the total number of the trip operations and
identical basic Time Current Curves should be set for all Reclosers connected in series.
The identical reclose interval time should be set for all Reclosers in series.
To coordinate the protection characteristics, an additional delay operation time (at least 100 ms)
should be applied to the Time Current Curve characteristics of Back-up Recloser, not to those of
Down-line Reclosers.
The reset time of Back-up Recloser should be set longer than any reclose interval time of all Down-
line Reclosers. This setting will prevent the reset operation of Back-up Recloser during the reclose
operation of Down-lines.
Starting
Reset Time
Counter
Close
Close
Down line EVR 2
Lockout Status
Open
Time
Faulted
8.2. Sectionalizer
This menu sets the auto sectionalizer function via fault indication. If the control type of ETR-300R
is set to 'SECTIONALIZER' mode, move the functions of this menu.
Place the cursor on “SECTIONALIZER” in GROUP# menu, press [ENT] button to move into this
menu. This menu is sub-divided as follow;
[SECTIONALIZER]
>1.PICKUP CURRENT
>2.INRUSH TIME
>3.AUTO SECTION
*. NOTE ) Setting for Ground, SEF and Neg Seq’ are same as Phase setting above.
Auto Sectionalizer(AS)
AS trips due to Fault current and Line Voltage.
When a fault has occurred in the load side of AS, C/B trips and High Voltage line becomes
Dead line Voltage(DV). Due to the number of Count, AS trips(is opened).
Please refer to “8.2.3.2. Auto Section Application” for more detail information of Auto
Sectionalizer function.
[AUTO SECTION]
Range 0.00~600.00
TIE Close TD: 30.00
TIE Open TD: 10.00
Default 1.00 Step 0.01
TIE Reset TD: 10.00
>TIE DL-VS TD: 1.00
TIE DL-VL TD: 1.00
Set deadline detection delay time of source side voltage.
[0.00~600.00:0.01 s]
VL Dead Line
VS Dead Line
Source Side
VOLTAGE
VOLTAGE
Load Side
SECTIONALIZER
CB AND RECLOSER - - -
2 Trip 4 Trip
Operate count - - -
Lockout Lockout
Step1 : At F1 location, when Permanent Fault occurs, RC1 conducts reclosing cycle.
AS1 counts “SEC Operate Cnt” when Dead line Voltage after sensing a Fault.
When RC1 trips three times, it reaches “SEC Operate Cnt” set value (3). Then F1
location is disconnected after “SEC Oper’ TD” Timer is finished.
AS2, AS3 is not operated because they did not sense the fault.
Step2 : AS1 is opened and RC1 is closed after Reclosing 3 times.
RC1 is closed after AS1 disconnect F1 location, and keep the rest of line normal.
Step3 : After removing the Fault, manually (local or remote) close AS1 and recover Live line.
Step1 : At F2 location, when Permanent Fault occurs, RC1 conducts reclosing cycle.
AS2 counts “SEC Operate Cnt” when Dead line Voltage after sensing a Fault.
When RC1 trips two times, it reaches “SEC Operate Cnt” set value (2).
Then F2 location is disconnected after “SEC Oper’ TD” Timer is finished.
AS1 is not operating because that “SEC Operate Cnt” is set for 3
AS3 is not operated because AS3 did not sense the fault.
Step2 : AS2 is opened and RC1 is closed after two times of reclosing.
RC1 is closed after AS2 disconnect F2 location, and keep the rest of line normal.
Step3 : After removing the Fault, manually (local or remote) close AS2 and recover live line.
Step1 : At F3 location, when Permanent Fault occurs, RC1 conducts reclosing cycle.
AS3 counts “SEC Operate Cnt” when Dead line Voltage after sensing a Fault.
When RC1 trips three times, it reaches “SEC Operate Cnt” set value (3). Then F3
location is disconnected after “SEC Oper’ TD” Timer is finished.
AS1, AS2 are not operating because that they did not sense the fault.
Step2 : AS3 is opened and RC1 is closed after three times of reclosing.
RC1 is closed after AS3 disconnect F3 location, and keep the rest of line normal.
Step3 : After removing the Fault, manually (local or remote) close AS3 and recover the live line.
SECTIONALIZER
CB AND RECLOSER
Step1 : At F1 location, when Permanent Fault occurs, CB1 locked out after conducting reclosing
cycle.
Step2 : SR1 counts Dead line Voltage time till a set time, then automatically opens (disconnects)
F1 location.
“TIE Operate Cnt” is set 2. When CB1 trips two times, “TIE Close TD” is run and after
30 seconds, TS1 is closed.
F1 is disconnected and the rest of live line shall be operated to the opposite direction.
Step3 : After removing the fault, close CB1 manually (local or remote), SR1 is automatically
closed after a setting time.
Step4 : Open TS1 manually (local or remote) and recover live line.
Step1 : At F1 location, when Permanent Fault occurs, CB1 locked out after conducting reclosing
cycle.
If SR1 trips two times, TS1 counts 2 and Close delay time is ran.
While Close delay time of TS1 is operating, SR1 becomes Live line Voltage by reclosing,
and Close delay time is reset.
If SR1 trips three times, TS1 counts 3, it is more than “TIE Operate Cnt” 2, so that Close
delay time doesn’t run.
When SR1 trips 4 times and locked out, TS1 counts 4. Close delay time doesn’t run.
Step2 : Open SR1 manually (local or remote) and recover live line.
Step1 : At F3 location, when Permanent Fault occurs, SR1 trips 4 times and locked out after
conducting reclosing cycle.
If SR1 trips two times, TS1 counts 2 and Close delay time runs.
While Close delay time of TS1 is operating, SR1 becomes Live line Voltage by reclosing,
and Close delay time is reset.
If SR1 trips three times, AS1 is automatically opened, TS1 counts 3, and it is more than
“TIE Operate Cnt” 2, so that Close delay time doesn’t run.
Step2 : After AS1 disconnects with F3, SR1 is reclosed and keeps the rest of live line normal.
Step3 : After removing the fault, close AS1 manually (local or remote) and recover live line.
8.3. Monitoring
Place the cursor on “MONITERING” in GLOBAL SETTING menu, press [ENT] button to move
into this menu. In this menu, it can set up monitoring function for line condition.
[MONITORING]
>1.PHASE DIFFERENCE
2.SYNCHRO’ CHECK
3.OPEN PHASE
4.LIVE LINE BLOCK
5.FAULT LOCATOR
6.LOAD CURR’ ALARM
7.POWER FACTOR
[PHASE DIFFERENCE]
Range 0.0 ~ 600.0sec
>Max Freq.Diff: 2.0
Check Phase: ALL Default 1.00 Step 0.01sec
>Time Delay: 1.00
The phase difference (ΔAngle) of the two circuits means the sum of the currently measured phase
difference(∆𝐴𝑛𝑔𝑙𝑒𝑠𝑡𝑎𝑡𝑖𝑐 ) and the compensation value (∆𝐴𝑛𝑔𝑙𝑒𝑐𝑜𝑚𝑝𝑒𝑛𝑠𝑎𝑡𝑒 ) of the phase difference
to be generated during body turn-in time by the slip frequency. The formula for calculating the
phase difference is as follows;
However, when the source side or load side circuit is diagonal, it is always closes regardless of
synchronous detection.
mZ (1-m)Z
IA
IF L
O
VA A
RF
D
The calculated “Fault Location” information be checked on the “Fault Cycle” event menu. For
more details, refer to “9.2. Fault Event” and “9.3. Fault Cycle - Summary”.
This function is only applied when the controller type of ETR300-R is “RECLOSER” mode.
*. NOTE ) Setting for Time Delay2 is same as Time Delay1 setting above.
Set the Block Time After Close for power factor elements.
[1.00~600.00:0.01s]
9. EVENT RECORDER
Place the cursor on “3.EVENT”, press [ENT] button to move into this menu.
ETR300-R records all events during the operation, occurred events are recorded separately such as
operation event, fault event, system event, set change event, load event and diagnostic event. All
events are recorded in order(FIFO). In this menu, all events can be checked and deleted. Also, all
events can be checked in interface program.
This menu has sub-menu as below. Press [ENT] to move into sub-menu.
[EVENT]
>1.OPERATION
2.FAULT
3.FAULT CYCLE
4.SYSTEM
5.SET CHANGE
6.AVER.LOAD/MIN
7.PEAK.LOAD/HOUR
8.PEAK.LOAD/DAY
9.DIGNOSTIC
10.PQM
11.ALARM CURRENT
12.CLEAR SAVED DATA
[▼][▲] are used to check event. [00001/30000] is the latest event record.
Trigger Source
STATUS
- CLOSE(OK) or CLOSE(FAIL)
- OPEN(OK) or CLOSE(FAIL)
CONTROL
- PL-HMI : Operation through control button at the front panel
- REMOTE : Operation through remote control
- MANUAL : Recloser (or Load breaker) mechanical manual operation.
- AUTO : Automatic operation through ETR300-R
- EXT’ : Operation through external command (External command condition is available
through PLC configuration)
Trigger Time
Monitor changes of Trigger source status in every 5 msec.
Trigger Capacity
Stores last 30000 events.
[▼][▲] buttons are used to check fault events. Press [ENT] button in fault event screen to check
fault current value. And press [ENT] again to return to previous screen. [00001/10000] is the latest
event record.
00001/10000 Shows the latest event in order and records 10000 events.
SEQ Fault sequence number
TARGET Records the fault detect phase and event trigger source.
- A: A Phase Fault
- B: B Phase Fault
- C: C Phase Fault
- G: Ground Fault
- S: Sensitive Earth Fault
- Q : Negative Sequence Fault
- TOC : Time Overcurrent Fault(Applied when “RECLOSER” type)
Trigger Source
Plesae refer to “TARGET” and “TYPE”of the above mentioned Fault Event Information.
Trigger Time
Moniters changes of Trigger source status in every 1/4 cycle.
Trigger Capacity
Stores last 10000 events.
Move to “MAIN MENU / EVENT / FAULT CYCLE” to confirm fault cycle summary.
[▼][▲] is used to check the fault event. [01/32] is the latest event record.
Trigger Source
Fault wave captured time.
- PU : Pick up time.
- TR : Trip time.
- PU&TR : Picku up & Trip time
Trigger Time
Moniters changes of Trigger source status in every 1/4 cycle.
Trigger Capacity
Maximum 32 events are recorded.
[SYSTEM] [SYSTEM]
No.00001/30000 No.00002/30000
[▼][▲] button is used to check the records. [00001/30000] is the latest event record.
Trigger Source
Protection element
52A Contact
Sequence status
Front panel control
AC supply
External control
Fail operation
External input status
System alarm
Sleep mode
Gas Status, etc.
Trigger Time
Monitors changes of Trigger source status in every 1/4 cycle.
Trigger type
Stores type of Trigger source : Pickup(assert) or Dropout(deassert)
Storage Capacity
Stores last 30000 events.
No.00001/30000 No.00002/30000
[▼][▲] button is used to check the records. [00001/30000] is the latest event record.
Trigger Source
Changed set menu
- GLOBAL SETTING (GLSCHG)
- GROUP 1~6 SETTING (GRSCH1 ~ GRSCH6)
Change method
The first name of the target name identifies the change method.;
- (L) LOCAL: Set change at local
- (R) REMOTE: Sec change in remote
- (P) PROGRAM: Set change by Interface software.
Trigger Time
Monitors changes of Trigger source status in every 5msec.
Storage Capacity
Stores last 30000 events.
To check the average value per minute Load & Energy events, please move to “MAIN MENU /
EVENT / LOAD&ENERGY/MIN” .
[LOAD&ENERGY/MIN] [LOAD&ENERGY/MIN]
ENT ENT
[LOAD&ENERGY/MIN] [LOAD&ENERGY/MIN]
ENT ENT
[LOAD&ENERGY/MIN] [LOAD&ENERGY/MIN]
*. NOTE ) Configuration display for Load&Energy/min events may be revised on user’s request.
[▼][▲] button is used to check the events. To check real active power and reactive power, press
[ENT] button. To return back to previous screen, press [ENT] again. [00001/27500] is the latest
event record.
Trigger Source
Demand Current – A, B, C, G
Demand Voltage – A, B, C, R, S, T
Demand Active Power - A, B, C, 3ф
Demand Reactive Power – A, B, C, 3ф
Demand Power Factor – A, B, C, 3ф
Demand Energy - Positive Watthour(3ф), Positive Varhour(3ф)
Trigger Time
Monitors to change Trigger source status every period set on “GLOBAL SETTING / EVENT
RECORDER / L&E Interval”.
Storage Capacity
Stores last 27500 events.
[LOAD&ENERGY/HOUR] [LOAD&ENERGY/HOUR]
ENT ENT
[LOAD&ENERGY/HOUR] [LOAD&ENERGY/HOUR]
ENT ENT
[LOAD&ENERGY/HOUR] [LOAD&ENERGY/HOUR]
*. NOTE ) Configuration display for peak. load/min events may be revised on user’s request.
[▼][▲] button is used to check the events. To check real active power and reactive power, press
[ENT] button in Current display screen. To return back to current display screen, press [ENT]
again. [00001/27500] is the latest event record.
Trigger Source
Demand Current – A, B, C, G
Demand Voltage – A, B, C, R, S, T
Demand Active Power - A, B, C, 3ф
Demand Reactive Power – A, B, C, 3ф
Trigger Time
Monitors changes of Trigger source status in every 1hour.
Storage Capacity
Stores last 27500 events.
Move to “MAIN MENU / EVENT / LOAD&ENERGY/DAY” to confirm Peak Load & Energy
/day events.
[LOAD&ENERGY/DAY] [LOAD&ENERGY/DAY]
ENT ENT
[LOAD&ENERGY/DAY] [LOAD&ENERGY/DAY]
ENT ENT
[LOAD&ENERGY/DAY] [LOAD&ENERGY/DAY]
*. NOTE ) Configuration display for peak. load/min events may be revised on user’s request.
[▼][▲] button is used to check the events. To check real active power and reactive power, press
[ENT] button in Current display screen. To return back to current display screen, press [ENT]
again. [00001/27500] is the latest event record.
Trigger Source
Demand Current – A, B, C, G
Demand Voltage – A, B, C, R, S, T
Demand Active Power - A, B, C, 3ф
Demand Reactive Power – A, B, C, 3ф
Demand Power Factor – A, B, C, 3ф
Demand Energy - Positive Watthour(3ф), Positive Varhour(3ф)
Trigger Time
Monitors changes of Trigger source status in every 1 day.
Storage Capacity
Stores last 27500 events.
1) Click “SETTING / LOAD & ENERGY FIELD CONFIG” to open ‘Load & Energy Field
Config Edit’.
Figure 9-1. Load & Energy Event Field Config Edit Window
2) In the ‘Load & Energy Field Config Edit’ window, configure fields recorded in Load & Energy
Event. The number of selected field is between 4 and 14 fields.
3) After completing the configuration, click the [Apply] button.
4) While ‘ONLINE’ communication status between Interface Software and ETR300-R, upload the
changed load profile field configuration in ETR300-R using “ONLINE / UPLOAD / LOAD &
ENERGY FIELD CONFIG” menu.
[DIAGNOSTIC] [DIAGNOSTIC]
No.00001/30000 No.00002/30000
[▼][▲] button is used to check the events. [00001/30000] is the latest event record.
Trigger Source
DSP Fail
ADC Fail
RTC Fail
Memory Fail
Flash-Rom Fail
Circuit voltage Fail
Global Setting Fail
Group Setting Fail
Event Fail
Count Fail
DO Fail
Close Fail
Open Fail, etc.
Trigger Time
Monitors status of Trigger source in every 5msec.
Trigger type
Stores type of Trigger source : Pickup(assert) or Dropout(deassert)
Storage Capacity
Stores last 30,000 events.
When Diagnostis Fail is occurred the treatment method is same as following.
Move to “MAIN MENU / EVENT / PQM” to confirm PQM events. In this menu, PQM event
item, phase occurence, measurement value and event maintaineance time can be checked (But,
event maintenance time is recorded only when events are sag, swell, interruption). PQM events are
generated by the “MAIN MENU/ GLOBAL SETTING/ GENERAL/ MONITORING/ POWER
QUALITY” setting.
[PQM] [PQM]
No.00001/10000 No.00002/10000
[▼][▲] button is used to check the event. [00001/10000] is the latest event record.
Trigger Source
PQM detect element.
Sag(SAG): Instantaneous(INST), Momentary(MOME), Temporary(TEMP),
Long Time(LONG)
Swell(SWL): Instantaneous(INST), Momentary(MOME), Temporary(TEMP),
Long Time(LONG)
Interruption(INT): Momentary(MOME), Temporary(TEMP), Sustained(LONG)
Voltage Harmonic distortion(VTH)
Current Harmonic distortion(ITH)
Source side Unbalance Voltage(UBV)
Load side Unbalance Voltage(UBL)
Current Unbalance(UBI)
Source side Over Voltage(OVS)
Load side Over Voltage(OVL)
Source side Under Voltage(UVS)
Load side Under Voltage(UVL)
Under Frequency(UNF)
PQM detected phase : A phase, B phase, C phase
PQM element related measured value.
PQM detect time(cycle)
Trigger Time
Monitors status of Trigger source in every 5msec.
Storage Capacity
Stores last 10,000 events.
Move to “MAIN MENU / EVENT / LOAD CURR’ ALARM” menu to check the load current
alarm event. In this menu, you can check the alarm occurrence and the current value of each phase
and the period of occurrence.
No.00001/10000 [00002/10000]
No.00002/10000
TARGET : A
VALUE : 00000 A DATA:
VALUE 1670v 337
: 00000 A Cyc
DURATION: 2 sec 01/01/2010 00:00:02
DURATION: 2 sec
[▼][▲] is used to check the event. [00001/10000] is the latest recorded event.
Trigger Source
Taget element
- A: Phase A Alarm current
- B: Phase B Alarm current
- C: Phase C Alarm current
- G: Ground Alarm current
Current of correspondent phase in case of alarm current event is occurred
Trigger Time
Check the status change of trigger source every 1/4 cycle.
Trigger Capacity
Max. 10000 events are saved.
[CLEAR EVENT]
10. MAINTENANCE
Place the cursor on “MAINTENANCE” in Main menu, press [ENT] button to move into this menu.
This menu displays Maintenance information.
This menu has sub-menu as below and by pressing [ENT] button, move into sub-menu.
[MAINTENANCE]
>1.COUNT
2.INTERRUT TIME
3.CONTACT WEAR
4.DATA RESET
5.CONTROLLER INFO
6.MECHANISM SCALE
10.1. Count
Counter information is displayed, it has sub-menus as below.
[COUNT]
>1.ETR300-R
2.FAULT
3.PQM
4.COMMUNICATION
5.USER COUNT
Diagnostic Count
ETR300-R diagnostic count is displayed.
Operation Count
Recloser operation counter is displayed.
[FAULT-IOC] [FAULT-UV]
No. 2/7 No. 4/7
TARGET A : 0 TARGET A : 0
TARGET B : 0 TARGET B : 0
TARGET C : 0 TARGET C : 0
TARGET G : 0
TARGET SEF : 0
TARGET Q : 0
FAULT-TOTAL (1/7)
Displays total count of faults.
TRIP : Displays trip operation count.
51 TOC : Displays time overcurrent trip count.
50 IOC : Dispalys instantaneous and instantaneous lockout overcurrent trip count.
27 UV : Displays under voltage trip count.
59 OV : Displays phase over voltage and neutral over voltage trip count.
81 FRE : Displays over frequency, under frequency and frequency decay trip count.
FAULT-TOC (2/7)
FAULT-IOC (3/7)
Displays the instantaneous and instantaneous lockout overcurrent trip count for each target.
FAULT-UV (4/7)
Displays under voltage trip count for each phase.
FAULT-OV (5/7)
Displays over voltage trip count for each phase.
Target N means the neutral over voltage trip count.
FAULT-FREQ(6/7)
Displays the trip count for other faults.
81 OVER : Displays over frequency trip count.
81 UNDER : Displays under frequency trip count.
81 DECAY : Displays frequency decay trip count.
FAULT-FREQ(7/7)
Displays the trip count for other faults.
DEMAND : Displays demand trip count.
46BC : Displays Broken Conductor trip count.
32POW : Displays 32 Power element trip count.
21YN : Displays 21 Zero Impedence trip count.
[PQM COUNT]
>1.INTERRUT
2.SAG
3.SWELL
4.HARMONICS
5.CURR UNBALANCE
6.VOLT UNBALANCE
7.UNDER VOLTAGE
8.OVER VOLTAGE
9.UNDER FREQUNCY
10.1.3.1. Interrupt
Move to “MAINTENANCE / PQM / INTERRUPT” to confirm interrup count.
MAINTENANCE / COUNT / PQM / INTERRUPT
[INTERRUPT] Number of Interruption is displayed.
TOTAL : 0
PHASE A : 0
PHASE B : 0
PHASE C : 0
MONENTARY : 0
TEMPORARY : 0
SUSSTAINED : 0
10.1.3.2. Sag
Move to “MAINTENANCE / COUNT / PQM / SAG” to confirm sag count.
MAINTENANCE / COUNT / PQM / SAG
[SAG] Number of Sag is displayed.
TOTAL : 0
PHASE A : 0
PHASE B : 0
PHASE C : 0
INSTANT : 0
MONENTARY : 0
TEMPORARY : 0
10.1.3.3. Swell
Move to “MAINTENANCE / COUNT / PQM / SWELL” to confirm swell count.
MAINTENANCE / COUNT / PQM / SWELL
[SWELL] Number of Swell occurred is displayed.
TOTAL : 0
PHASE A : 0
PHASE B : 0
PHASE C : 0
INSTANT : 0
MONENTARY : 0
TEMPORARY : 0
10.1.3.4. Harmonics
Move to “MAINTENANCE / COUNT / PQM / HARMONIC” to confirm sag count.
MAINTENANCE / COUNT / PQM / HARMONIC
[HARMONIC-VTHD COUNT]
Number of Harmonic distortion is displayed. The COUNT menu
No. 1/2
consists 2 pages and use [▼][▲] buttons to move into sub-menu.
TOTAL : 0
PHASE A : 0
PHASE B : 0
PHASE C : 0
VTHD(1/2)
Total number of Voltage Harmonic distortion and number of voltage
harmonic distortion per phase are displayed.
[HARMONIC-VTHD COUNT]
No. 1/2
ITHD(2/2)
TOTAL : 0
PHASE A : 0 Total number of current harmonic distortion and number of current
PHASE B : 0
PHASE C : 0 harmonic distortion per phase are displayed.
PHASE G : 0
Indicates the counter information of DNP3.0 protocol. This COUNT menu consists 4 pages. Use
[▼][▲] button to move into sub-menu.
[USER] 2/2
USER COUNT5: 0
USER COUNT6: 0
USER COUNT7: 0
USER COUNT8: 0
A : 100.00
B : 100.00
C : 100.00
10.6. IP INFORMATION
Move to “MAINTENANCE / IP INFOMATION” to confirm ETR300-R controller IP
information. In this menu, information such as MAC address and IP address for each ETH1 and
ETH2 is displayed.
MAINTENACE / IP INFORMATION
[IP INFORMATION] HW
ETHERNET1
HW 00:00:00:00:00:00 MAC address for each ETH1 and ETH2 port is displayed.
IP 000.000.000.000
ETHERNET2
HW 00:00:00:00:00:00 IP
IP 000.000.000.000
IP address for each ETH1 and ETH2 is displayed.
[RECLOSER AI SCALE]
VA, VB, VC, VR, VS, VT
VA:1.0000 IA:1.0000
VB:1.0000 IB:1.0000
Recloser Analog Input Scale Factor for each VT chanels are displayed.
VC:1.0000 IC:1.0000
VR:1.0000 IG:1.0000
VS:1.0000 IS:1.0000
VT:1.0000
IA, IB, IC, IG, IS
Recloser Analog Input Scale Factor for each CT chanels are displayed.
11. TIME
Place the cursor on “TIME” in Main menu, press [ENT] button to move in this menu.
TIME
[TIME] In this menu, you can check and set the current data and time. This
* CURRENT TIME * menu applies local time and UTC time is managed internally
2006/11/05 21:02:38
depending on the time zone setting.
PRESS <ENT> TO SET
[TIME]
2) To change a number, use [▲][▼] button and to move next item,
* SETTING TIME *
press [ENT] button.
2006/11/05 21:02:38 3) To save all changed setting, press [ENT].
USE [UP/DOWN/ENTER]
PRESS <FUNC> : ABORT
If “GLOBAL SETTING / GENERAL / DEVICE / TIME ZONE /
Time Syn’ Type” is “GMT” and “GLOBAL SETTING / GENERAL /
[TIME] DEVICE / H/W OPTION / IRIG Use” is “ON”, do not set current
* SAVE TIME * time manually.
2006/11/05 21:02:38
12. STATUS
Place the cursor on “STATUS” in Main menu, press [ENT] button to move in this menu. This
menu has sub-menu as below. Press [ENT] to move into sub-menu.
[STATUS]
>1.ETR300-R
2.INPUT PORTS
3.OUTPUT PORTS
4.GOOSE S-IN
5.GOOSE D-IN
6.GOOSE OUT
7.FAULT
8.DIAGONOSTIC
12.1. Recloser
Move to “MAINTENANCE / STATUS / ETR300-R” to confirm tank and ETR300-R status.
STATUS/ RECLOSER
[ETR300-R]
Present recloser and ETR300-R status are displayed.
>52A CONTACT: CLOSE
TYPE : REC
Use [▼] [▲] button to check all items.
PROTECTION : ENABLE
GND-PROTECT: ENABLE
SEF-PROTECT:DISABLE
RECLOSE :DISABLE 52A CONTACT
>CONTR’ LOCK: UNLOCK
CONTROL : LOCAL
Displays Circuit Breaker status.(OPEN, CLOSE, TROUBLE)
LOOP CONTR’:DISABLE
LC RESTORE :DISABLE
HOTLINE TAG:DISABLE TYPE
AUX1 :DISABLE
AUX2 :DISABLE Displays control type.(Recloser type(REC), Sectionalizer type(SEC))
79 LOCKOUT : ON
>AC POW FAIL: NORMAL
>BATTERY : NORMAL
>BAT’CHRGER : NORMAL PROTECTION
>DOOR OPEN : ON
>HANDLE LOCK: OFF Protection function status is displayed. (ENABLE/DISABLE)
>GAS : NORMAL
GND-PROTECT
Ground protection function status is displayed. (ENABLE/DISABLE)
SEF-PROTECT
Ground protection function status is displayed. (ENABLE/DISABLE)
STATUS/ RECLOSER
[ETR300-R] RECLOSE
52A CONTACT: CLOSE
TYPE : REC
Display whether to use reclosing function. (ENABLE/DISABLE)
PROTECTION : ENABLE
GND-PROTECT: ENABLE
SEF-PROTECT:DISABLE
>RECLOSE :DISABLE
CONTR’ LOCK
>CONTR’ LOCK: UNLOCK Displays panel control lock status.(LOCK, UNLOCK)
CONTROL : LOCAL
LOOP CONTR’:DISABLE
LC RESTORE :DISABLE
HOTLINE TAG:DISABLE CONTROL
AUX1 :DISABLE
AUX2 :DISABLE Operation control select is displayed.(REMOTE, LOCAL, TROUBLE)
79 LOCKOUT : ON
>AC POW FAIL: NORMAL
>BATTERY : NORMAL
>BAT’CHRGER : NORMAL LOOP CONTR’
>DOOR OPEN : ON
>HANDLE LOCK: OFF
Display whether to use loop control function. (ENABLE/DISABLE)
>GAS : NORMAL
LC RESTORE
Display whether to use loop control restore function.
(ENABLE/DISABLE)
HOTLINE TAG
Display whether to use hotline tag function. (ENABLE/DISABLE)
AUX1 / AUX2
Display whether to use AUX1 / AUX2 tag function.
(ENABLE/DISABLE)
79 LOCKOUT
Lockout of reclosing status is displayed(ON, OFF)
AC POW FAIL
External power supply status is displayed. (NORMAL, FAIL)
BATTERY
Battery status is displayed. (NORMAL, FAIL)
BAT’ CHARGER
Battery charger status is displayed. (NORMAL, FAIL)
STATUS/ RECLOSER
DOOR OPEN
Door open status is displayed(ON, OFF)
HANDLE LOCK
Display recloser handle lock status (ON, OFF)
GAS
Circuit breaker gas pressure status is displayed. (NORMAL, LOW)
Battery charger status is displayed. (NORMAL, FAIL)
[GOOSE S-IN] The ETR300-R provides 16 goose single inputs of IEC 61850
>GSIN01 ST : ON
>GSIN01 FAIL: OFF communication protocol. This menu displays the goose single input's
>GSIN02 ST : ON
>GSIN02 FAIL: OFF status provided by the ETR300-R.
>GSIN03 ST : ON
>GSIN03 FAIL: OFF
: GSIN## ST : Displays goose single input’s current status
:
>GSIN16 ST : ON GSIN## FAIL : Displays goose single input’s fail status.
>GSIN16 FAIL: OFF
[GOOSE D-IN] The ETR300-R provides 16 goose double inputs of the IEC 61850
>GDIN010 Bit0: ON
>GDIN011 Bit1: OFF communication protocol. This menu displays the goose double input's
>GDIN01F Fail: OFF
>GDIN020 Bit0: ON status provided by the ETR300-R.
>GDIN021 Bit1: OFF
>GDIN02F Fail: OFF
:
: GSIN##0 Bit0 : goose double input – displays the current status of
>GDIN160 Bit0: ON
>GDIN161 Bit1: OFF first bit(bit 0).
>GDIN16F Fail: OFF
GSIN##1 Bit1 : goose double input – displays the current status of
the second bit(bit 1).
GSIN##F Fail : Displays goose double input’s fail status.
[GOOSE OUT] The ETR300-R provides 16 goose outputs of the IEC 61850
>GOUT01: OFF
>GOUT02: OFF communication protocol. This menu displays the goose output's status
GOUT03: OFF
:
provided by the ETR300-R.
:
>GOUT16: OFF
Depending on input signal, “ON” or “OFF” is displayed.
[▼] [▲] button is used to check all input terminal status.
12.7. Fault
You can confirm in “MAIN MENU / STATUS / FAULT”.
STATUS/ FAULT
[FAULT] This menu displays the fault conditions that can not be indicated on the
>FAULT TRIP: OFF
27P1T : OFF front panel LEDs.
27P1AL : OFF
27P2T : OFF
27P2AL : OFF
27RSI : OFF Use [▼] [▲] button to check all items.
27RSCL : OFF
59P1T : OFF
59P1AL : OFF
59P2T : OFF FTRIP : Fault Trip Operation status.
59P2AL : OFF
59RSI : OFF 27P1T : Under Voltage 1 Trip status
59RSCL : OFF
81U1T : OFF 27P1A : Under Voltage 1 Alarm status
81U2T : OFF
81O1T : OFF 27P2T : Under Voltage 2 Trip status
81O2T : OFF
81D1T : OFF 27P2A : Under Voltage 2 Alarm status
81D2T : OFF
81RSI : OFF 27RSI : Under Voltage Auto Restoration Running status
81RSCL : OFF
27RSCL : Under Voltage Auto Restoration Close Operation stauts
59P1T : Over Voltage 1 Trip status
59P1A : Over Voltage 1 Alarm status
59P2T : Over Voltage 2 Trip status
59P2A : Over Voltage 2 Alarm status
STATUS/ FAULT
12.8. Diagonosic
You can confirm in “MAIN MENU / STATUS / DIGNOSTIC”
STATUS/ DIGNOSTIC
13. METERING
Place the cursor on “METERING” in Main menu, press [ENT] button to move in this menu. This
menu has sub-menu as below. Press [ENT] to move into sub-menu.
The accuracy of the measurement value displayed in this menu is “2.3. Metering Accuracy”.
[METERING]
>1.CURRENT
2.VOLTAGE
3.FREQUENCY
4.POWER
5.ENERGY
6.DEMAND
7.UNBALANCE
8.HARMONICS
9.TRUE R.M.S
10.TD
11.CONTROLLER REF
13.1. Current
Following values are contained in the current metering.
IA : Displays the measured phase A RMS current and phasor (A, deg°)
IB : Displays the measured phase B RMS current and phasor (A, deg°)
IC : Displays the measured phase C RMS current and phasor (A, deg°)
IG : Displays the measured ground RMS current and phasor (A, deg°)
IQ : Displays the measured negative sequence RMS current and phasor (A, deg°)
SEF: Displays the measured sensitive earth RMS current and phasor (A, deg°)
I1 : Indicates the measured normal voltage and phasor.(A, deg°)
I2: Indicates the measured negative phase sequence current and phasor. (A, deg°)
3I0: Indicates the zero sequence current and phasor. (A, deg°)
Peak IA : Displays the measured phase A Peak current (A)
Peak IB : Displays the measured phase B Peak current (A)
Peak IC : Displays the measured phase C Peak current (A)
Peak IG : Displays the measured ground Peak current (A)
Peak IQ : Displays the measured negative sequence Peak current (A)
NOTE
The peak current is updated by the recorded load current value when the load current alarm
event occurs. If the load current alarm function is DISABLE, the peak current is not
updated. The load current alarm function is described in “8.3.6. Load Current Alarm”.
13.2. Voltage
Following values are contained in the voltage metering.
SOURCE VOLT: Voltage and angle per phase at source side, Forward/Reverse/Zero sequence
voltage and angle at source side are displayed(㎸, deg°).
LOAD VOLT: Voltage and angle per phase at load side, Forward/Reverse/Zero sequence
voltage and angle at load side are displayed(㎸, deg°).
LINE VOLT: Phase to phase voltage and angle at source/load side are displayed (㎸, deg°).
You can confirm in “MAIN MENU / METERING / VOLTAGE”
MAIN MENU / METERING / VOLTAGE
Voltage and angle per phase are displayed. Use [▼][▲] button to check it.
13.3. Frequency
Following values are contained in the frequency metering.
Source: Metering value of present source side frequency is indicated.
Load : Metering value of present load side frequency is indicated.
Slip : Frequency difference between the power source side and the load side is indicated.
13.4. Power
Following values are contained in the power metering.
ACTIVE POWER: Each phase and three phase’s active power displayed.
REACTIVE POWER: Each phase and three phase’s reactive power displayed.
APPARENT POWER: Each phase and three phase’s apparent power displayed.
POWER FACTOR: Each phase and three phase’s power factor per phase is displayed.
A: 0 kW A: 0.0 %
B: 0 kW B: 0.0 %
C: 0 kW C: 0.0 %
3P: 0 Kw 3P: 0.0 %
A: 0 kVar A: 0 kVA
B: 0 kVar B: 0 kVA
C: 0 kVar C: 0 kVA
3P: 0 kVar 3P: 0 kVA
13.5. Energy
Following values are contained in the energy metering.
POS’ W/H: Each phase and three phase active power amount of forward direction are
indicated.
POS’ V/H: Each phase and three phase reactive power amount of forward direction are
indicated.
NEG’ W/H: Each phase and three phase active power amount of reverse direction are
indicated.
NEG’ V/H: Each phase and three phase reactive power amount of reverse direction are
indicated.
A: 0 kVarh
B: 0 kVarh
C: 0 kVarh
3P: 0 kVarh
SD:01/01/01/11:00:10
[NEG' V/H]
No. 3/4
A: 0 kWh
B: 0 kWh
C: 0 kWh
3P: 0 kWh
SD:01/01/01/11:00:10
[NEG' V/H]
No. 4/4
A: 0 kVarh
B: 0 kVarh
C: 0 kVarh
3P: 0 kVarh
SD:01/01/01/11:00:10
DEMAND CURRENT: Indicates the measured value of each phase and negative phase
sequence Demand current.
PHASE A CURRENT: Indicates the Demand current of present phase A, Demand current
maximum value of phase A and the time that have measured the maximum value.
PHASE B CURRENT: Indicates the Demand current of present phase B, Demand current
maximum value of phase B and the time that have measured the maximum value.
PHASE C CURRENT: Indicates the Demand current of present phase C, Demand current
maximum value of phase C and the time that have measured the maximum value.
PHASE G CURRENT: Indicates the Demand current of present phase G, Demand current
maximum value of phase G and the time that have measured the maximum value.
NEG SEQ’ CURRENT: Indicates the Demand current of present negative phase sequence,
Demand current maximum valueof negative phase sequence and the time that have measured
the maximum value.
POSITIVE ACTIVE POWER - A: Indicates the Demand active power of present phase A,
Demand active power maximum valueof phase A direction and the time that have measured
the maximum value for forward direction.
POSITIVE ACTIVE POWER – B: Indicates the Demand active power of present phase B,
Demand active power maximum valueof phase B and the time that have measured the
maximum value for forward direction.
POSITIVE ACTIVE POWER - C: Indicates the Demand active power of present phase C,
Demand active power maximum valueof phase C and the time that have measured the
maximum value for forward direction.
POSITIVE REAL POWER – 3P: Indicates the Demand active value of present three-phase,
Demand active power maximum valueof three-phase and the time that have measured the
maximum value for forward direction.
NEGATIVE REAL POWER - A: Indicates the Demand active power of present phase A,
Demand active power maximum valueof phase A direction and the time that have measured
the maximum value for reverse direction.
NEGATIVE REAL POWER – B: Indicates the Demand active power of present phase B,
Demand active power maximum valueof phase B and the time that have measured the
maximum value for reverse direction.
NEGATIVE REAL POWER - C: Indicates the Demand active power of present phase C,
Demand active power maximum valueof phase C and the time that have measured the
maximum value for reverse direction.
NEGATIVE REAL POWER – 3P: Indicates the Demand active value of present three-
phase, Demand active power maximum valueof three-phase and the time that have measured
the maximum value for reverse direction.
POSITIVE REACTIVE POWER - A: Indicates the Demand reactive power of present
phase A, Demand active power maximum valueof phase A and the time that have measured
the maximum value for forward direction.
POSITIVE REACTIVE POWER - B: Indicates the Demand reactive power of present
phase B, Demand active power maximum valueof phase B and the time that have measured
the maximum value for forward direction.
POSITIVE REACTIVE POWER - C: Indicates the Demand reactive power of present
phase C, Demand reactive power maximum valueof phase C and the time that have measured
the maximum value for forward direction.
POSITIVE REACTIVE POWER – 3P: Indicates the Demand reactive power of present
three-phase, Demand reactive power maximum valueof three-phase and the time that have
measured the maximum value for forward direction.
NEGATIVE REACTIVE POWER - A: Indicates the Demand reactive power of present
phase A, Demand active power maximum valueof phase A and the time that have measured
the maximum value for reverse direction.
NEGATIVE REACTIVE POWER - B: Indicates the Demand reactive power of present
phase B, Demand active power maximum valueof phase B and the time that have measured
the maximum value for reverse direction.
NEGATIVE REACTIVE POWER - C: Indicates the Demand reactive power of present
phase C, Demand reactive power maximum valueof phase C and the time that have measured
the maximum value for reverse direction.
NEGATIVE REACTIVE POWER – 3P: Indicates the Demand reactive power of present
three-phase, Demand reactive power maximum valueof three-phase and the time that have
measured the maximum value for reverse direction.
*. NOTE ) The aboive Max. Demand current and power of each phase and three-phase can be reset
by “MAIN MENU/ MAINTENANCE/ DATA RESET/ MAX DEMAND” menu.
[PHASE A CURRENT] [PHASE G CURRENT] [3P ACTIVE POWER] [P-A REACTIVE POWER]
No. 02/14 No. 05/14 No. 10/14 No. 11/14
DEMAND : 0 A DEMAND : 0 A
MAX : 0 A MAX : 0 A
01/01/0000 11:00:10 01/01/0000 11:00:10
Demand current and power is indicated. Use [▼][▲] key to check the Demand metering
information.
13.7. Unbalance
Following values are contained in the unbalance metering.
SOURCE-VOLT: Voltage unbalance at source side is displayed.
LOAD-VOLT: Voltage unbalance at load side is displayed.
CURRENT: Current unbalance is displayed.
SOURCE-VOLT: 0 %
LOAD-VOLT : 0 %
CURRENT : 0 %
13.8. Harmonics
You can confirm in “MAIN MENU / METERING / HARMONICS”
MAIN MENU / METERING / HARMONICS
[HARMONICS-THD] [HARMONICS-02H] [HARMONICS-31H]
IA : 0.0% IA : 0.0% IA : 0.0%
IB : 0.0% IB : 0.0% IB : 0.0%
IC : 0.0% IC : 0.0% IC : 0.0%
IG : 0.0% IG : 0.0% IG : 0.0%
VA : 0.0% VA : 0.0% VA : 0.0%
VB : 0.0% VB : 0.0% VB : 0.0%
VC : 0.0% VC : 0.0% VC : 0.0%
Voltage and current harmonic rate are displayed. Use [▼][▲] button to check harmonic rate
information.
13.11. TD Monitoring
You can confirm in “MAIN MENU / METERING / TD”
MAIN MENU / METERING / TD MONITORING
[TD MONITORING] TD input value is displayed.
TD1: 0.0 ETD1: 0.0
TD2: 0.0 ETD2: 0.0
TD3: 0.0 ETD3: 0.0
TD4: 0.0 ETD4: 0.0 TD1 ~ TD4 : Displays the input value of the DC input channel on
the front panel (But, when the 'TD Input Use' setting is OFF, it
always is marked 0).
ETD1 ~ ETD4 : Displays input value of external DC input channel
of External I/O ETIO10 (But, when ‘EXT.I/O Use’ setting is OFF, it
always is marked 0)
[REF. VALUE (1/2)] In this menu, the reference measurement value for checking the
BATTERY VOLT: 00.00V condition of ETR300-R is displayed. This menu consists of 2 pages
CHARGER VOLT: 00.00V
CHARGER I(+): 0.00A and use [▼] [▲] button to move into sub-menu.
BATTERY CAP.:100.00%
TEMPER.(IN) : 00D
TEMPER.(OUT): 00D BATTERY VOLT : Display the battery voltage.
CHARGER VOLT : Display the voltage of charge circuit.
CHARGER I : Displays charge current. When the measurement
[REF. VALUE (2/2)] value is positive, it’s charge current. On the other side, the
+12V : 12.00V
-12V :-12.00V measurement value is negavitve, it’s discharge current.
REF. VOLT : 2.50A
GAS PRE(bar): 00.00b BATTERY CAP.: Displays battery capacity by ‘Battery
GAS PRE(VOL): 00.00V Management’.
TEMPER.(IN) : Displays internal temperature of ETR300-R.
TEMPER.(OUT) : Displays external temperature of ETR300-R
(control box internal temperature)(But, ‘EXT. Temper’ Use’ is
OFF, it doesn’t indicate that item).
+12V : Displays +12V system power measurement value.
-12V : Displays -12V system power measurement value.
REF. VOLT : Displays reference voltage 2.5V measurement
value.
GAS PRE(bar) : Displays gas pressure(But, when ‘GAS
Sensor’ is NONE, it doesn’t indicate that item).
GAS PRE(VOL) : Displays input voltage value configured on
gas pressure input port. It calculates gas pressure using that
voltage value. (But, when ‘GAS Sensor’ is NONE, it doesn’t
indicate that item).
14. INSTALLATION
14.1. User Interface Door and Power Switch
Satellite-Synchronized
Clock Unit
(ETSSCU100)
Door switch
Handle
ETR300-R
VA / VR
User Interface
Panel
VB / VS
VC / VT
TYPE :
SERIAL No :
DATE : 20 . .
WEIGHT : kg
User Interface
Door
AC Power Outlet
For user convenience, AC Power Outlet is located on User Interface Door. Fuse is installed for
safety from overload. Location of fuse is referred to “Figure 14-4. Inner Structure”.
Air Vent
To prevent from humidity by temperature fluctuation, Vents are covered with left and right side.
443
Ø1
38 7
Ø
Ø 34
914.5
826.5
Earth Terminal
Φ12(113mm) 17mm dia.
292 86
322
Antenna hole
Spare hole
VG22 series
(34.9mm)
The top of the control box where the solar radiation is directly applied consists of a double
structure. The inside of the door is insulated with 5t insulator on the front side of the door so that it
can withstand rapid temperature changes. An air vent is installed at the top and bottom of the
control box to remove moisture from inside and it is also satisfying IP54 that can withstand dust /
moisture.
The control box is able to withstand the external environment and temperature changes for a long
time, and STS304 material is used to prevent rust. In addition, it is spray painted with Munsell No.
N5Y 7/1 (gray line), for durability of painting.
All metal parts of the control box are earthed to the enclosure and an earthing terminal for the
ground cable is provided on the outside of the enclosure. The ground terminal can be connected up
to 113mm of cable without separate auxiliary devices.
At the bottom of the control box, there are an antenna hole for remote communication and three
spare holes(Φ21) for user convenience in preparation for future improvement.
Door switch
Control Module
User Available space
350*200*H100mm
(Modem space)
Capacitor Bank
SMPS
FUS E
3 Point SPD
locking (Surge Protection Device)
TYPE :
Terminal
R A IL H O L D E R
R A IL H O L D E R
SER IAL No :
Block
DATE : 20 . .
PO W ER SUPPLY : VAC
W EIGH T : kg
E N D C O VE R
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
USL-5 SR 4
Power
Ph as e A ngl e
A m pl ifie r
PW
T
T
S
Transformer
PO W E R
R
CN1
C
OU TPU T
B
CN3
A
IN P U T
CN2
N L
Battery
A document pocket
Nameplate
MCB(Battery, AC Power)
AC Power Outlet
Heater(option)
Shows base plate measurements that can be attached in User Available Space.
On Base plate, 10㎜/M6 Nut is used to fix the base plate.
Available space for height of base plate is 100㎜
60W DC Power is provided. In case of the necessity of larger than 60W, additional power should
be attached. For more details, contact manufacturer.
Remove cable coating at the end of cable length of 8mm(0.315"). With using (+) PTR J
connector terminal on side panel should be connected to Wire size AWG24 up to AWG12.
When overload, automatically circuit breaks current. In case long-term overload time, there is a
fuse on analog circuits to protect circuits from failure.
1A
IA
C C 05 USB-B
16 IC
IG IG 06
CURRENT
D D 07
17 VC P7 IG
E E 1 CN1 08
18 VB 2 09
F F SEF
10
0.16A
VD 9 VA P1 P2
G G CN2 Eth1
1 1 CN3
P3 13 VT E01
H H 2 2 VA (TP/FX)
02
4V
14 VS 3 3 VB
J J 03
7 7 VC Eth2
3 15 VR 04
K K 4 4
05
6 10 5 5 VR (TP/FX)
06
VOLTAGE
L L
4V
6 6 VS
2 11 07
M M 8 8 VT
P1 08
5 12
N N
T/D
1 P P
RS232-1
4 S S L01 PS(V+)
69 02 PS(MONI')
PROTECTION C.T
T T
12 03 PS(GND)
U U
11 52b RS232-2
V V K01 IN201 (Open)
10 52a 02 IN202 (Close)
P2 W W
9 03 IN203 (Unlock)
INPUT
X X DOOR S/W 04 IN204 Spare 485+
8 05 IN205 (Door) 1
Z Z 485-
7 06 IN206 (CBP_OK) 2
a a RS485
VD 07 IN207 Spare FG
52b 3
b b 08 IN208 Spare
RECLOSER CONTROL ETR300-R
52a 09
PW
c c 10 ETSSCU100
d d J04 CAP+
C B A J05 CAP- GPS Module
e e (Option)
SOURCE SIDE f f
J01 IRIG-B 01 RS485+
g g CLOSE 02 RS485-
02
TRIP & CLOSE
+ OPEN + 03 RS485GND
CC h h 03 1
COM 04 IRIG-B(+)
j j - 2 05 IRIG-B(-)
06 N/C
m m 313
07 POW+
+ p p 401
TC Capacitor Bank 08 POW-
r r C1
k k
n n
SMPS-C Module
s s LD1 2 CN2
POWER ALARM SMA
R R OUTPUT 4
14.7. ETR300-R Wiring Diagram
Wifi
1 CN1
Shield Cable I01 (Option)
SMPS ON OUT205
INPUT PW
8M(standard) 2 02
03
LD3 1,2,3 CN3 OUT206
+ 04
DC120V OUTPUT DC120V
OUTPUT 4,5,6 05 OUT207
- 06
BATT' IN
FG ZG AC24V IN (DC24V)
ENHANCED TECHNOLOGY
+ -
1 2 4 3 2 1 Power output
TB1 TB2 MODEM 313
H01 +
401
POWER 02 - DC24V or DC12V
03 (40W / Continuous)
GPS Module
LEGEND
(60W / 1min)
04
Tr1 : Transformer
BATTERY
BAT1 310
G01 +
410 BATT.
TC : Trip Coil(120VDC)
G02 -
CC : Close Coil(120VDC)
C1 : Capacitor 680000uF/160WV
B 200 24VAC
220 8 digital output
G04 N
Neutral
C
429
RECLOSER CONTROL ETR300-R http://www.entecene.co.kr
F01
IA
2
3
IB
4
Current IN should be connected with
IC
6
SEF(F09, F10) of Side Panel in.
IN
8
Non Earthing System.
SEF
10
IN(F07,F08) should be connected to each CT
other.
F01
IA
2
3
IB
4
5
IC
6
7
IN
8
9
SEF
10
CT
Recloser Phase should match with User system. Refer to “Figure 14-9. Phase Rotation”
CT Phase rotation must be arranged comparing with Voltage Inputs Phase rotation.
VA
VB
2
VC
3
VN
4
VR
5
VS
6
VT
7
VN
8
PT
For Metering accuracy, phase rotations of User system and Recloser should be the same.
“Figure 14-9. Phase Rotation” shows the same phase rotation between User System and Recloser.
If the phase rotation is not the same in User system and Recloser, correct CT and VD wiring in side
panel to be matched.
ETR300-R Recloser phase A is the Bushing the nearest from Trip lever on the side.
“Figure 14-10. Control Receptacle” shows Female Receptacle installed in Control ETR300-R.
A AC Power Input
B AC Power Input (Neutral)
C EARTH
14.15. Fuses
Table 14-4. Fuses
Rating /
Positions Dimensions Purpose
External AC - Power Input
series.
Harness connector(CN11) from Battery Terminal is
connected to battery switch NFB1. In order to store
Battery for a long time, turn NFB1 “OFF” without
disconnecting Harness connector.
The self-discharge rate of batteries is approximately 3%
per month when batteries are stored at an ambient
temperature of +20℃(+68℉). The self-discharge rate
varies with ambient temperature. Figure 14-14. Battery
The approximate depth of discharge or remaining
capacity of an battery can be empirically determined
from “Figure 14-15. Open Circuit Voltage”.
Turn off NFB1 to disconnect Battery from circuits.
Remove Battery Connector CN11(3191-2R) and measure
the battery voltage.
If the battery voltage is less than 22.5Vdc, the residual
capacity is 0%. The voltage can be recharged but requires
maintenance.
24Vdc Battery supplies Relay Module and SMPS-C
Module through NFB1(Battery Switch).
Relay Module supplies through PTR G Connector in Side
Figure 14-15. Open Circuit Voltage
Panel and SMPS-C Module supplies through PTR J
Connector of SMPS-C Module.
VOLTAGE 6 VD
DIVIDER Main Process Module
INPUTS (ETR300-R(600))
Ethernet 1
TP or FX (Option)
Protocol Ethernet 2
PSM DNP 3.0 TP or FX (Option)
( Power Supply MODBUS
IEC 60870-5-101
Module) IEC 60870-5-104 RS232-1
IEC 61850 (Option)
52 CONTACT MONITORED
69 CONTACT
RS232-2
CLOSE/TRIP
RS485
MAGNETIC CONTROL
ACTUATOR
Capacitor IRIG-B
SMPS-C
120Vdc
(Capacitor
Charger)
SCADA Option
BATTERY
24Vdc
DIGITAL INPUTS 12
DC Power Output
(DC12V or DC24V)
Controller Recloser
INPUT
COM (12Vdc) 1114
K09 U
IN201 (Trip Status) 1115 52b
K01 V
IN202 (Close Status) 1116 52a
K02 W
IN203 (Unlock Status) 1117 69
K03 T
IN206 (Cap, Charge OK) 1120
K06 SMPS-C Module
CN2 2
ALARM
4 OUTPUT
OUT205 CN1 1
I01 3 TB1
SMPS ON AC24V IN 4
2 INPUT
I02
2 TB2
BATT' IN
CN3 1,2,3 1
Relay Module
(DC24V)
+120VDC
J04 +
DC120V
C1 OUTPUT
4,5,6
J05 -
J03
g CC
Close J01 j
Control
Trip J02 m TC
Control
p
0VDC r
CC Close Coil
TC Trip Coil
C Capacitor for Trip & Close
IGBT IGBT Contact for Trip & Close Control
SMPS-C is a module that receives AC 24V and BATT '(DC24V) input and charges the capacitor
for trip & close in CC (continuous current) mode.
SMPS ON INPUT: ON/OFF input terminal of SMPS module and operates ON when short
DC120V OUTPUT: DC120V output terminal for charging capacitor
LD1: Lights up when SMPS module operates
LD3: Lights up when capacitor charging is complete
ALARM OUTPUT: Capacitor charge completion signal contact
When the IGBT is "ON", the charged capacitor's power turns on the trip/close coil, resulting in
recloser operation.
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
124
125
126
127
INTERUPTERS
VACUUM
P1
2 9 1302 D
6
VC
3 13 1312 E
VB
14 1311 F
VA
P3
7 1310
15 G
8 VT
10 1318 H
9 VS
11 1316 J
P2
10 VR
12 K
11 1314 L
12
N
P
69
1112 12 1112 T
1111 11 1111 U
1110 10 V
52b
1109 9 1109 W
52a
1108 8 1108 a
1107 7 1107 b
52b
1106 6 1106 c
52a
1105 5 1105 d
1104 4 1104 e
1103 3 f
+ g
CC 1102 2 1102
+
TC 1101 1 1101 h
TB1 j
m
p
r
R
RE1
E VD Source Phase C
F VD Source Phase B
G VD Source Phase A
Voltage sensing device measures a voltage by using capacity of capacitor built or capacity of
resistance built in bushing of switch. Capacity of capacitor is 26㎊(±%), resistanc 100㏁.
Voltage sensing device divides a voltage by using Voltage Divider(VD) and secondary
capacitor or resistance, and then divided voltage is supplied to RTU through Amplifer(AMP)
circuit and Transformer.
MOV(TNR15G820K) is used to protect surge of control.
5.0
4.5
4.0
3.5
Output voltage(Vdc)
3.0
2.5
2.0
1.5
1.0
0.5
0.0
-0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Pressure (bar)
15. MAINTANANCE
15.1. Warning Events
ETR300-R possesses self-test and self-diagnostic function. If any abnormal behavior is detected in
the system, it records the corresponding events in the Diagnostic Event or System Event and
transmits it to SCADA system via remote.
“Table 15-1. Warning Events” is the list of self-diagnosis conditions managed by ETR300-R
system processing method and user’s recommended actions.. Users are requested to refer to “Table
15-1. Warning Events” in case of any abnormality in the system.
Connect between PC and ETR300-R using Ethernet cable. The Ethernet cable should be wired at
ethernet port(EN1 or EN2) for Ethernet on side panel of ETR300-R.
After executing FTP utility, enter IP address of ETR300-R required to patch firmware and No. 21 for
the number of port on TLS settings of FTP utility. IP address of ETR300-R refers to setting values
on “GLOBAL SETTING/ COMMUNICATION/ PORT SETUP / PORT4/ IP Addr Oct1~ 4”.
Password refers to ‘Admin PW’ setting on “GLOBAL SETTING / COMMUNICATION / FTP-
SSL / Admin PW”. Access “/home/entec_system/PACKAGE” on the FTP utility.
Upload a file named ‘UPDATE.fw’ on directory. DOES NOT REVISE the file name. If the file
name does not correspond, patching firmware is not supported. After completed to upload the file
on the directory, patching firmware starts automatically. Changed firmware version is checked on
device or through interface ETIMS interface software after patch process is sucessfully finished.
For reference this function supports on ETIMS interface software, too.
NOTE
Refer to ‘iResult.log’ file which is a generated error history of ETR300-R’. After it is
completed to import CSV files, the files will be removed. If any error generates, prefix
"Done_" adds name of the file generated error. Except on items generated error, import
function can continues to process. If error is generated, the error is logged on ‘iResult.log’
caused that any value gets out of a range and cannot be set.
17.3. COMFEDE
ETR300-R can download COMFEDE(Common Format for Event Data Exchange) format files
related on EVENT. After executing FTP utility, enter IP address of ETR300-R required to patch
firmware and No. 21 for the number of port on TLS settings of FTP utility. Password refers to
‘User1 PW’ setting on “GLOBAL SETTING / COMMUNICATION / FTP-SSL / User1 PW”.
Access “/home/ entec_user/COMFEDE” on the FTP utility.
Saved event information contains as follows; Fault indicator, Operation, System, Diagnostic,
Setting changed, Load & Energy (Load profile). Initial one hundred logs of each type of ETR300-R
events. Initial fifty event logs of each type of Load & Energy events. Generated more than one
hundred event logs, the events are saved on flash memory or micro SD card.
In case that micro SD card is inserted, micro SD card stores every 1000 events separately. Using
date and time when every 1000th event is generated, name of file is created, for example,
FI_20171010_235043.xml. So the events can be separated using the name of xml format files.
However, storing event logs is limited according to storage capacity of micro SD Card inserted. If
there is no storage capacity of SD Card, it will be removed in old order. Note that formatting
FAT32 is required for micro SD card which allocation unit is 32KB. If micro SD card is not
inserted, events saved on flash drive be possible to store 1000 events., Per type of events, two files
grouped each 1000 events(up to 2000 events) can be managed. And the files can be distinguished
using the file names. For example, names of xml files are ‘FI_EVENT.xml’ saved recently and
‘OLD_FI_EVENT.xml’ saved in the past.
17.4. COMTRADE
ETR-300R supports COMTRADE(Common Format for Transient Data Exchange) format files of
fault waveforms recorded on fault event log. After executing FTP utility, enter IP address of
ETR300-R required to patch firmware and No.21 for the number of ports on TLS settings of FTP
utility. Password refers to 'User 1 PW' setting on “GLOBAL SETTING / COMMUNICATION /
FTP-SSL / User1 PW”. Access “/home/ entec_user/COMTRADE” on the FTP utility.
Please refer to the ETIMS interface software manual for details of connection.
In order to establish a successful connection, check the following setting items in advance.
Please refer to the ETIMS interface software manual for details of connection.
18.3. Security
Wireless connection between ETR300-R and ETIMS interface software may be insecure.
Therefore, ETR300-R uses SSL / TLS and AES to enhance the security.
18.3.2. AES
Mobile ETIMS encrypts the packets transmitted to ETR300-R using Advanced Encryption
Standard (AES) encryption.
Only the control commands that change the settings of the ETR300-R are encrypted, other
commands are not encrypted.