Clearance between control cables, negative cable traction, positive cable traction,

How to protect all kind of cable from cable trench to ground level

Method to dewatering in tunnel cable when rainy season.

ID002-FOLIO 005: How to keep the gap 15mm between cable layer without barrier

How distance between two cable layer block.

Lack of typical cross section at position the cables change direction from cable tunnel up to ground
lever.

ID001-FOLIO 005:

To clarify how traction cables, change direction from cable tunnel to up.
The point that indicates to negative traction cables and positive traction cable is not correctly.

To supplement the cross section of traction cables is required.

ID01 FOLIO 012

Radial bending of traction cable should be clarified.

ID 02 FOLIO 002: we do not see cross section A1-A1 on plan drawing.

ID 02 FOLIO 003: we do not see cross section A2-A2 on plan drawing.

ID 02 FOLIO 004:

Radial bending of traction cable should be displayed.

ID 02 FOLIO 005 and ID 02 FOLIO 006:


Cross sections should be indicated the exact location does not show “Typical cross section” commonly.

How to keep traction cables separately without divider.

How to protect traction cables in cable tunnel to avoid under water level.

ID 02 FOLIO 007

Two cross sections with same name “B1-B1” but different content: Contractor is requested to clarify.

For continuity earthing wire on cable support: Contractor is requested to clarify.