Professional Documents
Culture Documents
Review
BROWN BOVERI
Brown Boveri
Review
M. Canay:
Overvoltages in the Field Circuit of Synchronous
Machines with Rectifier Excitation 217
P. Wutsdorff:
A Contribution to the Discussion Concerning
Methods of Balancing Flexible Rotors 228
In Brief
G. Ferrari:
A Continuous Light-Section Steel Mill
for the USA 248
G. Neidhöfer
D a m p i n g C o m p o n e n t s and Systems
This contribution deals firstly with the role played by in T u r b o r o t o r s
dampers in a solid cylindrical rotor and discusses their
duties and operational requirements in turbogenerators. The very nature of the solid cylindrical rotor ensures that
The damper winding used by Brown Boveri in their turbo- there are conducting ferromagnetic layers at its outer sur-
generators is then described with attention paid to its face which permit damping currents to flow. The electri-
design and features. Following this the results of some ca! resistivity of iron is high in comparison with that of
special investigations and measurements are reported; these the conductor materials. Relatively high losses are there-
dealing mainly with the losses and temperature rises in the fore incurred in damping non-synchronous fields. This is
rotor under unbalanced load conditions. The contribution to advantage for forming high asynchronous torques
concludes with certain information regarding the unbal- under non-steady-state conditions. However, the high
anced load capacity and the corresponding protection of damping losses are a drawback for other operating con-
Brown Boveri turbogenerators. ditions such as under three-phase unbalanced load. Also,
the excitation winding would be screened only slightly
by the solid iron of the rotor teeth.
It is therefore essential to provide the turborotor with an
additional damping system. There are two basic designs
for this purpose [5, 6];
Introduction
Fig. 1 - Turbogenerator rotor with single-layer damper winding (the
straps are required for assembly only and are removed later)
The damper cage or winding, originally designed as a
squirrel-cage armature for induction motors [1], found
application in synchronous machines at a relatively
early stage [2, 3]. It was used initially for damping rotor
hunting. However, these damping devices were soon
given the additional task of improving the Performance
of the synchronous machine, and also its properties in
general, under transient conditions as well as in certain
cases of steady-state operation. It are their stabilizing and
Screening properties that make the damper cage or wind-
ing particularly suitable for synchronous machines. In
addition to this the damper can be used in the synchro-
nous machine, in the same manner as an induction motor,
for a synchronous starting.
Although the phenomena occurring in a traditional
damper winding and their effects are clearly recognizable
in synchronous machines with laminated rotors, this is
not the case with solid rotors [4], Consequently, it is the
object of this contribution to deal more closely with the
significance and benefits of a damper in turbogenerator
rotors and, on the basis of experience gained in operation
and also in special investigations, to demonstrate the
advantages of an intrinsic damper winding.
BROWN BOVERI 162678.
In addition to these basic forms, which are virtually equiv- ing other rotor components. It permits the generator to
alent from the point of view of their electrical properties, operate under abnormal operating conditions and to cope
there are many combinations of damper cages and wind- with certain system faults without suffering damage.
ings. In addition to these arrangements there is the ex- In the case of the three-phase generator certain operating
pansion to a complete damping system where the pole conditions which deviate from normal duty result in con-
regions also have elements of good conducting materials tinuous or short-time unbalanced load, i.e. under super-
in particular slots. imposed single-phase load conditions, or with asymme-
trical current due to system faults, and also with harmon-
ics from rectifiers in the network. It then becomes the task
Tasks Performed by t h e D a m p i n g Systems of the damping system to ensure effective attenuation of
in T u r b o g e n e r a t o r Rotors the corresponding air-gap fields and that the induced
currents find predesignated and highly conducting paths.
Fundamentally the damper must improve the damping The extreme case of unbalanced load is encountered in
characteristics and operating reliability of the rotor by single-phase machines. Generators of this type with fairly
providing low-resistance axial current paths in the surface high ratings are required, for instance, for supplying rail-
layer of the rotor, thus relieving the solid iron and protect- way systems [7], In this case a particularly heavy and
BROWN BOVEF1I
BROWN BOVERI
U n b a l a n c e d Load C a p a b i l i t y of T h r e e -
Phase T u r b o g e n e r a t o r s and P r o t e c t i o n
If we assume the characteristic values h', 7a, am' and x&" Effects of Preload and Q u a d r a t u r e Axis
and also the terminal voltage before the short circuit u0
which, in most cases, corresponds to the rated voltage, as The operating ränge of a turbogenerator is shown in
given, then Tma,x depends decisively on the duty point Fig. 2. The current and voltage have been resolved into
before the short circuit. This determines the magnitude of their direct-axis and quadrature-axis components for a
the quadrature-axis component of the initial voltage uq0 given operating point. It follows from Eq. (1) that Tma,x
and the direct-axis component of the armature current ia 0 assumes high values especially where w q0 and ia 0 are
before the short circuit. simultaneously relatively small. However, as is clearly
It can also be shown that a three-phase short circuit shown in Fig. 2, this is exactly that case where the syn-
between the circuit-breaker and the machine transformer chronous generator is operating in the underexcited ränge
will nearly always yield the asymmetry of longest dur- near the given practical stability limit. As an example of
ation. this fact Fig. 3 shows an oscillogram of a sudden short-
Consequences of Rapid D e - e x c i t a t i o n tion, even in plants with a generator breaker between the
synchronous machine and the transformer. Consequently,
If the fault, viewed from the machine, is located in front purely as a matter of interest, the effects of rapid de-
of the circuit-breaker, i.e. in the machine itself, in the excitation on the short-circuit current are discussed in the
unit-connected transformer or at the connecting buses, following.
this section of the plant must be disconnected from the Rapid de-excitation affects only the direct-axis component,
network and, at the same time, rapid de-excitation must in the same manner as the regulator. The simplest means
be instigated. Rapid de-excitation quickly reduces the of providing rapid de-excitation is to connect a resistance
internal currents, thus preventing major damage. In this in thefield circuit to considerably reduce the transient short-
case the breaker must interrupt only the system current; circuit time constant T& in comparison to its normal
the operating condition of the machine and the response value. Consequently the periodic component of the short-
of the control system are normally of no significance circuit current in the direct axis decays to zero significantly
to this. more rapidly than normal. Where operating points
Plants with a generator breaker between the synchronous with predominant direct-axis components are concerned,
machine and the transformer usually have two differential a considerable increase in Tmax is to be expected, depend-
protection systems, i.e. one for the synchronous machine ing on the existing value of T& . If the synchronous
alone and one for the complete unit. If a fault occurs in machine is running with a large rotor angle (5 before the
the synchronous machine its differential protection system short circuit the conditions for interrupting the short-
responds. The same conditions apply as described above, circuit currents are decidedly unfavourable. These are
i.e. there is no relation between rapid de-excitation and made even worse by the rapid decay in the direct-axis
stress in the breaker. The alternative is a fault at or near component of the field.
the transformer. The most effective protection concept for The physical conditions are easily understood but to
the transformer is instantaneous interruption of the short- make them quite clear the calculated results for twn
circuit currents from the generator by means of the dilferent load angles of a turbogenerator are shown io
breaker and, at the same time, to isolate the complete unit Fig. 5. In both cases, after a short time, the resultant
from the network. Here, no rapid de-excitation is carried short-circuit current comprises mainly a direct current
out. The generator breaker can normally cope with inter- decaying exponentially with the time constant T& and
ruption on the low-voltage side. It can be seen from the having a small alternating current superimposed on it.
above that it would be expedient to carry out rapid de- The zero transitions shown earlier without rapid de-
excitation only where internal short circuits occur in the excitation and with a purely direct-axis component at
generator. This does not affect the breaker stress. t «s 0-195 s (Fig. 5a) or with a predominant quadrature-
However, one can be misled to form the idea of protecting axis component at t «s 0-385 s (Fig. 5b) have a far greater
the transformer region also by means of rapid de-excita- delay.
It has been shown that rapid de-excitation causes an operate at all in accordance with its intrinsic operating
exceptionally long delay to the first zero transition of the time and protection system, the subtransient component
short-circuit current. Consequently, no rapid de-excitation of the short-circuit current has already decayed and the
may be carried out if the circuit-breaker between the positive phase sequence reactance x, of the generator
generator and transformer is used for protecting the becomes at least equal to the transient reactance x&. As
transformer. This breaker, can, in fact, protect the trans- this is approximately 1 -4 times the negative phase sequence
former much more quickly and effectively than rapid de- reactance x2, Eq. (2) always applies in practice. Conse-
excitation. Rapid de-excitation is instigated exclusively quently there is no sudden reduction of the a.c. compo-
for short-circuits in the generator by its differential pro- nent; on the contrary, a slight and steady increase is to
tection systems. be expected.
From the above statements concerning the behaviour of
the a.c. (irJ) and d.c. (£_) components of the resulting
Realistic A s y m m e t r y and t h e Effects of t h e short-circuit current on interrupting a phase, we can dehne
Arc on t h e Breaker a new instant T max for which the condition
winding of large synchronous machines and thus signifi- assume that the arc resistance remains constant. With this
cantly reduces the armature d.c. time constant to arc resistance, which is much lower than the actual value
encountered in practice, we can be sure that the result of
the calculation will be on the safe side. The features of the
breaker, such as multiple quenching Chambers, can easily
be taken into account. For more accurate investigations it
ra
is quite possible to determine to the exact resistance J"l(0
Due to the arc in the breaker the d.c. components of the for any instantaneous value of the short-circuit current
short-circuit currents reduce very rapidly from the from the arc characteristic. It should be noted that this
instant of contact Separation. Because the a.c. compo- will have a different value in each phase and this makes the
nents are not affected by this increase in resistance, the calculation considerably more complex.
arcs soon force zero transitions of the phase currents and, The above statements are clearly illustrated by the calcu-
consequently, considerably reduce the stresses in the lated curves of short-circuit currents with and without the
breaker. effect of the breaker arc as shown in Fig. 7. Figure 7a
In order to calculate the effect described above we must shows the short-circuit currents of a 1500 MVA turbo-
first know the ratio /'T,/Va. The totally-enclosed generator generator following a preload (for machine data see
breaker shown in Fig. 6 has an arc voltage of about 1600 V Fig. 4). We have deliberately chosen the extremely un-
with a current of 100 kA (r.m.s. value of the a.c. compo- favourable operating point given by P 0-1 p.u., power
nent) flowing on one side of the zero line. At this current factor =0-189 (leading) and <5 & 80° as shown in Fig. 4b.
the arc has a mean resistance of 0-016 £2. As the arc If the breaker were intended to open after t = 0-2 s none
voltage remains virtually constant in the high-current of the phases would pass through zero. According to the
ränge the arc resistance will, in fact, increase with reduc- condition that t ^ T ' m a x one would have to wait almost
ing current. In order to keep the calculation within to t = 0-55 s before opening the breaker. Only then does
reasonable limits, we can select the smallest value for /"l the a.c. component become greater than 75% of the
in accordance with the maximum short-circuit current to d.c. component and fulfil the condition stipulated in
be expected using the steady-state arc characteristic, and Eq. (3).
-2-
;
v
w A /;
iU4U
mV V
M A A / W l/U/w
v / \ v * v • VV wV M
A/ W W
/ /
VA.'
If •' n V ••; ••
-6
0,1 0,2 0,3
•t/t
0,4 0,5
BROWN BOVERI 200120.1
A
A
%
b c
p.u. p.u.
,. 1 \
\ A \ 1-—
/
/ ^
\ \ }. \
i
r~ 1
r './ \ • V
,/
v" // V \ \ 1 \
2
w
' • \ I A * ' /\
•W--
V 1
'V-1-/-T
i i \ A / \ A/
JKT^-
\ / tfl K/
\/ /
r t / r
\ X /
. r
\ / \/ \1
-2
>J \j
0,20
\J
0,22
-r/s -tls
Fig. 7 - Short-circuit currents of a 1500 MVA turbogenerator (machine c: Curve with a j u m p in excitation voltage to the ceiling value at the
ratings as Fig. 4) following steady-state operation with P f» 0-1 p.u., instant of short circuit (regulator) and breaker responds again at
power factor = 0-189 (leading) and d k* 80° t = 0-2 s (arc resistance: 0-01 O)
a : UnafTected curve pattern at constant excitation — D.C. component of phase currents
b: Curve pattern at constant excitation where breaker trips after 0-2 s
and an arc resistance of n , = 0-0257 p.u. = 0-01 Q comes into effect
In actual fact the phase current curves are entirely diffe- operating point. The first phase is interrupted virtually
rent during the breaking process (Fig. 7b and c). From immediately after the breaker opens (t — 0-2 s) and the
t = 0-2 s the arc rapidly reduces the d.c. One phase has current in the remaining phases after not quite one cycle
a zero transition at t = 0-211 s and is interrupted (Fig. 7b). later at t = 0-212 s. This calculation is based uniformly on
At the same time there is a sudden jump in the d.c. of the a minimum and constant arc resistance of 0-01 Q (rijr&
phases which are still conducting [1], The currents in the = 12-92). It should be noted here, however, that the
other two phases therefore reach zero at t s=» 0-23 s. instant of response t = 0-2 s chosen for this example is not
Figure 7c shows the effect of the regulator for the same a lower limit. The breaker is perfectly capable of opening
H. Glavitsch
First, with the growing size of the turbogenerator
Reviewing the various operating conditions of a syn- various characteristic parameters have changed. The
chronous machine in an interconnected network the resulting adverse effects on system Performance have to
objectives of excitation control are worked out. These are be compensated by the excitation system.
small steady-state errors, sufßcient steady-state and Second, high-speed excitation systems result in a
transient stability margins, good voltage regulation under different system Performance and require detailed system
various system conditions. analysis and a new control system design.
For the assessment of the Performance of the excitation Third, more stringent requirements are posed for the
system a method of steady-state stability analysis is various operating conditions which the excitation system
presented whereby the dominant eigen values of the overall has to cope with.
system are taken as measure of system damping. As a Fourth, theoretical studies within the framework of
result loci of constant damping are identified in the modern control theory suggest that an improved
capability (P-Q) diagram of the generator. Performance of the overall system is possible, provided
With this tool at hand various system conditions, effects of all necessary signals (states) and real-time control
Parameters such as loop gain, compensation networks and algorithms are available.
time constants will be investigated. In addition, Computer methods providing improved
It will be demonstrated that a high-gain excitation system means of analysis have further supported this develop-
supported by signals derived from the motion of the rotor ment.
will meet the objectives in a satisfactory manner. Under these new aspects it seems appropriate to review
the objectives of excitation control under various
operating conditions and to demonstrate the effects of
control structures and signals.
Having made this survey it will be possible to give an
indication of how the structure of the excitation control
system should look in present-day technology and what
parameters should be chosen.
The following considerations are primarily concerned
with a turbogenerator equipped with an a. c. exciter
or static excitation system.
O b j e c t i v e s of Excitation C o n t r o l under
Various Operating Conditions
T
X
<D fM-
U T R ZL «T
<z>
J2 14 »Imln = 0 p.U.
15
10 11 19
+
/
A «T 1 (1 + p 1)(1 + p 0 , 0 7 ) K u
+Yr+
1 + p 0,03 (1 +p 7)(1 + / > 0 , 0 1 ) 1 + p 0,01
u
1 Iimax—
max = 5j P-U.
/^-S "fmin = - 1 P-U
at « T = 1 p.u
10 17 ds 18
P ViH 1 dt 5
t n . -
200125.1 1 + p 0,05 1 +p5 l + p 5
Fig. l a - Arrangement and block diagram of a generator with an a.c. Fig. l b - Arrangement and block diagram of a generator with a static
exciter excitation system
1 = Three-phase generator
2 = Diode bridge
3 = A.C. exciter
4 = Thyristor bridge
5 = Permanent magnet generator A = Gain Cs)
6 = Transducers B = Gain (ds/dt)
7 = Summation point K = Gain
8 = Regulator P = Active power
9 = Grid control set TF. = Time constant of a.c. exciter
10 = Transducer ds/dt = Acceleration
11 = Lead-lag filter ii = Field current
12 = Regulator P d/dt (Operator)
=
13 = Limiter s Slip
=
14 = A.C. exciter US = Field voltage
15 = Block to model Upper and lower UL max = Ceiling voltage
16 = Block for forming signals s and ds/dt Wf min = Minimum field voltage
17 = Block for forming the acceleration HT = Terminal voltage
18 = Block for forming the slip «Tr = Reference voltage
19 = Relationship between ceiling voltage and terminal voltage A«T = Voltage error
X X
200126.1 200127.1
than -0-4 and -0-5 are considerably wider particularly pole configuration in Fig. 10 and the small signal
for overexcited operation. In the underexcited region response in Fig. 11 which may be compared with the
damping is not as good as for xe = 0-6 p.u. corresponding figures Fig. 3 and Fig. 5.
Next, the excitation system was changed. The proportion- The signals generated are approximations to slip and
al gain was raised to K = 100 and a lead-lag acceleration of the turbogenerator and the feedback
compensation network was inserted as in the section system as a whole represents an approximation to State
'theory' above. The resulting capability diagrams are space feedback which is responsible for the improvement.1
shown in Fig. 8 and 9 for external reactances xe = 0-6
p.u. and xe = 0-3 p.u.
In comparison with Fig. 6 and 7 there is little difference Transient S t a b i l i t y
as far as the stability limit and the damping in the over
and underexcited region are concerned. This result can The test case studied with regard to transient stability
also be gathered from the small signal response in Fig. 4 was a three-phase fault with successful reclosure.
and 5. In the pre-fault condition the external reactance was
At this point it should be mentioned that it is advisable assumed to be 0-3 p.u. and the generator was loaded at
to check the result of the capability diagram by samples its rating, power factor = 0-9.
of the small signal behaviour since the curves of During the fault condition which lasted 0-15 s the short
constant damping do not reveal which of the pole pairs circuit reactance was 0-2 p.u.
is dominant, see Fig. 2 and 3. Before the faulted line was reclosed the network was
So far, only the normal voltage feedback has been assumed to have a reactance of xe = 0-5 p.u. for a time
investigated. Today there are additional feedback signals period of 0-3 s.
available which may be fed into the excitation system The post-fault network was identical to the pre-fault
and show a quite improved damping behaviour. The network.
manner in which these signals are generated is already The behaviour of the rotor angle and of the field voltage
indicated in the block diagram in Fig. 1. illustrate the characteristic behaviour of the system.
These signals have proved most useful in connection
with high-speed rectifier excitation. But also with an a.c. 1
D. Oeding, P. Nemetz: Stability and voltage regulation of large turbo-
exciter having a time constant of Te = 0-4 s, a better alternators in power systems; effect of machine data and excitation
systems. IEEE Winter Power Meeting 1970, Conference Paper No. 70 CP
damping behaviour can be noticed as illustrated by the 199-PWR.
0 1 2 3 4 s 5
200135.1 "" t
-X—*
-5,0
A\J
1,3
u{ 6 "Tl,2
| U
t f 1
1,0-
0,9
p.u. 1,0 2,0 3,0 4,0 5,0
4,0
p.u. b
3,0 3
| 2,0
50 "f
\
2,0
1,0 1,0
\ /
0 — — '
1,0 2,0 3,0 4,0 s 5,0 0 1,0 2,0 3,0 4,0 s 5,0
200137.1 200139.1
Fig. 13 - 666 M V A generator Fig. 15 - Voltage control after load shedding
Transient stability: three-phase fault with automatic reclosure P = 0
Excitation system as Fig. 3 Q = 0-5 p.u.
a = R o t o r angle Excitation system as Fig. 2
b = Field voltage Excitation system as Fig. 3
a = Terminal voltage
b = Field voltage
foreground is one where the turbogenerator is deter- In any case the steady-state voltage error should be
minant for the voltage level of a subsystem which, in the small. This may be achieved by integral action or by a
extreme case, may be isolated. high proportional gain. The high proportional gain has
the advantage that it offers a fast response during a
transient.
In this operating condition also stability has to be
emphasized.
To illustrate the effects of various adjustments of the
excitation system three test cases were chosen:
Fig. 14 - Transient stability of
a 2 X 750 M V A plant with - reactive load shedding, overexcited,
additional signals at exciter - reactive load shedding, underexcited, and
system. Fault duration 0 05 s,
no autoreclosure. - füll load rejection.
In Figure 15 the two excitation systems discussed previ-
ously are compared for reactive load shedding starting
from overexcited operation.
The maximum overvoltage is practically the same for
both systems. The return to the new steady-state value is
well damped, however, the steady-state values themsel-
ves differ considerably due to the set points which are
not the same for the two gain settings.
With a gain of K = 100 the field voltage drops to the
lower ceiling which is then determinant for the decay of
the terminal voltage. The steady-state value of the
terminal voltage is very close to 1-0 p.u., actually l-013p.u.
For the low gain system the steady-state value stays at
1-159 p.u.
The problem of having an offset in the set point value of
a low gain system is also reflected in the other test cases.
o Figure 16 illustrates load shedding starting from under-
200138.1
1,0 2,0 3,0 4,0 5,0 1,0 2,0 3,0 4,0 5,0
p.u. b p.u. b
3,0 3,0
"f "f
// ^
V 4 2,0 \
| 2,0 S \ ^
1,0
1,0 \ J _
N.
0 1,0 2.0 3,0 4,0 s 5,0 0 1,0 2,0 3,0 4,0 s 5,0
200140.1 200141.1
Fig. 16 - Voltage control after load shedding Fig. 17 - Voltage control after füll load rejection
P = 0 P = 0-9 p . u .
Q = 0-435 p.u.
Q = — 0 - 3 5 p.u.
Excitation system as Fig. 2 Excitation system as Fig. 2
— Excitation system as Fig. 3 Excitation system as Fig. 3
a = Terminal voltage a = Terminal voltage
b = Field voltage b = Field voltage
excited operation. The responses are similar to the over- exhibited complement the findings of this report as far
excited case. as the effects of generator reactances and high-speed
A somewhat different behaviour pattern is exhibited in excitation are concerned.
the case of füll load rejection, as shown in Fig. 17. The Four types of generator have been investigated and it
initial voltage rise is equal for both excitation systems. has been shown that high-speed rectiüer excitation
Afterwards the speed increases and drives the terminal considerably improves the Performance of a generator
voltage up further. The high gain system is able to having a high transient reactance. This applies to steady-
reduce it to a value near the set point whereas the low state and transient stability, as well as to voltage
gain system cannot suppress the overvoltage. regulation.
These cases illustrate quite clearly the need for a high Transient stability was studied in close detail. It was
proportional gain for reasons of maintaining a preset assessed in terms of critical fault duration, maximum
steady-state voltage level and achieving a satisfactory rotor angle and maximum permissible active power
response. Output.
As to the choice of a high loop gain it may again be Voltage regulation was compared by applying steps of
emphasized that steady-state stability with a high gain reference voltage, disconnecting inductive load, rejecting
system is equivalent and that it can be further improved füll load and applying capacitive load. In all cases high-
by additional signals. speed rectifier excitation showed superior Performance
Transient stability is affected only to a small degree by overexcitation by rotating machines.
the choice of the gain. It is the ceiling voltage which is Rectifier excitation systems lend themselves very con-
most important. veniently to the application of additional signals and
For the purposes of reactive power control it seems also yield an improved damping behaviour.
advantageous to choose a high gain in order to achieve
sufficient response and accuracy.
Conclusions
M. Canay
this particular test, when the field current could no longer
The field current of a synchronous machine can assume flow in the negative direction because the rectifier was
negative values during transient phenomena. However, as blocking. The calculated value of this voltage is, however,
it is impossible for the field current to flow in the negative about 7300 V.
direction in machines with rectifier excitation, overvoltages The results of standstill tests were possibly even more
occur in the field circuit which are of major significance for impressive and surprising when the induced voltage in the
the excitation equipment. The origin and calculation of open field winding loop is measured in relation to the
these overvoltages are discussed, using examples to illu- stator voltage. With single-phase supply to the Stator the
strate them. direct axis of the rotor must, of course, lie in the direc-
tion of the alternating field of the armature (position d).
These tests are easy to carry out and they also permit even
the small voltages and currents to be measured accurately
so that the Saturation effect can be eliminated from the
outset; this is often erroneously regarded as the origin of
the discrepancies mentioned above. The results of such
measurements carried out on eight synchronous machines
Introduction are compiled in Table I.
It can be seen from the Table that, in general, the calcu-
Düring many transient or quasi-steady-state phenomena lated values for turbogenerators are much higher than the
the field current of a synchronous machine flows in the measured values, but on the other hand the values calcu-
negative direction. This cannot occur, however, in ma- lated for salient-pole generators are much lower than
chines with rectifier excitation because the field circuit is those measured. This phenomenon cannot simply be ex-
virtually open, i.e. it remains blocked. Consequently, plained as a Saturation effect in the case of salient-pole
under certain circumstances, a very high voltage can occur machines. There are, of course, machines where these
at the terminals of the field winding. In order to protect discrepancies are very small, depending on the design of
the complete excitation system (diodes, thyristors, etc.) the rotor. It is particularly in small machines or laboratory
the maximum possible field voltage must be known, to specimens of a few kVA that these discrepancies can be
permit special protection measures to be taken if neces- very small [2], It should also be noted here that the shape
sary, such as installing appropriately designed discharge of the field current curve for a sudden three-phase short
resistors. circuit in a small generator is entirely different from that
The theoretical investigations involved, based on the con- of a large turbogenerator where the damper winding and
ventional two-axis theory, provide results which differ the solid rotor play a vital role. Consequently, many in-
considerably from reality. As an example we quote here vestigations carried out on small machines are not rep-
the results of such an investigation [1]. During loss of resentative for larger ones. If measurements carried out
synchronism at a 37-5 MVA turbogenerator with rectifier on such machines do not, by coincidence, show any large
excitation, about 700 V occurred in thefield circuit during discrepancies it must not be immediately assumed that
Table I: Comparison between the calculated and measured values of field voltages, static impedance measurement test
Machine 1 T T T T T T S S
I
h
j*Dc | j
J*ad ' \rm(\+l}.)lfs~
I
J*c j*fc
uI
-A-
I
h
J*Dc I I
}(x, - Ar ) j j rfE(\+]
r
D'S 1J
| 1^
I 1
Fig. 3 - Correct equivalent circuit diagrams of direct axis of an idealized
synchronous machine
a: x = x*a
Fig. 2 - Magnetic coupling between field and damper circuit in turbo- b: x = Xv
generators Reference values of field winding:
(For symbols, see text.) /tB = /n fei — x)
S x& XÄ —
UfB = —— = Un 7> to
/ i b xa — x
In = Air-gap exciter current
S = Rated apparent power
Although, in contrast to Fig. 3a, the equivalent circuit ing circuit is open, or periodically acts as an open loop
diagram in Fig. 3b cannot be interpreted physically, it due to the rectifier, currents can be induced in the solid
has a signihcance because of its similarity to the conven- slot walls (Fig. 2). These eddy currents in the slot walls
tional diagram in Fig. 1. It is, in fact, possible to use an considerably reduce the resultant field so that the induced
existing Computer programme based on the conventional voltage in the field winding is considerably smaller than
diagram to calculate the rotor quantities of an ideal ma- without this effect. The influence of the slot walls is not
chine if we use the new reactance xc in place of the stray taken into consideration in either the conventional meth-
field reactance xaa. od of calculation (Fig. 1) or in the equivalent circuit dia-
All components of the equivalent circuit diagrams in grams of idealized machines in Fig. 3 (without rfE).
Fig. 3 can be determined from Xd, xa', xa" and 7V, 7Y' if We can now summarize. The causes of the unrealistic
xc (or x r c ) is known. In order to simulate the direct axis results of conventional methods of calculating the rotor
mathematically, in addition to xa, xa, xa", T& and 7Y' quantities are:
we also require a value for the new reactance x c which can
be determined either experimentally or by using Eq. (1). 1. Incorrect Simulation of the rotor circuits in Fig. 1.
In the mathematical models of real machines the effect of 2. Not taking the rotor slot walls into account with an
the solid rotor must also be taken into account. During open field winding.
the transient phenomena, currents are induced not only in If we use the equivalent circuit diagrams in Fig. 3, which
the field and damper windings but also at the surface of correctly simulate the rotor circuits and also take the
the solid rotor. The rotor surface with its eddy-current effects of the solid rotor into account, we can calculate
resistance /"de acts as a damper circuit parallel to the the induced field voltages in advance with sufficient ac-
main inductance x a a- In addition to this, if the field wind- curacy.
in
O—1 1 — I 1 l—o
Phenomena
j 0,0187
The equivalent circuit diagrams of a large turbogenerator
\
were determined (Fig. 4) with approximated considera- d j 1,907 1 | 0,02(1 + j X)l]/T
tion of the solid rotor according to [4].
The eddy-current resistances at the rotor surface and the
slot walls depend largely on Saturation. The values
quoted for eddy-current resistances refer to nominal 0,0107 /s
linear current density.
Although these simulations have been checked by numer- A DE© DW fE
ous investigations and adequate agreement with the meas-
urements was attained in each case, they have a drawback.
There are certain restrictions to their use in Computer 0,0023 j 0,221 j 0,338 j 0,38
programmes for transient phenomena. There are certain o—C
Previously this was the only condition for idealizing a With this value of xc and the above characteristic quan-
synchronous machine and representing it according to tities it was possible to idealize the turbogenerator and
Fig. 1. The switchgear was calculated and is given in simulate it according to Fig. 3a. The components of
Table II. the two models are compiled in Table II for compar-
ison. Blondel's leakage coefficient atd between field and
2. The initial amplitude of the a.c. component of the
damper c i r c u i t s and also the reactance are much
x d c
field current under three-phase sudden short circuit with a
smaller in the new S i m u l a t i o n (Fig. 3) than in the traditional
terminal voltage u must be equal to the induced field cur-
model with arbitrary assumptions regarding the coupling
rent at s = 1.
between the magnetic fields. This indicates that the field
From this condition, which is based on a physical fact, we
winding of this turbogenerator is, in fact, much better
can calculate the necessary reactance x c for correct Simul-
screened by the damper circuit (xdc is smaller). The effects
ation according to Fig. 3. The conditional equation is:
of these discrepancies will be demonstrated more clearly in
later comparisons.
Xd — — XA' itju
= xa (2) It must be mentioned once again that the idealization car-
xä —XA — XA" UJU
ried out is not equally good for all quantities. For instance
For the generator in Fig. 4 we have = 0-508 and the asynchronous braking torque generated by the d.c.
from this field (s = I) of the stator is not determined correctly.
These details and further conditions for idealizing are not
= 0-262 investigated further here.
Xpc (*d — * d ' ) Fig. 5 - System configuration (for symbols, see text)
Ut 7f a> u (4)
*Dc Xä + X C ( x a — Xc)
r^-vcT v D
-0,5 0 0,5
r f B ( l + j 0-6) | = 33-5 n (5)
Fig. 7 - Operating diagram (for symbols, see text)
puter time, the calculation is carried out for füll load in Short-Circuit on the H.V. Side
the leading ränge (point E in Fig. 7): A three-phase sudden short circuit occurs on the h.v. side
of the transformer during operation (Fig. 5). After a given
p = 0-85 p.u. = 100% load, ^ = —0-31 p.u., u = 1-0p.u. time t it is interrupted by the breaker S so that the system
voltage is recovered immediately. Single-phase line-to-
The result is shown in Fig. 8. After the excitation voltage line sudden short circuits are not considered here because
is interrupted the internal generator voltage decays. The the change in field current, including the a.c. component,
rotor angle <5 increases so that the generator loses syn- is greater during three-phase sudden short circuits for the
chronism after about 3 s. At <5 = 180° the turbogenerator same conditions.
already has a slip of about s = 0-014. The induced rotor It is known that a sudden three-phase short circuit, which
voltage is approximately 24-3 p. u. = 3100 V. A check has in fact means a negative voltage surge, causes a temporary
shown that this value agrees with that for quasi-steady- increase of A in in the rotor current which then becomes
state asynchronous Operation under similar conditions even larger. When the short circuit has been cleared and
(f{E = constant and s = 0-014). the system voltage recovers suddenly, the rotor current, in
If we had taken the relationship between the eddy-current reply to this positive voltage surge, is subjected to a
resistance of the slot walls and frequency into account negative change — A in. The total current becomes
here also for transient phenomena, as in the case of quasi- smaller and can even become negative. Among other
steady-state asynchronous Operation, the maximum volt- factors the amounts and signs of these changes are, of
age would very probably be equal to or smaller than the course, largely dependent on the corresponding rotor
result of the calculation for quasi-steady-state asynchro- angle. They reach maxima when the short circuit occurs
nous operation in Fig. 6 (curve b), i.e. about 14 p.u. at d & 0 and the subsequent voltage recovery is at d «a 2 n,
The subsequent voltage peaks reduce because the field 4u, etc.
current, which is flowing only in the positive direction, Two calculations were carried out corresponding to the
causes a certain excitation in course of time and this re- rated operating point A in Fig. 7 for short-circuit dura-
duces the negative current waves. tions of t = 0-28 and t = 0-5 s. The curves with respect to
Xd —Xd'
ito < —- (k — coso) (6)
time of i, it and rotor angle d are shown in Fig. 9. In the Xd
first case, where t = 0-28 s, the generator remains in syn-
chronism, in the second case, where t = 0-5 s, synchro- It can be seen from this expression that the rotor current
nism is lost. Although the changes A/'n under short cir- under sudden short-circuit conditions in large turbo-
cuit and Mn during recovery of the network voltage are generators does not become negative as easily as in small
quite pronounced, the total field current remains positive turbogenerators or salient-pole machines. However, there
in both cases because the initial steady-state excitation are operating points where this condition can be fulfilled
current for rated operation is very large. for large generators with the smallest k value. If a sudden
The excitation level corresponding to operating points B short circuit should occur under such operating condi-
and C in Fig. 7 is low in the underexcited ränge. In the tions the excitation current can become negative. The
transient phenomenon under consideration here, it is extreme case occurs where the generator is running at the
easier for the total excitation current to become negative. stability limit (6 90°) almost without excitation and a
In case B (operating point B) with a short-circuit duration three-phase short-circuit occurs. The field current con-
of 0-5 s the field current would, in fact, become negative tains almost only the a.c. component of the short-circuit
(Fig. 10a). However, as the rectifier prevents it from flow- current and even the first negative half-wave is blocked by
ing, the result is a high rotor voltage of 10 p.u. Although the rectifier. As far as the rotor is concerned this means
we have taken a very unfavourable case for calculation asynchronous running at s = 1 and, at the same time, an
here, because rm (1 + j 0-6) ]/s is replaced by a constant open field winding in the stationary d.c. field of the arma-
resistance of 33-5 n, the result is, nevertheless, a lower ture. The fictitious asynchronous operation which has
value than that in asynchronous operation. been investigated above thus represents the worst pos-
In case C with the same short-circuit duration, but with sible case for the rotor overvoltages.
even lower excitation, the conditions become more fa-
vourable yet (Fig. 10b). The field current without an a.c.
component always remains positive and would only be- Conclusion
come temporarily negative due to the peaks in the a.c.
component, but no high voltage is induced. If the d.c. It has been shown that the traditional method of calculat-
component of the stator current would decay more rapidly ing the rotor voltages for large turbogenerators according
(Ta shorter), it would always remain positive. to the equivalent circuit diagram in Fig. 1 and without
If we further reduce the excitation and operate at point considering the slot wall effect in solid rotors gives un-
D in Fig. 7, the field current remains positive during the realistically high results. They do not agree with measured
Bibliography
P. Wutsdorff
T h e o r e t i c a l Fundamentais
Following a brief resume of the theoretical fundamentals, the
known methods of balancing flexible rotors are described. The theory has been dealt with in detail in the literature
The procedure followed in an overspeed bay is discussed. A mentioned above. Here we need consider only that part
Computer Programme for balancing flexible rotors is intro- which applies to this investigation.
duced. This permits the balancing procedure, to which the The flexure of a shaft rotating at an angular velocity of m
rotor is subjected in an overspeed bay, to be simulated for with isotropic bearing conditions is described by a rotating
a given eccentricity distribution. Various balancing runs are system of x, y and z coordinates. The z axis is considered
discussed using the rotor of a 600 M W turbogenerator as as a straight line between the centres of the bearings and,
an example. if the static flexure is disregarded, it is identical with the
axis of the undeformed rotor. The spacial deflection curve
di
where Ui = Mi
2'
Balancing at will
1. Rigid balancing in two
planes
2. Calculate füll set of balancing
weights:
2.1 Federn-Kellenberger
method
2.2 Modal balancing
3. Eliminate normal modes
in sequence by
3.1 Federn-Kellenberger
method
3.2 Modal balancing
Memorize balancing weights
J = Yes
N = No
200185.ME
Weight: 64-31 t Length: 16-09 m PD2: 35-31 . 103 kgfm2 m Sc m: 4320 1/min
9 10
I I I I
• •
250[xm
233
below the overspeed value, i.e. in this case, the first four order characteristic forms, or only to a minimum, when
characteristic forms. In all cases the first four development balancing characteristic forms of lower orders can be
coefficients were brought down to an average of 0-027 % referred to as 'forward balancing'.
of the value of the original balancing run. The optimum combination of planes must be found by
The sole determining factor is whether the balancing varying the balancing planes (run C015 for dynamic
criteria are fulfilled, i.e. how large the vibrations are at balancing and C016 for the Federn-Kellenberger method).
the journals. As can be seen by considering the uncom- Here the C016 run is clearly superior because not only
pensated development coefficients au the quality of are four characteristic forms balanced, but also, the
balancing has a deciding influence on the degree to which characteristic forms of higher orders are not excited. In
the higher characteristic forms are excited. This depends run C 016 the coefficient as retains its original value and
largely on the location of the selected balancing planes. coefficients a6 and a 7 are amplified only by a factor of 5.
This is illustrated by comparing run C016 with C 020 In contrast to this, in run C 015 the coefficient a6 is am-
and C015 with C021. The fact that there is undesired plified by a factor of 15.
excitation of higher characteristic forms is not considered An arbitrary combination of planes was chosen for runs
mathematically in compiling the balancing equations (5) C 020 and C021. Run C 020 (Federn-Kellenberger) is
and (6) and is therefore common to both balancing meth- better because the fifth development coefficient as was
ods. The balancing equations consider only that the reduced to 60% of its original value. This appears to be a
characteristic forms which have already been balanced coincidence because of the arbitrary choice of balancing
are not re-excited when balancing characteristic forms of planes. However, coefficient a6 and a1 are increased
higher Orders. The problem of not exciting the higher- drastically (89 times and 76 times respectively).
Table II
Run C013A Balancing method: Original unbalance No. of char. forms required: 0
ai - 0-553 E-2 0-121 E-3 0-173 E-l 0-470 E-l 0-257 E-3 0-234 E-2
Plane/G 0 0 0 0 0 0 0
äi -5-28 E-5 -4-44 E-5 -7-36 E-5 1-15E-4 1-31 -14-73 -2-09
1 600 0 1 1 1 0 1
2 1700 2 - 5 4 9 4 - 5
3 2800 8 - 18 15 35 121 19
4 3600 20 - 43 35 94 25 50
5 4320 54 -112 82 261 52 -132
1 600 0 2 0 2 4 2
2 1700 - 3 21 3 16 37 11
3 2800 - 9 62 8 52 106 34
4 3600 -14 111 13 110 188 36
5 4320 -14 170 17 232 292 170
Run C021 Balancing method: Modal balancing No. of char. forms required: 4
äi 5-73 E-5 2-94 E-4 5-45 E-5 2-90 E-4 3-69 -78-36 -51-37
All gases generated by insulation decomposition are solu- The limiting values quoted are to be regarded as guide-
ble in the transformer oil. If the gases are generated slowly lines and it is safe to say that their orders of magnitude
they are quantitatively dissolved in the oil and therefore are correct. Figure 1 shows diagrammatically the concentra-
the gas collector relay cannot respond to this form of gas tions of these gases as measured in the oil of 72 dilferent
formation. Typical causes of this form of slow gas forma- high-power transformers which operate perfectly. The
tion are local overheating of conductors or zones in the outer rings represent the limiting values according to
iron core, weak discharges in gas pockets within the solid Table I.
,
ii iiiiiii 1
4 6 i 4 6 4 6 8 4 6 8 20 40 > 4 0
< 4 • 10 1 10"' 1 • 10"1 10 _ [C 2 H 2 ]
[C 2 H 4 ]
Table II: Ranges of characteristic values for mixture The combination of mixture ratios
ratios of gases dissolved in transformer oil
[CH4] [C2 H 2 ]
Mixture ratio in [CH4] [C2H2] [C2H6] [C2H2] [H 2 ] a n d
[C2H4]
relation to the [Ha] [C2H4] [C2H2] [CH4]
concentrations of can be used together if
dissolved gases
(volume/volume) [CH 4 ] > 100 ppm (V/V) and, at the same time,
[C2 H 4 ] > 60 ppm (V/V) or if
Type of fault [H 2 ] > 200 ppm (V/V) and
[C2 H 2 ] > 30 ppm (V/V) and so on.
Local overheating >1 <0-7 >0-4 <0-3
Weak discharges ^ , • • [C2 H 6 ] [C2H2]
in gas pockets <0-1 * >0-4 <0-3 The additional mixture ratios —_ and are
[C 2 H 2 J [C H 4 J
All other types of <1
>0-7 <0-4 >0-3 acceptable as additional confirmation of the diagnosis if
discharge >0-1
at least one of each pair of gases in the ratio exceeds the
* Not indicative of this type of discharge, generally not applicable. concentration quoted in the Table I.
If this mixture ratio is applicable and > 1 this indicates that the dis- 3. This method of diagnosis may be used only with ex-
charge is increasing.
treme caution if the gases dissolved in the oil originate
from a fault which has no longer been present for some
considerable time; the various gases of decomposition
The following rules are criteria for the extent to which travel at various speeds towards the surface of the oil in
these mixture ratios are useful in the diagnosis: the expansion tank and escape to atmosphere. When the
generation of gases stops this distorts the mixture ratio.
1. A Single mixture ratio can be used in the diagnosis only
if the concentration of one of the two gases is twice as 4. Carbon monoxide and carbon dioxide are found typi-
high as the limiting value quoted in Table I. cally as a result of decomposition of the solid insulation
and are not used in the characteristic mixture ratios. In
2. Several mixture ratios can be used together in the di-
the case of gradual faults it is generally not possible to
agnosis if at least one of the first and second mixture
decide whether and to what degree the solid insulation
ratios can be used alone according to the first rule above
has been attacked.
and at least one gas of those whose concentrations are
formed by the other ratio, exceeds the limiting value in 5. In the case of transformers with a gas cushion (nitrogen
Table I. cushion) above the oil level, the limiting values quoted in
110"
uu " u
110
,4 6 4 6 4 6 4 6 8 20 40 > 4 0
<4-10" 1 • 10"' 1-101 10 [C 2 Hs]
[C2 H2]
> 40
[CH. , 4 0 -
~[H 2
20 -
10 -
6
4
1
8
6
1 • 10"1
8
6
I -10
4 6 f 4 6 8 4 6 8 4 6 8 20 40 > 4 0
<4-10 1 10"' 1 • 10"1 10 [C2Hz]
200095.11 [CH 4 ]
Table II for the mixture ratios can be applied only to a Figures 2 and 3 show more clearly than any description
limited extent. If the volumes of oil and gas cushion are the mixture ratios of gases dissolved in the oil of various
known quantities, the applicable limiting values can be transformers. The faults in these transformers were located
calculated. by inspection or defined by measurement. The causes
Those ranges of values which are typical for a given type discovered were not exclusively incipient faults in the
of fault are given in Table II in relation to the mixture transformers but also cases of spontaneous damage caus-
ratios quoted in the above rules. ing gases to collect in the Buchholz relay; the values
A diagnosis is adequately confirmed if two or more of the quoted, however, refer without exception to the gas con-
mixture ratios used are within the ranges of values which centration found in the insulating oil and determined in
are typical for the same type of fault. units of gas volume per oil volume (e.g. ppm [V/V]).
10"
10"'
10"
H, ch4 c2h6 c2h4 c2h2 co co2 h2 ch4 c2h6 c2h4 c2h2 C O'2 CO.
200096.1
10"'
10"'
10"- t /
/ /
/ /
: / /
/ / /
10 - / -
/
/ /
/ /
f
/
10"- X /
/
/ /
/
;
10"'
- 7* _
/
/
f /
/
10" /
/
/ /
2 /
h2 ch4 c 2 h 6 c 2 h 4 c 2 h 2 CO CO H2 C H 4 C 2 H & C2H4 C2H2 C O CO2
of the fault has gone into Solution in the oil. On the con- relay. It is known from the exchange with the oil that it
trary, as a general rule a much higher proportion of the takes place fundamentally only in one direction: in the
gases formed in this way are dissolved in the oil than that direction of establishing equilibrium between the dissolved
which isfinally discovered at the Buchholz relay. However, and free gas. We also know that equilibrium must be
the oil volume in a transformer tank is so large in com- reached provided that sufficient time is available. Our
parison with the gas volume in the Buchholz relay that method of fault diagnosis is based on two facts for the
the dissolved concentrations of gases due to decomposi- case of gas Separation in the Buchholz relay which is not
tion found in the oil are small and the concentration of in equilibrium with the gas concentration in the oil as
free gases in the Buchholz relay are relatively high. described in this section:
A simple calculation of the quantities of dissolved and
free gases — concentration of dissolved gases X the oil 1. on the facts determined experimentally that a partial
volume in the transformer and concentrations of free quantity of oil is directly involved with the exchange
gases X the gas volume in the Buchholz — shows that the which is large in comparison with the volume of free
majority of the gaseous products due to decomposition gas in the Buchholz relay, and
are, in fact, dissolved in the oil. In other words: as the 2. on the principle that the objective of the gas exchange
gas rises to the Buchholz relay considerable gas exchange with the oil is to establish equilibrium.
takes place between the gas bubble and the column of oil From this we immediately have the following conditions
through which the bubble passes. The quantity of oil in- which form the basis for diagnosing the fault from the
volved in this exchange represents only a fraction of the gases present in the Buchholz relay: We assume that the
total oil volume in the transformer. However, the volume gas separated in the Buchholz relay is of a composition
of gas involved is large in comparison to the gas volume such as if it had been in contact with an unknown quantity
which reaches the Buchholz relay without going into Solu- of oil with which it would have continued to exchange gas
tion. This portion of the oil involved in the exchange mixes until equilibrium had been reached, and of this unknown
with the major volume of the transformer oil 2 and this, quantity of oil we further assume that its volume is large
in turn, naturally contains only small concentrations of the in comparison with the remainder of the gas which finally
gases originating from the process of decomposition. reaches the Buchholz relay.
It can thus be established that a considerable exchange has
From these assumptions simple calculations bring us to a
taken place between the original gas and the oil and only
set of formulae with which we can approximately deter-
a small proportion of the gas has reached the Buchholz
mine the original mixture ratios of the individual com-
ponents of the gas created by the fault if these gases are
found in any given mixture ratio in the Buchholz relay.
1 Attention must be paid that the oil is well mixed before taking samples. These formulae thus render information concerning how
Samples should therefore be taken as rapidly as possible following an the gas composition has changed during its journey from
alarm from the Buchholz relay. Oil samples should be taken as long as
possible after such an alarm and, if possible, the oil pumps should be set
the fault location to the Buchholz relay by means of ex-
in motion and the fans left operating. change with the oil.
110"
4 68 4 68 4 6 4 6 20 40 > 4 0
< 4 • 10 1 • 10"' 1 • 10"1 10 ^ [C2 H 6 ]
[C2 H 2 ]
200099.1
>4
[CHi]4
[H 2 ] 2
Ai
1 A
A
A A
A
A
A
0 « 0
I 10"
O 0 6
O O 00
6
« < « 0
4
2 O
O O
2 O
110r8 . 0
6
4
2
1 • 10
3
,4 6 4 6 8 2 4 6 4 6 ! 20 40 > 4 0
< 4 • 10" 1 • 10"' I • 10'1 H> ^ [C2 H 2 ]
200100.1
[CHI]
Pi C,
--- = Mixture ratio of gas component / to gas component — = Mixture (concentration) ratio of the gas dissolved in
P.i j in the free gas collected at the Buchholz relay Cj the insulating oil of the complete transformer after
a sufficient time has elapsed from the alarm given by
Kr = Solubility of gas component r in the insulating oil the Buchholz relay
4 68 4 6 8 4 68 4 68 20 40 > 4 0
< 4 - 10" 1 • 10"' MO"1 1 10
| [C 2 H 2 ]
[C 2 H„]
Applying these simple rules the formulae for calculating for determining the mixture ratios of the components in
the various mixture ratios are as follows: the original gas from the gas dissolved in the insulating
oil.
Pi Ki Pi The equation (1) is important because the partial pres-
K,
(1) sures of the gases due to decomposition in the Buchholz
Pi relay are generally relatively high and easily measured
whereas the concentrations in the oil are often low and oil
for determining the mixture ratios of the components in samples should be taken only after a considerably time
the original gas from the analysis of the gas in the Buch- has elapsed from discovery of the fault, while the gas
holz relay; taken from the Buchholz relay can be sampled immediate-
ly the alarm has been given and should be analysed im-
mediately. Using equation (1) we can now convert the
Pi Ci values in Table II with the solubility Kr so that the ranges
(2)
Pi of values for the gases in the Buchholz relay can be used in
A Continuous Light-Section
Steel Mill for the USA
G. Ferrari
Fig. I - Power supply for rolling mill
The steel mill of the New Jersey Structural Steel Company a: 34-5 k V outdoor switchgear
b: Arc furnace
(NJSSCo) is on the eastern seaboard ot the United States c: Rolling mill
and is intended to supply the local market with structural d: 440 V auxiliaries
steel.
The initial output is 100000 t/a and can be considerably
increased to satisfy market requirements. Within the
230 k V , 6 0 H z
framework of our ränge of products for mini steel plants,
the electrical equipment for the continuous mill train and
the voltage distribution equipment for the complete plant
was handed over to the client in July 1973.
Power Supply
Rolling Mill
\
I 7
\ \ \
1
e 8
-m- -m- -m- -m-
750 k W 750 k W
L 0 — 0 - J 1 ® j - 0 -
1,2,3 4,5,6 - 0 -
2x450 k W 370 k W 370 k W 370 k W 370 k W 370 k W 370 k W
7,8 11 12 13 14 15 16
Fig. 4 - Power supply for main drives 200123.1