Inverter System 48 V DC
for Telecommunication

1 / 10
Inverter system IS920 IS920 Inverter system
Input: 48 V DC
Output: 230 V AC / 50 Hz
5400 W / 6750 VA

A no-break power supply is a


major prerequisite for data and
Highlights:
communications systems. It is
well known that the public AC Compact design
system is not always sufficiently
secure and stable. Low weight
Our inverter units are specially Very high degree of availability
tailored to meet the needs of AC Controlled by digital signalling processor
consumers in telecommunica-
tions systems. Digital regulation for optimized synchronization
speed
Using existing equipment, such
as rectifiers and batteries, they Overload protection
reliably protect the loads from
damage which is caused by bad
Short circuit proof
voltage quality and may result, Mains priority or inverter priority selectable
for instance, in the loss of
valuable data.
Switch over threshold for mains quality
programmable
Parallel operation of inverter modules
Ability for redundant operation
LCD display
CAN communication interface
Isolated alarm relay output
On site scalability
Easy module exchange
Reduced maintenance and service costs

2/9
Inverter system IS920 Scalability Modular design
The 19” subrack includes 3 prewired slots for The modular design makes it possible to
inverter module WR92. According to the exchange easily faulty equipment or increase
actual power profile different output power output power by additional inverter modules.
levels can be reached (1.8 kW, 3.6 kW or
5.4 kW).
Low storage costs
Due to the limited number of required compo-
Quick installation nents for building up a complete inverter
The subrack is equipped with a backplane system the costs for stocking and administra-
including several connection points to wire tion of different parts are very low.
input and output cables and fuses. Installa-
tion of modules is quick and easy by hot The system requires only few components:
plug-in.
• prewired 19” subrack
High power density • inverter modules WR92 and
• static transfer switch STS92
In only 5 HU height a total output power of
5400 W / 6750 VA including static transfer • AC distribution unit IS920
switch can be installed. • Manual bypass switch

High degree of availability Easy in use & configuration


A total loss of load supply is almost impossi- The text based LCD display shows all impor-
ble due to tant system data including inverter output
values. With the front side push buttons all
• modular design of the system menu levels can be selected and all mains
• redundant and parallel inverter operation monitoring thresholds can be adjusted. For
critical system parameters a special login code
• the included static transfer switch for
is necessary.
system monitoring and automated
switching to a second source
Safe AC power
A safe 48 V battery backup system is installed
in nearly each telecommunication application.
The inverter system IS920 can take advantage
of this existing infrastructure for generating
safe AC power. Therefore AC loads can be fed
also during mains power loss.

Type Order Number

Subrack IS920 G48E230/30 FG02HE IS920 S30050-G6390-X19

Connection unit IS920 G48E230/120(32) FG03HE IS920 S30050-H6390-X19

Inverter unit WR92 G48E230/10 WRUFG-FGE WR92 S30050-K6390-X22

Electronic transfer switch STS92 G48E230E230/30-FGE STS92 S30050-K6390-X67

3 / 10
Operation Modes DC input (battery) AC input (mains)

INV

STS

INV Inverter WR92


MBS Manual bypass switch MBS
STS Electronic transfer switch STS92
*optional; not required for standard operation AC output (Load)

Fuses and MBS are not included in standard delivery

Online operation Offline operation


During online operation the inverter modules During offline operation the mains supplies the AC
supply the AC load. load.
The inverters are fed by a safe 48 V battery bank. The inverters are fed by a safe 48 V battery bank
The static transfer switch STS92 operates in and operate in standby mode. The static transfer
automatic mode with inverter priority selection. switch operates in automatic mode with mains
priority selection.
In case of inverter overload or short circuit on
outgoing feeders the STS92 switches over to the In case of mains power loss the STS92 switches
second source (mains) within 4 msec. Antiparal- over to the second source (inverter) within
lel thyristors are used to reduce the lag during 4 msec. Antiparallel thyristors are used to reduce
switching process. The load does not detect this the lag during switching process. The load does
short interruption. not detect this short interruption.
As soon as the reason for the switch-over process As soon as mains is back, the STS92 automati-
is cleared the STS92 automatically switches back cally switches back to main source (mains).
to the main source (inverter).
During normal operation the inverter’s output
During normal operation the inverter’s output frequency is synchronised to the mains frequency.
frequency is synchronised to the second source This feature guarantees that the load is supplied
(mains) frequency. This feature guarantees that with the same phase polarity during switch-over
during switch-over process the load is supplied process.
with the same phase polarity.

The online operation mode is recommended, because of the better quality of the output AC voltage (no
voltage deviations and spikes). If the reduction of system’s power consumption is the main target besides the
safe AC feeding, the offline mode should be used.

4 / 10
Inverter System IS920 Modular design
The subrack combines prewired slots for 3 inverters of series WR92 and 1
static transfer switch STS92. The connection to the incoming and outgoing
cables and between the modules are made on a backplane.
The power modules are cooled by internal fans. The fans are speed controlled
and monitored. The air flow direction is from the front to the rear side.
A minimum space of 50 mm between the air outlets of the modules and the
rear panel of the cabinet is needed. Therefore the installation within standard
ETSI cabinets with a depth of 400 mm is possible.

Technical Data IS920


Nominal DC voltage 48 V DC
DC voltage range 40.8 – 60 V DC
DC current (@54 V DC) 111 A DC
Input
Nominal AC voltage 230 V AC (+/-12% programmable)
AC current (@230 V AC) 29.3 A AC
Nominal frequency 50 / 60 Hz programmable

Nominal AC voltage 230 V AC


Nominal AC current 29.3 A AC
Output
Nominal AC power 6.75 kVA / 5.4 kW
Nominal AC frequency 50 / 60 Hz according to input frequency

Efficiency 91 %
Dimensions (WxHxD) 483 (19”) x 88.5 (2 HU) x 350 mm
Temperature range Operation 0°C…+40°C
Cooling Fan cooling (speed controlled, monitored)
Protection class 1 (electrical); IP20 (mechanical) front panel
Safety standards EN60950, VDE0110, VDE0100 part 410, EN60146
General EMC standards EN55011/22 class “B”, EN61000-4 part 2/3/4/5
Data EN50081-1, EN61000-6-2
Noise < 50 dB(A) at 1 m distance
Switch over time < 4 ms (after detection)
Ambient conditions IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2
Colouring (front panel only) RAL7035 (powder coated)
Max. installation altitude <= 1500 m altitude
Weight app. 19 kg

5 / 10
Connection Unit IS920 Connection unit with Manual Bypass Switch
The connection unit with 3 HUs houses up to four loads. The connection of
loads needs few time and effort the terminals being accessible from the front.
The connection unit includes a manual bypass switch. It allows switching off the
subrack IS920 from AC voltage for maintenance work. During this time the load
is supplied with voltage directly from mains, such ensuring the uninterrupted
supply of AC consumers.

Technical Data connection unit IS920


Rated voltage DC 48 V DC
Current DC 120 A DC
Fusing DC Input STS: C4 A DC
Input Rated voltage AC 230 A AC
Current AC 32 A AC
Fusing Mains input STS: C32 A AC
Manual Bypass: C32 A AC
Rated voltage AC 230 V AC
Rated current AC 32 A AC
Output
Load circuit breakers 1 x C32 A; 3 x C16 A
Rated power AC 6,75 kVA

Dimensions (WxHxD) 483 (19”) x 133,5 (3 HU) x 120 mm


Temperature range operation 0°C…+50°C

General Protection class 1 (electrical); IP20 (mechanical) front panel


Data Safety standards EN60950, VDE0110, VDE0100 Teil 410, EN60146
Ambient conditions IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2
Weight App. 3 kg

6 / 10
Inverter Unit WR92 WR92 with digital control
The inverter WR92 includes the newest switching
technology with controlling by digital signal
processor.
The inverter is able to run in parallel operation
without any additional components and increases
the reliability of the AC system.
WR92 modules can be integrated in empty slots
of a system during normal operation (hot plug-in).
For higher reliability the synchronisation bus is
working in a redundant mode.
Up to 3 modules together with a static transfer
switch unit can be installed in a 19” subrack with 2
HU.

Technical Data WR92


Nominal DC voltage 48 V DC
DC voltage range 40.8 – 60 V DC
Input
DC current (@54 V DC) 37.0 A DC
Internal fuse 50 A T 6x32

Nominal AC voltage 230 V AC


Nominal AC current 9.8 A
Overload capability 150 % for 5 sec.; 110 % for 1 min.
Short circuit protection 2 – 2.5 x In for 2.5 sec. (delayed restart)
Output Internal fuse 16 A
Nominal AC power 2.25 kVA / 1.8 kW
Nominal AC frequency 50 / 60 Hz according to input frequency
Power factor range 0.5 ind. – 1 – 0.5 cap.
Crest factor <= 3
Efficiency 91 %
Dimensions (WxHxD) 106.4 (21 HP) x 88.5 (2 HU) x 325 mm
Temperature range operation 0°C…+40°C
Cooling Fan cooling (speed controlled, monitored)
Protection class 1 (electrical); IP20 (mechanical) front panel
Safety standards EN60950, VDE0110, VDE0100 part 410, EN60146
General EMC standards EN55011/22 class “B”, EN61000-4 part 2/3/4/5
Data EN50081-1, EN61000-6-2
Noise < 50 dB(A) at 1 m distance
Ambient conditions IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2
Colouring (front panel only) RAL7035 (powder coated)
Max. installation altitude < = 1500 m altitude
Weight App. 4.8 kg
LED signals Operation (green), Uo OK (green), Po> (red), Alarm (red)

7 / 10
Static Transfer Switch STS92 Highest reliability
The static transfer switch STS92 is a compact electronic
switch. The digital regulation guarantees minimized synchro-
nisation time of inverter and mains frequency. Due to this
high synchronisation speed the unit can be used together
with diesel Genset as transfer mains supply.
The transfer time between the two inputs is less than 4 msec.
Therefore the STS92 is suitable for use in IT environment.
The static transfer switch monitors the voltage level, fre-
quency and the synchronisation of both incoming sources. In
combination with the inverter WR92 the unit can operate in
online- or offline-mode. This function is programmable at site.
All main functional parameters and measuring values will be
displayed on the LCD panel.

Technical Data STS92


Nominal AC input voltage 230 V AC (+/-12% deviation; threshold programma-
(input source 1 and 2) ble)
Nominal AC current 30.4 A AC (@230 V AC)
Nominal frequency 50 / 60 Hz (programmable)

Input Synchronisation range +/- 2 %


Maximal deviation speed of <1.5 Hz/sec (operation with Genset possible)
frequency for synchronisation
Nominal DC voltage 48 / 60 V DC
DC voltage range 40.8 – 75 V DC (for redundant supply of internal
circuitry)
Nominal AC voltage 230 V AC (max. deviation acc. to input thresholds)
Nominal AC frequency 50 / 60 Hz according to input frequency
Output
Nominal AC power 7 kVA
Maximal overload ability 1000% for 10 ms

Dimensions (WxHxD) 106.4 (21 HP) x 88.5 (2 HU) x 325 mm


Temperature range Operation 0°C…+40°C
Cooling Fan cooling (speed controlled, monitored)
Protection class 1 (electrical); IP20 (mechanical) front panel
Safety standards EN60950, VDE0110, VDE0100 part 410, EN60146
EMC standards EN55011/22 class “B”, EN61000-4 part 2/3/4/5
EN50081-1, EN61000-6-2
General
Data Noise < 50 dB(A) at 1 m distance
Ambient conditions IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2
Colouring (front panel only) RAL7035 (powder coated)
Max. installation altitude <= 1500 m altitude
Weight app. 3.4 kg
LED signals Standby (green), Mains (green), Inverter (green),
Load on Mains (green), Load on inverter (green),
CAN (green), Alarm (red)

8 / 10
LCD display of the
Static Transfer Switch STS92
Static Transfer Switch

Measurement values Adjustable


Thresholds & Parameters
The following measuring values can be indicated Following parameters and thresholds can be
on the LCD: changed within code protected menu items:
• Input source 1: voltage and frequency • Selection of operation mode (online / offline)
• Input source 2: voltage and frequency • Monitoring threshold of input voltages min /
max (source 1 and 2)
• Output: voltage and current
• Monitoring threshold of battery voltage min /
• Battery: voltage (for redundant supply of the max
STS92)
• Overload threshold
• Inverter modules: input and output current,
status • Number of connected inverters
• Number of redundant inverters
• LCD contrast and brightness
• Assignment of alarms
• Delay of alarm switching
• Language

9 / 10
Nokia Siemens Networks GmbH & Co. KG
Power Supply Systems
Rudolf - Vogel - Bogen 5
D-81739 München

Postal address: D-81730 München

Phone: (089) 722 – 2 12 41


Fax.: (089) 722 – 4 11 66
E-Mail: powersupply@nsn.com

© Nokia Siemens Networks GmbH &


Co. KG 2007, München

Order No.
A30050-X6390-X92-2-76K6

The information provided in this


brochure contains merely general
descriptions or characteristics of
performance which in case of actual
use do not always apply as described
or which may change as a result of
further development of the products.
An obligation to provide the respective
characteristics shall only exist if
expressly agreed in the terms of
contract.
Availability and technical specifications
are subject to change without notice.
The trademarks used are owned by
Nokia Siemens Networks or their
respective owners.