ANNEXURE - 2

MOTOR = 123KW RV = 475V RA = 156A

D E F RV
K=
1.732 X RA

475
K= = 1.758 Ω
D4 E4 F4 1.732 X 156
RESISTANCE DETAILS
STEPS RESISTANCE / PHASE
D3 E3 F3
OD1 / OE1 / OF1 100% K = 1.758 Ω
D1-D2 / E1-E2 / F1-F2 25% K = 0.4395 Ω

D2 E2 F2 D2-D3 / E2-E3 / F2-F3 14% K = 0.246 Ω


D3-D4 / E3-E4 / F3-F4 8% K = 0.141 Ω
D4-D / E4-E / F4-F 4% K = 0.071 Ω