You are on page 1of 9

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/233379299

Testing and evaluating grounding systems for substations located in urban


areas

Article  in  IET Generation Transmission & Distribution · February 2011


DOI: 10.1049/iet-gtd.2009.0665

CITATIONS READS

6 463

1 author:

Ljubivoje Popovic
Electric Power Industry of Serbia, retired
91 PUBLICATIONS   366 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

The book about HV substation grounding systens View project

All content following this page was uploaded by Ljubivoje Popovic on 02 June 2014.

The user has requested enhancement of the downloaded file.


www.ietdl.org
Published in IET Generation, Transmission & Distribution
Received on 23rd November 2009
Revised on 17th August 2010
doi: 10.1049/iet-gtd.2009.0665

ISSN 1751-8687

Testing and evaluating grounding systems for


substations located in urban areas
Lj.M. Popović
Faculty of Electrical Engineering, Bulevar kralja Aleksandra 73, 11020 Beograd, Serbia
E-mail: ljubivoje@beotel.net

Abstract: This study presents a method that enables elimination of the influence of metal installations surrounding a test circuit on
the results of measurements. For substations located in urban areas, this influence is unavoidable and so intensive that it cannot be
disregarded. Consequently, the test values of the potential differences (touch and step voltages) appearing on the grounding
system and grounding system impedance can be significantly different in comparison with the actual values. Owing to this,
estimated safety conditions of certain urban high-voltage/medium-voltage substations may be completely incorrect. The
presented analytical method is developed on the basis of analysis of a complex electrical circuit formed during the ground
fault by feeding line conductors and the many different metal installations involved with a fluctuating magnetic field around
and along the feeding line.

1 Introduction Using the previously described procedure, it is possible to


measure the potential and maximal potential gradients created
The grounding system parameters of a high-voltage (HV) by the test current on the grounding system of the tested HV/
installation, as is well known, can be estimated only on the MV substation. In order to obtain the potential of the
basis of calculations at the design stage. However, because substation grounding electrode under actual ground fault
of the voluminous insufficiently known, but relevant, data, conditions, the test values are multiplied by the ratio of the
at the design stage, only an approximate estimation can be actual ground fault current to the test current. If this
achieved in this way. Owing to this, the final judgment potential is greater than the maximum tolerable touch
concerning the safety conditions within and in the vicinity voltages, then the potential differences, especially those
of a certain substation can be obtained only by appearing as a consequence of potential transferred to the
measurements [1]. However, this is not always the case nearest MV/low-voltage (LV) substation [3], should be
with the HV/medium-voltage (MV) substations located in carefully examined. They are also determined under actual
urban and suburban areas. ground fault conditions by multiplying the test values with
According to practice in contemporary electric power the ratio of the actual ground fault current to the test current
distribution companies, the grounding system parameters of [4]. Thus, it could be said that the value of the substation
HV/MV substations are tested by using a version of the grounding impedance is unnecessary data for the estimation
‘fall-of-potential’ method adapted for urban conditions. The of safety conditions.
basic measurement consists essentially of passing a test The foregoing procedure, however, provides the real
current through the grounding system of the tested picture concerning the safety conditions inside and in the
substation via a phase conductor of the feeding line and the vicinity of a particular HV/MV substation, only if the test
grounding system of the supply station or the adjacent current circulates over the entire length of the feeding line
transit substation supplied by the same line. The or from the supply to the tested substation [5]. Problem
transformer that serves for peculiar consumption in any of arises because of the fact that this requirement is not always
these substations is usually used as a voltage source for easy to fulfil in practice. Namely, in many cases, there are
the test circuit formed in this manner. As is known, the one or more transit stations between the tested and the
potential measuring circuit is formed by using a provisory supply substation. This/these substation(s) should be
potential electrode positioned on the ‘remote earth’. Here, it temporarily out of operation and it can be very difficult to
is important to mention that the potential measuring circuit obtain permission to interrupt the power supply to so many
should be laid by following as much as possible the rules consumers, including those that are essential for the normal
defined for the example in [1]. The ‘remote earth’ can functioning of public services in a city. The nearest transit
usually be found at a distance that is between 300 and substation is therefore, as a rule, used as an auxiliary
500 m from the tested HV/MV substation. However, in the grounding electrode in forming an indispensable test circuit.
areas with high values of soil resistivity, this distance can However, in these cases, the metal installations participating
be significantly greater [2]. as return paths of the test current (overhead ground wires,

IET Gener. Transm. Distrib., 2011, Vol. 5, Iss. 2, pp. 231– 238 231
doi: 10.1049/iet-gtd.2009.0665 & The Institution of Engineering and Technology 2011
www.ietdl.org
cable metal sheaths, distribution neutrals and other for undesirable and harmful interruption in the supply of
underground metallic conductors such as water pipes and electrical energy.
railway tracks) are not entirely the same as in the cases of Finally, it is important to mention that, without using the
the test current circulating over the entire length of the method presented in this paper, the assessment of the safety
feeding line. According to this, their influences on test conditions within and in the vicinity of a certain
current distribution also cannot be the same. distribution HV/MV substation can be completely wrong.
The described problem has been firstly noted in [6] and Or, in other words, the prescribed safety requirements could
considered in a simple example in [1]. Also, numerical be considered as fulfilled where this is not the case.
methods have been developed with the aim of solving this
problem at the design stage [7, 8]. They are based on the 2 Basic problem description
following procedure: grounding system elements, including
an HV feeding cable line, are fictitiously divided into All safety problems emanate from only one fraction of the
several sections to model their grounding effects and total ground fault current. This is the current that is injected
mutual inductive influence. However, the problems appear through the substation grounding system into the
at the stage of preparing complete and exact input data for surrounding earth. Thus, for correct estimation of safety
their application. The structure and topology of the conditions, it is of prime importance to correctly determine
underground metal installations surrounding the feeding line this fraction of the ground fault current [1, 5, 6, 9].
are usually almost completely unknown and the data However, this is not an easy task in the case of substations
concerning equivalent resistivity of the soil along the located in urban and suburban areas. Grounding systems of
feeding line are quite uncertain. distribution HV/MV substations consist of a substation
Possibilities for determining ground fault current grounding electrode and many outgoing MV cable lines
distribution in the grounding system of an urban HV/MV acting as external grounding electrodes and/or conductive
substation are separately investigated in [5]. On the basis of connections with the grounding systems of the supplied
this, mainly experimental investigation, and on the basis of MV/LV substations [3, 10]. Outgoing cable lines
introducing a fictitious equivalent conductor (in the farther spontaneously form a very complex grounding system on a
text: equivalent conductor), a corresponding analytical large urban area around the HV/MV substation. This
procedure is developed for determining the actual reduction grounding system includes, through the terra-neutral (TN)
factor of the feeding line passing through the urban area. earthing system in the LV network and consumer
The relevant parameters of the mentioned equivalent installations, many, known and unknown, metallic
conductor are determined under the condition that its installations typical for the urban area. As a consequence of
influence on the ground fault distribution is equivalent to this, outgoing cable lines simultaneously become the
the one obtained by site measurements for the influence of conductive connections with the metal installations laid
all metal installations located along the feeding line. along the same street(s) as the feeding line. Owing to this,
It has been shown that the part of the ground fault current the current appearing in the metal sheath of each outgoing
flowing through the earth is several times smaller than was cable line depends on its disposition in relation to the other
previously considered. This fact throws a whole new light elements of the grounding system and in relation to the
on the entire grounding problem of urban substations and feeding line [11]. Thus, it is not difficult to imagine that the
dramatically changes our perception of the magnitude of current passing through the grounding system elements only
this problem. It can now be seen in a realistic framework as a consequence of the inductive influence of the feeding
that generally leads to more economical solutions. line is distributed in a very complex way between the many
Certainly, greater economical effects can be expected in external elements of the grounding system. It is also easily
cases where, because of high soil resistivity and/or a high noticed that the total current passing through the whole
short-circuit level, special measurements (e.g. bare copper grounding system has two, essentially different, fractions.
conductor laid in the same trench as the cable feeding line, One of them is dissipated into the surrounding earth,
counterpoises etc.) are considered necessary, [6, 9]. whereas the other is induced in the metal installations
Besides, one can expect elimination of the strict surrounding the feeding line. Since the split between these
requirement for the application of expensive MV cables two fractions occurs along the many external grounding
acting as grounding conductors (cables with an uncovered electrodes and under the surface of the ground, none of
metal sheath) as was the case with the MV distribution these fractions can be separated and determined by direct
network in Belgrade. The only difficulty arises from the measurements. However, without the correctly determined
fact that the actual reduction factor depends on the area current dissipated into the earth, it is not possible to
through which the feeding line passes, and as a correctly determine the grounding system impedance of the
consequence of this, the actual reduction factor should be tested substation. The analytical procedure developed here
determined for each concrete feeding line separately. enables the determination of current passing through the
This paper is a logical continuation of the investigation earth by using measured values of the test current and
presented in [5]. The developed analytical procedure the current induced in one of the neutral conductors of the
enables elimination of the influence of metal installations feeding line, or its section used for the test circuit.
surrounding the test circuit on the result of measurements of
the grounding system impedance. The input data consist of 3 Grounding system impedance
measured values of the test current and its fraction determination
appearing in the neutral conductor (cable metal sheath or
overhead ground wire) of the feeding line. Only on the 3.1 Test circuit formed through the cable line
basis of precisely determined grounding system impedance
of the tested substation, the useful preliminary estimation The case will be considered when the test circuit is formed by
procedure of safety conditions can be correct. In many using the feeding line section between the tested and the
practical situations, this enables the elimination of the need nearest transit substation which serves as a current

232 IET Gener. Transm. Distrib., 2011, Vol. 5, Iss. 2, pp. 231 –238
& The Institution of Engineering and Technology 2011 doi: 10.1049/iet-gtd.2009.0665
www.ietdl.org
electrode. When this line section is realised using three single
core cables, the test circuit should be formed in the following
manner: only the metal sheath of the cable with the test
current should be grounded at both the test circuit ends,
whereas the other two metal sheathes should be ungrounded
at one of them.
In actual conditions, besides the applied phase conductor
and its accompanying metal sheath, many other metal
installations typical for urban areas spontaneously
participate in forming the test circuit. Many of these
installations are laid in the same pavement(s) or in the same
street(s) as a feeding line section used for obtaining the test
circuit. Also, many of these installations are mutually
conductively connected by applying the TN earthing system Fig. 2 Equivalent circuit of the test circuit
in each building along each of the town streets. Thus,
independent of their basic functions, these installations
spontaneously form a unique network of different mutually In order to determine grounding impedance ZB by
connected conductors. Its structure and topology are usually measurements, it is necessary to have test values of the
very complex, depend on many local factors and cannot be potential appearing at the substation grounding electrode and
visually verified. Finally, it can be said that the test circuit current Ie (Fig. 1). However, current Ie is dissipated into the
represents a very complicated electrical circuit placed ground through many elements of the grounding system and
mainly under the surface of the ground or in places that are cannot be separated from current Ic that also, as mentioned
not accessible for measurements. earlier, cannot be determined by direct measurement. Owing
In order to simplify the problem and enable its solution, an to this, an actual value of the grounding system impedance
equivalent conductor of the cylindrical shape is introduced cannot be obtained by direct use of test results. Its value,
[5]. This conductor substitutes all known and unknown used in today’s practice, is obtained as a ratio between the
metal installations participating in test current underground tested electrode potential and the difference of the measured
distribution. By using this substitution, the simple physical currents It and Is . However, according to Fig. 2, this is just
model of the test circuit can be presented as shown in Fig. 1. an apparent value that can be, as presented later (Section 5),
The notation used has the following meaning: several times smaller than the actual one.
The used notation has the following meaning:
A(B) – transit (tested) substation,
Ua – auxiliary voltage source, Zs – self-impedance of the cable metal sheath,
It – test current, Zc – self-impedance of the equivalent conductor,
Is – current induced in the cable metal sheath, Z0s – mutual impedances between the cable phase conductor
Ic – current induced in the equivalent conductor, and its metal sheath with common earth return,
Ie – current injected into the earth through the grounding Z0c – mutual impedance between the phase conductor and
system of substation B, equivalent conductor with common earth return,
ZA (ZB) – grounding system impedance of substation A(B), Zsc – mutual impedance between the cable metal sheath and
G – remote ground. equivalent conductor with common earth return.

On the basis of the given simple physical model, any actual For the determination of Ie it is a prerequisite that the relevant
test circuit can be presented by the equivalent circuit shown in parameters of the mentioned equivalent conductor be
Fig. 2. determined. A cross-section shape and a space position of this
conductor towards the cable feeding line have been, according
to [5], defined in accordance with the diagram in Fig. 3.

Fig. 1 Simple physical model equivalent to the actual electrical Fig. 3 Cross-section of the equivalent conductor and cable line of
circuit three single-core cables

IET Gener. Transm. Distrib., 2011, Vol. 5, Iss. 2, pp. 231– 238 233
doi: 10.1049/iet-gtd.2009.0665 & The Institution of Engineering and Technology 2011
www.ietdl.org
The notation used has the following meaning: its application, the following inequality should be satisfied
re – medium radius of the cylinder representing an equivalent
conductor. ZA ≃ ZB ≪ Zs′ L (9)
On the basis of Figs. 1 and 3, the mathematical form of the
analytical expressions for all impedances of the equivalent where L – length of the feeding line section between stations
circuit in Fig. 2 becomes known. These impedances are, A and B.
according to [12], given by In other words, a current appearing in the metal sheath only
as a consequence of the potentials on the grounding
m0 m d electrodes of substations A and B should be negligible. In
ZS′ = R′S + v + jv 0 ln , V/km (1) actual conditions, relationships between relevant parameters
8 2p rS are such that this criterion is satisfied for each substation
′ m0 m d and its feeding line section in an HV cable network.
Z0S =v + jv 0 ln , V/km (2) Simultaneously, it means that the influence of feeding line
8 2p rS
length on the considered ground fault current distribution
m0 m d can be disregarded in practice.
ZC′ = R′e + v + jv 0 ln , V/km (3) When data about parameters R c′ and re are known, the
8 2p re
impedances Zc , Z0c and Zsc can be determined by using (3)
′ ′ m0 m d and (4). Then, by using the equivalent circuit given in
Z0C ≃ ZSC =v + jv 0 ln , V/km (4) Fig. 2 and Kirchhoff’s laws, the following equations can be
8 2p re
written
where R s′ – cable sheath resistance per unit length, V/km; rs – ′
medium radius of the cable sheath, m; v – angular frequency, Ie = (ZS′ ZC′ − Z0S

ZC′ − Z0C

ZS′ − ZSC
′ ′
Z0C ′
)It − (ZSC ZS′ − ZSC
2
)IS
v ¼ 2pf; m0 – magnetic permeability of vacuum 4p × (10)
1027 Vs/Am; mr – relative magnetic permeability, d –
equivalent earth penetration depth and prime (′ ) denotes
Finally, the grounding system impedance of the tested
quantities given per unit length.
substation B can be, according to Fig. 1, determined by
The equivalent earth penetration depth is determined by
 Vt
r ZB = (11)
d = 658 , m (5) Ie
f
where Vt – potential of the tested electrode.
where r – equivalent soil resistivity along the cable line,
In the aim to eliminate the influences of the test circuit and
f – test circuit frequency.
metal installations surrounding the potential measurement
On the basis of the given expressions, it can be seen that,
circuit, this potential is, according to [13], determined by
for determining impedances Zc , Z0c and Zsc , it is a
prerequisite that the relevant parameters of the equivalent
conductor be known. This conductor can be also considered Vt = k1 k2 Vm (12)
as a fictitious additional metal sheath for all cables of the
feeding line (Fig. 3). By using equivalent circuit in Fig. 2 where Vm – tested electrode potential obtained by
and the assumption that grounding impedances ZA and ZB measurement, k1 – voltmeter correction factor, k2 – relative
are negligible (ZA ≃ ZB ≃ 0), necessary parameters R e′ and position correction factor.
re can be determined on the basis of the following equation Voltmeter correction factor is given by

′ RV + (Zp + RE )
2
rm ZSC − ZC′ [ZS′ (rm − 1) + Z0S

]=0 (6) k1 = (13)
RV
In the given equation, rm represents a coefficient expressing
the reduction of the current Ie caused by the current induced where RV – internal resistance of the voltmeter (nameplate
only in the metal sheath Is . It is given by value), Zp + RE – impedance of the potential measurement
circuit seen from the voltmeter terminals (this value is
Is measured by connecting a Megger directly to the voltmeter
rm = 1 − (7) terminals) and RE – grounding resistance of the potential
It
electrode.
The relative position correction factor is determined by
Since (6) gives the relationship between complex quantities, it
can be presented as the following system of two equations
1
k2 = (14)
′ (p/da ) + (p/db ) + (p/dc ) + 1
2
Re{rm ZSC − ZC′ [ZS′ (rm − 1) + Z0S

]} = 0

(8)
2
Im{rm ZSC − ZC′ [ZS′ (rm − 1) + Z0S

]} = 0 where

On the basis of this system of equations, it is possible to 1 AB
p= , m
determine the relevant parameters of the equivalent 2 p
conductor in each concrete case. Having in mind the
assumptions made by the derivation of this system of AB – area of the substation mat under measurement, in m2 da –
equations (ZA ≃ ZB ≃ 0), it is necessary to mention that, for distance, in metres, between the current and potential

234 IET Gener. Transm. Distrib., 2011, Vol. 5, Iss. 2, pp. 231 –238
& The Institution of Engineering and Technology 2011 doi: 10.1049/iet-gtd.2009.0665
www.ietdl.org
electrodes, db – distances, in metres, between the potential following relation
electrode and the limits of the tested electrode and dc ,
distance, in metres, between the current electrode and the 3
limits of the tested electrode. Na =   (17)
ln 1 + (|LS Zw′ |/R)
The value of the grounding resistance RE should be kept
small, in order to improve the quality of the measurements.
However, when an electronic voltmeter of high internal where Na – active length of the ground wire(s) as grounding
resistance (.107 V) is used, this requirement is of conductor, expressed in number of average spans R – average
secondary importance. Also, the direction of the cable used tower footing resistance LS – length of one span of average
for this potential measurement shall be as perpendicular as length.
possible to the test circuit in order to minimise interferences. Where the length of the section between substations A and
B is shorter than two active ground wire lengths, measurement
of current Is should be performed somewere in the middle of
3.2 Test circuit formed through the overhead line this line section.
Overhead lines are also used in contemporary HV distribution
networks, especially in areas with a lower degree of 4 Preliminary estimation of the safety
urbanisation. Because of this, when the feeding line section conditions
between the tested and transit substations is an overhead
line, test current underground distribution should be also On the basis of the determined value of the grounding system
considered in the previously described manner. impedance and the value of the anticipated ground fault
The only difference in comparison with the previous case current in the substation B, the potential on the grounding
lies in fact that, instead of the phase conductor and the electrode of this station can be determined by
metal sheath of the cable line, there is now a phase
conductor and ground wire(s) of an overhead line. Since the V g = rc Z t I f (18)
analogy is obvious, the same physical model and the same
equivalent circuit can be used as from the previous case whereas the potential differences (touch and step voltages)
(Figs. 1 and 2). Only the notations used in Fig. 2 now have essential for the estimation of the safety conditions can be
somewhat different meaning, as follows: determined by
Zw – self impedance of the ground wire(s), Z0w – mutual
impedance between the ground wire(s) and the most distant
Vg
phase conductor, Z0c – mutual impedance between the Um = Umt (19)
mentioned phase conductor and the equivalent conductor Vt
and Zwc – mutual impedance between ground wire(s) and
the equivalent conductor. where If – anticipated ground fault current passing through the
The impedances Zw and Z0w given per unit length are, grounded neutrals in supply network, rc – feeding line reduction
according to [12], determined by factor obtained by calculation, Um – maximal touch voltage that
can appear on the grounding system, Umt – maximal touch
  voltage obtained by test measurements.
m0 m0 mr d
Zw′ = R′w
+ v + jv + ln (15) The reduction factor of the feeding line of three single core
8 2 4 rw
cables is, according to [15], calculated by for cables laid in flat
  formation
′ m m mr d
Z0w = v 0 + jv 0 + ln (16)
8 2 4 dw
R′S
rc = ′ − Z ′ ((Z ′ − Z ′ )/(Z ′ − Z ′ )) (20)
where R w ′
– resistance of the ground wire(s) per unit length, Z ′ + Zm′ + Zm2 m m m2 m
rw – equivalent ground wire radius for one or more ground
wires, dw – distance between the ground wire(s) and the for cables laid in three-angular formation
most distant phase conductor.
Since we are interested only in the critical circumstances R′S
from the safety conditions standpoint, the phase conductor rc =  (21)
R′S + 3v(m0 /8) + j3v(m0 /2p) ln(d/ 3 rS d 2 )
most distant from the ground wire(s) is used for the test
circuit. ′
In this case, we will assume that the equivalent conductor is where Z m – mutual impedance between two adjacent cable

also a cylinder and that its centre is in the middle of the sheaths with common earth return, Z m2 – mutual
fictitious line connecting the ground wire and said phase impedance between two outer cable sheaths with common
conductor. On the basis of these assumptions, one can earth return, d – distance between two adjacent cables,
obtain the relevant parameters of the equivalent conductor according to Fig. 4.
and the grounding system impedance of substation B by
using the same calculation procedure as in the previous
case. However, it is important to emphasise that the part of
the test current appearing in the ground wire(s) as a
consequence of the potentials on the grounding electrodes
at the test circuit ends can be significant in this case.
Because of this, current Is should be measured at a place
that is sufficiently distant from substation B. This distance
can be, according to [14], approximately determined by the Fig. 4 Single-core cables disposed in flat formation

IET Gener. Transm. Distrib., 2011, Vol. 5, Iss. 2, pp. 231– 238 235
doi: 10.1049/iet-gtd.2009.0665 & The Institution of Engineering and Technology 2011
www.ietdl.org

The mutual impedance Z m is, according to [14], determined that this method enables correct estimation for each,
by including extremely complex, practical situation. Some
inaccuracy can appear only as a consequence of the
m0 m d inductive influence of the nearby power distribution lines.
Zm′ = v + jv 0 ln , V/km (22) This influence can be efficiently avoided by using for the
8 2p d
test circuit, somewhat higher frequency that can be easily
′ discriminated from the omnipresent power frequency
The mutual impedance Z m2 is also determined by (22), only,
according to Fig. 4, ‘2d ’ appears in it instead of ‘d ’. currents [10].
On the basis of Fig. 4 and the consideration given in [15], it
is not difficult to show that the reduction factor for the cable 5 Practical example
line with the applied cross-bonding technique can be
calculated by Experimental investigations on the influence of metal
installations typical of urban areas with respect to the value
2ro + ri of the feeding line reduction factor are performed on a
rc = (23) cable line that supplies, in series, two substations in the
3
110 kV distribution network in Belgrade, Serbia [5]. The
where ro – reduction factor when ground fault current length of the line to the closer of the supplied substations
circulates through the cable taking one of the outer measured from the supply substation is 2320 m, whereas
positions, ri – reduction factor when ground fault current the total feeding line length to the tested substation is
circulates through the cable taking the inner position. 6590 m. The line is realised by XHLP cables with mutually
Reduction factor ro is calculated by expression (20), identical design parameters, laid in a triangular formation
whereas reduction factor ri is, according to [15], calculated by on the entire length. The cross-bounding technique
necessary for the reduction of circulating currents was not
R′S applied to the line.
ri = ′ )/(Z ′ − Z ′ )) (24) In the areas through which the line passes, the equivalent
Z ′ + 2Zm′ − Zm′ ((Zm′ − Zm2 m soil resistivity is roughly estimated to be in the range of
from 30 to 50 Vm, and the lower of these values is used for
Owing to the influence of the metal installations surrounding necessary calculations. The line section between the supply
a feeding line, the actual value of the reduction factor can be substation and the transit one passes through an area with a
significantly smaller than the one obtained by calculations [5], lower degree of urbanisation than the rest of the line. The
because of which, the previously described estimation phase conductors are made of aluminium with a cross-
procedure can give results that are excessively on the section of 1000 mm2, whereas the metallic sheaths are made
conservative side for the substations located in typical urban of copper strings with a total cross-section of 95 mm2 and a
surroundings. medium diameter equal to 91 mm. The main elements of
When the test circuit passes through an area with an the grounding system in both of the supplied substations are
obviously greater degree of urbanisation than the rest of the the station building foundation and the 44 MV outgoing
feeding line, one other preliminary estimation can be made. cable lines realised by an armoured lead-sheathed three-core
Instead of using the calculated reduction factor, one can use MV cable.
the actual reduction factor of the feeding line obtained for In the first attempt, the test circuit was formed by using
transit substation A. Certainly, this reduction factor can be only a feeding line section between the tested and the
used at the design stage of substation B, as well. transit substations. The length of this feeding line section is
In critical cases, when preliminary estimated touch and step 4270 m. The second test circuit was formed by using the
voltages exceed tolerable limits, it is necessary to make whole feeding line. While measurements were being taken
estimation by using the actual value of the reduction factor. in both of these cases, only the metal sheath of the cable
This means that the test circuit should be formed in such a with the test current was grounded at both of the test circuit
manner that the test current circulates over the entire ends.
feeding line length [5]. On the basis of the measurements of the test current and
It should be also mentioned that the HV/MV distribution current through the cable sheath, the following results have
substations usually have more than one connected HV line been obtained
that can be used as a feeding line in certain regular or
irregular circumstances in the HV network. The maximum
rm = 0.2555 + j0.3790, for the shorter test circuit
(critical) fault current passing through the earth in such
cases cannot be known in advance. The largest value of this rm = 0.2415 + j0.3623, for the longer test circuit
current can be in cases when total ground fault current, If ,
is not the largest possible one. This can be encountered in
cases when the feeding line causing maximum total ground With the aim of enlarging the ground current, Ie , and
fault current passes through the most highly urbanised area. obtaining the apparent value of the ground system
Owing to this, in some cases it is necessary to perform test impedance, one more measurement was performed. This
measurements for each of the possible feeding lines, and, was made by disconnecting all feeding line metal sheaths at
on the basis of comparing the different values for current Ie , one of the test circuit ends. Then, the test current and
obtain the maximum possible value of this current, or the potential at the grounding electrode of the tested 110/10 kV
worst case from the standpoint of safety conditions. substation were measured. The results obtained were
According to the presented analytical procedure, the
application of this method enables taking into account the It = 136 A and Vt = 1.14 V, for shorter test circuit
influence of all relevant factors and parameters, including
even those whose importance is negligibly small. It means It = 85 A and Vt = 1.20 V, for longer test circuit

236 IET Gener. Transm. Distrib., 2011, Vol. 5, Iss. 2, pp. 231 –238
& The Institution of Engineering and Technology 2011 doi: 10.1049/iet-gtd.2009.0665
www.ietdl.org
On the basis of (8) and the measurement results obtained for than the one presented by expression (21) in [5], or
rm , it follows that the relevant parameters of the equivalent
conductor are: m0
R′eq = R′S + 2v (25)
8
R′e = 0.031 V/km and re = 7.1 m, for the shortertest circuit
In order to obtain a final estimation however, a necessary
R′e = 0.053 V/km and re = 8.1 m, for the longer test circuit condition is that the test current circulates over the entire
feeding line length. The disadvantage of this procedure is,
Results given in [5], for the shorter line: re ¼ 8.1 m and for as mentioned earlier, that transit substation(s) should be
the longer line: re ¼ 12.3 m, were accidentally switched. temporarily out of operation.
By using (10) and results obtained for R e′ and re , the values The value of the actual reduction factor for the feeding line
obtained for the earth current are section between the tested and transit substations in the
considered case is only 0.019 2 j0.010. Since this value is
Ie = (4.23 − j14.15) A, for the shorter test circuit significantly lower than the actual reduction factor for the
feeding line, ra , it is clear that the test circuit formed by
Ie = (5.89 − j15.00) A, for the longer test circuit using the transit substation grounding system can be used
only for obtaining the actual value of the grounding system
When this current is known, on the basis of the measured impedance and a correct preliminary estimation of the
value of the corresponding Vt , the identical value for the safety conditions.
substation grounding impedance is obtained in both the The results presented in [5] relate to two different cases
cases being considered. This value is from the standpoint of the feeding line length and the
surrounding metal installations (the feeding line to the
ZB ≃ 0.075 V tested and the feeding line to the transit substation). The
investigation presented here is directed to the case when,
Without taking into account the influence of the metal for test purpose, only one section of the actual feeding line
installations surrounding the test circuit, this impedance is used.
would be considered as 70.9% smaller for the longer and On the basis of both the earlier investigations and the
88.6% smaller for the shorter test circuit. In the previous results presented here, for current engineer practice it is
investigations presented in [5], these apparent values were important to emphasise the following facts: The grounding
treated as actual ones. This is the main explanation of the problem of distribution HV/MV substations has been
fact that the measured values of the grounding system efficiently and cost effectively solved, thanks to the
impedance for all HV/MV substations in the distribution different metal installations that exist in the urban areas,
network of Belgrade were almost always several times independent of our need for solving this problem. Some of
smaller than the ones obtained by calculations at the design them, surrounding these substations, significantly reduce the
stage. impedance of their grounding systems [3, 7, 8, 10], whereas
Only on the basis of the correctly determined grounding others, surrounding their feeding lines, according to the
system impedance and the value of the calculated feeding results presented in [5] and here, significantly reduce the
line reduction factor, preliminary estimation of the safety fraction of the ground fault current passing through the earth.
conditions for the tested HV/MV substation can be correct. In order not to remain at only a single practical example, we
By using (21), the calculated reduction factor in the case of will assume the cases where the urban environment is
the considered line is identical, but only the equivalent soil resistivity is gradually
increased. Then, as well as in the case of the current
through feeding line metal sheaths, for example, [15], the
rc = 0.032 − j0.105 current through the surrounding metal installations becomes
greater and greater, whereas the current through the earth
However, since the feeding line section from the supply becomes smaller and smaller. According to this, the final
station to the transit station passes through an obviously calculation results will be slightly on the conservative side
less urbanised area, more accurate preliminary estimation if we adopt a value of the equivalent soil resistivity that can
can be made by using the actual reduction factor of the be considered as minimal possible for the urban area along
feeding line for the transit substation. By using the given a considered feeding line. The effects of the reduction of
relevant data, this reduction factor is the current passing through the earth are also greater if the
urban environment is on the greater degree of urbanisation.
rt∗ = 0.041 − j0.036 Finally, on the basis of the presented results, it is clear that
a significant part of the test current passes through the
Finally, the correct estimation of the safety conditions realised different metal installations surrounding the feeding line.
in the tested substation can be obtained by using the value of This means that under actual ground fault conditions, this
the actual feeding line reduction factor. Its value in the case current can be several kilo Amperes. Consequently, from
under consideration is the standpoint of public safety, it is important to say that all
these metal installations should be solidly connected.
ra∗ = 0.030 − j0.021 However, as is well known, this requirement is already
fulfilled through the consistent application of TN earthing

The actual reduction factors rt and ra were determined by system in LV networks and customers installations.
using the procedure presented in [5] and also the corrected Since it is quite a realistic assumption that similar effects
expression for self resistance of the equivalent metal sheath can be anticipated for all other HV/MV substations supplied
for the line consisting of three single-core cables. Namely, by cable lines and located in urban or suburban areas, the
this expression somewhat has a different mathematical form following question emanates: Is it necessary in the future to

IET Gener. Transm. Distrib., 2011, Vol. 5, Iss. 2, pp. 231– 238 237
doi: 10.1049/iet-gtd.2009.0665 & The Institution of Engineering and Technology 2011
www.ietdl.org
pay so much attention to the calculation and performance of 6 Fortin, J., Sarmieto, H.G., Mukhekar, D.: ‘Field measurements of
the grounding systems in urban areas? ground fault current distribution at LG-2, Quebec’, IEEE Trans.
Power Deliv., 1986, PWRG-1, (3), pp. 48–60
7 Meliopoulos, S.A.P.: ‘An advanced computer model for grounding
6 Conclusion system analysis’, IEEE Trans. Power Deliv., 1993, 8, (1), pp. 13– 23
8 Nahman, J.M., Djordjevic, V.D., Salamon, D.D.: ‘Grounding effects of
This paper describes the calculation procedure that, on the HV and MV underground cables associated with urban distribution
substations’, IEEE Trans. Power Deliv., 2002, 17, (1), pp. 111–116
basis of test measurements, enables a correct preliminary 9 Wilas, J., Mukhedkar, D., Fernandes, V., Magalhaes, A.: ‘Grounding
estimation and correct final estimation of the safety conditions grid design of a transition station – a typical example of fault
within and in the vicinity of the HV/MV substations located transfer’, IEEE Trans. Power Deliv., 1989, 5, (1), pp. 124–129
in urban and suburban areas. The influence of the metal 10 Popović, Lj.M.: ‘Comparative analysis of grounding systems formed by
feeders in one case with uninsulated and in the other case with insulated
installations surrounding the test circuit is taken into account metallic sheath’. Proc. CIRED 18th Int. Conf. on Electricity
through the measured values of the test current and the Distribution, Turin, Italy, June 2005
current induced in one of the neutral conductors of the 11 Waes, J., Riet, M., Proroost, F., Cobben, S.: ‘Measurements of the
feeding line, or its section used for the test circuit. current distribution near a substation during a single phase to ground
fault’. Proc. CIRED 17th Int. Conf. on Electrical Distribution,
Barcelona, Spain, May 2003
7 References 12 Int. Std., 2003, ref. CEI/IEC 60909-3, Short-circuit currents in three-
phase a.c. systems – Part 3: ‘Currents during two separate
1 Pilai, P.R., Dick, E.P.: ‘A review on testing and evaluating substation simultaneous line-to-earth short circuits and partial short-circuits
grounding systems’, IEEE Trans. Power Deliv., 1992, 7, (1), pp. 53–61 following through earth’, 2003
2 Popović, Lj.M.: ‘Active length of the cable line with an uninsulated 13 Sobral, S.T., Horta Santos, J.J., Mukhedkar, D.: ‘A proposal for ground
metal sheath from the standpoint of grounding effects’. Proc. IEEE measurement techniques in substations fed exclusively by power
EUROCON, St. Petersburg, Russia, May 2009 cables’, IEEE Trans. Power Deliv., 1988, 3, (4), pp. 1403–1409
3 Popović, Lj.M.: ‘Practical method for the analysis of earthing systems 14 Popović, Lj.M.: ‘Practical method for evaluating ground fault current
with long external electrodes’, IEE Proc. C, 1993, 140, (3), pp. 213 –220 distribution in station, towers and ground wire’, IEEE Trans. Power
4 IEEE Guide for Safety in Substations Grounding, Std. 80-2000 Deliv., 1998, 13, (1), pp. 123– 129
5 Popović, Lj.M.: ‘Influence of the metallic installations surrounding the 15 Popović, Lj.M.: ‘Improved analytical expressions for the determination
feeding cable line on the ground fault current distribution in supplied of the reduction factor of the feeding line consisting of tree single-core
substations’, IEEE Trans. Power Deliv., 2008, 23, (4), pp. 2583–2590 cables’, Eur. Trans. Electr. Power, 2008, 18, pp. 190– 203

238 IET Gener. Transm. Distrib., 2011, Vol. 5, Iss. 2, pp. 231 –238
& The Institution of Engineering and Technology 2011 doi: 10.1049/iet-gtd.2009.0665

View publication stats

You might also like