You are on page 1of 2

T EC H N I C A L D ATA S H E E T

Secondary Skid Unit (SSU)


Solar Power Collection application with central inverter
High safety design for equipment,
personnel and environment

Factory-delivered solution with external


connection done at site results in reduced
installation time

Simple and modular concept with pre-engi-


neered designs shorten design time,
eliminating design errors

— A Secondary Skid Unit (SSU) is an assembly comprised • Economic solution


Secondary Skid Unit
of medium voltage (MV) switchgear, a transformer • Locking system for MV compartment to prevent un-
packaged and central inverter for power conversion. authorized entry
The SSU is the Power Collection unit which converts
the solar energy generated by the solar panels into a Medium voltage
usable grid voltage. The SSU is a plug-and-play solu- The SSU can be provided with different options of
tion, usually installed as close to the solar strings as medium voltage switchgear from ABB’s SF6 or its
possible, enabling solar power to be easily and rapidly air-insulated switchgear portfolio. The MV switchgear
connected to the electrical grid. can be provided with an SF6 gas alarm, switch posi-
tion contacts, plug-in MV surge arresters or auto re-
Features closing functions.
• Simple and quick installation – pre-test units at the
factory, drop in place and connect cables Transformer
• Pre-engineered products reduce time to quote and The SSU is designed and manufactured to be installed
supply, while reducing risks with liquid filled or dry type transformers. The trans-
• Engineered for efficient cooling in order to extend former can be provided with an alarm and trip con-
the life of the equipment tacts for temperature and gas pressure.
• All ABB designs are green to support the
environment Central inverter
• No exposed live parts, providing safety for operator ABB PVS980 central inverters are ideal for large PV
and personnel power plants. They provide a rapid return on invest-
• SCADA ready ment through their high DC input voltage, high effi-
• All equipment contained in the solar modules are ciency, proven components, compact and modular de-
type tested according to their relevant standards sign and a host of life cycle services.
• Easy access to equipment for visual inspection and
service
• Open-air cooling for maximum efficiency
• Compact and easily transportable
The PVS980 inverter is one of the most efficient and with the most common inverter power ratings. The
cost-effective ways to convert the direct current (DC), solutions are equipped with medium voltage switch-
generated by solar modules, into high quality and CO2- gear SafeRing CCV configuration (cable loop with
free alternating current (AC) that can be fed into the breaker and relay protection). The transformer in-
power distribution network. cludes standard integrated protection for pressure
and gas (RIS). Product data sheets are available with
Pre-engineered solution technical data an overview of other options available. Pre-designed
Pre-designed solutions are available for optimized de- solutions for Power Collection are shown below:
signs and quicker delivery. Power ratings are aligned

Style number SSU-A-N-E-C-23L-S-3-N SSU-A-N-E-C-46L-B-3-3


Overall parameters
Length x width x height, mm 7200 x 2300 x 2530 12000 x 2300 x 2530
Approximate weight (metric tons) 12 21
MV switchgear
Switchgear type SafeRing /SafePlus SafeRing /SafePlus
Protection relay Various Various
Transformer
Transformer type oil immersed oil immersed
Power rating (kVA) 2300 4600
Standard protection RIS RIS
Inverter
Recommended PV power (kWp) 2910 ~ 3346 (2910 ~ 334) X 2
Maximum AC output power (kVA) 2000 ~ 2300 (2000 ~ 2300) X 2
Efficiency 98% ~ 98.8% 98% ~ 98.8%
Power consumption(W) ≤2500 (2500) X 2

Single line diagram


General technical data
(Style N : SSU-A-N-E-C-23L-S-3)
Nominal output voltage range 6 kV to 40.5 kV
Ambient temperature range -25 °C to +40 °C

MV TR Central inverter Relative humidity, non-condensing 95%


Max altitude above sea level w/out derating 1000m
Skid base frame Corrosion class (ISO 12944-2) HDG
MV/LV enclosure IP rating IP54

1YNE182002 REV A FEB 2019

— —
ABB Ltd. We reserve the right to make technical We reserve all rights in this document and in
49, 3gongdan 4-ro changes or modify the contents of this doc- the subject matter and illustrations con-
P.O. Box 31093 ument without prior notice. With regard to tained therein. Any reproduction, disclosure
Cheon-an City, South Korea purchase orders, the agreed particulars to third parties or utilization of its contents
shall prevail. ABB AG does not accept any – in whole or in parts – is forbidden without
­responsibility whatsoever for potential er- prior written consent of ABB AG.
rors or possible lack of information in this ­Copyright© 2019 ABB
document. All rights reserved
abb.com/mediumvoltage

You might also like